You are on page 1of 2

FT12-150

Specification

(12V150Ah)

FT (Front Terminal) Series is specially designed for telecom use with 10+
years design life in float service. By adopting a new AGM separator and
centralised venting system, the battery can be installed in any position
while maintaining high relaibility. The dimensions of the FT series is
designed for 19" and 23" cabinet installation. It is suitable for UPS/EPS
applications.

Cells Per Unit

Voltage Per Unit

12

Capacity

150Ah@10hr-rate to 1.80V per cell @25 oC

Weight

Approx.45.0Kg ( Tolerance1.5 %)

Max. Discharge Current

1500 A (5 sec)

Internal Resistance

Approx. 4 m

Operating Temperature Range

Discharge: -20 C ~60 C


Charge: 0 oC~50 oC
Storage: -20 oC~60 oC

Normal Operating Temperature Range

25 oC5 oC

Float charging Voltage

13.6 to 13.8 VDC/unit Average at 25 oC

Recommended Maximum Charging


Current Limit

45 A

Equalization and Cycle Service

14.6 to 14.8 VDC/unit Average at 25 oC

Self Discharge

RITAR Valve Regulated Lead Acid (VRLA) batteries can be stored


for more than 6 months at 25 oC. Self-discharge ratio less than 3%
per month at 25 oC. Please charge batteries before using.

Terminal

Terminal F9

Container Material

A.B.S. UL94-HB, UL94-V0 Optional.

Dimensions
Unit: mm

Dimension: 555(L)110(W)288(H)
555

110

46

288

Terminal F9

550

Constant Current Discharge Characteristics: A (25 oC)


F.V/Time
9.60V
10.0V
10.2V
10.5V
10.8V
11.1V

15MIN

30MIN

1HR

2HR

3HR

4HR

5HR

8HR

256.1
250.8
245.5
233.8
215.5
193.3

150.7
148.8
146.5
142.5
137.8
132.5

93.63
92.38
91.50
90.38
89.12
87.01

57.81
56.64
56.04
55.31
54.85
52.65

39.28
38.56
38.21
37.87
37.43
36.70

31.68
31.23
30.91
30.46
29.41
28.99

26.29
26.06
25.89
25.67
25.55
25.36

17.32
17.25
17.10
16.94
16.87
16.74

10HR

15.61
15.46
15.30
15.15
15.01
14.84

20HR

8.26
8.11
7.95
7.80
7.72
7.41

Constant Power Discharge Characteristics: W (25 oC)


F.V/Time

15MIN

30MIN

1HR

2HR

3HR

4HR

5HR

8HR

9.60V

2781
2742
2711
2589
2417
2201

1725
1707
1692
1658
1619
1574

1085
1075
1069
1062
1048
1033

677.4
669.1
664.4
656.0
651.1
626.7

462.5
455.6
453.6
449.9
444.9
437.4

379.1
373.8
370.3
365.3
353.0
347.9

315.0
312.2
310.3
307.8
306.4
305.3

207.4
206.6
205.0
203.3
202.4
201.0

10.0V
10.2V
10.5V
10.8V
11.1V

All mentioned values are average values ( Tolerance2%) .

10HR

20HR

187.2
185.7
184.1
182.2
180.4
178.5

99.54
97.81
96.00
94.19
93.28
89.94

FT12-150

12V150Ah
Storage characteristic

15

100
Supplementary charge required
(Carry out supplementary charge
before use if 100% capacity is
requires)

Capacity (%)

L ife E x p e c ta n c y (y e a rs )

12

80
10

Supplementary charge required


before use.
This supplementary charge will help
to recover the capacity and should
be made as early as possible.

60
20

40

30

40

Supplementary charge may often


fail to recover the capacity.
The battery should never be left
standing till this state is reached

20

0
0

10

20

30

40

50

Battery Temperature

Charge characteristic Curve for standby use


15 7.5

Discharge characteristic Curve

5.0

0.24

120
Chcrge Volume

11 5.5

80
Discharge
100%0.05CA20h
50%0.05CA10h
Charge
Chcrge Voltage2.275V/C
Charge Current0.1CA
Temperature 25

4.0

3.7

60

40

0.16

0.12

0.08

T erm inal V oltage (V )

12 6.0

4.3

13

6.5

4.3

12

6.0

4.0

11

5.5

3.7

0.20

100

Chcrge Voltage

C h a rg e C u rre n t (C A )

13 6.5

4.7

C h a rg e V o lu m e (% )

C h a rg e V o lta g e V

14 7.0

0.05C
0.16C 0.093C

10

5.0

3.3

4.5

3.0

0.35C
0.62C
1C

3C

10 5.0

Supplementary charge and storage


guidelines

10 12 14 16 18 20 22 24

Storage Time (months)

3.3

20

0.04

Charge Current

4.5

3.0
0

0.6

1.2

12

30

10 12 14 16 18 20 24 28

10

20

24

Hr

min
Discharge Time

Charge Timeh

Capacity Factors With Different Temperature


Battery Type

-20

-10

10

20

25

30

40

45

GEL
6V&12V
Battery
2V

50%

70%

83%

85%

90%

98%

100%

102%

104%

105%

60%

75%

85%

88%

92%

99%

100%

103%

105%

106%

AGM
6V&12V
Battery
2V

46%

66%

76%

83%

90%

98%

100%

103%

107%

109%

55%

70%

80%

85%

92%

99%

100%

104%

108%

110%

Maintenance & Cautions

Discharge Current VS. Discharge Voltage


Final Discharge
Voltage V/cell

1.75V

Discharge
Current (A)

A 0.2C

1.60V

1.70V
0.2C A 1.0C

A 1.0C

Charge the batteries at least once every six months,


if they are stored at 25 o C.

Float Service:
Every month, recommend inspection every battery voltage.
Every three months, recommend equalization charge for one time.
Equalization charge method:

Charging Method:

Discharge: 100% rate capacity discharge.

Constant Voltage

-0.2Cx2h+2.4-2.45V/cellx24h,Max. Current 0.3C

Constant Current

-0.2Cx2h+0.1Cx 12h

Fast

-0.2Cx2h+0.3Cx4h

M5

Bolt
Terminal

F3 F4 F13 F18 T25 T26

Torque

6~7N-m

SHENZHEN RITAR POWER CO.,LTD.


URL:www.ritarpower.com

M6

Charge: Max. current 0.3CA, constant voltage 2.4-2.45V/Cell charge 24h.


Effect of temperature on float charge voltage: -3mV//Cell.
M8

F8 F11 F12-1 F15

F5 F9 F10 F12 F14 F16

8~10N-m

10~12N-m

Length of service life will be directly affected by the number of discharge


.
cycles, depth of discharge, ambient temperature and charging voltage.