You are on page 1of 2

The margin below installed & absorbed power shall not be less than

Motor Margin above drive machine


absorbed power Followin fuse rating is suggested by Sieme
<22KW 25%
22kw to 75kw 15% Use Fuse Size(in
ampere)

above 75kw 10% 4


6
10
Motor Rating Cable Size(3C & in mm2) 16
<3.7 2.5 Cu 20
3.7< <=9.3 6 Cu 25
9.3< <=15 16 Al 32
15< <=25 35 Al 50
25< <=30 50 Al 63
37< <=55 120 Al 80
55< <=75 185 Al 100
75< <=90 240 Al 125
90< <=110 400 Al 160
200
250
4718 KWhr/hr = 4.057 Gcal / hour (860Kcal /Kwhr) 315
5425 KWhr/hr = 4.666 Gcal / hour (860Kcal /Kwhr) 400

Specific consumption of electrical power 0.064 Gcal / Hr per MT of Ammonia


in fuse rating is suggested by Siemens Ltd.

Motor Kw Current
Rating (FLC) is
less than
0.37-0.55 1.3
0.75-1.1 2.6
1.5 3.7
2.2 4.8
3.7 7.8
5.5 11.2
7.5 16
9.3-11 20.8
15-18.5 34
22 40
30 53
37-45 78
55 96
75 131
90-110 189
132 227
160 271

You might also like