You are on page 1of 1

Page 1 of 3

Exova T: +1 (780) 438-5522


7217 Roper Road NW F: +1 (780) 438-0396
Edmonton, Alberta E: Edmonton@exova.com
T6B 3J4, Canada W: www.exova.com

Analytical Report

Bill To: Pure Spirit Water Services Project: Lot ID: 759963
Report To: Pure Spirit Water Services ID: Control Number: A135707
Spirit River, AB, Canada Name: Date Received: Aug 31, 2010
T0H 3G0 Location: Date Reported: Sep 3, 2010
Attn: Vern Howrish LSD: Report Number: 1353725
Sampled By: P.O.:
Company: Acct code:

Reference Number 759963-1


Sample Date
Sample Time
Sample Location
Sample Description Potable H2O / 17.3°C / DI System
Sample Matrix Water
Nominal Detection Guideline Guideline
Analyte Units Result Limit Limit Comments
Physical and Aggregate Properties
Colour Apparent, Potable Colour units <5 5 15 Below AO
Turbidity NTU 0.2 0.1 0.1 Above OG
Routine Water
pH 6.07 6.5 - 8.5 Below AO
Temperature of observed °C 19.7
pH
Electrical Conductivity µS/cm at 25 C 2 1
Calcium Extractable mg/L <0.2 0.2
Magnesium Extractable mg/L <0.2 0.2
Sodium Extractable mg/L <0.4 0.4 200 Below AO
Potassium Extractable mg/L <0.4 0.4
Iron Extractable mg/L <0.01 0.01 0.3 Below AO
Manganese Extractable mg/L <0.005 0.005 0.05 Below AO
Chloride Dissolved mg/L <0.4 0.4 250 Below AO
Fluoride mg/L <0.05 0.05 1.5 Below MAC
Nitrate - N mg/L 0.03 0.01 10 Below MAC
Nitrite - N mg/L <0.005 0.005 1 Below MAC
Nitrate and Nitrite - N mg/L 0.03 0.01 10 Below MAC
Sulfate (SO4) mg/L <0.9 0.9 500 Below AO
Hydroxide mg/L <5 5
Carbonate mg/L <6 6
Bicarbonate mg/L <5 5
P-Alkalinity as CaCO3 mg/L <5 5
T-Alkalinity as CaCO3 mg/L <5 5
Total Dissolved Solids mg/L <1 1 500 Below AO
Hardness as CaCO3 mg/L <1
Ionic Balance % <1

Approved by:
Anthony Neumann, MSc
Laboratory Operations Manager
Terms and Conditions: www.exova.ca/terms&conditions

You might also like