‫ﺍﳉﻤﻬﻮﺭﻳﺔ ﺍﻟﻌﺮﺑﻴﺔ ﺍﻟﺴـﻮﺭﻳﺔ‬

‫ﻭﺯﺍﺭﺓ ﺍﻟﺩﻓﺎﻉ‬ ‫ﻭﺯﺍﺭﺓ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻤﺤﻠﻴﺔ ﻭﺍﻟﺒﻴﺌﺔ‬

‫ﺍﻟﻤﺩﻴﺭﻴﺔ ﺍﻟﻌﺎﻤﺔ ﻟﻠﺩﻓﺎﻉ ﺍﻟﻤﺩﻨﻲ‬

‫ﺘﺼﻤﻴﻡ ﻭﺘﺭﻜﻴﺏ ﺃﻨﻅﻤﺔ ﺍﻹﻁﻔﺎﺀ‬


‫ﺒﺎﺴـﺘﺨﺩﺍﻡ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪CO2‬‬

‫ﺩﻤﺸـﻕ ‪2004‬‬
‫ﻓﻬﺭﺱ ﺍﻟﻤﺤﺘﻭﻴﺎﺕ‬

‫ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ﻓﻲ ﺍﻹﻁﻔﺎﺀ‬


‫‪4‬‬ ‫ﺨﺼﺎﺌﺹ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪..........................................‬‬
‫‪5‬‬ ‫ﺍﻷﺜﺭ ﺍﻟﻔﻴﺯﻴﻭﻟﻭﺠﻲ ﻻﺴـﺘﺨﺩﺍﻡ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪......................‬‬
‫‪6‬‬ ‫‪................................‬‬ ‫ﺸـﺭﻭﻁ ﺍﺴﺘﺨﺩﺍﻡ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ‬
‫‪6‬‬ ‫ﺍﻷﺜﺭ ﺍﻟﺒﻴﺌﻲ ﻻﺴﺘﺨﺩﺍﻡ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪................................‬‬
‫‪6‬‬ ‫‪................................‬‬ ‫ﺍﻟﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﻔﻴﺯﻴﺎﺌﻴﺔ ﻟﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ‬
‫ﺍﻟﻜﺭﺒﻭﻥ‬

‫ﻗﻭﺍﻋﺩ ﻫﺎﻤﺔ‬
‫‪8‬‬ ‫‪..................................................................‬‬ ‫ﻟﻤﺤﺔ ﻋﺎﻤﺔ‬
‫‪10‬‬ ‫‪..................................................................‬‬ ‫ﺘﻌﺎﺭﻴﻑ‬
‫‪11‬‬ ‫ﺘﻌﻠﻴﻤﺎﺕ ﺴﻼﻤﺔ ﺍﻷﺸﺨﺎﺹ ‪...................................................‬‬

‫ﺘﺼﻤﻴﻡ ﻨﻅﺎﻡ ﻋﺎﻤل ﺒﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ‬


‫‪13‬‬ ‫ﻁﺒﻴﻌﺔ ﻭﻤﺘﻁﻠﺒﺎﺕ ﺍﻟﺘﺼﻤﻴﻡ ‪....................................................‬‬
‫‪14‬‬ ‫ﺤﺴـﺎﺏ ﺍﻟﻜﻤﻴﺔ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﻠﻐﺎﺯ ‪..............................................‬‬
‫‪15‬‬ ‫ﺤﺴـﺎﺏ ﺍﻟﻜﻤﻴﺔ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﻠﻐﺎﺯﺍﺕ ﺍﻟﺨﺎﻤﻠﺔ ‪....................................‬‬
‫‪15‬‬ ‫ﺤﺴـﺎﺏ ﺘﺭﻜﻴﺯ ﺍﻟﻐﺎﺯ ﻓﻲ ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﻤﺤﺴﻭﺒﺔ ‪....................................‬‬
‫‪16‬‬ ‫ﻤﻼﺤﻅﺎﺕ ﻫﺎﻤﺔ ‪..............................................................‬‬
‫‪16‬‬ ‫ﺍﺨﺘﻴﺎﺭ ﻤﻌﺎﻤل ﺍﻟﺘﺭﻜﻴﺯ ‪.................................................... KB‬‬
‫‪19‬‬ ‫ﺤﺴـﺎﺏ ﻜﻤﻴﺔ ﺍﻟﻐﺎﺯ ﺍﻟﻭﺍﺠﺏ ﺘﺭﻜﻴﺒﻬﺎ ﻓﻲ ﺍﻟﻨﻅﺎﻡ ‪................................‬‬
‫‪20‬‬ ‫‪..................................................‬‬ ‫ﻜﻤﻴﺔ ﺍﻟﻐﺎﺯ ﺍﻟﻭﺍﺠﺏ ﺘﺨﺯﻴﻨﻬﺎ‬
‫‪20‬‬ ‫ﺘﺨﺯﻴﻥ ﻭﻭﺼل ﺃﺴﻁﻭﺍﻨﺎﺕ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪..........................‬‬
‫‪21‬‬ ‫ﺸﺭﻭﻁ ﻤﻜﺎﻥ ﺘﺨﺯﻴﻥ ﺃﺴﻁﻭﺍﻨﺎﺕ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪......................‬‬
‫‪22‬‬ ‫‪..................................................................‬‬ ‫ﺯﻤﻥ ﺍﻟﻐﻤﺭ‬
‫‪22‬‬ ‫ﺯﻤﻥ ﺍﻹﺒﻘﺎﺀ ‪..................................................................‬‬

‫ﺘﺼﻤﻴﻡ ﺸـﺒﻜﺔ ﺍﻟﺘﻭﺯﻴﻊ‬


‫‪23‬‬ ‫ﺍﻷﻨﺎﺒﻴﺏ ‪......................................................................‬‬
‫‪24‬‬ ‫ﻤﺜﺒﺘﺎﺕ ﺍﻷﻨﺎﺒﻴﺏ ‪............................................................‬‬
‫‪26‬‬ ‫ﺼﻤﺎﻤﺎﺕ ﺍﻟﺘﺤﻜﻡ ‪............................................................‬‬
‫‪27‬‬ ‫ﻓﻭﻫﺎﺕ ﻨﻔﺙ ﺍﻟﻐﺎﺯ ‪............................................................‬‬
‫‪28‬‬ ‫ﺍﺨﺘﺒﺎﺭ ﺍﻟﺸﺒﻜﺔ ‪................................................................‬‬

‫‪2‬‬
‫ﻤﻨﻅﻭﻤﺔ ﺍﻟﺘﺤﻜﻡ ﻭﺍﻹﻨﺫﺍﺭ‬
‫‪29‬‬ ‫‪..............................................................‬‬ ‫ﻨﻅﺎﻡ ﺍﻟﻜﺸـﻑ‬
‫‪31‬‬ ‫ﺠﻬﺎﺯ ﺍﻟﺘﺄﺨﻴﺭ ﺍﻟﺯﻤﻨﻲ ‪..........................................................‬‬
‫‪31‬‬ ‫‪................................................................‬‬ ‫ﺠﻬﺎﺯ ﺍﻹﻨﺫﺍﺭ‬
‫‪32‬‬ ‫ﻜﺒﺴﺎﺕ ﺘﻌﻁﻴل ﺍﻟﻨﻅﺎﻡ ﻴﺩﻭﻴﺎ" ‪....................................................‬‬

‫ﺘﻔﺘﻴـﺵ ﺍﻟﻨﻅﺎﻡ‬
‫‪33‬‬ ‫‪..............................................................‬‬ ‫ﺍﻟﺘﻔﺘﻴﺵ ﺍﻟﻴﻭﻤﻲ‬
‫‪33‬‬ ‫ﺍﻟﺘﻔﺘﻴﺵ ﺍﻷﺴﺒﻭﻋﻲ ‪............................................................‬‬
‫‪33‬‬ ‫ﺍﻟﺘﻔﺘﻴﺵ ﺍﻟﺸﻬﺭﻱ ‪..............................................................‬‬

‫‪34‬‬ ‫ﻤﺨﻁﻁ ﺼﻨﺩﻭﻗﻲ ﻟﻨﻅﺎﻡ ﺇﻁﻔﺎﺀ ﺒﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪....................‬‬

‫‪3‬‬
‫ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻓﻲ ﺍﻹﻁﻔﺎﺀ‬

‫ﻴﺴـﺘﺨﺩﻡ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﺘﺠﺎﺭﻴﺎ" ﻓﻲ ﺃﻨﻅﻤﺔ ﺍﻹﻁﻔﺎﺀ ﺍﻟﺜﺎﺒﺘﺔ‬


‫ﻜﻭﺴﻴﻁ ﺇﻁﻔﺎﺀ ﻨﻅﻴﻑ ﻤﻨﺫ ﺃﻜﺜﺭ ﻤﻥ ﺨﻤﺴـﻴﻥ ﻋﺎﻤﺎ"‪ .‬ﻭﻴﻌﺘﻤﺩ ﺘﺼﻤﻴﻡ ﺃﻨﻅﻤﺔ ﻏﺎﺯ‬
‫ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻋﻠﻰ ﺇﻴﺼﺎل ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﺤﺠﻤﻲ ﻟﻬﺫﻩ ﺍﻟﻐﺎﺯ ﺃﺜﻨﺎﺀ ﻤﻜﺎﻓﺤﺔ‬
‫ﺍﻟﺤﺭﻴﻕ ﺇﻟﻰ ﻨﺴﺒﺔ ﻤﻥ ﺤﺠﻡ ﺍﻟﻤﻜﺎﻥ ﺒﺤﻴﺙ ﻴﺅﺩﻱ ﺇﻟﻰ ﺨﻔﺽ ﺘﺭﻜﻴﺯ ﺍﻷﻭﻜﺴﺠﻴﻥ‬
‫ﺍﻟﻤﺘﺎﺡ ﻓﻲ ﺫﻟﻙ ﺍﻟﻤﻜﺎﻥ ﻤﻥ )ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﻁﺒﻴﻌﻲ ﻓﻲ ﺍﻟﻬﻭﺍﺀ( ‪ 20.95‬ﻟﻴﺘﺭﺍﻭﺡ ﺘﺭﻜﻴﺯ‬
‫ﺍﻷﻭﻜﺴﺠﻴﻥ ﺍﻟﺤﺠﻤﻲ ﻤﺎ ﺒﻴﻥ ‪ %10‬ﻭ ‪ ،%12‬ﺤﻴﺙ ﻤﻥ ﺍﻟﻤﻌﺭﻭﻑ ﺃﻨﻪ ﻻﺴﺘﻤﺭﺍﺭ‬
‫ﺍﺸﺘﻌﺎل ﺍﻟﺤﺭﻴﻕ ﻴﺠﺏ ﺃﻥ ﻴﻜﻭﻥ ﺘﺭﻜﻴﺯ ﺍﻷﻭﻜﺴﺠﻴﻥ ﺍﻟﺤﺠﻤﻲ ﻋﻠﻰ ﺍﻷﻗل ﻤﻥ ‪%12‬‬
‫ﺤﺘﻰ ‪.%14‬‬

‫ﺨﺼﺎﺌﺹ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪:CO2‬‬

‫ﺒﺸﻜل ﻋﺎﻡ ﻴﺸـﺘﺭﻙ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﺒﻌﺩﺩ ﻤﻥ ﺍﻟﺨﺼﺎﺌﺹ ﻤﻊ‬
‫ﺒﺎﻗﻲ ﺍﻟﻐﺎﺯﺍﺕ ﺍﻟﺨﺎﻤﻠﺔ ﻭﻴﻌﺘﺒﺭ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻏﻴﺭ ﻤﻭﺼل‬
‫ﻟﻠﻜﻬﺭﺒﺎﺀ ﻭﻴﻭﺼﻑ ﺒﺄﻨﻬﺎ ﻤﻥ ﻭﺴﺎﺌﻁ ﺍﻹﻁﻔﺎﺀ ﺍﻟﻨﻅﻴﻔﺔ ﻭﻴﺸﺘﺭﻙ ﻤﻊ ﺒﺎﻗﻲ ﻭﺴﺎﺌﻁ‬
‫ﺍﻹﻁﻔﺎﺀ ﻓﻲ ﺍﻟﻌﺩﻴﺩ ﻤﻥ ﺍﻟﻤﻴﺯﺍﺕ ﺍﻟﻌﺎﻤﺔ‪ ،‬ﻭﻟﻜﻨﻪ ﻴﺨﺘﻠﻑ ﻋﻥ ﻤﻌﻅﻤﻬﺎ ﻓﻲ ﺍﻟﻤﻭﺍﺼﻔﺎﺕ‬
‫ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬
‫‪ .1‬ﺘﺴﺘﺨﺩﻡ ﺍﻷﻨﻅﻤﺔ ﺍﻟﻌﺎﻤﻠﺔ ﺒﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻤﺨﻔﺽ‬
‫ﻀﻐﻁ ﻋﻨﺩ ﺃﻭ ﻗﺭﻴﺏ ﺠﺩﺍ" ﻤﻥ ﺼﻤﺎﻡ ﺍﻟﺘﺤﻜﻡ ﻤﻤﺎ ﻴﺅﺩﻱ ﺇﻟﻰ ﺍﻨﻌﺩﺍﻡ‬
‫ﺍﻟﺤﺎﺠﺔ ﻻﺴﺘﺨﺩﺍﻡ ﺃﻨﺎﺒﻴﺏ ﺫﺍﺕ ﺠﺩﺭﺍﻥ ﺴﻤﻴﻜﺔ ﻓﻲ ﺍﻟﻨﻅﺎﻡ‪.‬‬
‫‪ .2‬ﻴﺤﺘﺎﺝ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻓﻲ ﺍﻟﻨﻅﺎﻡ ﻋﻨﺩ ﺇﺨﻤﺎﺩﻩ‬
‫ﻟﻠﺤﺭﻴﻕ ﺇﻟﻰ ﻭﻗﺕ ﻤﻥ ﺩﻗﻴﻘﺔ ﺇﻟﻰ ﺩﻗﻴﻘﺘﻴﻥ ﻟﻠﻭﺼﻭل ﺇﻟﻰ ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﻼﺯﻡ‬
‫ﻓﻲ ﺍﻟﻤﻜﺎﻥ ﻭﺒﺎﻟﺘﺎﻟﻲ ﻓﺈﻨﻪ ﻴﻨﺼﺢ ﺒﻌﺩﻡ ﺍﺴﺘﺨﺩﺍﻤﻪ ﻓﻲ ﺍﻷﻤﻜﻨﺔ ﺍﻟﺘﻲ‬
‫ﺘﺘﻁﻠﺏ ﺯﻤﻨﺎ" ﺃﻗﺼﺭ ﻟﻠﺴﻴﻁﺭﺓ ﻋﻠﻰ ﺍﻟﺤﺭﻴﻕ‪.‬‬
‫‪ .3‬ﻻ ﻴﺘﻔﺎﻋل ﻭﻻ ﻴﺸﻜل ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﺃﻱ ﻤﺭﻜﺒﺎﺕ‬
‫ﺃﺨﺭﻯ ﺒﺴﺒﺏ ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﻨﺎﺠﻤﺔ ﻋﻥ ﺍﻟﺤﺭﻴﻕ‪.‬‬
‫‪ .4‬ﻜﻠﻔﺔ ﺃﻨﻅﻤﺔ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﺃﺩﻨﻰ ﻤﻥ ﺒﺎﻗﻲ ﺃﻨﻅﻤﺔ‬
‫ﺍﻹﻁﻔﺎﺀ ﺍﻟﻌﺎﻤﻠﺔ ﺒﻭﺴـﺎﺌﻁ ﺃﺨﺭﻯ‪.‬‬
‫‪ .5‬ﻴﻤﻜﻥ ﺘﺨﺯﻴﻨﻪ ﻜﺴـﺎﺌل ﻓﻲ ﺃﺴـﻁﻭﺍﻨﺎﺕ ﺘﺤﺕ ﻀﻐﻁ ‪ 60‬ﺒﺎﺭ‪.‬‬
‫‪ .6‬ﻤﺘﻭﻓﺭ ﻓﻲ ﺍﻷﺴـﻭﺍﻕ ﺒﻜﻠﻑ ﻤﻨﺨﻔﻀﺔ ﻨﺴـﺒﻴﺎ"‪.‬‬

‫‪4‬‬
‫ﺃﺜﺭ ﺍﺴﺘﺨﺩﺍﻡ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻋﻠﻰ ﺍﻹﻨﺴﺎﻥ‪:‬‬

‫ﺇﻥ ﺍﻷﺜﺭ ﺍﻟﻤﻤﻴﺕ ﺍﻟﻨﺎﺠﻡ ﻋﻥ ﺍﺴﺘﺨﺩﺍﻡ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻭﻴﺘﺄﺘﻰ ﻤﻥ‬
‫ﺘﺄﺜﻴﺭﺍﺘﻪ ﺍﻻﺨﺘﻨﺎﻗﻴﺔ ﺍﻟﻌﺎﻟﻴﺔ ﺠﺩﺍ" ﺤﺘﻰ ﻓﻲ ﺍﻟﺘﺭﺍﻜﻴﺯ ﺍﻟﻤﻨﺨﻔﻀﺔ‪.‬‬

‫ﻭﻴﻭﻀﺢ ﺍﻟﺠﺩﻭل ﺍﻟﺘﺎﻟﻲ ﺘﺄﺜﻴﺭ ﺯﻴﺎﺩﺓ ﺍﻟﻨﺴـﺒﺔ ﺍﻟﺤﺠﻤﻴﺔ ﻟﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ‬
‫‪ CO2‬ﻓﻲ ﺍﻟﻤﻜﺎﻥ ﻋﻠﻰ ﺍﻹﻨﺴـﺎﻥ‪:‬‬

‫ﺃﺜﺭ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪CO2‬‬ ‫ﺘﺭﻜﻴﺯ ﺍﻷﻭﻜﺴﺠﻴﻥ‬ ‫ﺘﺭﻜﻴﺯ ‪CO2‬‬
‫ﻋﻠﻰ ﺍﻹﻨﺴﺎﻥ‬ ‫ﺍﻟﺤﺠﻤﻲ ‪%‬‬ ‫ﺍﻟﺤﺠﻤﻲ ‪%‬‬
‫ﻏﻴﺭ ﻀﺎﺭ ﺒﺎﻹﻨﺴـﺎﻥ‬ ‫‪20.5‬‬ ‫‪2.5‬‬
‫ﺴﺭﻋﺔ ﻓﻲ ﺍﻟﺘﻨﻔﺱ ﻭﺍﻨﺨﻔﺎﺽ ﻓﻲ ﺍﻟﻨﺒﺽ‬
‫ﻤﻊ ﺃﻟﻡ ﻓﻲ ﺍﻟﺭﺃﺱ ﻤﻊ ﺒﺩﺀ ﺍﻹﺤﺴﺎﺱ ﺒﻔﻘﺩﺍﻥ‬ ‫‪20.4‬‬ ‫‪3‬‬
‫ﺍﻟﻭﻋﻲ ﻭﻴﺸﻜل ﺨﻁﺭﺍ" ﻋﻠﻰ ﺍﻟﺤﻴﺎﺓ ﻤﻥ‬ ‫‪20.2‬‬ ‫‪4‬‬
‫ﻨﺼﻑ ﺴﺎﻋﺔ ﻭﺤﺘﻰ ﺍﻟﺴﺎﻋﺔ‬
‫ﺴﺭﻋﺔ ﻓﻲ ﺍﻟﺘﻨﻔﺱ ﺒﺸﻜل ﻭﺍﻀﺢ‪ ،‬ﺇﻤﻜﺎﻨﻴﺔ‬ ‫‪20.1‬‬ ‫‪4.5‬‬
‫ﺍﻟﻭﻓﺎﺓ ﺨﻼل ﻨﺼﻑ ﺴﺎﻋﺔ‬ ‫‪19.7‬‬ ‫‪6.1‬‬
‫ﻏﻴﺎﺏ ﺴـﺭﻴﻊ ﻋﻥ ﺍﻟﻭﻋﻲ ﻭﻭﻓﺎﺓ ﻤﺅﻜﺩﺓ‬ ‫‪19.3‬‬ ‫‪8‬‬
‫ﺒﺴﺒﺏ ﺘﺭﺍﻜﻡ ﺍﻟﻐﺎﺯ ﻓﻲ ﺍﻟﺩﻡ‬ ‫‪18.9‬‬ ‫‪10‬‬
‫‪16.8‬‬ ‫‪20‬‬
‫‪16‬‬ ‫‪24‬‬
‫‪12‬‬ ‫‪43‬‬
‫‪14‬‬ ‫‪33‬‬
‫ﺸـﻠل ﻓﻲ ﺍﻷﺠﻬﺯﺓ ﺍﻟﺤﻴﻭﻴﺔ ﻭﻭﻓﺎﺓ ﻓﻲ‬
‫‪9‬‬ ‫‪57‬‬
‫ﻏﻀﻭﻥ ﺜﻭﺍﻥ ﻤﻌﺩﻭﺩﺓ‬
‫‪10‬‬ ‫‪52‬‬
‫‪6‬‬ ‫‪71‬‬
‫ﺃﻗل ﻤﻥ ‪8‬‬ ‫ﺃﻜﺜﺭ ﻤﻥ ‪71‬‬

‫‪5‬‬
‫ﺸـﺭﻭﻁ ﺍﺴـﺘﺨﺩﺍﻡ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪:CO2‬‬

‫ﺇﻥ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻴﺨﻀﻊ ﺒﺸـﻜل ﻋﺎﻡ ﻓﻲ ﺍﺨﺘﻴﺎﺭﻩ ﻭﻁﺭﻕ‬
‫ﺍﺴـﺘﺨﺩﺍﻤﻪ ﺇﻟﻰ ﺸـﺭﻭﻁ ﺼﺎﺭﻤﺔ ﺘﺤﻜﻤﻬﺎ ﻤﺠﻤﻭﻋﺔ ﻤﻥ ﺍﻟﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﻌﺎﻟﻤﻴﺔ‬
‫ﺍﻟﻤﺘﺸـﺎﺒﻬﺔ ﺍﻟﺼﺎﺩﺭﺓ ﻋﻥ ﺍﻟﻬﻴﺌﺎﺕ ﺍﻟﺩﻭﻟﻴﺔ ﻨﺫﻜﺭ ﻤﻨﻬﺎ‪:‬‬

‫ﺭﻗﻡ ﺍﻟﺘﻭﺼﻴﻑ‬ ‫ﺍﺴـﻡ ﺍﻟﺠﻬﺔ‬


‫‪VDS 2093‬‬ ‫‪VDS‬‬
‫‪4007‬‬ ‫‪CEA‬‬
‫‪6183‬‬ ‫‪ISO‬‬
‫‪12‬‬ ‫‪NFPA‬‬

‫ﺍﻷﺜﺭ ﺍﻟﺒﻴﺌﻲ ﻻﺴﺘﺨﺩﺍﻡ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪:CO2‬‬

‫ﻻ ﻴﺴﺒﺏ ﺍﺴﺘﺨﺩﺍﻡ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﺃﻱ ﺃﺜﺭ ﺴﻠﺒﻲ ﻋﻠﻰ ﺍﻟﺒﻴﺌﺔ ﻤﻥ‬
‫ﻨﺎﺤﻴﺔ ﺍﺴﺘﻨﻔﺎﺩ ﺍﻷﻭﺯﻭﻥ ﻭﻟﻜﻨﻪ ﻴﻌﺘﺒﺭ ﺫﺍ ﺃﺜﺭ ﺴـﻠﺒﻲ ﻋﻠﻰ ﻅﺎﻫﺭﺓ ﺍﻻﺤﺘﺒﺎﺱ‬
‫ﺍﻟﺤﺭﺍﺭﻱ‪.‬‬

‫ﺍﻟﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﻔﻴﺯﻴﺎﺌﻴﺔ ﻟﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪:CO2‬‬

‫ﺇﻥ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻏﺎﺯ ﻋﺩﻴﻡ ﺍﻟﻠﻭﻥ ﻭﺍﻟﺭﺍﺌﺤﺔ ﻏﻴﺭ ﻓﻌﺎل ﻜﻴﻤﻴﺎﺌﻴﺎ"‬
‫)ﻏﻴﺭ ﻤﺴـﺒﺏ ﻟﻠﺼﺩﺃ( ﻭﻜﺜﺎﻓﺘﻪ ﺃﻜﺒﺭ ﻤﻥ ﻜﺜﺎﻓﺔ ﺍﻟﻬﻭﺍﺀ ﺒﺤﻭﺍﻟﻲ ‪ %50‬ﻭﻴﺨﺯﻥ ﻋﺎﺩﺓ‬
‫ﺒﺸـﻜل ﺴـﺎﺌل ﺘﺤﺕ ﺍﻟﻀﻐﻁ‪.‬‬

‫ﻭﻴﺒﻴﻥ ﺍﻟﻤﺨﻁﻁ ﺍﻟﻠﻭﻏﺎﺭﻴﺘﻤﻲ ﺍﻟﺘﺎﻟﻲ ﺤﺎﻟﺔ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻜﻌﻼﻗﺔ‬
‫ﺒﻴﻥ ﺍﻟﻀﻐﻁ ﻭﺩﺭﺠﺔ ﺍﻟﺤﺭﺍﺭﺓ‪:‬‬

‫‪6‬‬
‫ﻓﻲ ﺤﻴﻥ ﺃﻥ ﺍﻟﻘﻴﻡ ﺍﻟﻨﻭﻋﻴﺔ ﻟﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻋﻨﺩ ﺍﻟﺸـﺭﻭﻁ‬
‫ﺍﻟﻨﻅﺎﻤﻴﺔ ﻫﻲ‪:‬‬

‫ﺍﻟﻘﻴﻤﺔ‬ ‫ﺍﻟﻭﺤﺩﺓ‬ ‫ﺍﻟﻤﻭﺍﺼﻔﺔ‬


‫‪0.506‬‬ ‫ﻡ‪/3‬ﻜﻎ‬ ‫ﺍﻟﺤﺠﻡ ﺍﻟﻨﻭﻋﻲ ‪v‬‬
‫‪3‬‬
‫‪1.977‬‬ ‫ﻜﻎ‪/‬ﻡ‬ ‫ﻜﺜﺎﻓﺔ ﺍﻟﻐﺎﺯ ‪ρ‬‬

‫‪7‬‬
‫ﻗـﻭﺍﻋـﺩ ﻫـﺎﻤـﺔ‬

‫ﺘﻡ ﻭﻀﻊ ﻫﺫﺍ ﺍﻟﻜﺘﻴﺏ ﻷﻨﻅﻤﺔ ﺍﻹﻁﻔﺎﺀ ﻋﻠﻰ ﺃﺴـﺎﺱ ﺘﺼﻤﻴﻡ ﻭﺘﺭﻜﻴﺏ ﺃﻨﻅﻤﺔ ﻏﺎﺯ‬
‫ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻭﻤﻥ ﺜﻡ ﻴﻤﻜﻥ ﺍﻋﺘﻤﺎﺩ ﺃﻱ ﻤﻥ ﺍﻟﻐﺎﺯﺍﺕ ﺍﻟﺨﺎﻤﻠﺔ‬
‫ﺒﺎﺴـﺘﺨﺩﺍﻡ ﻤﻌﺎﻤﻼﺕ ﺘﺼﺤﻴﺢ ﺨﺎﺼﺔ‪.‬‬

‫ﻴﻤﻜﻥ ﺃﻥ ﻨﺴـﺘﺨﺩﻡ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻟﻺﻁﻔﺎﺀ ﻓﻲ ﺤﺎل ﺤﻤﺎﻴﺔ ﺃﻱ‬
‫ﻤﻥ ﺍﻟﻤﻭﺍﺩ ﻭﺍﻷﻤﺎﻜﻥ ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬

‫ﺍﻟﻤﻭﺍﺩ ﺍﻟﺴـﺎﺌﻠﺔ ﺍﻟﻘﺎﺒﻠﺔ ﻟﻼﺸـﺘﻌﺎل‪.‬‬ ‫•‬


‫ﺍﻟﻤﻭﺍﺩ ﺍﻟﻐﺎﺯﻴﺔ ﺍﻟﻘﺎﺒﻠﺔ ﻟﻼﺸـﺘﻌﺎل ﺒﺸـﺭﻁ ﺃﻥ ﻻ ﺘﺸـﻜل ﻫﺫﻩ ﺍﻟﻤﻭﺍﺩ ﻓﻲ‬ ‫•‬
‫ﻅﺭﻭﻑ ﺍﻟﺤﺭﻴﻕ ﻭﻭﺠﻭﺩ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ﺃﻱ ﻤﺭﻜﺒﺎﺕ ﺃﺨﺭﻯ‪.‬‬
‫ﻗﺎﻋﺎﺕ ﺍﻟﺘﺠﻬﻴﺯﺍﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻭﺍﻹﻟﻜﺘﺭﻭﻨﻴﺔ ﻭﻟﻭﺤﺎﺕ ﺍﻟﺘﺤﻜﻡ‪.‬‬ ‫•‬
‫ﺍﻟﻤﻭﺍﺩ ﺍﻟﺼﻠﺒﺔ ﺍﻟﻘﺎﺒﻠﺔ ﻟﻼﺸـﺘﻌﺎل ﻋﻠﻰ ﺃﻥ ﻴﻼﺤﻅ ﻓﻲ ﺍﻟﺤﺴـﺎﺏ ﻜﺜﺎﻓﺔ ﺍﻟﻐﺎﺯ‬ ‫•‬
‫ﺍﻟﻼﺯﻤﺔ ﻭﺯﻤﻥ ﺍﻹﺒﻘﺎﺀ ﺍﻟﻼﺯﻡ‪.‬‬
‫ﺍﻷﻤﺎﻜﻥ ﺍﻟﺤﺎﻭﻴﺔ ﻋﻠﻰ ﺘﺠﻬﻴﺯﺍﺕ ﺘﻜﻨﻭﻟﻭﺠﻴﺎ ﺍﻟﻤﻌﻠﻭﻤﺎﺕ )ﻜﻤﺒﻴﻭﺘﺭﺍﺕ‪ ،‬ﻗﺎﻋﺎﺕ‬ ‫•‬
‫ﺇﺩﺨﺎل‪ ،‬ﻏﺭﻑ ﺍﻷﻨﻅﻤﺔ ﺍﻟﻤﺭﻜﺯﻴﺔ ﻟﻤﻌﺎﻟﺠﺔ ﺍﻟﺒﻴﺎﻨﺎﺕ‪.(... ،‬‬
‫ﻤﻨﺸـﺂﺕ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ ﻭﻏﺭﻑ ﺍﻷﻻﺕ ‪.‬‬ ‫•‬

‫ﺇﻥ ﺍﻟﻤﻌﺭﻓﺔ ﺍﻟﺠﻴﺩﺓ ﻭﺍﻟﺨﺒﺭﺓ ﺘﺴـﻤﺤﺎﻥ ﻓﻲ ﺒﻌﺽ ﺍﻷﺤﻴﺎﻥ ﺒﺎﺴـﺘﺨﺩﺍﻡ ﻫﺫﺍ ﺍﻟﻨﻭﻉ ﻤﻥ‬
‫ﺍﻷﻨﻅﻤﺔ ﻓﻲ ﺃﻤﺎﻜﻥ ﺃﺨﺭﻯ ﻤﺨﺘﻠﻔﺔ ﻋﻥ ﺘﻠﻙ ﺍﻷﻤﺎﻜﻥ ﺍﻟﻤﺫﻜﻭﺭﺓ ﺃﻋﻼﻩ ﻭﻟﻜﻥ ﺫﻟﻙ‬
‫ﺒﺤﺎﺠﺔ ﺇﻟﻰ ﻋﻨﺎﻴﺔ ﺨﺎﺼﺔ ﻓﻴﻤﺎ ﻴﺨﺘﺹ ﺒﺘﺭﻜﻴﺯ ﺍﻟﻐﺎﺯ ﻭﺯﻤﻥ ﺍﻻﻨﻔﻼﺕ‪.‬‬

‫ﻟﻤﺤﺔ ﻋﺎﻤﺔ‪:‬‬

‫ﺇﻥ ﺍﻟﻤﻭﺍﺼﻔﺎﺕ ﻭﺍﻹﺠﺭﺍﺀﺍﺕ ﺍﻟﻤﺫﻜﻭﺭﺓ ﻓﻲ ﻫﺫﺍ ﺍﻟﻔﺼل ﺘﻔﺭﺽ ﻤﺘﻁﻠﺒﺎﺕ ﺨﺎﺼﺔ‬


‫ﻟﺘﺼﻤﻴﻡ ﻭﺘﺭﻜﻴﺏ ﻭﺼﻴﺎﻨﺔ ﺃﻨﻅﻤﺔ ﺍﻟﻐﻤﺭ ﺍﻟﻜﻠﻲ ﺍﻟﻌﺎﻤﻠﺔ ﺒﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ‬
‫‪ CO2‬ﺍﻟﻤﺴـﺘﺨﺩﻤﺔ ﻓﻲ ﺍﻷﺒﻨﻴﺔ ﻭﺍﻟﻤﻨﺸـﺂﺕ ﺍﻟﺼﻨﺎﻋﻴﺔ ﻭﻜﺫﻟﻙ ﻟﺘﻭﺴـﻴﻊ ﺃﻭ ﺘﻌﺩﻴل‬
‫ﻨﻅﺎﻡ ﺇﻁﻔﺎﺀ ﻤﻭﺠﻭﺩ‪.‬‬

‫‪8‬‬
‫ﻤﻥ ﺍﻟﻤﻔﻴﺩ ﺍﻟﺘﺄﻜﻴﺩ ﺒﺄﻥ ﺠﻤﻴﻊ ﻤﺘﻁﻠﺒﺎﺕ ﺘﺼﻤﻴﻡ ﺍﻷﻨﻅﻤﺔ ﺍﻟﻤﺫﻜﻭﺭﺓ ﻓﻲ ﻫﺫﺍ ﺍﻟﻔﺼل‬
‫ﺘﺸـﻜل ﺍﻟﺤﺩ ﺍﻷﺩﻨﻰ ﻟﻤﻜﻭﻨﺎﺕ ﺍﻟﻨﻅﺎﻡ ﺍﻟﺘﻲ ﻻ ﻴﻤﻜﻥ ﺘﺠﺎﻭﺯﻫﺎ‪ ،‬ﺤﻴﺙ ﻴﺒﻘﻰ ﻤﻭﻀﻭﻉ‬
‫ﺍﺨﺘﻴﺎﺭ ﻁﺭﻴﻘﺔ ﻋﻤل ﻨﻅﺎﻡ ﺍﻹﻁﻔﺎﺀ ﻴﺩﻭﻴﺎ" ﺃﻭ ﺃﻭﺘﻭﻤﺎﺘﻴﻜﻴﺎ" ﻭﻴﻔﻀل ﺍﺴـﺘﺨﺩﺍﻡ ﺍﻟﻨﻅﺎﻡ‬
‫ﺍﻷﻭﺘﻭﻤﺎﺘﻴﻜﻲ‪.‬‬

‫ﺇﻥ ﻤﺒﺩﺃ ﻋﻤل ﺃﻨﻅﻤﺔ ﺍﻹﻁﻔﺎﺀ ﺍﻟﻌﺎﻤﻠﺔ ﺒﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻫﻭ ﺘﺨﻔﻴﺽ‬
‫ﻨﺴـﺒﺔ ﺍﻷﻭﻜﺴـﺠﻴﻥ ﺍﻟﻤﺘﺎﺡ ﻓﻲ ﺍﻟﻤﻜﺎﻥ ﻤﻤﺎ ﻴﺅﺩﻱ ﺇﻟﻰ ﻋﺯل ﺃﺤﺩ ﻋﻨﺎﺼﺭ ﻤﺜﻠﺙ‬
‫ﺍﻟﺤﺭﻴﻕ ﺍﻷﺴـﺎﺴـﻴﺔ ﻭﺫﻟﻙ ﻓﻲ ﻤﺭﺤﻠﺔ ﻤﺘﻘﺩﻤﺔ ﻤﻥ ﺒﺩﺀ ﺍﻟﺤﺭﻴﻕ‪ ،‬ﻭﻓﻲ ﺒﻌﺽ‬
‫ﺍﻟﺤﺎﻻﺕ ﻴﻌﻤﺩ ﺇﻟﻰ ﺍﺴـﺘﺨﺩﺍﻡ ﻫﺫﻩ ﺍﻷﻨﻅﻤﺔ ﺒﺎﻟﺘﻭﺍﺯﻱ ﻤﻊ ﺃﻨﻅﻤﺔ ﺃﺨﺭﻯ ﻭﺫﻟﻙ ﺘﺒﻌﺎ"‬
‫ﻟﻨﻭﻉ ﺍﻟﺨﻁﺭ ﺃﻭ ﺍﻟﻤﺎﺩﺓ ﺍﻟﻤﺤﺘﺭﻗﺔ‪.‬‬

‫ﻴﻤﻜﻥ ﺍﺴـﺘﺨﺩﺍﻡ ﺃﻨﻅﻤﺔ ﺍﻹﻁﻔﺎﺀ ﺍﻟﻌﺎﻤﻠﺔ ﺒﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻓﻲ ﺍﻟﻌﺩﻴﺩ‬
‫ﻤﻥ ﺍﻷﻤﺎﻜﻥ‪ ،‬ﻭﻟﻜﻥ ﻴﻤﻨﻊ ﺍﺴـﺘﺨﺩﺍﻤﻬﺎ ﻓﻲ ﻜل ﻤﻥ ﺍﻷﻤﺎﻜﻥ ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬

‫ﺃﻤﺎﻜﻥ ﺘﺨﺯﻴﻥ ﺍﻟﻤﻭﺍﺩ ﺍﻟﻜﻴﻤﻴﺎﺌﻴﺔ ﺍﻟﻤﻭﻟﺩﺓ ﻟﻸﻭﻜﺴـﺠﻴﻥ ﻜﻨﻴﺘﺭﺍﺕ ﺍﻟﺴﻴﻠﻴﻠﻭﺯ‪.‬‬ ‫•‬


‫ﺃﻤﻜﻨﺔ ﺘﺨﺯﻴﻥ ﺍﻟﺨﻼﺌﻁ ﺍﻟﻜﻴﻤﻴﺎﺌﻴﺔ ﺍﻟﻤﺅﻜﺴـﺩﺓ ﻜﻜﻠﻭﺭﺍﺕ ﺍﻟﺼﻭﺩﻴﻭﻡ‪.‬‬ ‫•‬
‫ﺃﻤﺎﻜﻥ ﺘﺨﺯﻴﻥ ﺍﻟﻤﻭﺍﺩ ﺍﻟﻜﻴﻤﻴﺎﺌﻴﺔ ﺍﻟﻘﺎﺒﻠﺔ ﻟﻠﺘﻔﻜﻙ ﺍﻟﺒﻴﺭﻭﻜﺴـﻴﺩﺍﺕ ﺍﻟﻌﻀﻭﻴﺔ‪.‬‬ ‫•‬
‫ﺃﻤﺎﻜﻥ ﺘﺨﺯﻴﻥ ﺍﻟﻤﻭﺍﺩ ﺍﻟﻨﺸـﻁﺔ ﻜﻴﻤﻴﺎﺌﻴﺎ" ﻜﺎﻟﺼﻭﺩﻴﻭﻡ ﻭﺍﻟﺒﻭﺘﺎﺴـﻴﻭﻡ‪.‬‬ ‫•‬
‫ﺃﻤﺎﻜﻥ ﺘﺨﺯﻴﻥ ﺍﻟﻤﻭﺍﺩ ﺍﻟﺼﻠﺒﺔ ﺍﻟﺘﻲ ﻗﺩ ﻴﺘﺤﻭل ﻓﻴﻬﺎ ﺍﻟﺤﺭﻴﻕ ﺇﻟﻰ ﺤﺭﻴﻕ ﻜﺎﻤﻥ‬ ‫•‬
‫ﻜﺎﻷﺨﺸـﺎﺏ‪.‬‬

‫‪9‬‬
‫ﺘﻌﺎﺭﻴﻑ‪:‬‬

‫ﺠﻬﺎﺯ ﺍﻹﻨﺫﺍﺭ ‪ :Alarm Device‬ﺠﻬﺎﺯ ﻴﺼﺩﺭ ﺘﺤﺫﻴﺭﺍ" ﺼﻭﺘﻴﺎ" ﺃﻭ ﺒﺼﺭﻴﺎ"‬ ‫•‬


‫ﺃﻭ ﻤﺸـﺘﺭﻜﺎ" ﻤﻨﺒﻬﺎ" ﺇﻟﻰ ﺤﺩﻭﺙ ﺤﺭﻴﻕ ﻓﻲ ﺍﻟﻤﻜﺎﻥ‪.‬‬
‫ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﻤﺤﺴﻭﺒﺔ ‪ :Calculation Zone‬ﻭﻫﻲ ﺍﻟﺤﻴﺯ ﻤﻥ ﺍﻟﻔﺭﺍﻍ ﺍﻟﺫﻱ‬ ‫•‬
‫ﺘﺠﺭﻯ ﻋﻠﻴﻪ ﺍﻟﺤﺴـﺎﺒﺎﺕ ﺍﻟﻜﻤﻴﺔ ﻟﺘﺼﻤﻴﻡ ﺍﻟﻨﻅﺎﻡ ﺒﺸـﻜل ﻤﺴـﺘﻘل‪.‬‬
‫ﺠﻬﺎﺯ )ﻨﻅﺎﻡ( ﺍﻟﺘﺤﻜﻡ ‪ :Control (System) Device‬ﺠﻬﺎﺯ ﻴﻌﻤل ﻋﻠﻰ‬ ‫•‬
‫ﺘﻔﻌﻴل ﺠﻬﺎﺯ ﺍﻹﻨﺫﺍﺭ ﻭﻴﺘﺤﻜﻡ ﺒﻌﻤﻠﻴﺔ ﺍﻟﻐﻤﺭ ﺍﻟﻜﻠﻲ ﺒﺎﻟﻐﺎﺯ ﻜﻤﺎ ﻗﺩ ﻴﻌﻤل ﻋﻠﻰ‬
‫ﺘﻔﻌﻴل ﺍﻟﺘﺤﻜﻡ ﺒﺎﻟﺘﺠﻬﻴﺯﺍﺕ ﺍﻹﻀﺎﻓﻴﺔ ﺍﻷﺨﺭﻯ )ﺃﺒﻭﺍﺏ ﺃﻭﺘﻭﻤﺎﺘﻴﻜﻴﺔ‪ ،‬ﺇﻨﺫﺍﺭ‬
‫ﻤﺤﻠﻲ‪(... ،‬‬
‫ﺍﻟﺤﺭﻴﻕ ﺍﻟﻜﺎﻤﻥ ‪ :Deep-seated Fire‬ﻫﻭ ﺍﻟﺤﺭﻴﻕ ﺍﻟﺫﻱ ﻗﺩ ﻴﺤﺩﺙ ﻟﺒﻌﺽ‬ ‫•‬
‫ﺍﻟﻤﻭﺍﺩ ﺍﻟﺼﻠﺒﺔ ﺍﻟﺘﻲ ﻻ ﺘﻤﻜﻥ ﻭﺴـﻴﻁ ﺍﻹﻁﻔﺎﺀ ﻏﻴﺭ ﺍﻟﻤﻨﺎﺴـﺏ ﻤﻥ ﺍﻟﻭﺼﻭل‬
‫ﺇﻟﻰ ﺍﻟﺤﺭﻴﻕ‪.‬‬
‫ﺯﻤﻥ ﺍﻟﺘﺄﺨﻴﺭ‪ :‬ﻫﻭ ﺍﻟﻤﺩﺓ ﺍﻟﺯﻤﻨﻴﺔ ﺍﻟﻤﻀﺒﻭﻁﺔ ﻤﺴـﺒﻘﺎ" ﺒﻴﻥ ﺒﺩﺀ ﺘﻔﻌﻴل ﺠﻬﺎﺯ‬ ‫•‬
‫)ﻨﻅﺎﻡ( ﺍﻟﺘﺤﻜﻡ ﻭﻋﻤﻠﻴﺔ ﺘﺤﺭﻴﺭ ﻏﺎﺯ ﺍﻹﻁﻔﺎﺀ‪.‬‬
‫ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﺘﺼﻤﻴﻤﻲ ‪ :Design Concentration‬ﻫﻭ ﺍﻟﺘﺭﻜﻴﺯ ﺍﻷﺼﻐﺭﻱ‬ ‫•‬
‫ﺍﻟﻭﺍﺠﺏ ﺘﺤﻘﻴﻘﻪ ﻟﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ﻓﻲ ﺍﻟﻤﻜﺎﻥ ﻋﻨﺩ ﺘﺤﺭﻴﺭ ﺍﻟﻐﺎﺯ‪.‬‬
‫ﺍﻟﻜﻤﻴﺔ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ‪ :Design Quantity‬ﻫﻲ ﻜﻤﻴﺔ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ‬ ‫•‬
‫ﺍﻟﻜﺭﺒﻭﻥ ﺍﻷﺼﻐﺭﻴﺔ ﺍﻟﺘﻲ ﻴﺠﺏ ﺘﺤﺭﻴﺭﻫﺎ ﻟﻠﻭﺼﻭل ﺇﻟﻰ ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﺘﺼﻤﻴﻤﻲ‬
‫ﻓﻲ ﺍﻟﻤﻜﺎﻥ ﻋﻨﺩ ﺘﺤﺭﻴﺭ ﺍﻟﻐﺎﺯ‪.‬‬
‫ﺯﻤﻥ ﺍﻟﻐﻤﺭ ‪ :Discharge Time‬ﻫﻭ ﺍﻟﻔﺘﺭﺓ ﺍﻟﺯﻤﻨﻴﺔ ﺍﻟﻼﺯﻤﺔ ﻟﺘﺤﺭﻴﺭ ﺍﻟﻜﻤﻴﺔ‬ ‫•‬
‫ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻤﻥ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ‪.‬‬
‫ﻜﺒﺴـﺔ ﺍﻟﻁﻭﺍﺭﻯﺀ ‪ :Emergency Triggering Device‬ﻭﻫﻲ ﺠﻬﺎﺯ‬ ‫•‬
‫ﺘﺸـﻐﻴل ﻨﻅﺎﻡ ﺍﻹﻁﻔﺎﺀ ﻴﺩﻭﻴﺎ" ﻋﻨﺩ ﻓﺸـل ﻨﻅﺎﻡ ﺍﻟﺘﺸـﻐﻴل ﺍﻷﻭﺘﻭﻤﺎﺘﻴﻜﻲ‪.‬‬
‫ﻜﺒﺴـﺔ ﺘﻌﻁﻴل ﺍﻟﻨﻅﺎﻡ ‪ :Emergency Stop Device‬ﻭﻫﻲ ﺠﻬﺎﺯ ﺇﻟﻐﺎﺀ‬ ‫•‬
‫ﺘﻔﻌﻴل ﻨﻅﺎﻡ ﺍﻟﺘﺤﻜﻡ ﻗﺒل ﺤﺩﻭﺙ ﺍﻟﻐﻤﺭ ﻭﺘﺴـﺘﺨﺩﻡ ﻋﻨﺩ ﺤﺩﻭﺙ ﺇﻨﺫﺍﺭ ﺨﺎﻁﻰﺀ‬
‫ﺃﻭ ﻓﻲ ﻅﺭﻭﻑ ﺇﻤﻜﺎﻨﻴﺔ ﺍﻟﺴـﻴﻁﺭﺓ ﻋﻠﻰ ﺍﻟﺤﺭﻴﻕ ﻤﺤﻠﻴﺎ"‪.‬‬
‫ﺠﻬﺎﺯ ﻜﺸﻑ ﺍﻟﺤﺭﻴﻕ ‪ :Fire Detecting Device‬ﻫﻭ ﺠﻬﺎﺯ ﻴﺘﺤﺴـﺱ‬ ‫•‬
‫ﺒﺩﺀ ﺍﻟﺤﺭﻴﻕ ﻋﻥ ﻁﺭﻴﻕ ﺍﻟﺩﺨﺎﻥ ﺃﻭ ﺍﻟﺤﺭﺍﺭﺓ ﺃﻭ ﺍﻟﻠﻬﺏ ﻭﻴﻌﻁﻲ ﺇﺸـﺎﺭﺓ ﺒﺫﻟﻙ‬
‫ﻟﺠﻬﺎﺯ )ﻨﻅﺎﻡ( ﺍﻟﺘﺤﻜﻡ‪.‬‬
‫ﻤﻨﻁﻘﺔ ﺍﻟﻐﻤﺭ ‪ :Flooding Zone‬ﻫﻲ ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﻤﺅﻟﻔﺔ ﻤﻥ ﻤﺠﻤﻭﻉ ﻤﻨﺎﻁﻕ‬ ‫•‬
‫ﺍﻟﺤﺴـﺎﺏ ﺍﻟﺘﻲ ﻴﺘﻡ ﺘﺤﺭﻴﺭ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ﻓﻴﻬﺎ ﺒﺸـﻜل ﻤﺘﺯﺍﻤﻥ‪.‬‬

‫‪10‬‬
‫• ﺯﻤﻥ ﺍﻹﺒﻘﺎﺀ ‪ :Holding Time‬ﻫﻲ ﺍﻟﻔﺘﺭﺓ ﺍﻟﺯﻤﻨﻴﺔ ﺒﻴﻥ ﻟﺤﻅﺔ ﺍﻟﻭﺼﻭل ﺇﻟﻰ‬
‫ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﺘﺼﻤﻴﻤﻲ ﻭﺒﺩﺀ ﺘﻬﻭﻴﺔ ﺍﻟﻤﻜﺎﻥ‪.‬‬
‫• ﺃﺠﻬﺯﺓ ﺍﻹﻨﺫﺍﺭ ﺍﻟﻤﺤﻔﺯﺓ ‪ :Aspirating Detection Device‬ﺃﺠﻬﺯﺓ‬
‫ﺍﻹﻨﺫﺍﺭ ﺍﻟﻤﺤﻔﺯﺓ ﺘﺘﻜﻭﻥ ﻤﻥ ﺤﺴﺎﺴﺎﺕ ﺘﻘﻴـﺱ ﺍﻟﺘﺭﻜﻴﺏ ﺍﻟﻜﻴﻤﻴﺎﺌﻲ ﻟﻬﻭﺍﺀ‬
‫ﺍﻟﻤﻜﺎﻥ ﻋﻥ ﻁﺭﻴﻕ ﺃﺠﻬﺯﺓ ﻤﺎﺼﺔ ﺘﻘﻭﻡ ﺒﺄﺨﺫ ﻋﻴﻨﺎﺕ ﻤﻥ ﺍﻟﻬﻭﺍﺀ‪.‬‬

‫ﺘﻌﻠﻴﻤﺎﺕ ﺴـﻼﻤﺔ ﺍﻷﺸـﺨﺎﺹ‪:‬‬

‫ﺇﻥ ﺍﻟﺤﻘﻴﻘﺔ ﺍﻟﺘﻲ ﻴﺠﺏ ﺃﻥ ﻻ ﺘﻐﻴﺏ ﻫﻲ ﺃﻥ ﺘﺭﻜﻴﺯ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ‬ ‫•‬
‫‪ CO2‬ﺍﻟﻼﺯﻡ ﻟﺘﺤﻘﻴﻕ ﺇﻁﻔﺎﺀ ﻓﻌﺎل ﺘﺸـﻜل ﺨﻁﺭﺍ" ﺤﻘﻴﻘﻴﺎ" ﻋﻠﻰ ﺤﻴﺎﺓ‬
‫ﺍﻷﺸـﺨﺎﺹ ﺍﻟﻤﻭﺠﻭﺩﻭﻥ ﻓﻲ ﺍﻟﻤﻜﺎﻥ‪.‬‬
‫ﻴﺠﺏ ﺍﻷﺨﺫ ﺒﻌﻴﻥ ﺍﻻﻋﺘﺒﺎﺭ ﺃﻥ ﺘﻌﻠﻴﻤﺎﺕ ﺍﻹﺨﻼﺀ ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﻭﺍﻀﺤﺔ‬ ‫•‬
‫ﻭﻤﻌﺭﻭﻓﺔ ﻟﺩﻯ ﺍﻷﺸـﺨﺎﺹ ﺍﻟﻠﺫﻴﻥ ﻗﺩ ﻴﺘﺼﺎﺩﻑ ﻭﺠﻭﺩﻫﻡ ﻓﻲ ﺍﻟﻤﻜﺎﻥ ﻋﻨﺩ‬
‫ﺤﺩﻭﺙ ﺍﻟﺤﺭﻴﻕ‪ ،‬ﻟﺫﻟﻙ ﻴﺠﺏ ﻭﻀﻊ ﻟﻭﺤﺎﺕ ﺇﺭﺸـﺎﺩﻴﺔ ﺘﺴـﺎﻋﺩ ﻫﺅﻻﺀ‬
‫ﺍﻷﺸـﺨﺎﺹ ﻋﻠﻰ ﺍﻹﺨﻼﺀ ﺍﻟﺘﺎﻡ ﺒﺄﻗﺼﺭ ﺯﻤﻥ ﻤﻤﻜﻥ‪.‬‬
‫ﻴﺠﺏ ﻤﺭﺍﻋﺎﺓ ﻋﺩﺩ ﺍﻷﺸـﺨﺎﺹ ﺍﻟﻤﺘﻭﺍﺠﺩﻴﻥ ﻓﻲ ﺍﻟﻤﻜﺎﻥ ﺍﻟﻤﺤﻤﻲ ﺒﻨﻅﺎﻡ ﻏﺎﺯ‬ ‫•‬
‫ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ﻋﻨﺩ ﺘﺼﻤﻴﻡ ﺯﻤﻥ ﺍﻟﺘﺄﺨﻴﺭ‪.‬‬
‫ﻴﺠﺏ ﺍﻟﺤﺭﺹ ﻋﻠﻰ ﻭﻀﻊ ﻟﻭﺤﺎﺕ ﻤﻀﺎﺀﺓ ﻟﻤﺨﺎﺭﺝ ﺍﻟﻨﺠﺎﺓ ﻓﻲ ﺍﻟﻤﻨﻁﻘﺔ‬ ‫•‬
‫ﺍﻟﻤﺤﻤﻴﺔ ﺒﺤﻴﺙ ﺘﻜﻭﻥ ﻫﺫﻩ ﺍﻟﻤﺨﺎﺭﺝ ﻏﻴﺭ ﻤﻌﺭﻀﺔ ﻟﻠﻐﻤﺭ ﺒﺎﻟﻐﺎﺯ‪ ،‬ﻭﻴﺠﺏ‬
‫ﻤﺭﺍﻋﺎﺓ ﺃﻥ ﻻ ﺘﻜﻭﻥ ﺇﺤﺩﻯ ﺍﻟﻤﻨﺎﻁﻕ ﺍﻟﻤﺤﻤﻴﺔ ﺒﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ‬
‫ﻤﺨﺭﺝ ﻨﺠﺎﺓ ﻭﺤﻴﺩ ﻟﻤﻨﻁﻘﺔ ﺃﺨﺭﻯ )ﻓﻲ ﺤﺎل ﺍﻟﻨﻅﺎﻡ ﻤﺘﻌﺩﺩ ﺍﻟﻤﻨﺎﻁﻕ(‪.‬‬
‫ﻴﺠﺏ ﺘﺯﻭﻴﺩ ﺍﻟﻤﻨﺎﻁﻕ ﺒﺄﺒﻭﺍﺏ ﺨﺎﺼﺔ ﻟﻤﻜﺎﻓﺤﺔ ﺍﻟﺤﺭﻴﻕ )ﻏﻴﺭ ﻗﺎﺒﻠﺔ‬ ‫•‬
‫ﻟﻺﺸـﺘﻌﺎل( ﻋﻠﻰ ﺃﻥ ﺘﻜﻭﻥ ﻫﺫﻩ ﺍﻷﺒﻭﺍﺏ ﺫﺍﺘﻴﺔ ﺍﻹﻏﻼﻕ ﻭﺘﻔﺘﺢ ﻓﻘﻁ ﻤﻥ ﺩﺍﺨل‬
‫ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﻤﺤﻤﻴﺔ‪.‬‬
‫ﻴﺠﺏ ﺘﺼﻤﻴﻡ ﺍﻹﻨﺫﺍﺭ ﺍﻟﺼﻭﺘﻲ ﺒﺤﻴﺙ ﻴﺨﺘﻠﻑ ﻋﻥ ﺒﺎﻗﻲ ﺃﻨﻭﺍﻉ ﺍﻹﻨﺫﺍﺭ ﺍﻟﺘﻲ ﻗﺩ‬ ‫•‬
‫ﺘﻜﻭﻥ ﻤﺴـﺘﻌﻤﻠﺔ ﻓﻲ ﺍﻟﻤﻨﺸـﺄﺓ ﻋﻠﻰ ﺃﻥ ﻴﻌﻤل ﻤﺒﺎﺸـﺭﺓ ﻋﻨﺩ ﺘﺤﺴـﺱ ﻭﺠﻭﺩ‬
‫ﺇﺤﺘﻤﺎل ﺤﺭﻴﻕ‪.‬‬
‫ﻴﺠﺏ ﻭﻀﻊ ﻟﻭﺤﺎﺕ ﺤﻤﺎﻴﺔ ﻤﻥ ﺍﻟﺩﺨﻭل ﻋﻠﻰ ﺃﻥ ﺘﻜﻭﻥ ﻤﻀﺎﺀﺓ" ﻋﻨﺩ ﻤﺩﺍﺨل‬ ‫•‬
‫ﺍﻟﻤﻨﺎﻁﻕ ﺍﻟﻤﺤﻤﻴﺔ ﺒﻨﻅﺎﻡ ﻴﻌﻤل ﺒﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ﻭﺫﻟﻙ ﻟﻤﻨﻊ ﺩﺨﻭل‬
‫ﺍﻷﺸـﺨﺎﺹ ﺇﻟﻰ ﻫﺫﻩ ﺍﻟﻤﻨﺎﻁﻕ ﻗﺒل ﺍﻟﺘﺄﻜﺩ ﻤﻥ ﺴـﻼﻤﺔ ﺍﻟﻤﻨﻁﻘﺔ ﻤﻥ ﻨﺎﺤﻴﺔ‬
‫ﺍﺭﺘﻔﺎﻉ ﺘﺭﻜﻴﺯ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ﺩﺍﺨﻠﻬﺎ ﻭﺫﻟﻙ ﺤﺭﺼﺎ" ﻋﻠﻰ ﺤﻴﺎﺓ‬
‫ﺍﻷﺸـﺨﺎﺹ ﺍﻟﻤﻌﺭﻀﻴﻥ ﻟﻠﺩﺨﻭل‪.‬‬

‫‪11‬‬
‫ﻴﺠﺏ ﺘﺯﻭﻴﺩ ﺍﻟﻤﻨﺎﻁﻕ ﺍﻟﻤﺤﻤﻴﺔ ﺒﻨﻅﺎﻡ ﻴﻌﻤل ﺒﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪CO2‬‬ ‫•‬
‫ﺒﻨﻅﺎﻡ ﺘﻬﻭﻴﺔ ﺃﻭﺘﻭﻤﺎﺘﻴﻜﻲ ﺨﺎﺹ ﻭﺫﻟﻙ ﻟﺘﻬﻭﻴﺔ ﺍﻟﻤﻜﺎﻥ ﺒﻌﺩ ﻤﻜﺎﻓﺤﺔ ﺍﻟﺤﺭﻴﻕ‬
‫ﻭﻗﺒل ﺍﻟﺴـﻤﺎﺡ ﺒﻔﺘﺢ ﺍﻟﻤﻜﺎﻥ ﻟﺩﺨﻭل ﺍﻷﺸـﺨﺎﺹ‪.‬‬
‫ﻴﺠﺏ ﻤﺭﺍﻋﺎﺓ ﺨﺼﻭﺼﻴﺔ ﺍﻟﻤﻜﺎﻥ ﻭﺘﺼﻤﻴﻡ ﺘﻌﻠﻴﻤﺎﺕ ﻭﺇﺠﺭﺍﺀﺍﺕ ﺍﻟﺴـﻼﻤﺔ‬ ‫•‬
‫ﺍﻟﺨﺎﺼﺔ ﺒﻪ ﻭﺍﺨﺘﻴﺎﺭ ﻨﻭﻉ ﺃﻨﻅﻤﺔ ﺍﻟﺴـﻼﻤﺔ ﻭﻁﺭﻕ ﺘﻔﻌﻴﻠﻬﺎ ﺍﻋﺘﻤﺎﺩﺍ" ﻋﻠﻰ‬
‫ﻁﺒﻴﻌﺔ ﺍﻟﻤﻜﺎﻥ ﻭﺴـﻴﻨﺎﺭﻴﻭ ﺍﻟﺤﺭﻴﻕ ﺍﻟﻤﺤﺘﻤل‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﺘﺯﻭﺩ ﺍﻟﻤﻨﺎﻁﻕ ﺍﻟﻤﺤﻤﻴﺔ ﺒﻨﻅﺎﻡ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ﺒﻤﻌﺩﺍﺕ‬ ‫•‬
‫ﺘﻨﻔـﺱ ﺨﺎﺼﺔ ﻻﺴـﺘﻌﻤﺎل ﺍﻷﺸـﺨﺎﺹ ﺍﻟﻠﺫﻴﻥ ﻗﺩ ﻻ ﻴﺘﻤﻜﻨﻭﺍ ﻤﻥ ﻤﻐﺎﺩﺭﺓ‬
‫ﺍﻟﻤﻜﺎﻥ ﻗﺒل ﺍﻟﻐﻤﺭ ﺒﺎﻟﻐﺎﺯ ﻋﻠﻰ ﺃﻥ ﻴﺘﻡ ﺘﺩﺭﻴﺏ ﺍﻷﺸـﺨﺎﺹ ﻋﻠﻰ ﺍﺴـﺘﺨﺩﺍﻡ‬
‫ﻫﺫﻩ ﺍﻟﻤﻌﺩﺍﺕ‪.‬‬
‫ﻴﺠﺏ ﻤﺭﺍﻋﺎﺓ ﺇﻤﻜﺎﻨﻴﺔ ﺍﺴـﺘﺨﺩﺍﻡ ﻤﻭﺍﺩ ﻏﻴﺭ ﻗﺎﺒﻠﺔ ﻟﻼﺸـﺘﻌﺎل ﻓﻲ ﺒﻌﺽ‬ ‫•‬
‫ﺍﻷﻤﺎﻜﻥ ﻋﻨﺩ ﺘﺼﻤﻴﻡ ﺍﻟﻤﻜﺎﻥ ﺇﻨﺸـﺎﺌﻴﺎ"‪.‬‬
‫ﻴﺠﺏ ﺘﺯﻭﻴﺩ ﻜل ﻤﻨﻁﻘﺔ ﻤﻥ ﺍﻟﻤﻨﺎﻁﻕ ﺍﻟﻤﺤﻤﻴﺔ ﺒﻨﻅﺎﻡ ﻴﻌﻤل ﺒﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ‬ ‫•‬
‫ﺍﻟﻜﺭﺒﻭﻥ ﺒﻜﺒﺴـﺔ ﺘﻭﻗﻑ ﻴﺩﻭﻴﺔ ﻭﺫﻟﻙ ﻹﻴﻘﺎﻑ ﻋﻤل ﺍﻟﻨﻅﺎﻡ ﺨﻼل ﻓﺘﺭﺓ ﺯﻤﻥ‬
‫ﺍﻟﺘﺄﺨﻴﺭ ﻴﺩﻭﻴﺎ" ﻓﻲ ﺤﺎل ﺍﻹﻨﺫﺍﺭ ﺍﻟﺨﺎﻁﻰﺀ ﺃﻭ ﺍﺤﺘﻭﺍﺀ ﺍﻟﺤﺭﻴﻕ ﻤﻜﺎﻨﻴﺎ"‪.‬‬
‫ﻴﻔﻀل ﺃﻥ ﻴﻀﺎﻑ ﺭﺍﺌﺤﺔ ﻏﻴﺭ ﻗﺎﺒﻠﺔ ﻟﻼﺸـﺘﻌﺎل ﺃﻭ ﺍﻟﺘﻔﻜﻙ ﺒﺎﻟﺤﺭﺍﺭﺓ ﻟﻐﺎﺯ‬ ‫•‬
‫ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ﺍﻟﻤﺴـﺘﺨﺩﻡ ﻓﻲ ﺍﻹﻁﻔﺎﺀ‪.‬‬

‫‪12‬‬
‫ﺘﺼﻤﻴﻡ ﻨﻅﺎﻡ ﻋﺎﻤل ﺒﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪CO2‬‬

‫ﻁﺒﻴﻌﺔ ﻭﻤﺘﻁﻠﺒﺎﺕ ﺍﻟﺘﺼﻤﻴﻡ‪:‬‬

‫ﺇﻥ ﺍﻟﺤﺴـﺎﺒﺎﺕ ﺍﻟﻤﺫﻜﻭﺭﺓ ﻓﻲ ﻫﺫﺍ ﺍﻟﻔﺼل ﺼﺎﻟﺤﺔ ﻓﻘﻁ ﻷﻨﻅﻤﺔ ﺍﻟﻐﻤﺭ ﺍﻟﻜﻠﻲ‬ ‫•‬
‫ﺍﻟﻌﺎﻤﻠﺔ ﺒﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪. CO2‬‬
‫ﻴﻭﺠﺩ ﻨﻭﻋﻴﻥ ﻤﻥ ﺃﻨﻅﻤﺔ ﺍﻹﻁﻔﺎﺀ ﺍﻟﻌﺎﻤﻠﺔ ﺒﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪،CO2‬‬ ‫•‬
‫ﺃﻨﻅﻤﺔ ﺍﻟﻀﻐﻁ ﺍﻟﻤﻨﺨﻔﺽ ﻭﺃﻨﻅﻤﺔ ﺍﻟﻀﻐﻁ ﺍﻟﻤﺭﺘﻔﻊ ﻭﻴﻤﻜﻨﻨﺎ ﺍﺨﺘﻴﺎﺭ ﺍﺤﺩ‬
‫ﺍﻟﻨﻅﺎﻤﻴﻥ ﻭﻜﻤﻴﺔ ‪ CO2‬ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻭﻁﺭﻴﻘﺔ ﺍﻟﺘﻭﺯﻴﻊ ﺤﺴﺏ ﺍﻟﺩﺭﺍﺴﺔ‪.‬‬
‫ﺘﻔﺘﺭﺽ ﺍﻟﻤﻌﻁﻴﺎﺕ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﺃﻥ ﻁﺒﻴﻌﺔ ﺍﻟﻤﻜﺎﻥ ﺍﻟﻤﺤﻤﻲ ﺒﺎﻟﻨﻅﺎﻡ ﻭﺠﻤﻴﻊ‬ ‫•‬
‫ﺍﻟﻤﻭﺍﺩ ﺍﻟﻤﺴـﺘﻌﻤﻠﺔ ﻓﻴﻪ ﺘﺴـﻤﺢ ﺒﻭﺼﻭل ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪CO2‬‬
‫ﺇﻟﻰ ﻜﺎﻤل ﺍﻟﺤﺠﻡ ﻜﻤﺎ ﺘﺴـﻤﺢ ﺒﺒﻘﺎﺌﻪ ﺍﻟﻔﺘﺭﺓ ﺍﻟﻜﺎﻓﻴﺔ ﺘﺼﻤﻴﻤﻴﺎ" ﻹﻁﻔﺎﺀ ﺍﻟﺤﺭﻴﻕ‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﺘﺘﺤﻤل ﻋﻨﺎﺼﺭ ﺍﻟﻤﻜﺎﻥ ﺍﻟﻤﺤﻤﻲ ﺒﺎﻟﻨﻅﺎﻡ )ﻨﻭﺍﻓﺫ‪ ،‬ﺠﺩﺭﺍﻥ‪ ،‬ﺴـﻘﻑ‪،‬‬ ‫•‬
‫‪ ..‬ﺇﻟﺦ( ﺯﻴﺎﺩﺓ ﺍﻟﻀﻐﻁ ﺍﻟﻨﺎﺠﻤﺔ ﻋﻥ ﺍﻨﻔﻼﺕ ﺍﻟﻐﺎﺯ ﻓﻲ ﺍﻟﺤﻴﺯ ﺍﻟﻤﺤﻤﻲ ﺩﻭﻥ ﺃﻥ‬
‫ﻴﺅﺜﺭ ﺫﻟﻙ ﻋﻠﻰ ﺇﺤﻜﺎﻡ ﺍﻟﻤﻜﺎﻥ‪.‬‬
‫ﻓﻲ ﺤﺎل ﻋﺩﻡ ﺘﺤﻘﻴﻕ ﻋﻨﺎﺼﺭ ﺍﻟﻤﻜﺎﻥ ﺍﻟﻤﺤﻤﻲ ﺒﺎﻟﻨﻅﺎﻡ ﻟﻠﺸـﺭﻁ ﺍﻟﻭﺍﺭﺩ ﻓﻲ‬ ‫•‬
‫ﺍﻟﻔﻘﺭﺓ ﺍﻟﺴـﺎﺒﻘﺔ ﻴﺠﺏ ﺇﻀﺎﻓﺔ ﻤﺄﺨﺫ ﺃﻭﺘﻭﻤﺎﺘﻴﻜﻲ ﻟﺘﺨﻔﻴﺽ ﺍﻟﻀﻐﻁ ﻋﻠﻰ ﺃﻥ ﻻ‬
‫ﻴﺅﺜﺭ ﺫﻟﻙ ﻋﻠﻰ ﻓﻌﺎﻟﻴﺔ ﻨﻅﺎﻡ ﺍﻹﻁﻔﺎﺀ‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﺘﺤﻘﻕ ﺍﻟﻔﻭﺍﺼل ﺒﻴﻥ ﺍﻟﻤﻨﺎﻁﻕ ﺍﻟﻤﺤﻤﻴﺔ ﻤﻥ ﺠﺩﺭﺍﻥ ﺃﻭ ﺃﺴـﻘﻑ ﺃﻭ‬ ‫•‬
‫ﺃﺒﻭﺍﺏ )ﻓﻲ ﺤﺎل ﺍﻟﻨﻅﺎﻡ ﻤﺘﻌﺩﺩ ﺍﻟﻤﻨﺎﻁﻕ( ﺍﻟﻤﺘﻁﻠﺒﺎﺕ ﺍﻟﻘﻴﺎﺴـﻴﺔ ﺍﻟﺘﻲ ﺴـﺘﺭﺩ‬
‫ﻻﺤﻘﺎ" ﻓﻲ ﻫﺫﺍ ﺍﻟﻜﺘﻴﺏ ﻤﻥ ﺤﻴﺙ ﻗﺎﺒﻠﻴﺘﻬﺎ ﻟﻼﺸـﺘﻌﺎل ﺃﻭ ﻁﺒﻴﻌﺔ ﺘﺤﻤﻠﻬﺎ‬
‫ﻟﻠﺤﺭﻴﻕ‪.‬‬
‫ﻓﻲ ﺤﺎل ﻭﺠﻭﺩ ﻓﺘﺤﺎﺕ ﻓﻲ ﺍﻟﻤﻜﺎﻥ ﺍﻟﻤﺤﻤﻲ ﺒﺎﻟﻨﻅﺎﻡ ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﻫﺫﻩ‬ ‫•‬
‫ﺍﻟﻔﺘﺤﺎﺕ ﻗﺎﺒﻠﺔ ﻟﻺﻏﻼﻕ ﻭﻴﻔﻀل ﺃﻥ ﻴﺘﻡ ﺇﻏﻼﻗﻬﺎ ﺃﻭﺘﻭﻤﺎﺘﻴﻜﻴﺎ" ﺒﻭﺍﺴـﻁﺔ ﺁﻟﻴﺔ‬
‫ﻤﺭﺘﺒﻁﺔ ﺒﻨﻅﺎﻡ ﺍﻟﻭﻗﺎﻴﺔ ﻤﻥ ﺍﻟﺤﺭﻴﻕ‪.‬‬
‫ﻓﻲ ﺤﺎل ﻋﺩﻡ ﺘﺤﻘﻴﻕ ﻓﺘﺤﺎﺕ ﺍﻟﻤﻜﺎﻥ ﺍﻟﻤﺤﻤﻲ ﺒﺎﻟﻨﻅﺎﻡ ﻟﻠﺸـﺭﻁ ﺍﻟﻭﺍﺭﺩ ﻓﻲ‬ ‫•‬
‫ﺍﻟﻔﻘﺭﺓ ﺍﻟﺴـﺎﺒﻘﺔ ﻓﺈﻥ ﻫﺫﻩ ﺍﻟﻔﺘﺤﺎﺕ ﺘﺩﺨل ﻓﻲ ﺍﻟﺤﺴـﺎﺒﺎﺕ ﻋﻠﻰ ﺃﻨﻬﺎ‬
‫ﻤﺴـﺎﺤﺎﺕ ﻤﻔﺘﻭﺤﺔ ‪.Ao‬‬
‫ﺇﻥ ﺍﻟﻤﺴـﺎﺤﺔ ﺍﻹﺠﻤﺎﻟﻴﺔ ﻟﻠﻔﺘﺤﺎﺕ ﺍﻟﻤﺤﺘﻤل ﻭﺠﻭﺩﻫﺎ ﻓﻲ ﻭﻗﺕ ﺍﻨﺩﻻﻉ ﺍﻟﺤﺭﻴﻕ‬ ‫•‬
‫‪ Ao‬ﻴﺠﺏ ﺃﻥ ﻻ ﻴﺅﺜﺭ ﺘﺼﻤﻴﻤﻴﺎ" ﻋﻠﻰ ﺯﻤﻥ ﺍﻹﺒﻘﺎﺀ ﺍﻟﺘﺼﻤﻴﻤﻲ‪.‬‬

‫‪13‬‬
‫ﺤﺴـﺎﺏ ﺍﻟﻜﻤﻴﺔ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﻐﺎﺯ‪:CO2‬‬

‫ﺘﺤﺴـﺏ ﺍﻟﻜﻤﻴﺔ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﺍﻟﻼﺯﻤﺔ ﻤﻥ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴـﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪CO2‬‬


‫ﺒﻤﻭﺠﺏ ﺍﻟﻤﻌﺎﺩﻟﺔ ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬

‫)‪Q (kg) = KB ( 0.75 . V + 0.2 . A‬‬

‫ﺤﻴﺙ ﺘﻌﺒﺭ ﺍﻟﺭﻤﻭﺯ ﺍﻟﻤﺫﻜﻭﺭﺓ ﻋﻥ ﻤﺎ ﻴﻠﻲ‪:‬‬

‫‪ A (m2) = Av + 30 . Ao‬ﺍﻟﺴـﻁﺢ ﺍﻟﻭﺍﺠﺏ ﺤﻤﺎﻴﺘﻪ‬


‫] )‪ V (m3) = Vv + [4 . (Vz - VG‬ﺍﻟﺤﺠﻡ ﺍﻟﻭﺍﺠﺏ ﺤﻤﺎﻴﺘﻪ‬

‫‪ :‬ﺍﻟﻜﻤﻴﺔ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﺒﺎﻟﻜﻴﻠﻭ ﻏﺭﺍﻡ‬ ‫‪Q‬‬


‫‪ :‬ﻤﻌﺎﻤل ﺍﻟﺘﺭﻜﻴﺯ ﻟﻠﻤﺎﺩﺓ ﺍﻟﻤﺤﻤﻴﺔ ﺃﻭ ﻟﻨﺸـﺎﻁ ﺍﻟﻤﻜﺎﻥ ﺍﻟﻤﺫﻜﻭﺭ ﻓﻲ ﺍﻟﺠﺩﺍﻭل‬ ‫‪KB‬‬
‫ﺭﻗﻡ ‪ /1/‬ﻭ ‪ /2/‬ﻭ ‪/3/‬‬
‫‪ :‬ﻤﺴـﺎﺤﺔ ﺍﻟﺴـﻁﺢ ﺍﻹﺠﻤﺎﻟﻲ ﻟﻠﻤﻨﻁﻘﺔ ﺍﻟﻤﺤﺴﻭﺒﺔ ﻤﺘﻀﻤﻨﺔ" ﻤﺠﻤﻭﻉ‬ ‫‪Av‬‬
‫ﺍﻟﻤﺴـﺎﺤﺎﺕ ﺍﻟﻤﻔﺘﻭﺤﺔ ‪Ao‬‬
‫‪ :‬ﻤﺠﻤﻭﻉ ﺍﻟﻤﺴـﺎﺤﺎﺕ ﺍﻟﻤﻔﺘﻭﺤﺔ ﻓﻲ ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﻤﺤﺴﻭﺒﺔ‬ ‫‪Ao‬‬
‫‪ :‬ﺍﻟﺤﺠﻡ ﺍﻹﺠﻤﺎﻟﻲ ﻟﻠﻤﻨﻁﻘﺔ ﺍﻟﻤﺤﺴﻭﺒﺔ‬ ‫‪Vv‬‬
‫‪ :‬ﺤﺠﻡ ﺍﻟﻬﻭﺍﺀ ﺍﻟﻤﻤﻜﻥ ﺘﺴـﺭﺒﻪ ﺨﻼل ﺯﻤﻥ ﺍﻟﻭﺼﻭل ﺇﻟﻰ ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﺘﺼﻤﻴﻤﻲ‬ ‫‪Vz‬‬
‫ﺃﻭ ﺯﻤﻥ ﺍﻹﺒﻘﺎﺀ ﺍﻹﻟﺯﺍﻤﻲ ﻤﻥ ﺍﻟﻔﺘﺤﺎﺕ ﺍﻟﻐﻴﺭ ﻗﺎﺒﻠﺔ ﻟﻺﻏﻼﻕ ﻓﻲ ﺍﻟﻤﻜﺎﻥ‬
‫ﺤﺠﻡ ﻋﻨﺎﺼﺭ ﻭﻤﻜﻭﻨﺎﺕ ﺒﻨﺎﺀ ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﻤﺤﺴﻭﺒﺔ ﺃﻭ ﻤﻭﺠﻭﺩﺍﺘﻬﺎ ﻏﻴﺭ ﺍﻟﻘﺎﺒﻠﺔ‬ ‫‪VG‬‬
‫ﻟﻼﺤﺘﺭﺍﻕ ﻭﺍﻟﺘﻲ ﺘﺸـﻐل ﺤﻴﺯﺍ" ﻤﻥ ﻓﺭﺍﻏﻬﺎ‬

‫ﻭﻓﻲ ﺤﺎل ﺘﺤﻘﻕ ﺃﺤﺩ ﺍﻟﺸـﺭﻁﻴﻥ ﺍﻟﺘﺎﻟﻴﻴﻥ‪:‬‬

‫‪0.75 . V + 0.2 . Av > 1.1 . V‬‬ ‫ﺃﻭ‬


‫‪A / VR > 1.75‬‬

‫ﻓﺈﻥ ﻜﻤﻴﺔ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴـﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﺍﻷﻋﻅﻤﻴﺔ ﺍﻟﻤﺴـﺘﺨﺩﻤﺔ‬


‫ﻓﻲ ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﻤﺤﺴـﻭﺒﺔ‪ ،‬ﺘﺤﺴـﺏ ﺒﻤﻭﺠﺏ ﺍﻟﻤﻌﺎﺩﻟﺔ ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬

‫] )‪Qmax (kg) = KB [ (1.1 . V) + (0.2 . 30 . Ao‬‬

‫‪14‬‬
‫ﺤﺴـﺎﺏ ﺍﻟﻜﻤﻴﺔ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﻠﻐﺎﺯﺍﺕ ﺍﻟﺨﺎﻤﻠﺔ ﺍﻨﻁﻼﻗﺎ" ﻤﻥ ﺤﺴـﺎﺏ ﺍﻟﻜﻤﻴﺔ‬
‫ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴـﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ‪:‬‬

‫ﺘﺤﺴـﺏ ﺍﻟﻜﻤﻴﺔ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﻠﻐﺎﺯ ﺍﻟﺨﺎﻤل ﻏﻴﺭ ﺍﻟﻘﺎﺒل ﻟﻼﻨﻀﻐﺎﻁ ﺍﺴـﺘﻨﺎﺩﺍ" ﻟﻠﻜﻤﻴﺔ‬
‫ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴـﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ﺍﻋﺘﻤﺎﺩﺍ" ﻋﻠﻰ ﻤﻔﻬﻭﻡ ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﻨﺴـﺒﻲ‬
‫ﺍﻟﻼﺯﻡ ﻟﻠﻐﺎﺯ ﺍﻟﺨﺎﻤل ‪ CI‬ﻭﺍﻟﺫﻱ ﻴﻤﻜﻥ ﺘﻌﻭﻴﻀﻪ ﻤﻥ ﺍﻟﺠﺩﻭل ﺍﻟﺘﺎﻟﻲ‪:‬‬

‫ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﻨﺴـﺒﻲ ﻟﻠﻐﺎﺯ‬


‫ﺍﻟﻜﺘﻠﺔ ﺍﻟﻤﻭﻟﻴﺔ ‪Mmol‬‬ ‫ﺍﺴـﻡ ﺍﻟﻐﺎﺯ‬
‫ﺍﻟﺨﺎﻤل ‪CI‬‬
‫‪0.91‬‬ ‫‪39.95‬‬ ‫ﺃﺭﻏﻭﻥ ‪Ar‬‬
‫‪1‬‬ ‫‪44.01‬‬ ‫ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪CO2‬‬
‫‪0.77‬‬ ‫‪34.07‬‬ ‫ﺍﻨﻴﺭﻏﻥ ‪Inergen‬‬
‫‪0.64‬‬ ‫‪28.01‬‬ ‫ﺍﻟﻨﺘﺭﻭﺠﻴﻥ ‪N2‬‬
‫‪0.77‬‬ ‫‪33.98‬‬ ‫ﺃﺭﻏﻭﻨﺎﻴﺕ ‪Argonite‬‬

‫ﻋﻥ ﻁﺭﻴﻕ ﺍﻟﻤﻌﺎﺩﻟﺔ‪:‬‬


‫‪QI (kg) = CI . QCO2‬‬

‫ﺤﺴـﺎﺏ ﺘﺭﻜﻴﺯ ﻏﺎﺯ ﺍﻹﻁﻔﺎﺀ ﻓﻲ ﺍﻟﻤﻜﺎﻥ ‪:CGas‬‬

‫ﻴﺤﺴـﺏ ﺘﺭﻜﻴﺯ ﺍﻟﻐﺎﺯ ﻓﻲ ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﻤﺤﺴـﻭﺒﺔ ﺍﻨﻁﻼﻗﺎ" ﻤﻥ ﺍﻟﻤﻌﺎﺩﻟﺔ ﺍﻟﺘﺎﻟﻴﺔ ﻭﺍﻟﺘﻲ‬


‫ﻴﻤﻜﻥ ﺘﻁﺒﻴﻘﻬﺎ ﻋﻠﻰ ﻜل ﻤﻥ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴـﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ﻭﺍﻟﻐﺎﺯﺍﺕ ﺍﻟﺨﺎﻤﻠﺔ‬
‫ﺍﻷﺨﺭﻯ‪:‬‬
‫] )‪CGas (%) = 100 [1 – (1 / eX‬‬

‫‪ e‬ﺍﻟﻌﺩﺩ ﺍﻟﻨﻴﺒﻴﺭﻱ )ﺃﺴﺎﺱ ﺍﻟﻠﻭﻏﺎﺭﻴﺜﻡ ﺍﻟﻁﺒﻴﻌﻲ(‬


‫ﺤﻴﺙ ‪:‬‬
‫)‪X = QGas / (ρGas . VR‬‬

‫ﺒﻴﻨﻤﺎ ﻴﺤﺴـﺏ ﺘﺭﻜﻴﺯ ﺍﻷﻭﻜﺴـﺠﻴﻥ ﺍﻟﻤﺘﺒﻘﻲ ﻓﻲ ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﻤﺤﺴـﻭﺒﺔ ﺒﻤﻭﺠﺏ‬


‫ﺍﻟﻤﻌﺎﺩﻟﺔ ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬

‫‪CO2 (%) = 20.9 (100 – CGas) / 100‬‬

‫‪15‬‬
‫ﻤﻼﺤﻅﺎﺕ ﻫﺎﻤﺔ‪:‬‬
‫• ﺇﺫﺍ ﻜﺎﻨﺕ ﻁﺒﻴﻌﺔ )ﺍﻟﺠﺩﺭﺍﻥ ﺃﻭ ﺍﻷﺴـﻘﻑ( ﺍﻟﺘﻲ ﺘﺸـﻜل ﺤﺩﻭﺩ ﺍﻟﻤﻨﻁﻘﺔ‬
‫ﺍﻟﻤﺤﺴﻭﺒﺔ ﻓﻲ ﻨﻅﺎﻡ ﻤﺘﻌﺩﺩ ﺍﻟﻤﻨﺎﻁﻕ ﻤﺼﻨﻌﺔ ﻤﻥ ﻤﻭﺍﺩ ﻗﺎﺒﻠﺔ ﻟﻼﺸـﺘﻌﺎل ﺃﻭ ﻻ‬
‫ﺘﺤﻘﻕ ﺍﻟﻤﺘﻁﻠﺒﺎﺕ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﺍﻟﻤﺫﻜﻭﺭﺓ ﻓﻲ ﺒﺩﺍﻴﺔ ﺍﻟﻔﺼل ﻓﻴﺠﺏ ﺃﻥ ﻴﻌﺩل‬
‫ﺍﻟﺘﺼﻤﻴﻡ ﺒﺤﻴﺙ ﺘﺘﺴـﻊ ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﻤﺤﺴﻭﺒﺔ ﺤﺘﻰ ﻨﺼل ﺇﻟﻰ ﺤﺩﻭﺩ ﺘﺤﻘﻕ‬
‫ﺍﻟﻤﺘﻁﻠﺒﺎﺕ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﺍﻟﻤﺫﻜﻭﺭﺓ‪.‬‬
‫• ﻋﻨﺩ ﺤﺴـﺎﺏ ‪ Av‬ﻴﺠﺏ ﺃﻥ ﻨﺴـﻘﻁ ﻤﻨﻬﺎ ﺤﺩﻭﺩ ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﻤﺤﺴﻭﺒﺔ ﺍﻟﺘﻲ‬
‫ﺘﺤﻘﻕ ﻤﺘﻁﻠﺒﺎﺕ ﺍﻟﺘﺼﻤﻴﻡ ﺍﻟﻤﺫﻜﻭﺭﺓ ﻓﻲ ﺒﺩﺍﻴﺔ ﺍﻟﻔﺼل‪.‬‬

‫ﺍﺨﺘﻴﺎﺭ ﻤﻌﺎﻤل ﺍﻟﺘﺭﻜﻴﺯ ‪:KB‬‬

‫ﻴﺘﻡ ﺍﺨﺘﻴﺎﺭ ﻤﻌﺎﻤل ﺍﻟﺘﺭﻜﻴﺯ ‪ KB‬ﺍﻟﻭﺍﺠﺏ ﺍﺴـﺘﺨﺩﺍﻤﻪ ﺒﻨﺎﺀ" ﻋﻠﻰ ﻁﺒﻴﻌﺔ ﺍﻟﻤﻜﺎﻥ‬
‫ﺍﻟﻤﺤﻤﻲ ﻭﻨﻭﻉ ﺍﻟﺨﻁﺭ ﺍﻟﻤﺤﺘﻤل ﻤﻊ ﺍﻷﺨﺫ ﺒﻌﻴﻥ ﺍﻻﻋﺘﺒﺎﺭ ﺃﻥ ﺍﻟﻘﻴﻡ ﺍﻟﻤﺫﻜﻭﺭﺓ ﻓﻲ‬
‫ﺍﻟﺠﺩﺍﻭل ﻤﻥ ‪ 1‬ﺤﺘﻰ ‪ 3‬ﺘﻘﺭﻴﺒﺎ" ﻴﺠﺏ ﺇﺩﺭﺍﺠﻬﺎ ﻓﻲ ﺍﻟﻤﻌﺎﺩﻟﺔ ﺍﻟﺘﻲ ﺘﺤﺩﺩ ﻜﻤﻴﺔ ﻏﺎﺯ ﺜﺎﻨﻲ‬
‫ﺃﻭﻜﺴـﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﺍﻟﻤﻁﻠﻭﺒﺔ‪ ،‬ﺃﻤﺎ ﺒﺎﻟﻨﺴـﺒﺔ ﻟﻁﺒﻴﻌﺔ ﺍﻻﺴـﺘﺨﺩﺍﻡ ﺍﻟﺘﻲ ﻟﻡ ﺘﺭﺩ‬
‫ﻓﻲ ﺍﻟﺠﺩﻭل ﻓﺈﻨﻨﺎ ﻻ ﻨﺴـﺘﻁﻴﻊ ﺍﻓﺘﺭﺍﺽ ﺍﻟﻤﻌﺎﻤل ﻭﺇﻨﻤﺎ ﻴﺠﺏ ﺴـﺅﺍل ﺠﻬﺔ ﻤﺨﻭﻟﺔ‬
‫ﺒﺈﻋﻁﺎﺀ ﻗﻴﻤﺔ ﺍﻟﻤﻌﺎﻤل ﺘﺠﺭﻴﺒﻴﺎ"‪ .‬ﻭﻟﻜﻥ ﻻ ﻴﻤﻜﻥ ﺍﺴـﺘﺨﺩﺍﻡ ﻤﻌﺎﻤل ﺍﻟﺘﺭﻜﻴﺯ ‪KB‬‬
‫ﻟﻤﻜﻭﻨﺎﺕ ﺍﻟﺤﺭﺍﺌﻕ ﺍﻟﻜﺎﻤﻨﺔ ﻓﻲ ﺍﻟﺤﺎﻻﺕ ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬
‫• ﻓﻲ ﺁﻻﺕ ﺍﻟﻁﺒﺎﻋﺔ ﻭﺍﻟﻔﻭﻡ ﻋﻨﺩ ﺘﻭﺍﺠﺩ ﻁﺒﻘﺔ ﻭﺭﻕ ﻭﺍﺤﺩﺓ‪.‬‬
‫• ﻓﻲ ﺤﺎل ﻭﺠﻭﺩ ﻁﺒﻘﺎﺕ ﻭﺭﻕ ﻟﻔﺼل ﻤﻭﺍﺩ ﺼﻠﺒﺔ ﻤﺨﺯﻨﺔ ﻋﻠﻰ ﺃﻥ ﺘﻜﻭﻥ ﻫﺫﻩ‬
‫ﺍﻟﻤﻭﺍﺩ ﻤﺼﻨﻔﺔ ﻜﻤﻭﺍﺩ ﻤﺤﺘﻤﻠﺔ ﻟﺤﺭﺍﺌﻕ ﺍﻟﺩﺭﺠﺔ ‪. B‬‬
‫• ﺍﻷﻟﻭﺍﺡ ﺍﻟﺨﺸﺒﻴﺔ ﺍﻟﻤﻐﻠﻔﺔ ﺒﻤﻭﺍﺩ ﻏﻴﺭ ﻗﺎﺒﻠﺔ ﻟﻼﺸـﺘﻌﺎل‪.‬‬

‫ﻭﻴﺒﻴﻥ ﺍﻟﺠﺩﻭل ﺃﺩﻨﺎﻩ ﻗﻴﻤﺔ ﻤﻌﺎﻤل ﺍﻟﺘﺭﻜﻴﺯ ‪ KB‬ﻟﻠﻤﻭﺍﺩ ﺍﻟﺼﻠﺒﺔ ﺍﻟﻤﺫﻜﻭﺭﺓ ﻭﺍﻟﺘﻲ ﺘﺒﻴﻥ‬
‫ﺍﻹﺸـﺎﺭﺓ )*( ﺇﻤﻜﺎﻨﻴﺔ ﺤﺩﻭﺙ ﺤﺭﻴﻕ ﻜﺎﻤﻥ‪:‬‬
‫ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﺘﺼﻤﻴﻤﻲ ﺍﻟﻼﺯﻡ ‪%‬‬ ‫‪KB‬‬ ‫ﻨﻭﻉ ﺍﻟﻤﻭﺍﺩ‬
‫‪%61‬‬ ‫‪2.25‬‬ ‫ﺍﻟﻤﻭﺍﺩ ﺍﻟﺘﻲ ﺘﺤﻭﻱ ﺍﻟﺴﻴﻠﻴﻠﻭﺯ*‬
‫‪%57‬‬ ‫‪2.00‬‬ ‫ﺍﻟﻘﻁﻥ*‬
‫‪%61‬‬ ‫‪2.25‬‬ ‫ﺍﻟﻭﺭﻕ ﻭ ﺍﻟﻤﻭﺍﺩ ﺍﻟﻭﺭﻗﻴﺔ*‬
‫‪%57‬‬ ‫‪2.00‬‬ ‫ﺍﻟﻤﻭﺍﺩ ﺍﻟﺒﻼﺴﺘﻴﻜﻴﺔ*‬
‫‪%34‬‬ ‫‪1.00‬‬ ‫ﺍﻟﺒﻭﻟﻴﺴﺘﻴﺭﻴﻥ ﺍﻟﺨﺎﻡ ﻭﻤﺭﻜﺒﺎﺘﻪ ﺍﻟﻤﻌﺎﻟﺠﺔ‬
‫ﺠﺩﻭل )‪(1‬‬
‫* ‪ -‬ﻴﺠﺏ ﺇﺒﻘﺎﺀ ﺘﺭﻜﻴﺯ ﺃﺼﻐﺭﻱ ‪ %34‬ﻤﻥ ﺍﻟﻐﺎﺯ ﻟﻤﺩﺓ ‪ 20‬ﺩﻗﻴﻘﺔ ﻋﻠﻰ ﺍﻷﻗل‬

‫‪16‬‬
‫ﺃﻤﺎ ﻗﻴﻤﺔ ﻤﻌﺎﻤل ﺍﻟﺘﺭﻜﻴﺯ ‪ KB‬ﻟﻠﻤﻭﺍﺩ ﺍﻟﺴـﺎﺌﻠﺔ ﻭﺍﻟﻐﺎﺯﻴﺔ ﻓﻬﻲ ﻜﻤﺎ ﻴﻠﻲ‪:‬‬

‫ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﺘﺼﻤﻴﻤﻲ‬
‫‪Material‬‬ ‫‪KB‬‬ ‫ﺍﻟﻤـــﺎﺩﺓ‬
‫ﺍﻟﻼﺯﻡ ‪%‬‬
‫‪Acetone‬‬ ‫‪34‬‬ ‫‪1.00‬‬ ‫ﺃﺴـﻴﺘﻭﻥ‬
‫‪Acetylene‬‬ ‫‪66‬‬ ‫‪2.57‬‬ ‫ﺃﺴـﺘﻴﻠﻴﻥ‬
‫‪Aviation fuel‬‬ ‫ﻭﻗﻭﺩ ﻁﺎﺌﺭﺍﺕ ﻋﻴﺎﺭ‬
‫‪36‬‬ ‫‪1.06‬‬
‫‪grades 115/145‬‬ ‫‪145/115‬‬
‫‪Benzene Benzol‬‬ ‫ﺒﻨﺯﻭل‬
‫‪37‬‬ ‫‪1.10‬‬ ‫ﺒﻨﺯﻴﻥ‬
‫‪Butadiene‬‬ ‫‪41‬‬ ‫‪1.26‬‬ ‫ﺒﻭﺘﺎﺩﻴﻥ‬
‫‪Butane‬‬ ‫‪34‬‬ ‫‪1.00‬‬ ‫ﺒﻭﺘﺎﻥ‬
‫‪Butane-1‬‬ ‫‪37‬‬ ‫‪1.10‬‬ ‫ﺒﻭﺘﺎﻥ‪1-‬‬
‫‪Carbon‬‬ ‫ﺩﻴﺴﻭﻟﻔﻴﺕ ﺍﻟﻜﺎﺭﺒﻭﻥ‬
‫‪72‬‬ ‫‪3.03‬‬
‫‪disulphide‬‬
‫‪Carbon monoxide‬‬ ‫‪64‬‬ ‫‪2.43‬‬ ‫ﺃﻭل ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ‬
‫‪Coal or natural‬‬ ‫ﺍﻟﻔﺤﻡ ﺃﻭ ﺍﻟﻐﺎﺯ ﺍﻟﻁﺒﻴﻌﻲ‬
‫‪37‬‬ ‫‪1.10‬‬
‫‪gas‬‬
‫‪Cyclopropane‬‬ ‫‪37‬‬ ‫‪1.10‬‬ ‫ﺴﺎﻴﻜﻠﻭ ﺒﺭﻭﺒﻴﻥ‬
‫‪Diesel fuel‬‬ ‫‪34‬‬ ‫‪1.00‬‬ ‫ﻭﻗﻭﺩ ﺍﻟﺩﻴﺯل‬
‫‪Diethyl ether‬‬ ‫‪46‬‬ ‫‪1.47‬‬ ‫ﺩﻴﺜﻴل ﺍﻴﺜﺭ‬
‫‪Dimethyl ether‬‬ ‫‪40‬‬ ‫‪1.22‬‬ ‫ﺩﻴﻤﻴﺜﻴل ﺇﻴﺜﺭ‬
‫‪Dowtherm‬‬ ‫‪46‬‬ ‫‪1.47‬‬ ‫ﺩﺍﻭ ﺜﻴﺭﻡ‬
‫‪Ethane‬‬ ‫‪40‬‬ ‫‪1.22‬‬ ‫ﺍﻴﺜﺎﻥ‬
‫‪Ethyl alcohol‬‬ ‫‪43‬‬ ‫‪1.34‬‬ ‫ﺍﻟﻜﺤﻭل ﺍﻻﻴﺜﻴﻠﻲ‬
‫‪Ethyl ether‬‬ ‫‪46‬‬ ‫‪1.47‬‬ ‫ﺍﻻﻴﺜﺭ ﺍﻻﻴﺘﻴﻠﻲ‬
‫‪Ethylene‬‬ ‫‪49‬‬ ‫‪1.60‬‬ ‫ﺍﻻﻴﺜﻴﻠﻴﻥ‬
‫‪Ethylene‬‬ ‫ﺍﻴﺜﻴﻠﻴﻥ ﺜﻨﺎﺌﻲ ﺍﻟﻜﻠﻭﺭ‬
‫‪34‬‬ ‫‪1.00‬‬
‫‪dichloride‬‬
‫‪Ethylene oxide‬‬ ‫‪53‬‬ ‫‪1.80‬‬ ‫ﺃﻭﻜﺴﻴﺩ ﺍﻻﻴﺜﻴﻠﻴﻥ‬
‫‪Gasoline‬‬ ‫‪34‬‬ ‫‪1.00‬‬ ‫ﺍﻟﻐﺎﺯﻭﻟﻴﻥ‬
‫‪Hexane‬‬ ‫‪35‬‬ ‫‪1.03‬‬ ‫ﺍﻟﻬﻴﻜﺴﺎﻥ‬
‫‪n-Heptane‬‬ ‫‪35‬‬ ‫‪1.03‬‬ ‫ﻥ‪-‬ﻫﻴﺒﺘﺎﻥ‬
‫‪Hydrogen‬‬ ‫‪75‬‬ ‫‪3.30‬‬ ‫ﻫﻴﺩﺭﻭﺠﻴﻥ‬

‫‪17‬‬
‫ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﺘﺼﻤﻴﻤﻲ‬
‫‪Material‬‬ ‫‪KB‬‬ ‫ﺍﻟﻤـــﺎﺩﺓ‬
‫ﺍﻟﻼﺯﻡ ‪%‬‬
‫‪Hydrogen‬‬ ‫ﺴﻠﻔﺎﺕ ﺍﻟﻬﻴﺩﺭﻭﺠﻴﻥ‬
‫‪36‬‬ ‫‪1.06‬‬
‫‪sulphide‬‬
‫‪Isobutane‬‬ ‫‪36‬‬ ‫‪1.06‬‬ ‫ﺇﻴﺯﻭﺒﻭﺘﺎﻥ‬
‫‪Isobutylene‬‬ ‫‪34‬‬ ‫‪1.00‬‬ ‫ﺇﻴﺯﻭﺒﻭﺘﻴﻠﻴﻥ‬
‫‪Isobutyl formate‬‬ ‫‪34‬‬ ‫‪1.00‬‬ ‫ﻤﺭﻜﺒﺎﺕ ﺍﻹﻴﺯﻭﺒﻭﺘﻴل‬
‫‪JP-4‬‬ ‫‪36‬‬ ‫‪1.06‬‬ ‫‪JP-4‬‬
‫‪Kerosene‬‬ ‫‪34‬‬ ‫‪1.00‬‬ ‫ﻜﻴﺭﻭﺴـﻴﻥ‬
‫‪Methane‬‬ ‫‪34‬‬ ‫‪1.00‬‬ ‫ﻤﻴﺜﺎﻥ‬
‫‪Methyl acetate‬‬ ‫‪35‬‬ ‫‪1.03‬‬ ‫ﻤﻴﺜﻴل ﺃﺴﻴﺘﺎﺕ‬
‫‪Methyl alcohol‬‬ ‫‪40‬‬ ‫‪1.22‬‬ ‫ﺍﻟﻜﺤﻭل ﺍﻟﻤﻴﺜﻴﻠﻲ‬
‫‪Methyl butane-1‬‬ ‫‪36‬‬ ‫‪1.06‬‬ ‫ﺍﻟﺒﻭﺘﺎﻥ ﺍﻟﻤﻴﺜﻴﻠﻲ‪1-‬‬
‫‪Methyl ethyl‬‬ ‫‪Methyl ethyl‬‬
‫‪40‬‬ ‫‪1.22‬‬
‫‪ketone‬‬ ‫‪ketone‬‬
‫‪Methyl formate‬‬ ‫‪39‬‬ ‫‪1.18‬‬ ‫ﻤﺭﻜﺒﺎﺕ ﺍﻟﻤﻴﺜﻴل‬
‫‪n-octane‬‬ ‫‪35‬‬ ‫‪1.03‬‬ ‫ﻥ‪-‬ﺃﻭﻜﺘﺎﻥ‬
‫‪Natural gas‬‬ ‫‪37‬‬ ‫‪1.10‬‬ ‫ﺍﻟﻐﺎﺯ ﺍﻟﻁﺒﻴﻌﻲ‬
‫‪Pentane‬‬ ‫‪35‬‬ ‫‪1.03‬‬ ‫ﺍﻟﺒﻨﺘﺎﻥ‬
‫‪Propane‬‬ ‫‪36‬‬ ‫‪1.06‬‬ ‫ﺒﺭﻭﺒﺎﻥ‬
‫‪Propylene‬‬ ‫‪36‬‬ ‫‪1.06‬‬ ‫ﺒﺭﻭﺒﻴﻠﻴﻥ‬
‫‪Toluene‬‬ ‫‪42‬‬ ‫‪1.30‬‬ ‫ﺍﻟﺘﻭﻟﻭﻭﻴﻥ‬
‫‪Quench/lube oils‬‬ ‫‪34‬‬ ‫‪1.00‬‬ ‫ﺯﻴﺕ ﺴﻘﺎﻴﺔ ﺍﻟﻔﻭﻻﺫ‬
‫ﺠﺩﻭل )‪(2‬‬

‫ﻭﻴﺒﻴﻥ ﺍﻟﺠﺩﻭل ﺍﻟﺘﺎﻟﻲ ﻗﻴﻤﺔ ﻤﻌﺎﻤل ﺍﻟﺘﺭﻜﻴﺯ ‪ KB‬ﻟﺒﻌﺽ ﺃﻤﺎﻜﻥ ﺍﻟﺘﺠﻬﻴﺯﺍﺕ ﺍﻟﺨﺎﺼﺔ‪:‬‬

‫ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﺘﺼﻤﻴﻤﻲ ﺍﻟﻼﺯﻡ ‪%‬‬ ‫‪KB‬‬ ‫ﻁﺒﻴﻌﺔ ﻋﻤل ﺍﻟﻤﻜﺎﻥ‬


‫‪47‬‬ ‫)‪1.50(a‬‬ ‫ﺤﺠﺭ ﻭﻤﺠﺎﺭﻱ ﺍﻟﻜﺎﺒﻼﺕ‬
‫ﺍﻟﺤﺎﺴﻭﺏ ﻭﺍﻟﻤﻌﺩﺍﺕ‬
‫‪40‬‬ ‫)‪1.20(a) (b‬‬ ‫ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‬
‫‪47‬‬ ‫)‪1.50(a‬‬ ‫ﺘﺠﻬﻴﺯﺍﺕ ﺍﻟﺤﻭﺍﺴﻴﺏ‬

‫‪18‬‬
‫ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﺘﺼﻤﻴﻤﻲ ﺍﻟﻼﺯﻡ ‪%‬‬ ‫‪KB‬‬ ‫ﻁﺒﻴﻌﺔ ﻋﻤل ﺍﻟﻤﻜﺎﻥ‬
‫ﺍﻟﻘﻭﺍﻁﻊ ﺍﻟﻜﻬﺭﺒﻠﺌﻴﺔ‬
‫‪40‬‬ ‫)‪1.20(a‬‬ ‫ﻭﻏﺭﻑ ﺍﻟﺘﻭﺯﻴﻊ‬
‫‪57‬‬ ‫)‪2.00(a) (c‬‬ ‫ﺍﻟﻤﻭﻟﺩﺍﺕ ﻭﺃﻨﻅﻤﺔ ﺍﻟﺘﻜﻴﻴﻑ‬
‫ﺍﻟﻤﺤﻭﻻﺕ ﺍﻟﺘﻲ ﺘﺤﺘﻭﻱ‬
‫‪57‬‬ ‫)‪2.00(a‬‬ ‫ﺍﻟﺯﻴﺕ‬
‫‪61‬‬ ‫)‪2.25(a) (d‬‬ ‫ﻜﺎﻓﺔ ﺃﻨﻭﺍﻉ ﺍﻟﻁﺒﺎﻋﺔ‬
‫ﺭﺵ ﺍﻟﺩﻫﺎﻥ ﻭﺃﺩﻭﺍﺕ‬
‫‪40‬‬ ‫‪1.20‬‬ ‫ﺍﻟﺘﺠﻔﻴﻑ‬
‫‪57‬‬ ‫)‪2.00(a‬‬ ‫ﺁﻻﺕ ﺍﻟﻐﺯل‬
‫ﺠﺩﻭل )‪(3‬‬

‫ﺤﻴﺙ‪:‬‬

‫)‪: (a‬ﻴﺠﺏ ﺍﻹﺒﻘﺎﺀ ﻋﻠﻰ ﺘﺭﻜﻴﺯ ‪ %34‬ﻋﻠﻰ ﺍﻷﻗل ﻟﻤﺩﺓ ‪ 10‬ﺩﻗﺎﺌﻕ‪.‬‬ ‫•‬
‫)‪: (b‬ﺃﻤﺎﻜﻥ ﻤﺴـﺘﺨﺩﻤﺔ ﻓﻘﻁ ﻟﻠﺘﺠﻬﻴﺯﺍﺕ ﺍﻹﻟﻴﻜﺘﺭﻭﻨﻴﺔ ﺍﻟﺘﻲ ﻻ ﻴﺴـﻤﺢ ﻓﻴﻬﺎ‬ ‫•‬
‫ﺒﺘﺨﺯﻴﻥ ﺃﻭ ﺘﺩﺍﻭل ﺃﻱ ﻤﻭﺍﺩ ﺃﺨﺭﻯ ﻗﺎﺒﻠﺔ ﻟﻼﺸﺘﻌﺎل‪.‬‬
‫)‪: (c‬ﻴﺠﺏ ﺇﻁﺎﻟﺔ ﺯﻤﻥ ﺍﻹﺒﻘﺎﺀ ﺤﺘﻰ ﺘﻭﻗﻑ ﺍﻟﻤﻭﻟﺩ ﺍﻟﻜﻬﺭﺒﺎﺌﻲ ﻋﻥ ﺍﻟﻌﻤل‪.‬‬ ‫•‬
‫)‪: (d‬ﻴﺴـﻤﺢ ﻓﻲ ﻫﺫﻩ ﺍﻷﻤﺎﻜﻥ ﺒﻤﻌﺎﻤﻠﺔ ﺍﻟﻭﺭﻕ ﻭﻟﻴـﺱ ﺒﺘﺨﺯﻴﻨﻪ‪.‬‬ ‫•‬

‫ﺤﺴـﺎﺏ ﻜﻤﻴﺔ ﺍﻟﻐﺎﺯ ﺍﻟﻭﺍﺠﺏ ﺘﺭﻜﻴﺒﻬﺎ ﻓﻲ ﺍﻟﻨﻅﺎﻡ‪:‬‬

‫ﺇﻥ ﻜﻤﻴﺔ ﺍﻟﻐﺎﺯ ﺍﻟﻤﺭﻜﺒﺔ ﻋﻠﻰ ﺍﻟﻨﻅﺎﻡ ﻟﻤﻨﻁﻘﺔ ﻤﺤﺴـﻭﺒﺔ ﻤﺎ‪ ،‬ﻴﺠﺏ ﻋﻠﻰ ﺍﻷﻗل ﺃﻥ‬
‫ﺘﺴـﺎﻭﻱ ﻜﻤﻴﺔ ﺍﻟﻐﺎﺯ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﻬﺫﻩ ﺍﻟﻤﻨﻁﻘﺔ ﻤﻀﺎﻓﺎ" ﺇﻟﻴﻬﺎ ﺍﻟﻜﻤﻴﺎﺕ ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬
‫‪ .1‬ﻴﺠﺏ ﺇﻀﺎﻓﺔ ﻜﻤﻴﺔ ﺃﺨﺭﻯ ﻟﺘﻐﻁﻴﺔ ﺍﻟﺘﺴـﺭﺏ ﺍﻟﺫﻱ ﻗﺩ ﻴﺤﺼل ﻋﻠﻰ ﺍﻟﺭﻏﻡ ﻤﻥ‬
‫ﺍﻹﺤﻜﺎﻡ ﻭﻜﺫﻟﻙ ﻜﻤﻴﺔ ﺍﻟﻐﺎﺯ ﺍﻟﻤﻭﺠﻭﺩﺓ ﻓﻲ ﺍﻷﻨﺎﺒﻴﺏ ﻭﺍﻟﺘﻭﺼﻴﻼﺕ‪ ،‬ﻭﺘﻘﺩﺭ‬
‫ﺍﻟﻜﻤﻴﺔ ﺍﻹﻀﺎﻓﻴﺔ ﺒﺤﻭﺍﻟﻲ ‪ %10‬ﻤﻥ ﺍﻟﻜﻤﻴﺔ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﻸﻨﻅﻤﺔ ﺍﻟﺤﺎﻭﻴﺔ ﻋﻠﻰ‬
‫ﺃﺴـﻁﻭﺍﻨﺎﺕ ﺤﺘﻰ ‪ 19‬ﺃﺴـﻁﻭﺍﻨﺔ‪ ،‬ﻓﻲ ﺤﻴﻥ ﻨﺤﺘﺴـﺏ ﺍﻟﻜﻤﻴﺔ ﺍﻹﻀﺎﻓﻴﺔ‬
‫‪ %15‬ﻤﻥ ﺍﻟﻜﻤﻴﺔ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﻸﻨﻅﻤﺔ ﺍﻟﺤﺎﻭﻴﺔ ﻋﻠﻰ ‪ 20‬ﺃﺴـﻁﻭﺍﻨﺔ ﺃﻭ ﺃﻜﺜﺭ‪.‬‬
‫‪ .2‬ﺒﺎﻟﻨﺴﺒﺔ ﻷﻨﻅﻤﺔ ﺍﻟﻀﻐﻁ ﺍﻟﻤﻨﺨﻔﺽ ﻤﻥ ‪ CO2‬ﻴﺠﺏ ﺃﻥ ﺘﺤﺴـﺏ ﻜﻤﻴﺔ ﻏﺎﺯ‬
‫‪ CO2‬ﺍﻟﻤﺴﻴل ﻭﺍﻟﺘﻲ ﺘﻤﻸ ﺍﻷﻨﺎﺒﻴﺏ ﻓﻲ ﻁﻭﺭﻩ ﺍﻟﺴـﺎﺌل ﻭﺃﻥ ﺘﻀﺎﻑ ﻫﺫﻩ‬
‫ﺍﻟﻜﻤﻴﺔ ﺇﻟﻰ ﺍﻟﻜﻤﻴﺔ ﺍﻟﻤﺭﻜﺒﺔ‪.‬‬

‫‪19‬‬
‫ﻓﻲ ﺤﺎل ﻭﺠﻭﺩ ﺴـﻭﺍﺌل ﻗﺎﺒﻠﺔ ﻟﻼﺸﺘﻌﺎل ﻭﺫﺍﺕ ﺤﺭﺍﺭﺓ ﻋﺎﻟﻴﺔ ﻀﻤﻥ ﺍﻟﻤﻨﻁﻘﺔ‬ ‫‪.3‬‬
‫ﺍﻟﻤﺤﺴﻭﺒﺔ ﻴﺠﺏ ﺃﻥ ﻴﺼﻤﻡ ﺍﻟﻨﻅﺎﻡ ﺒﺤﻴﺙ ﺘﻜﻭﻥ ﻫﻨﺎﻙ ﺇﻤﻜﺎﻨﻴﺔ ﻟﻐﻤﺭ ﺍﻟﻤﻨﻁﻘﺔ‬
‫ﻤﺭﺘﻴﻥ ﺒﺎﻟﻐﺎﺯ‪ ،‬ﻋﻠﻰ ﺃﻥ ﻴﻜﻭﻥ ﺍﻟﺘﺤﻜﻡ ﻤﺴـﺘﻘل ﺒﻴﻥ ﺍﻟﻤﺭﺘﻴﻥ‪.‬‬
‫ﻓﻲ ﺤﺎل ﻜﻭﻥ ﺩﺭﺠﺔ ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﻤﺤﻴﻁﻴﺔ ﺃﻜﺒﺭﻤﻥ )‪ (+100‬ﺩﺭﺠﺔ ﻤﺌﻭﻴﺔ‪،‬‬ ‫‪.4‬‬
‫ﻴﺠﺏ ﺇﻀﺎﻓﺔ ‪ %2‬ﻤﻥ ﺍﻟﻜﻤﻴﺔ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﻜل ﺨﻤﺱ ﺩﺭﺠﺎﺕ ﺃﻋﻠﻰ ﻤﻥ ﺩﺭﺠﺔ‬
‫ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﻤﺫﻜﻭﺭﺓ‪.‬‬
‫ﻓﻲ ﺤﺎل ﻜﻭﻥ ﺩﺭﺠﺔ ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﺨﺎﺭﺠﻴﺔ ﺃﻗل ﻤﻥ )‪ (-20‬ﺩﺭﺠﺔ ﻤﺌﻭﻴﺔ‪ ،‬ﻴﺠﺏ‬ ‫‪.5‬‬
‫ﺇﻀﺎﻓﺔ ‪ %2‬ﻤﻥ ﺍﻟﻜﻤﻴﺔ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﻜل ﺩﺭﺠﺔ ﺃﺨﻔﺽ ﻤﻥ ﺩﺭﺠﺔ ﺍﻟﺤﺭﺍﺭﺓ‬
‫ﺍﻟﻤﺫﻜﻭﺭﺓ‪.‬‬
‫ﻻ ﻴﺴـﻤﺢ ﺒﻭﺼل ﺃﻜﺜﺭ ﻤﻥ ‪ 30‬ﻤﻨﻁﻘﺔ ﻤﺤﺴـﻭﺒﺔ ﻋﻠﻰ ﻨﻅﺎﻡ ﻭﺍﺤﺩ ﻤﺘﻌﺩﺩ‬ ‫‪.6‬‬
‫ﺍﻟﻤﻨﺎﻁﻕ‪.‬‬

‫ﻜﻤﻴﺔ ﺍﻟﻐﺎﺯ ﺍﻟﻭﺍﺠﺏ ﺘﺨﺯﻴﻨﻬﺎ‪:‬‬

‫ﻴﺠﺏ ﺃﻥ ﺘﺨﺯﻥ ﻓﻲ ﺍﻟﻤﻭﻗﻊ ﻜﻤﻴﺔ ﻤﻤﺎﺜﻠﺔ ﻟﻠﻜﻤﻴﺔ ﺍﻟﻤﺭﻜﺒﺔ ﻋﻠﻰ ﺃﻱ ﻨﻅﺎﻡ ﻓﻲ ﺃﻱ ﻤﻥ‬
‫ﺍﻟﺤﺎﻻﺕ ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬
‫‪ .1‬ﻨﻅﺎﻡ ﻤﺘﻌﺩﺩ ﺍﻟﻤﻨﺎﻁﻕ ﻴﻐﻁﻲ ﺃﻜﺜﺭ ﻤﻥ ﺨﻤـﺱ ﻤﻨﺎﻁﻕ ﺤﺴـﺎﺒﻴﺔ ﻤﻨﻔﺼﻠﺔ‪.‬‬
‫‪ .2‬ﻓﻲ ﺤﺎل ﻋﺩﻡ ﺇﻤﻜﺎﻨﻴﺔ ﺘﻌﻭﻴﺽ ﺍﻟﻜﻤﻴﺔ ﺍﻟﺘﻲ ﻗﺩ ﺘﺴـﺘﺨﺩﻡ ﻓﻲ ﺯﻤﻥ ﻻ ﻴﺯﻴﺩ ﻋﻥ‬
‫‪ 36‬ﺴـﺎﻋﺔ‪.‬‬

‫ﺘﺨﺯﻴﻥ ﻭﻭﺼل ﺃﺴـﻁﻭﺍﻨﺎﺕ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪:CO2‬‬

‫ﻴﺠﺏ ﺘﺨﺯﻴﻥ ﺃﺴـﻁﻭﺍﻨﺎﺕ ‪ CO2‬ﺍﻟﻤﺭﻜﺒﺔ ﻋﻠﻰ ﺍﻟﻨﻅﺎﻡ ﺃﻭ ﺍﻟﻤﺨﺯﻨﺔ ﻟﻼﺴـﺘﺒﺩﺍل‬


‫ﺒﺤﻴﺙ ﻴﺴـﻬل ﺍﻟﻭﺼﻭل ﺇﻟﻴﻬﺎ ﻓﻲ ﺃﻱ ﻭﻗﺕ ﻤﻥ ﻗﺒل ﺍﻷﺸـﺨﺎﺹ ﺍﻟﻤﺨﻭﻟﻴﻥ ﻭﺒﺤﻴﺙ‬
‫ﻻ ﻴﻤﻜﻥ ﺍﺴـﺘﺨﺩﺍﻤﻬﺎ ﻷﻏﺭﺍﺽ ﺃﺨﺭﻯ‪.‬‬

‫ﻜﻤﺎ ﻴﺠﺏ ﺃﻥ ﻴﺘﻡ ﺘﻭﺤﻴﺩ ﺃﺤﺠﺎﻡ ﺍﻷﺴـﻁﻭﺍﻨﺎﺕ ﻭﻀﻐﻭﻁﻬﺎ ﺒﺎﻟﻨﺴـﺒﺔ ﻟﻠﻨﻅﺎﻡ ﻭﺃﻥ‬
‫ﺘﺘﺭﺍﻭﺡ ﺒﻴﻥ ‪ 10.4‬ﺃﻭ ‪ 67.5‬ﻟﻴﺘﺭﺍ" ﻟﻸﺴـﻁﻭﺍﻨﺔ ﺍﻟﻭﺍﺤﺩﺓ‪.‬‬

‫ﻓﻲ ﺤﺎل ﺍﺤﺘﻭﻯ ﺍﻟﻨﻅﺎﻡ ﺫﻭ ﺍﻟﻀﻐﻁ ﺍﻟﻤﺭﺘﻔﻊ ﻋﻠﻰ ﺃﻜﺜﺭ ﻤﻥ ﺃﺴـﻁﻭﺍﻨﺔ ﻴﺠﺏ ﺃﻥ‬
‫ﺘﺘﻭﻀﻊ ﺍﻷﺴـﻁﻭﺍﻨﺎﺕ ﺒﺸـﻜل ﻋﺎﻤﻭﺩﻱ ﻭﺃﻥ ﻴﺘﻴﺢ ﺍﻟﺘﺼﻤﻴﻡ ﻓﻙ ﻭﺘﺭﻜﻴﺏ ﺃﻱ ﻤﻥ‬
‫ﺍﻷﺴـﻁﻭﺍﻨﺎﺕ ﺩﻭﻥ ﺃﻥ ﻴﺅﺜﺭ ﺫﻟﻙ ﻋﻠﻰ ﺍﻟﻨﻅﺎﻡ ﻭﺃﻥ ﺘﺯﻭﺩ ﻜل ﺃﺴـﻁﻭﺍﻨﺔ ﺒﺼﻤﺎﻡ‬
‫‪ Check Valve‬ﻗﺒل ﺃﻥ ﺘﻭﺼل ﺇﻟﻰ ﺍﻟﻤﺎﻨﻴﻔﻭﻟﺩ‪.‬‬

‫‪20‬‬
‫ﻴﺠﺏ ﺃﻥ ﺘﺘﻡ ﻤﺭﺍﻗﺒﺔ ﺍﻟﻜﻤﻴﺔ ﺍﻟﻤﺨﺯﻨﺔ ﻭﺍﻟﻜﻤﻴﺔ ﺍﻟﻤﺘﺼﻠﺔ ﺒﺎﻟﻨﻅﺎﻡ ﻤﻥ ﺠﻬﺔ ﺤﺩﻭﺙ‬
‫ﺘﺴـﺭﺒﺎﺕ ﻁﺎﺭﺌﺔ ﻭﻓﻲ ﺤﺎل ﻨﻘﺼﺎﻥ ﺍﻟﻜﻤﻴﺔ ﺒﻤﻌﺩل ﻗﺭﻴﺏ ﻤﻥ ‪ %10‬ﻴﺠﺏ ﺃﻥ ﻴﺘﻡ‬
‫ﺇﺠﺭﺍﺀ ﻓﺤﺹ ﺸـﺎﻤل ﻟﻸﺴـﻁﻭﺍﻨﺎﺕ ﻭﻟﻨﻅﺎﻡ ﺍﻟﻭﺼل ﻭﺍﻟﺘﺤﻜﻡ‪.‬‬

‫ﺒﺎﻟﻨﺴﺒﺔ ﻷﻨﻅﻤﺔ ﺍﻟﻀﻐﻁ ﺍﻟﻤﻨﺨﻔﺽ ﻴﺠﺏ ﺃﻥ ﺘﺯﻭﺩ ﺒﻨﻅﺎﻡ ﺘﺒﺭﻴﺩ ﺃﻭﺘﻭﻤﺎﺘﻴﻜﻲ ﻟﺘﺒﻘﻲ‬
‫ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﺒﻀﻐﻁ ﻤﺎ ﺒﻴﻥ ‪ 19‬ﻭ ‪ 21‬ﺒﺎﺭ‪ ،‬ﻜﻤﺎ ﻴﺠﺏ ﻋﺯﻟﻬﺎ‬
‫ﻟﺘﺨﻔﻴﻑ ﻀﻴﺎﻉ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪.CO2‬‬

‫ﻻ ﻴﺴـﻤﺢ ﺒﺘﺭﻜﻴﺏ ﻨﻅﺎﻡ ﻀﻐﻁ ﻤﻨﺨﻔﺽ ﺇﺫﺍ ﻜﺎﻨﺕ ﺩﺭﺠﺔ ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﻤﺤﻴﻁﻴﺔ ﻗﺩ‬
‫ﺘﺭﺘﻔﻊ ﻷﻜﺜﺭ ﻤﻥ ‪ 35‬ﺩﺭﺠﺔ ﻤﺌﻭﻴﺔ‪.‬‬

‫ﻻ ﻴﺠﺏ ﺃﻥ ﻴﺯﻴﺩ ﻤﻌﺩل ﺍﻟﺘﺴـﺭﺏ ﻋﻥ ‪ %1.5‬ﻜل ‪ 24‬ﺴﺎﻋﺔ ﻓﻲ ﺤﺎل ﺘﻭﻗﻑ ﻨﻅﺎﻡ‬


‫ﺍﻟﺘﺒﺭﻴﺩ ﺍﻷﻭﺘﻭﻤﺎﺘﻴﻜﻲ ﻟﻨﻅﺎﻡ ﺫﻭ ﻀﻐﻁ ﻤﻨﺨﻔﺽ‪.‬‬

‫ﻴﺠﺏ ﺃﻥ ﻴﺘﻡ ﻭﺼل ﺼﻤﺎﻡ ﺃﻤﺎﻥ ﻤﻥ ﺍﺭﺘﻔﺎﻉ ﺍﻟﻀﻐﻁ ﻟﺨﺯﺍﻥ ﻨﻅﺎﻡ ﺍﻟﻀﻐﻁ ﺍﻟﻤﻨﺨﻔﺽ‬
‫ﺒﺤﻴﺙ ﻴﺘﺴـﺭﺏ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴـﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ﺍﻟﻤﻨﻁﻠﻕ ﻨﺘﻴﺠﺔ ﻻﺭﺘﻔﺎﻉ ﺍﻟﻀﻐﻁ ﺇﻟﻰ‬
‫ﻤﻜﺎﻥ ﻻ ﻴﺴـﺒﺏ ﻓﻴﻪ ﺍﻟﺘﺴـﺭﺏ ﺃﺫﻯ ﻟﻸﺸـﺨﺎﺹ‪.‬‬

‫ﺸـﺭﻭﻁ ﻤﻜﺎﻥ ﺘﺨﺯﻴﻥ ﺃﺴـﻁﻭﺍﻨﺎﺕ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪:CO2‬‬

‫ﻴﺠﺏ ﺃﻥ ﺘﺨﺯﻥ ﺃﺴـﻁﻭﺍﻨﺎﺕ ﺍﻟﻨﻅﺎﻡ ﺍﻟﻌﺎﻤل ﺒﻐﺎﺯ‪ CO2‬ﻓﻲ ﻏﺭﻓﺔ ﻤﻨﻔﺼﻠﺔ ﻏﻴﺭ‬
‫ﻤﻌﺭﻀﺔ ﻟﻠﺤﺭﻴﻕ )ﻋﺩﻡ ﻭﺠﻭﺩ ﺇﻤﻜﺎﻨﻴﺔ ﺤﺩﻭﺙ ﺤﺭﻴﻕ ﻓﻴﻬﺎ( ﻭﻗﺭﻴﺒﺔ ﻗﺩﺭ ﺍﻹﻤﻜﺎﻥ ﻤﻥ‬
‫ﺍﻟﺤﻴﺯ ﺍﻟﻤﺤﻤﻲ ﺒﻬﺫﺍ ﺍﻟﻨﻅﺎﻡ )ﺴـﻭﺍﺀ ﻜﺎﻥ ﻨﻅﺎﻡ ﻤﺘﻌﺩﺩ ﺍﻟﻤﻨﺎﻁﻕ ﺃﻭ ﻭﺤﻴﺩ ﺍﻟﻤﻨﻁﻘﺔ(‪،‬‬
‫ﻜﻤﺎ ﻴﺠﺏ ﺃﻥ ﺘﺤﻘﻕ ﺍﻟﺸـﺭﻭﻁ ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬
‫• ﺴـﻬﻭﻟﺔ ﺍﻟﻭﺼﻭل ﺇﻟﻴﻬﺎ ﺤﺘﻰ ﻓﻲ ﺤﺎل ﻭﺠﻭﺩ ﺤﺭﻴﻕ ﻓﻲ ﺍﻟﻤﻜﺎﻥ ﺍﻟﻤﺤﻤﻲ ﺒﻬﺫﺍ‬
‫ﺍﻟﻨﻅﺎﻡ‬
‫• ﻤﺤﻤﻴﺔ ﻤﻥ ﺩﺨﻭل ﺍﻟﻌﻨﺎﺼﺭ ﻏﻴﺭ ﺍﻟﻤﺨﻭﻟﻴﻥ ﺒﺎﻟﺩﺨﻭل‪.‬‬
‫• ﻤﺴـﺘﺨﺩﻤﺔ ﻟﻐﺭﺽ ﺘﺨﺯﻴﻥ ﺍﻷﺴـﻁﻭﺍﻨﺎﺕ ﻓﻘﻁ‪.‬‬
‫• ﺍﻟﻤﺤﺎﻓﻅﺔ ﻋﻠﻰ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺘﺘﺭﺍﻭﺡ ﺒﻴﻥ ﺼﻔﺭ ﻭ ‪ 35‬ﺩﺭﺠﺔ ﻤﺌﻭﻴﺔ ﺩﺍﺨل‬
‫ﺍﻟﻐﺭﻓﺔ‪.‬‬
‫• ﻤﺯﻭﺩﺓ ﺒﻨﻅﺎﻡ ﺘﻬﻭﻴﺔ ﻗﺴـﺭﻴﺔ ﻟﺘﺠﻨﺏ ﺘﻌﺭﺽ ﺍﻷﺸـﺨﺎﺹ ﺍﻟﻠﺫﻴﻥ ﻗﺩ ﻴﺘﻭﺍﺠﺩﻭﺍ‬
‫ﻓﻲ ﻫﺫﻩ ﺍﻟﻐﺭﻓﺔ ﻟﻼﺨﺘﻨﺎﻕ ﻓﻲ ﺤﺎل ﺤﺩﻭﺙ ﺘﺴـﺭﺏ‪.‬‬
‫• ﻴﺠﺏ ﺃﻥ ﻴﻜﻭﻥ ﺘﻭﻀﻊ ﺃﺴـﻁﻭﺍﻨﺎﺕ ﻭﻤﻜﻭﻨﺎﺕ ﺍﻟﻨﻅﺎﻡ ﺒﻁﺭﻴﻘﺔ ﺘﺴـﻬل ﺇﺠﺭﺍﺀ‬
‫ﺍﻟﺼﻴﺎﻨﺔ ﻭﺍﻻﺨﺘﺒﺎﺭ ﻟﻬﺫﺍ ﺍﻟﻨﻅﺎﻡ‪.‬‬
‫• ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﺍﻟﻐﺭﻓﺔ ﻤﻨﺎﺭﺓ ﺒﺸـﻜل ﻜﺎﻓﻲ‪.‬‬

‫‪21‬‬
‫• ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﺍﻟﻐﺭﻓﺔ ﻤﺤﻤﻴﺔ ﻤﻥ ﺃﺸـﻌﺔ ﺍﻟﺸـﻤﺱ ﺍﻟﻤﺒﺎﺸـﺭﺓ‪.‬‬
‫• ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﺘﻌﻠﻴﻤﺎﺕ ﺘﺸـﻐﻴل ﺍﻟﻨﻅﺎﻡ ﻤﺜﺒﺘﺔ ﺩﺍﺌﻤﺎ" ﺒﺸـﻜل ﻭﺍﻀﺢ ﺩﺍﺨل‬
‫ﺍﻟﻐﺭﻓﺔ‪.‬‬
‫• ﻴﺠﺏ ﺃﻥ ﻴﺘﻭﺍﺠﺩ ﺩﺍﺨل ﺍﻟﻐﺭﻓﺔ ﻭﺒﺸـﻜل ﺩﺍﺌﻡ ﺴـﺠل ﺨﺎﺹ ﺒﺎﻟﻨﻅﺎﻡ ﻴﺫﻜﺭ ﻓﻴﻪ‬
‫ﻜﺎﻓﺔ ﺍﻟﻤﻌﻠﻭﻤﺎﺕ ﺍﻟﻀﺭﻭﺭﻴﺔ ﻋﻥ ﺍﻟﻨﻅﺎﻡ ﻭﺘﻌﻠﻴﻤﺎﺕ ﺍﻟﺘﺸـﻐﻴل ﻭﺍﻟﺘﻔﺘﻴـﺵ‬
‫ﻭﺍﻟﺼﻴﺎﻨﺔ ﺍﻟﻤﺫﻜﻭﺭﺓ ﻓﻲ ﺍﻟﺘﻌﻠﻴﻤﺎﺕ ﺍﻟﺘﻨﻔﻴﺫﻴﺔ‪.‬‬

‫ﺯﻤﻥ ﺍﻟﻐﻤﺭ‪:‬‬

‫ﺇﻥ ﺯﻤﻥ ﺍﻟﻐﻤﺭ ﺒﺎﻟﻨﺴـﺒﺔ ﻟﻸﻨﻅﻤﺔ ﺍﻟﻌﺎﻤﻠﺔ ﺒﻐﺎﺯ ‪ CO2‬ﻴﺠﺏ ﺃﻥ ﻻ ﻴﺯﻴﺩ ﻋﻥ )‪(60‬‬
‫ﺜﺎﻨﻴﺔ‪ ،‬ﺒﺎﺴﺘﺜﻨﺎﺀ ﺍﻟﻜﻤﻴﺎﺕ ﺍﻟﺘﻲ ﺘﺘﺠﺎﻭﺯ ‪ 3‬ﻁﻥ ﻤﻥ ‪ CO2‬ﺤﻴﺙ ﻴﺼل ﺍﻟﺯﻤﻥ‬
‫ﺇﻟﻰ)‪(120‬ﺜﺎﻨﻴﺔ ﻭﻴﺠﺏ ﺃﻥ ﻻ ﺘﺯﻴﺩ ﻓﺘﺭﺓ ﺍﻟﻭﺼﻭل ﺇﻟﻰ ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﺘﺼﻤﻴﻤﻲ ﻋﻥ‬
‫)‪ (240‬ﺜﺎﻨﻴﺔ‪.‬‬

‫ﺯﻤﻥ ﺍﻹﺒﻘﺎﺀ‪:‬‬

‫ﻴﺠﺏ ﺃﻥ ﻻ ﻴﻘل ﺯﻤﻥ ﺍﻹﺒﻘﺎﺀ ﻟﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ﻓﻲ ﺍﻟﻤﻜﺎﻥ ﺍﻟﻤﺤﻤﻲ ﻋﻥ‬
‫ﻋﺸـﺭ ﺩﻗﺎﺌﻕ ﻭﺫﻟﻙ ﻟﺘﻘﻠﻴل ﺍﺤﺘﻤﺎل ﺘﺠﺩﺩ ﺍﻟﺤﺭﻴﻕ ﻤﺭﺓ ﺃﺨﺭﻯ‪.‬‬

‫‪22‬‬
‫ﺘﺼﻤﻴﻡ ﺸـﺒﻜﺔ ﺍﻟﺘﻭﺯﻴﻊ‬

‫ﺇﻥ ﺍﻟﺤﺴـﺎﺒﺎﺕ ﺍﻟﻬﻴﺩﺭﻭﻟﻴﻜﻴﺔ ﻟﻤﻜﻭﻨﺎﺕ ﺍﻟﻨﻅﺎﻡ ﻴﺠﺏ ﺃﻥ ﺘﺄﺨﺫ ﺒﻌﻴﻥ ﺍﻻﻋﺘﺒﺎﺭ ﺃﻥ‬
‫ﺍﻟﻜﻤﻴﺔ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴـﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻭﺍﻟﺘﻲ ﺘﻡ ﺤﺴـﺎﺒﻬﺎ ﺴـﺎﺒﻘﺎ"‬
‫ﻴﺠﺏ ﺃﻥ ﺘﺘﺤﺭﺭ ﺨﻼل ﺯﻤﻥ ﺍﻟﻐﻤﺭ ﺍﻟﺫﻱ ﻴﺠﺏ ﺃﻥ ﻻ ﻴﺯﻴﺩ ﻋﻥ ‪ 60‬ﺜﺎﻨﻴﺔ ﻜﻤﺎ ﺴـﺒﻕ‬
‫ﺫﻜﺭﻩ‪ ،‬ﻭﻓﻲ ﻫﺫﺍ ﺍﻟﻤﺠﺎل ﺘﻌﺘﻤﺩ ﺍﻟﻤﻌﻁﻴﺎﺕ ﺍﻟﺘﻲ ﺘﻭﺭﺩﻫﺎ ﺍﻟﺸـﺭﻜﺎﺕ ﺍﻟﺼﺎﻨﻌﺔ ﻟﻔﻭﻫﺎﺕ‬
‫ﻨﻔﺙ ﺍﻟﻐﺎﺯ ﻭﺒﺎﻗﻲ ﻤﻜﻭﻨﺎﺕ ﺍﻟﻨﻅﺎﻡ‪.‬‬

‫ﺍﻷﻨﺎﺒﻴﺏ‪:‬‬

‫ﺴـﻨﻭﺭﺩ ﻫﻨﺎ ﺍﻟﻤﺒﺎﺩﻯﺀ ﺍﻷﺴـﺎﺴـﻴﺔ ﺍﻟﺘﻲ ﻴﺠﺏ ﺃﻥ ﺘﺤﻜﻡ ﺍﺨﺘﻴﺎﺭﻨﺎ ﻟﻸﻨﺎﺒﻴﺏ ﻭﺍﻟﺘﻲ‬
‫ﻴﻤﻜﻥ ﺇﻴﺠﺎﺯﻫﺎ ﺒﻤﺎ ﻴﻠﻲ‪:‬‬

‫ﺇﻥ ﺠﻤﻴﻊ ﺍﻷﻨﺎﺒﻴﺏ ﻭﺍﻟﻭﺼﻼﺕ ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﻤﻌﺩﻨﻴﺔ‪.‬‬ ‫•‬


‫ﻴﺠﺏ ﺃﻥ ﺘﺘﺤﻤل ﺍﻷﻨﺎﺒﻴﺏ ﻭﺍﻟﻭﺼﻼﺕ ﻀﻐﻁ ﺍﺨﺘﺒﺎﺭ ﺍﻟﻨﻅﺎﻡ )‪ 1.5‬ﻤﺭﺓ ﻤﻥ‬ ‫•‬
‫ﻀﻐﻁ ﻋﻤل ﺍﻟﻨﻅﺎﻡ( ﻜﻤﺎ ﻴﺠﺏ ﺃﻥ ﻻ ﻴﺅﺜﺭ ﺍﻨﺨﻔﺎﺽ ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﻨﺎﺠﻡ ﻋﻥ‬
‫ﺍﻨﻔﻼﺕ ﺍﻟﻐﺎﺯ ﻋﻠﻰ ﺍﻷﻨﺎﺒﻴﺏ ﺃﻭ ﺍﻟﻭﺼﻼﺕ‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﻴﻜﻭﻥ ﺍﻟﺠﺯﺀ ﺍﻟﻤﻐﻠﻕ ﻤﻥ ﺸـﺒﻜﺔ ﺍﻷﻨﺎﺒﻴﺏ ﻭﺍﻟﻤﺘﻌﺭﺽ ﻟﻀﻐﻭﻁ‬ ‫•‬
‫ﺍﺴـﺘﺎﺘﻴﻜﻴﺔ ﻤﺤﻤﻴﺎ" ﺒﻭﺍﺴـﻁﺔ ﺼﻤﺎﻡ ﺤﻤﺎﻴﺔ ﻋﻴﺎﺭﻱ ﻤﻥ ﺍﺭﺘﻔﺎﻉ ﺍﻟﻀﻐﻁ‪.‬‬
‫ﻻ ﻴﺴـﻤﺢ ﺒﺎﺴـﺘﺨﺩﺍﻡ ﺃﻨﺎﺒﻴﺏ ﺒﺄﻗﻁﺎﺭ ﺃﻗل ﻤﻥ ‪ 10‬ﻤﻡ ﻓﻲ ﺃﻨﻅﻤﺔ ﻏﺎﺯ ﺜﺎﻨﻲ‬ ‫•‬
‫ﺃﻭﻜﺴـﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﺠﻤﻴﻊ ﺃﻨﺎﺒﻴﺏ ﺍﻷﻨﻅﻤﺔ ﺍﻟﻌﺎﻤﻠﺔ ﺒﺎﻟﻐﺎﺯ ﻤﺤﻤﻴﺔ ﻤﻥ ﺍﻟﺩﺍﺨل‬ ‫•‬
‫ﻭﺍﻟﺨﺎﺭﺝ ﻀﺩ ﺍﻟﺼﺩﺃ ﻭﺫﻟﻙ ﺤﻔﺎﻅﺎ" ﻋﻠﻰ ﺍﻟﺘﺠﻬﻴﺯﺍﺕ ﺍﻟﻤﺤﻤﻴﺔ ﻭﻓﻭﻫﺎﺕ ﺍﻟﻨﻔﺙ‬
‫ﻤﻥ ﺠﺯﻴﺌﺎﺕ ﺍﻟﺼﺩﺃ ﺍﻟﺘﻲ ﻗﺩ ﺘﺘﻁﺎﻴﺭ ﺒﺴـﺒﺏ ﻀﻐﻁ ﺍﻟﻐﺎﺯ ﻋﻨﺩ ﻋﻤل ﺍﻟﻨﻅﺎﻡ‪،‬‬
‫ﻭﻟﺫﻟﻙ ﻓﺈﻥ ﺍﺴـﺘﺨﺩﺍﻡ ﺍﻷﻨﺎﺒﻴﺏ ﺍﻟﻤﻐﻠﻔﻨﺔ ﻴﻌﺘﺒﺭ ﻤﻥ ﺍﻟﺸـﺭﻭﻁ ﺍﻟﺤﺩﻴﺔ ﺍﻟﺩﻨﻴﺎ‬
‫ﻻﺨﺘﻴﺎﺭ ﺍﻷﻨﺎﺒﻴﺏ‪.‬‬
‫ﻻ ﻴﺴـﻤﺢ ﺒﻭﺼل ﺍﻷﻨﺎﺒﻴﺏ ﺍﻟﺘﻲ ﻴﺴـﺎﻭﻱ ﻗﻁﺭﻫﺎ ﺍﻹﺴـﻤﻲ ﺃﻭ ﻴﺯﻴﺩ ﻋﻥ‬ ‫•‬
‫‪ 50‬ﻤﻡ ﺒﻭﺍﺴـﻁﺔ ﺍﻟﻠﺤﺎﻡ‪.‬‬
‫ﻓﻲ ﺤﺎل ﺍﺤﺘﻤﺎل ﺘﺸـﻜل ﺭﻁﻭﺒﺔ ﻤﺘﻜﺎﺜﻔﺔ ﺩﺍﺨل ﺸـﺒﻜﺔ ﺍﻷﻨﺎﺒﻴﺏ ﻴﺠﺏ ﺃﻥ‬ ‫•‬
‫ﺘﺯﻭﺩ ﺍﻟﺸـﺒﻜﺔ ﺒﻔﺘﺤﺔ ﺘﺠﻤﻴﻊ ﻭﺘﺼﺭﻴﻑ ﻭﻴﺠﺏ ﺃﻥ ﻴﺤﻅﺭ ﺍﻟﺘﻌﺎﻤل ﻤﻊ ﻫﺫﻩ‬
‫ﺍﻟﻔﺘﺤﺔ ﻤﻥ ﻗﺒل ﺃﺸـﺨﺎﺹ ﻏﻴﺭ ﻤﺨﻭﻟﻴﻥ ﺒﺫﻟﻙ‪.‬‬

‫‪23‬‬
‫ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﺸـﺒﻜﺔ ﺍﻷﻨﺎﺒﻴﺏ ﻤﻘﺎﻭﻤﺔ ﻟﺠﻤﻴﻊ ﺍﻟﻌﻭﺍﻤل ﺍﻟﺨﺎﺭﺠﻴﺔ ﺍﻟﺘﻲ ﻗﺩ‬ ‫•‬
‫ﺘﻔﺭﻀﻬﺎ ﻁﺒﻴﻌﺔ ﻤﻜﺎﻥ ﺍﻟﺘﺭﻜﻴﺏ ﺃﻭ ﺍﻟﻨﺎﺠﻤﺔ ﻋﻥ ﺠﺭﻴﺎﻥ ﺍﻟﻐﺎﺯ ﻀﻤﻨﻬﺎ‪ ،‬ﻜﻤﺎ‬
‫ﻴﺠﺏ ﺃﻥ ﻴﻜﻭﻥ ﺍﻟﻭﺼﻭل ﺇﻟﻴﻬﺎ ﺴـﻬﻼ"‪.‬‬
‫ﻴﺴـﻤﺢ ﺒﺎﺴـﺘﺨﺩﺍﻡ ﻭﺼﻼﺕ ﻤﺭﻨﺔ ﻓﻲ ﺒﻌﺽ ﻨﻘﺎﻁ ﺍﻟﺸـﺒﻜﺔ ﺍﻟﺘﻲ ﻻ ﻴﻤﻜﻥ‬ ‫•‬
‫ﻓﻴﻬﺎ ﺍﺴـﺘﺨﺩﺍﻡ ﻨﻘﺎﻁ ﻭﺼل ﺜﺎﺒﺘﺔ‪ ،‬ﻋﻠﻰ ﺃﻥ ﺘﺤﻘﻕ ﻫﺫﻩ ﺍﻟﻭﺼﻼﺕ ﺸـﺭﻭﻁ‬
‫ﺍﻟﺘﺤﻤل ﻭﺍﻟﻤﻘﺎﻭﻤﺔ ﻟﺠﻤﻴﻊ ﺍﻟﻌﻭﺍﻤل ﺍﻟﻤﺫﻜﻭﺭﺓ ﺃﻋﻼﻩ‪.‬‬
‫ﻴﺠﺏ ﻭﺒﺸـﻜل ﻀﺭﻭﺭﻱ ﺘﺯﻭﻴﺩ ﺸـﺒﻜﺔ ﺍﻷﻨﺎﺒﻴﺏ ﻭﺍﻟﻨﻅﺎﻡ ﺒﺸـﻜل ﻋﺎﻡ‬ ‫•‬
‫ﺒﺸـﺒﻜﺔ ﺘﺄﺭﻴﺽ ﻭﻴﺠﺏ ﻤﺭﺍﻋﺎﺓ ﺫﻟﻙ ﻓﻲ ﺤﺎل ﺍﺴـﺘﺨﺩﺍﻡ ﻭﺼﻼﺕ ﻤﺭﻨﺔ‬
‫ﻟﻀﻤﺎﻥ ﺴـﻼﻤﺔ ﺘﺄﺭﻴﺽ ﺍﻟﺸـﺒﻜﺔ ﺒﺸـﻜل ﺩﺍﺌﻡ‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﺘﺘﺤﻤل ﺍﻷﻨﺎﺒﻴﺏ ﻀﻐﻭﻁ ﺍﻟﻌﻤل ﺍﻟﻤﺫﻜﻭﺭﺓ ﻓﻲ ﺍﻟﺠﺩﻭل ﺃﺩﻨﺎﻩ ﻷﻨﻅﻤﺔ‬ ‫•‬
‫ﺍﻟﻀﻐﻁ ﺍﻟﻤﻨﺨﻔﺽ ﻭﺍﻟﻀﻐﻁ ﺍﻟﻤﺭﺘﻔﻊ‪:‬‬

‫ﺍﻟﻀﻐﻁ ﺩﺍﺨل ﺍﻷﻨﺎﺒﻴﺏ )ﺒﺎﺭ(‬ ‫ﻤﻜﺎﻥ ﺘﺭﻜﻴﺏ ﺍﻷﻨﺎﺒﻴﺏ ﻓﻲ ﺍﻟﻨﻅﺎﻡ‬


‫ﻓﺤﺹ ﺍﻟﻨﻅﺎﻡ‬ ‫ﻋﻤل ﺍﻟﻨﻅﺎﻡ‬
‫ﻓﻲ ﺃﻨﻅﻤﺔ ﺍﻟﻀﻐﻁ ﺍﻟﻤﺭﺘﻔﻊ ﺒﻴﻥ ﺍﻷﺴﻁﻭﺍﻨﺎﺕ‬
‫‪160‬‬ ‫‪120‬‬ ‫ﻭﺼﻤﺎﻤﺎﺕ ﺍﻟﺘﺤﻜﻡ‬
‫ﻓﻲ ﺃﻨﻅﻤﺔ ﺍﻟﻀﻐﻁ ﺍﻟﻤﺭﺘﻔﻊ ﻤﺎ ﺒﻌﺩ ﺼﻤﺎﻤﺎﺕ‬
‫‪80‬‬ ‫‪60‬‬ ‫ﺍﻟﺘﺤﻜﻡ‬
‫ﻓﻲ ﺃﻨﻅﻤﺔ ﺍﻟﻀﻐﻁ ﺍﻟﻤﻨﺨﻔﺽ ﺒﻴﻥ ﺍﻷﺴﻁﻭﺍﻨﺎﺕ‬
‫‪40‬‬ ‫‪25‬‬ ‫ﻭﺼﻤﺎﻤﺎﺕ ﺍﻟﺘﺤﻜﻡ ﻭﻤﺎ ﺒﻌﺩ ﺼﻤﺎﻤﺎﺕ ﺍﻟﺘﺤﻜﻡ‬
‫ﺠﺩﻭل )‪(4‬‬

‫• ﻓﻲ ﺠﻤﻴﻊ ﺍﻷﺤﻭﺍل ﺘﻨﺼﺢ ﺠﻤﻴﻊ ﺍﻟﺠﻬﺎﺕ ﺍﻟﺩﻭﻟﻴﺔ ﺒﺎﺴـﺘﺨﺩﺍﻡ ﺍﻷﻨﺎﺒﻴﺏ‬


‫ﺍﻟﻤﺴـﺤﻭﺒﺔ‪.‬‬

‫ﻤﺜﺒﺘﺎﺕ ﺍﻷﻨﺎﺒﻴﺏ‪:‬‬

‫ﺇﻥ ﻤﺜﺒﺘﺎﺕ ﺍﻷﻨﺎﺒﻴﺏ ﺘﺸـﻜل ﺠﺯﺀﺍ" ﺃﺴـﺎﺴـﻴﺎ" ﻤﻥ ﺍﻟﻨﻅﺎﻡ ﻭﺨﺼﻭﺼﺎ" ﻓﻲ ﻤﺎ ﻴﺘﻌﻠﻕ‬


‫ﺒﺜﺒﺎﺕ ﺍﻟﺸـﺒﻜﺔ ﻭﻤﻨﻌﻬﺎ ﻤﻥ ﺍﻻﻨﻬﻴﺎﺭ ﻋﻨﺩ ﻋﻤل ﺍﻟﻨﻅﺎﻡ ﻓﻲ ﺇﻁﻔﺎﺀ ﺤﺭﻴﻕ ﻤﺎ‪ .‬ﻟﻬﺫﺍ‬
‫ﻴﺠﺏ ﺃﻥ ﺘﺅﺨﺫ ﺍﻟﻨﻘﺎﻁ ﺍﻟﺘﺎﻟﻴﺔ ﺒﻌﻴﻥ ﺍﻻﻋﺘﺒﺎﺭ ﻷﻫﻤﻴﺘﻬﺎ ﺒﺎﻟﻨﺴـﺒﺔ ﻟﻠﻨﻅﺎﻡ ﻜﻜل‪:‬‬

‫• ﻤﻥ ﺍﻟﺜﺎﺒﺕ ﺒﺄﻥ ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﻤﻨﺨﻔﻀﺔ ﺠﺩﺍ" ﺍﻟﻨﺎﺠﻤﺔ ﻋﻥ ﺍﻨﻔﻼﺕ ﺍﻟﻐﺎﺯ ﻀﻤﻥ‬


‫ﺍﻟﺸـﺒﻜﺔ ﺴـﺘﺅﺩﻱ ﺇﻟﻰ ﺍﻨﻜﻤﺎﺵ ﺍﻷﻨﺎﺒﻴﺏ ﻁﻭﻟﻴﺎ" )ﻭﻗﻁﺭﻴﺎ" ﺃﻴﻀﺎ" ﻭﺇﻥ‬
‫ﺒﺸـﻜل ﺃﻗل ﻭﻀﻭﺤﺎ" ﻭﺘﺄﺜﻴﺭﺍ"( ﻟﺫﻟﻙ ﻓﺈﻥ ﻫﺫﻩ ﺍﻟﺤﻘﻴﻘﺔ ﻴﺠﺏ ﺃﻥ ﻻ ﺘﻐﻴﺏ ﻋﻥ‬
‫ﺃﺫﻫﺎﻨﻨﺎ ﻋﻨﺩ ﺍﺨﺘﻴﺎﺭ ﻨﻭﻉ ﺍﻟﻤﺜﺒﺘﺎﺕ ﺍﻟﺫﻱ ﻴﺠﺏ ﺃﻥ ﻴﺴـﻤﺢ ﺒﺫﻟﻙ‪.‬‬

‫‪24‬‬
‫• ﻴﺠﺏ ﺃﻥ ﺘﺨﺘﺎﺭ ﺍﻟﻤﺜﺒﺘﺎﺕ ﺒﺤﻴﺙ ﺘﺘﺤﻤل ﺍﻟﺤﻤل ﺍﻟﺩﻴﻨﺎﻤﻴﻜﻲ ﻭﺍﻟﺤﻤل‬
‫ﺍﻻﺴـﺘﺎﺘﻴﻜﻲ ﺍﻟﻨﺎﺠﻤﻴﻥ ﻋﻥ ﻋﻤل ﺍﻟﻨﻅﺎﻡ ﻭﺒﺤﻴﺙ ﻨﻜﻭﻥ ﻤﺘﺄﻜﺩﻴﻥ ﻤﻥ ﺃﻥ ﺍﻟﻨﻅﺎﻡ‬
‫ﻟﻥ ﻴﺘﻀﺭﺭ ﺒﻨﺘﻴﺠﺔ ﺍﻨﻬﻴﺎﺭ ﺍﻟﻤﺜﺒﺘﺎﺕ ﻋﻨﺩ ﺍﻟﺤﻤل ﺍﻷﻋﻅﻤﻲ‪.‬‬
‫• ﻻ ﻴﺴـﻤﺢ ﺒﺎﺴـﺘﺨﺩﺍﻡ ﻤﺜﺒﺘﺎﺕ ﻤﺼﻨﻭﻋﺔ ﻤﻥ ﻤﻭﺍﺩ ﻗﺎﺒﻠﺔ ﻟﻼﺸـﺘﻌﺎل ﺃﻭ ﻤﻭﺍﺩ‬
‫ﻴﻨﺨﻔﺽ ﺘﺤﻤﻠﻬﺎ ﺒﺄﻜﺜﺭ ﻤﻥ ‪ %25‬ﻋﻨﺩ ﺍﺭﺘﻔﺎﻉ ﺩﺭﺠﺔ ﺍﻟﺤﺭﺍﺭﺓ ﺤﺘﻰ ‪200‬‬
‫ﺩﺭﺠﺔ ﻤﺌﻭﻴﺔ‪.‬‬
‫• ﻴﺠﺏ ﺃﻥ ﻻ ﺘﻘل ﻤﺴـﺎﺤﺔ ﻤﻘﻁﻊ ﻜل ﺒﺭﻏﻲ ﻴﺴـﺘﻌﻤل ﻟﺘﺜﺒﻴﺕ ﻤﺜﺒﺕ ﺍﻷﻨﺒﻭﺏ‬
‫ﻋﻥ ‪ 30‬ﻤﻡ‪ ،2‬ﻭﻓﻲ ﺠﻤﻴﻊ ﺍﻷﺤﻭﺍل ﻴﻭﻀﺢ ﺍﻟﺠﺩﻭل ﺍﻟﺘﺎﻟﻲ ﺍﻷﻗﻁﺎﺭ‬
‫ﻭﺍﻟﺤﻤﻭﻻﺕ ﺍﻟﻤﺴـﻤﻭﺤﺔ ﻟﺒﺭﺍﻏﻲ ﺍﻟﺘﺜﺒﻴﺕ ﻨﺴـﺒﺔ ﺇﻟﻰ ﺍﻟﻘﻁﺭ ﺍﻻﺴـﻤﻲ‬
‫ﻟﻸﻨﺒﻭﺏ ‪:DN‬‬

‫ﺍﻟﻌﻤﻕ ﺍﻷﺼﻐﺭﻱ‬ ‫ﺍﻟﻘﻴﺎﺱ‬ ‫ﺍﻟﻤﻘﻁﻊ ﺍﻷﺼﻐﺭﻱ‬ ‫ﺍﻟﺤﻤﻭﻟﺔ‬ ‫ﺍﻟﻘﻁﺭ ﺍﻹﺴﻤﻲ ﻟﻸﻨﺒﻭﺏ‬


‫ﻟﺒﺭﻏﻲ ﺍﻟﺘﺜﺒﻴﺕ‬ ‫ﺍﻷﺼﻐﺭﻱ‬ ‫ﻟﺒﺭﻏﻲ ﺍﻟﺘﺜﺒﻴﺕ‬ ‫ﺍﻟﻤﺴـﻤﻭﺤﺔ ‪/‬‬ ‫‪ /‬ﻤﻡ‬
‫ﺩﺍﺨل ﺍﻟﺒﻴﺘﻭﻥ ‪ /‬ﻤﻡ‬ ‫ﻟﻠﺒﺭﻏﻲ‬ ‫ﻤﻡ‪2‬‬ ‫ﻨﻴﻭﺘﻥ‬
‫‪30‬‬ ‫‪8M‬‬ ‫‪30‬‬ ‫‪2000‬‬ ‫ﺃﺼﻐﺭ ﺃﻭ ﻴﺴﺎﻭﻱ ‪50‬‬
‫‪40‬‬ ‫‪10 M‬‬ ‫‪50‬‬ ‫‪3500‬‬ ‫ﻤﻥ ‪ 50‬ﺇﻟﻰ ‪100‬‬
‫‪40‬‬ ‫‪12 M‬‬ ‫‪70‬‬ ‫‪5000‬‬ ‫ﻤﻥ ‪ 100‬ﺇﻟﻰ ‪150‬‬
‫‪50‬‬ ‫‪16 M‬‬ ‫‪125‬‬ ‫‪8500‬‬ ‫ﻤﻥ ‪ 150‬ﺇﻟﻰ ‪200‬‬
‫‪60‬‬ ‫‪20 M‬‬ ‫‪150‬‬ ‫‪10000‬‬ ‫ﻤﻥ ‪ 200‬ﺇﻟﻰ ‪250‬‬
‫ﺠﺩﻭل )‪(5‬‬

‫ﻴﺠﺏ ﻓﻲ ﺤﺎل ﺍﺴـﺘﺨﺩﺍﻡ ﺃﻜﺜﺭ ﻤﻥ ﺒﺭﻏﻲ ﻟﻠﺘﺜﺒﻴﺕ ﺃﻥ ﻴﺤﻘﻕ ﻤﺠﻤﻭﻉ ﺃﺤﻤﺎل‬ ‫•‬
‫ﺍﻟﺒﺭﺍﻏﻲ ‪ %50‬ﻤﻌﺎﻤل ﺃﻤﺎﻥ ﺇﻀﺎﻓﻲ‪ ،‬ﻤﻊ ﻤﺭﺍﻋﺎﺓ ﺍﻟﺠﺩﻭل ﺃﻋﻼﻩ‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﻴﺤﻴﻁ ﻤﺜﺒﺕ ﺍﻷﻨﺒﻭﺏ ﺒﺎﻷﻨﺒﻭﺏ ﺒﺸـﻜل ﻜﺎﻤل‪.‬‬ ‫•‬
‫ﻴﺠﺏ ﺃﻥ ﺘﺭﺍﻋﻰ ﺴـﻤﺎﻜﺔ ﻤﺜﺒﺘﺎﺕ ﺍﻷﻨﺎﺒﻴﺏ‬ ‫•‬
‫ﻴﺠﺏ ﺃﻥ ﻴﺜﺒﺕ ﻜل ﺃﻨﺒﻭﺏ ﻴﺯﻴﺩ ﻁﻭﻟﻪ ﻋﻥ ‪ 1‬ﻤﺘﺭ ﺒﻤﺜﺒﺕ ﻋﻠﻰ ﺍﻷﻗل‪ ،‬ﻭﻴﻌﺘﻤﺩ‬ ‫•‬
‫ﺍﻟﺠﺩﻭل ﺍﻟﺘﺎﻟﻲ ﻟﺤﺩﻭﺩ ﺍﻷﺒﻌﺎﺩ ﺍﻷﻋﻅﻤﻴﺔ ﺒﻴﻥ ﺍﻟﻤﺜﺒﺘﺎﺕ ﺤﺴـﺏ ﻗﻁﺭ ﺍﻷﻨﺒﻭﺏ‪:‬‬

‫ﺍﻟﻤﺴﺎﻓﺔ ﺍﻟﻘﺼﻭﻯ ﺒﻴﻥ ﺍﻟﺤﻤﺎﻴﺎﺕ ﺒﺎﻟﻤﺘﺭ‬ ‫ﻗﻁﺭ ﺍﻷﻨﺒﻭﺏ ﺒﺎﻟﻤﻠﻡ‬


‫‪2‬‬ ‫ﺃﺼﻐﺭ ﺃﻭ ﻴﺴـﺎﻭﻱ ‪25‬‬
‫‪3‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ ‪ 25‬ﻭﺃﺼﻐﺭ ﻤﻥ ‪50‬‬
‫‪4‬‬ ‫ﺃﻜﺒﺭ ﺃﻭ ﻴﺴـﺎﻭﻱ ‪50‬‬
‫ﺠﺩﻭل )‪(6‬‬

‫‪25‬‬
‫ﻴﺠﺏ ﺃﻥ ﻻ ﻴﻘل ﻁﻭل ﺍﻟﻤﺜﺒﺕ ﻋﻥ ‪ 25‬ﻤﻡ‬ ‫•‬
‫ﻴﻤﻜﻥ ﺘﺜﺒﻴﺕ ﺍﻟﻤﺜﺒﺘﺎﺕ ﻋﻠﻰ ﺍﻟﺴـﻁﻭﺡ ﺍﻟﻤﺎﺌﻠﺔ ﺒﺸـﺭﻁ ﺃﻥ ﻻ ﻴﺯﻴﺩ ﻤﻴﻠﻬﺎ ﺃﻓﻘﻴﺎ"‬ ‫•‬
‫ﻋﻥ ‪ 10‬ﺩﺭﺠﺎﺕ‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﻻ ﺘﺴـﺘﺨﺩﻡ ﻤﺜﺒﺘﺎﺕ ﺃﻨﺎﺒﻴﺏ ﺍﻟﻨﻅﺎﻡ ﻷﻱ ﺃﻏﺭﺍﺽ ﺃﺨﺭﻯ‪.‬‬ ‫•‬
‫ﻴﻔﻀل ﺃﻥ ﺘﺘﻭﻀﻊ ﺍﻟﻤﺜﺒﺘﺎﺕ ﻗﺭﻴﺒﺎ" ﻤﻥ ﻭﺼﻼﺕ ﺍﻷﻨﺎﺒﻴﺏ‪.‬‬ ‫•‬
‫ﻴﺠﺏ ﺃﻥ ﻴﺘﻡ ﺘﺜﺒﻴﺕ ﻤﺜﺒﺘﺎﺕ ﺍﻷﻨﺎﺒﻴﺏ ﻤﺒﺎﺸـﺭﺓ ﻋﻠﻰ ﻤﻜﻭﻨﺎﺕ ﺍﻟﺒﻨﺎﺀ‬ ‫•‬
‫ﺍﻷﺴـﺎﺴـﻴﺔ )ﺃﺴـﻘﻑ ﺃﻭ ﺠﺩﺭﺍﻥ( ﻭﻴﻤﻨﻊ ﺘﺜﺒﻴﺘﻬﺎ ﻋﻠﻰ ﺃﻱ ﻤﻥ ﻤﻜﻭﻨﺎﺕ ﺍﻟﺒﻨﺎﺀ‬
‫ﺍﻟﻤﻀﺎﻓﺔ )ﺠﺩﺭﺍﻥ ﺃﻭ ﺃﺴـﻘﻑ ﻤﺴـﺘﻌﺎﺭﺓ(‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﻴﺘﻡ ﺘﺜﺒﻴﺕ ﻤﺜﺒﺘﺎﺕ ﺍﻷﻨﺎﺒﻴﺏ ﻋﻠﻰ ﺒﻌﺩ ‪ 15‬ﺴـﻡ ﻋﻠﻰ ﺍﻷﻗل ﻤﻥ‬ ‫•‬
‫ﺤﺭﻑ ﺍﻟﺠﺩﺍﺭ ﺃﻭ ﺍﻟﺴـﻘﻑ‪.‬‬
‫ﻴﺠﺏ ﺇﻀﺎﻓﺔ ﻤﺜﺒﺕ ﺇﻀﺎﻓﻲ ﻋﻠﻰ ﺍﻷﻗل ﻋﻨﺩ ﻭﺠﻭﺩ ﺼﻤﺎﻡ ﺃﻭ ﺘﻔﺭﻴﻌﺔ ﻤﺘﻌﺩﺩﺓ‬ ‫•‬
‫ﺍﻻﺘﺠﺎﻫﺎﺕ ﻋﻠﻰ ﺍﻷﻨﺒﻭﺏ‪.‬‬
‫ﻴﺠﺏ ﺍﻟﺘﻘﻴﺩ ﺒﺎﻥ ﻴﻜﻭﻥ ﺍﻟﺒﻌﺩ ﺍﻷﻋﻅﻤﻲ ﺒﻴﻥ ﺍﻟﻤﺜﺒﺕ ﻭﻓﻭﻫﺔ ﻨﻔﺙ ﺍﻟﻐﺎﺯ ﺍﻷﺨﻴﺭﺓ‬ ‫•‬
‫ﻨﺴـﺒﺔ ﺇﻟﻰ ﻗﻁﺭ ﺍﻷﻨﺒﻭﺏ ﻜﻤﺎ ﻴﻠﻲ‪:‬‬

‫ﺍﻟﺒﻌﺩ ﺍﻷﻋﻅﻤﻲ ﻟﻠﻤﺜﺒﺕ ﻋﻥ ﺍﻟﻔﻭﻫﺔ ‪ /‬ﻤﺘﺭ‬ ‫ﻗﻁﺭ ﺍﻷﻨﺒﻭﺏ ‪ /‬ﻤﻡ‬


‫‪0.1‬‬ ‫ﺃﺼﻐﺭ ﺃﻭ ﻴﺴـﺎﻭﻱ ‪25‬‬
‫‪0.25‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ ‪25‬‬
‫ﺠﺩﻭل )‪(7‬‬

‫ﺼﻤﺎﻤﺎﺕ ﺍﻟﺘﺤﻜﻡ‪:‬‬

‫ﻴﻘﺼﺩ ﺒﺼﻤﺎﻤﺎﺕ ﺍﻟﺘﺤﻜﻡ ﻤﺠﻤﻭﻋﺔ ﺍﻟﺼﻤﺎﻤﺎﺕ ﺍﻟﺘﻲ ﻗﺩ ﺘﻜﻭﻥ ﻤﺭﻜﺒﺔ ﻋﻠﻰ‬


‫ﺃﺴـﻁﻭﺍﻨﺎﺕ ﺍﻟﻨﻅﺎﻡ ﺃﻭ ﻋﻠﻰ ﺍﻟﺸـﺒﻜﺔ ﻓﻲ ﺤﺎل ﺍﻟﻨﻅﺎﻡ ﻤﺘﻌﺩﺩ ﺍﻟﻤﻨﺎﻁﻕ )ﺘﻜﻭﻥ ﻋﺎﺩﺓ"‬
‫ﺼﻤﺎﻡ ﻭﺍﺤﺩ ﻟﻜل ﻤﻨﻁﻘﺔ(‪ .‬ﻭﻴﺠﺏ ﺃﻥ ﻨﺘﻘﻴﺩ ﺒﻤﺎ ﻴﻠﻲ ﻓﻲ ﺍﺨﺘﻴﺎﺭ ﻭﺘﺭﻜﻴﺏ ﺼﻤﺎﻤﺎﺕ‬
‫ﺍﻟﺘﺤﻜﻡ‪:‬‬

‫• ﻴﺠﺏ ﻭﻀﻊ ﺼﻤﺎﻡ ﺍﻟﺘﺤﻜﻡ ﺨﺎﺭﺝ ﻤﻨﻁﻘﺔ ﺍﻟﺨﻁﺭ‪.‬‬


‫• ﻴﺠﺏ ﻋﺩﻡ ﺘﺤﺯﻴﻥ ﺃﻱ ﻤﺎﺩﺓ ﻗﺎﺒﻠﺔ ﻟﻼﺸﺘﻌﺎل ﻓﻲ ﻤﻨﻁﻘﺔ ﺘﺭﻜﻴﺏ ﺼﻤﺎﻡ ﺍﻟﺘﺤﻜﻡ‪.‬‬
‫• ﻴﺠﺏ ﺍﺨﺘﻴﺎﺭ ﺼﻤﺎﻤﺎﺕ ﺍﻟﺘﺤﻜﻡ ﺒﺤﻴﺙ ﻻ ﺘﺘﺄﺜﺭ ﺒﺎﻻﻫﺘﺯﺍﺯ ﺍﻟﺫﻱ ﻗﺩ ﻴﻨﺠﻡ ﻋﻥ‬
‫ﻓﺘﺢ ﺼﻤﺎﻡ ﺍﻟﺘﺤﻜﻡ ﻷﻱ ﻤﻨﻁﻘﺔ‪.‬‬

‫‪26‬‬
‫ﻴﺠﺏ ﺃﻥ ﺘﻔﺘﺢ ﺼﻤﺎﻤﺎﺕ ﺍﻟﺘﺤﻜﻡ ﺃﻭﺘﻭﻤﺎﺘﻴﻜﻴﺎ" ﺒﺎﻟﺘﺘﺎﺒﻊ ﺒﺩﺀﺍ" ﻤﻥ ﺼﻤﺎﻡ ﺍﻟﺨﺯﺍﻥ‬ ‫•‬
‫ﺃﻭ ﺍﻷﺴـﻁﻭﺍﻨﺎﺕ ﺤﺴـﺏ ﻨﻭﻉ ﺍﻟﻨﻅﺎﻡ‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﻴﺯﻭﺩ ﺍﻷﻨﺒﻭﺏ ﻓﻴﻤﺎ ﺒﻴﻥ ﺼﻤﺎﻡ ﺍﻟﺨﺯﺍﻥ ﻭﺼﻤﺎﻡ ﺍﻟﺘﺤﻜﻡ ﺒﺼﻤﺎﻡ ﺤﻤﺎﻴﺔ‬ ‫•‬
‫ﻤﻥ ﺍﺭﺘﻔﺎﻉ ﺍﻟﻀﻐﻁ‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﻴﺘﻡ ﺇﻏﻼﻕ ﺼﻤﺎﻤﺎﺕ ﺍﻟﻨﻅﺎﻡ ﺃﻭﺘﻭﻤﺎﺘﻴﻜﻴﺎ" ﺒﻌﺩ ﺘﺤﺭﻴﺭ ﺍﻟﻐﺎﺯ ﻭﺫﻟﻙ‬ ‫•‬
‫ﺒﺎﻟﺘﺘﺎﺒﻊ ﺒﺩﺀﺍ" ﻤﻥ ﺃﺒﻌﺩ ﻤﻨﻁﻘﺔ ﻭﺤﺘﻰ ﺍﻟﺨﺯﺍﻥ ﺃﻭ ﺍﻷﺴـﻁﻭﺍﻨﺎﺕ ﺤﺴـﺏ ﻨﻭﻉ‬
‫ﺍﻟﻨﻅﺎﻡ‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﻴﺨﺘﺎﺭ ﺼﻤﺎﻡ ﺍﻟﺘﺤﻜﻡ ﺒﺤﻴﺙ ﻴﺴـﻤﺢ ﺒﺴـﻬﻭﻟﺔ ﻓﺤﺼﻪ ﺩﻭﻥ ﺍﻟﺤﺎﺠﺔ‬ ‫•‬
‫ﺇﻟﻰ ﺘﻔﻌﻴل ﺍﻟﻨﻅﺎﻡ ﻋﻨﺩ ﺍﻟﻔﺤﺹ‪.‬‬
‫ﻯ ﻓﻲ ﺤﺎل‬ ‫ﻴﺠﺏ ﺃﻥ ﻴﺘﻤﺘﻊ ﺼﻤﺎﻡ ﺍﻟﺘﺤﻜﻡ ﺒﺨﺎﺼﻴﺔ ﺍﻟﺘﺸـﻐﻴل ﺍﻟﻴﺩﻭﻱ ﺍﻟﻁﺎﺭ ْ‬ ‫•‬
‫ﻓﺸـل ﺍﻟﻨﻅﺎﻡ ﺍﻷﻭﺘﻭﻤﺎﺘﻴﻜﻲ‪.‬‬
‫ﻴﺠﺏ ﻋﺩﻡ ﺍﺴـﺘﺨﺩﺍﻡ ﺃﻱ ﻨﻭﻉ ﻤﻥ ﺍﻟﻭﺼﻼﺕ ﺍﻟﻤﺴـﺘﺨﺩﻤﺔ ﻹﻨﻘﺎﺹ ﺍﻟﻘﻁﺭ‬ ‫•‬
‫ﻋﻨﺩ ﻭﺼل ﺼﻤﺎﻡ ﺍﻟﺘﺤﻜﻡ‪.‬‬

‫ﻓﻭﻫﺎﺕ ﻨﻔﺙ ﺍﻟﻐﺎﺯ‪:‬‬

‫ﺇﻥ ﻓﻭﻫﺎﺕ ﻨﻔﺙ ﺍﻟﻐﺎﺯ ﺘﻌﺘﺒﺭ ﻤﻥ ﺍﻟﻌﻨﺎﺼﺭ ﺫﺍﺕ ﺍﻷﻫﻤﻴﺔ ﺍﻟﺨﺎﺼﺔ ﻓﻲ ﺍﻻﺨﺘﻴﺎﺭ ﻭﺫﻟﻙ‬
‫ﻟﻤﺎ ﻟﻬﺎ ﻤﻥ ﺘﺄﺜﻴﺭ ﻋﻠﻰ ﺴـﺭﻋﺔ ﻭﻓﺎﻋﻠﻴﺔ ﻋﻤل ﺍﻟﻨﻅﺎﻡ ﻭﻴﺠﺏ ﺃﻥ ﺘﺭﺍﻋﻲ ﻤﺎ ﻴﻠﻲ‪:‬‬

‫ﻴﺠﺏ ﺍﻟﺘﺄﻜﺩ ﻤﻥ ﺍﺨﺘﻴﺎﺭ ﻓﻭﻫﺎﺕ ﻨﻔﺙ ﺍﻟﻐﺎﺯ ﺒﺤﻴﺙ ﺘﺤﻘﻕ ﺸـﺭﻁ ﻭﺼﻭل‬ ‫•‬
‫ﺘﺭﻜﻴﺯ ﺍﻟﻐﺎﺯ ﺇﻟﻰ ﺍﻟﺘﺭﻜﻴﺯ ﺍﻟﺘﺼﻤﻴﻤﻲ ﻓﻲ ﺍﻟﺯﻤﻥ ﺍﻟﻤﺤﺩﺩ‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﻻ ﺘﺯﻴﺩ ﺍﻟﻤﺴـﺎﺤﺔ ﺍﻟﻤﺤﻤﻴﺔ ﺒﻔﻭﻫﺔ ﻭﺍﺤﺩﺓ ﻋﻥ ‪ 30‬ﻤﺘﺭ ﻤﺭﺒﻊ‪.‬‬ ‫•‬
‫ﻴﺠﺏ ﺘﻭﺨﻲ ﺍﻟﺤﺫﺭ ﻋﻨﺩ ﺘﻭﺯﻴﻊ ﻓﻭﻫﺎﺕ ﻨﻔﺙ ﺍﻟﻐﺎﺯ ﺒﺤﻴﺙ ﻻ ﺘﺅﺩﻱ ﺇﻟﻰ ﺒﻌﺜﺭﺓ‬ ‫•‬
‫ﺍﻟﻤﻭﺍﺩ ﺍﻟﻤﺤﺘﺭﻗﺔ ﺃﺜﻨﺎﺀ ﺍﻨﻔﻼﺕ ﺍﻟﻐﺎﺯ‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﺘﻭﺯﻉ ﺍﻟﻔﻭﻫﺎﺕ ﺒﺤﻴﺙ ﻻ ﺘﺅﺩﻱ ﺇﻟﻰ ﺍﻹﻀﺭﺍﺭ ﺒﻤﺤﺘﻭﻴﺎﺕ ﺍﻟﻤﻜﺎﻥ‬ ‫•‬
‫ﻋﻨﺩ ﻨﻔﺜﻬﺎ ﻟﻠﻐﺎﺯ‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﺘﻭﺯﻉ ﻓﻭﻫﺎﺕ ﻨﻔﺙ ﺍﻟﻐﺎﺯ ﺃﻋﻠﻰ ﺍﻟﻤﻜﺎﻥ ﺍﻟﻤﺤﻤﻲ ﻋﻠﻰ ﺃﻥ ﻻ ﻴﺯﻴﺩ‬ ‫•‬
‫ﺍﻻﺭﺘﻔﺎﻉ ﻋﻥ ‪ 5‬ﻤﺘﺭ‪.‬‬
‫ﻓﻲ ﺤﺎل ﻜﺎﻥ ﺍﺭﺘﻔﺎﻉ ﺍﻟﻤﻜﺎﻥ ﺍﻟﻤﺤﻤﻲ ﻤﺎ ﺒﻴﻥ ‪ 5‬ﻭ ‪ 10‬ﺃﻤﺘﺎﺭ ﻴﺠﺏ ﺇﻀﺎﻓﺔ‬ ‫•‬
‫ﻓﻭﻫﺔ ﺇﻀﺎﻓﻴﺔ ﻟﻜل ﻓﻭﻫﺔ ﻭﺘﺭﻜﺏ ﺍﻟﻔﻭﻫﺎﺕ ﺍﻹﻀﺎﻓﻴﺔ ﻋﻠﻰ ﺍﺭﺘﻔﺎﻉ ﻴﺴـﺎﻭﻱ‬
‫ﺜﻠﺙ ﺍﺭﺘﻔﺎﻉ ﺍﻟﻤﻜﺎﻥ ﻋﻠﻰ ﺃﻥ ﻴﺘﻡ ﺘﺤﺭﻴﺭ ﺜﻠﺙ ﺍﻟﻜﻤﻴﺔ ﺍﻟﻼﺯﻤﺔ ﻤﻥ ﺍﻟﻐﺎﺯ ﻟﻠﻤﻜﺎﻥ‬
‫ﻋﺒﺭ ﻫﺫﻩ ﺍﻟﻔﻭﻫﺔ ﺍﻹﻀﺎﻓﻴﺔ‪.‬‬
‫ﺒﺸـﻜل ﻋﺎﻡ ﻻ ﻴﺴـﻤﺢ ﺒﺘﺭﻜﻴﺏ ﺍﻟﻔﻭﻫﺎﺕ ﻓﻲ ﺍﻷﻤﺎﻜﻥ ﺍﻟﺘﻲ ﻴﺯﻴﺩ ﺍﺭﺘﻔﺎﻋﻬﺎ‬ ‫•‬
‫ﻋﻥ ‪ 10‬ﺃﻤﺘﺎﺭ‪.‬‬

‫‪27‬‬
‫• ﻴﺠﺏ ﺍﻟﺘﺄﻜﺩ ﺩﻭﻤﺎ" ﻤﻥ ﺃﻥ ﻁﺒﻴﻌﺔ ﻤﻜﺎﻥ ﺘﺭﻜﻴﺏ ﻓﻭﻫﺎﺕ ﻨﻔﺙ ﺍﻟﻐﺎﺯ ﺘﺤﺎﻓﻅ ﻋﻠﻰ‬
‫ﻨﻅﺎﻓﺘﻬﺎ ﺒﺤﻴﺙ ﻨﺤﺩ ﻤﻥ ﺇﻤﻜﺎﻨﻴﺔ ﺍﻨﺴـﺩﺍﺩ ﺍﻟﻔﻭﻫﺎﺕ‪.‬‬

‫ﺍﺨﺘﺒﺎﺭ ﺍﻟﺸـﺒﻜﺔ‪:‬‬

‫ﻋﻨﺩ ﺍﻻﻨﺘﻬﺎﺀ ﻤﻥ ﺃﻋﻤﺎل ﺘﺭﻜﻴﺏ ﺍﻷﻨﺎﺒﻴﺏ ﻴﺠﺏ ﺃﻥ ﻴﺘﻡ ﻀﻐﻁ ﺍﻷﻨﺎﺒﻴﺏ ﺒﺎﻟﻤﺎﺀ ﻭﻓﻕ‬
‫ﺍﻟﻀﻐﻭﻁ ﺍﻟﻭﺍﺭﺩﺓ ﺃﺩﻨﺎﻩ‪ ،‬ﻋﻠﻰ ﺃﻥ ﻴﺤﺼﺭ ﺍﻟﻀﻐﻁ ﻀﻤﻥ ﺍﻟﺸـﺒﻜﺔ ﻟﻤﺩﺓ ﻻ ﺘﻘل ﻋﻥ‬
‫‪ 30‬ﺩﻗﻴﻘﺔ ﻭﺃﻥ ﻻ ﻴﻜﻭﻥ ﻫﺒﻭﻁ ﺍﻟﻀﻐﻁ ﻓﻲ ﻨﻬﺎﻴﺔ ﺍﻟﻤﺩﺓ ﺃﻜﺒﺭ ﻤﻥ ‪ %5‬ﻤﻥ ﻀﻐﻁ‬
‫ﺍﻻﺨﺘﺒﺎﺭ‪:‬‬

‫ﻀﻐﻁ ﺍﻻﺨﺘﺒﺎﺭ ﻟﻸﻨﻅﻤﺔ ﺫﺍﺕ‬ ‫ﻀﻐﻁ ﺍﻻﺨﺘﺒﺎﺭ ﻟﻸﻨﻅﻤﺔ‬


‫ﺠﺯﺀ ﺍﻟﻨﻅﺎﻡ ﺍﻟﻭﺍﻗﻊ‬
‫ﺍﻟﻀﻐﻁ ﺍﻟﻤﻨﺨﻔﺽ )ﺒﺎﺭ(‬ ‫ﺫﺍﺕ ﺍﻟﻀﻐﻁ ﺍﻟﻌﺎﻟﻲ )ﺒﺎﺭ(‬
‫ﺒﻴﻥ ﺨﺯﺍﻥ )ﺃﺴﻁﻭﺍﻨﺎﺕ(‬
‫‪2 -/+ 35‬‬ ‫‪5 -/+ 160‬‬ ‫ﺍﻟﻨﻅﺎﻡ ﻭﺒﻴﻥ ﺼﻤﺎﻤﺎﺕ‬
‫ﺍﻟﺘﺤﻜﻡ‬
‫‪2 -/+ 35‬‬ ‫‪3 -/+ 80‬‬ ‫ﻜﺎﻓﺔ ﺍﻷﻨﺎﺒﻴﺏ ﺍﻷﺨﺭﻯ‬

‫‪28‬‬
‫ﻤﻨﻅﻭﻤﺔ ﺍﻟﺘﺤﻜﻡ ﻭﺍﻹﻨﺫﺍﺭ ﻓﻲ ﺍﻟﻨﻅﺎﻡ‬

‫ﺘﺸـﻜل ﺍﻷﺠﺯﺍﺀ ﺍﻟﻤﺫﻜﻭﺭﺓ ﻓﻲ ﻫﺫﺍ ﺍﻟﻔﺼل ﺍﻟﺤﺩ ﺍﻷﺩﻨﻰ ﺍﻟﻤﻁﻠﻭﺏ ﻟﻤﻨﻅﻭﻤﺔ ﺍﻟﺘﺤﻜﻡ‬
‫ﻭﺍﻹﻨﺫﺍﺭ ﻓﻲ ﻨﻅﺎﻡ ﻋﺎﻤل ﺒﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪.CO2‬‬

‫ﻨﻅﺎﻡ ﺍﻟﻜﺸـﻑ‪:‬‬

‫ﺇﻥ ﺃﻫﻤﻴﺔ ﺍﺨﺘﻴﺎﺭ ﻨﻅﺎﻡ ﻜﺸـﻑ ﺒﺩﺀ ﺍﻟﺤﺭﻴﻕ ﺒﺸـﻜل ﺠﻴﺩ ﺘﺸـﻜل ﺍﻟﻌﻨﺼﺭ‬
‫ﺍﻷﺴـﺎﺴـﻲ ﻟﻠﺤﻤﺎﻴﺔ ﺍﻟﻔﻌﺎﻟﺔ ﻤﻥ ﺨﻁﺭ ﺍﻟﺤﺭﻴﻕ‪ ،‬ﺤﻴﺙ ﺘﻌﺘﻤﺩ ﻓﻠﺴـﻔﺔ ﺘﺼﻤﻴﻡ ﺃﻨﻅﻤﺔ‬
‫ﺍﻟﻭﻗﺎﻴﺔ ﻤﻥ ﺍﻟﺤﺭﻴﻕ ﻋﻠﻰ ﻜﺸـﻑ ﺍﻟﺤﺭﻴﻕ ﻋﻨﺩ ﺒﺩﺍﻴﺔ ﺤﺩﻭﺜﻪ ﻭﺍﻟﻌﻤل ﻋﻠﻰ ﺇﻁﻔﺎﺌﻪ‬
‫ﺒﺄﻗﺼﺭ ﻭﻗﺕ ﻤﻤﻜﻥ ﻭﺒﺄﻗل ﺍﻷﻀﺭﺍﺭ ﺍﻟﻤﻤﻜﻨﺔ‪.‬‬

‫ﻭﻤﻥ ﻫﻨﺎ ﻨﺠﺩ ﺃﻥ ﺍﺨﺘﻴﺎﺭ ﻨﻅﺎﻡ ﺍﻟﻜﺸـﻑ ﻴﻌﺘﻤﺩ ﺒﺸـﻜل ﺃﺴـﺎﺴـﻲ ﻋﻠﻰ ﺍﻟﺨﺒﺭﺓ ﻓﻲ‬
‫ﺘﺤﻠﻴل ﺨﻁﺭ ﺍﻟﺤﺭﻴﻕ ﺍﻟﻤﺤﺘﻤل ﻭﻨﻭﻉ ﺍﻟﻤﺎﺩﺓ ﺍﻟﻤﺤﺘﺭﻗﺔ ﺍﻟﻤﺤﺘﻤل ﻭﻁﺒﻴﻌﺔ ﺍﻟﻤﻜﺎﻥ‬
‫ﺍﻹﻨﺸـﺎﺌﻴﺔ )ﻜﺎﺭﺘﻔﺎﻉ ﺍﻷﺴﻘﻑ ﻤﺜﻼ"(‪.‬‬

‫ﻭﺘﺘﻨﻭﻉ ﺃﺠﻬﺯﺓ ﺍﻟﻜﺸـﻑ ﺒﺘﻨﻭﻉ ﻁﺒﻴﻌﺔ ﺍﺴـﺘﺠﺎﺒﺘﻬﺎ ﻭﻟﻜﻥ ﻴﻤﻜﻥ ﺘﺼﻨﻴﻔﻬﺎ ﺒﺸـﻜل‬
‫ﻋﺎﻡ ﺇﻟﻰ‪:‬‬

‫ﺃﺠﻬﺯﺓ ﻜﺸـﻑ ﺍﻟﺩﺨﺎﻥ‪ :‬ﻭﺘﺘﺤﺴﺱ ﻫﺫﻩ ﺍﻷﺠﻬﺯﺓ ﻭﺠﻭﺩ ﺍﻟﺩﺨﺎﻥ ﻓﻲ ﺍﻟﻤﻜﺎﻥ‬ ‫•‬
‫ﺍﻟﻤﺤﻤﻲ‪.‬‬
‫ﺃﺠﻬﺯﺓ ﻜﺸـﻑ ﺍﻟﻠﻬﺏ‪ :‬ﻭﺘﺘﺤﺴﺱ ﻫﺫﻩ ﺍﻷﺠﻬﺯﺓ ﺍﻷﺸـﻌﺔ ﻓﻭﻕ ﺍﻟﺒﻨﻔﺴـﺠﻴﺔ‬ ‫•‬
‫ﺍﻟﺼﺎﺩﺭﺓ ﻋﻥ ﻟﻬﺏ ﻤﺎ ﻓﻲ ﺍﻟﻤﻜﺎﻥ ﺍﻟﻤﺤﻤﻲ‪.‬‬
‫ﺃﺠﻬﺯﺓ ﻜﺸـﻑ ﺍﻟﺤﺭﺍﺭﺓ‪ :‬ﻭﺘﺘﺤﺴﺱ ﻫﺫﻩ ﺍﻷﺠﻬﺯﺓ ﺍﺭﺘﻔﺎﻉ ﺍﻟﺤﺭﺍﺭﺓ ﻓﻲ ﺍﻟﻤﻜﺎﻥ‬ ‫•‬
‫ﺍﻟﻤﺤﻤﻲ ﻋﻥ ﻁﺭﻴﻕ ﻭﺠﻭﺩ ﻓﺎﺼﻤﺔ ﻤﻨﺼﻬﺭﺓ ﻓﻲ ﺍﻟﺠﻬﺎﺯ‪.‬‬
‫ﺃﺠﻬﺯﺓ ﺍﻟﻜﺸﻑ ﺍﻟﺤﺭﺍﺭﻴﺔ ﺍﻟﺘﻔﺎﻀﻠﻴﺔ‪ :‬ﻭﺘﺘﺤﺴﺱ ﻫﺫﻩ ﺍﻷﺠﻬﺯﺓ ﻓﺭﻕ ﺩﺭﺠﺎﺕ‬ ‫•‬
‫ﺍﻟﺤﺭﺍﺭﺓ ﻓﻲ ﺍﻟﻤﻜﺎﻥ ﺍﻟﻤﺤﻤﻲ‪.‬‬
‫ﺃﺠﻬﺯﺓ ﻜﺸـﻑ ﺍﻟﻐﺎﺯﺍﺕ‪ :‬ﻭﺘﺘﺤﺴﺱ ﻫﺫﻩ ﺍﻷﺠﻬﺯﺓ ﺍﻟﻐﺎﺯﺍﺕ ﺍﻟﻨﺎﺠﻤﺔ ﻋﻥ‬ ‫•‬
‫ﺍﻻﺤﺘﺭﺍﻕ ﻓﻲ ﺍﻟﻤﻜﺎﻥ ﺍﻟﻤﺤﻤﻲ‪.‬‬

‫‪29‬‬
‫ﻫﻨﺎﻙ ﻤﺠﻤﻭﻋﺔ ﻤﻥ ﺍﻟﻌﻭﺍﻤل ﺍﻟﺘﻲ ﻴﺠﺏ ﺃﻥ ﺘﺅﺨﺫ ﺒﻌﻴﻥ ﺍﻻﻋﺘﺒﺎﺭ ﻋﻨﺩ ﺍﺨﺘﻴﺎﺭ ﺃﺠﻬﺯﺓ‬
‫ﺍﻟﻜﺸـﻑ‪:‬‬

‫ﻴﻔﻀل ﻓﻲ ﺤﺎل ﻭﺠﻭﺩ ﺨﻁﺭ ﺤﺭﻴﻕ ﻴﻤﻜﻥ ﺃﻥ ﻴﻨﺘﺞ ﺩﺨﺎﻨﺎ" ﻜﺜﻴﻔﺎ" ﺩﻭﻥ ﻭﺠﻭﺩ‬ ‫•‬
‫ﺤﺭﺍﺭﺓ ﻋﺎﻟﻴﺔ ﺃﻭ ﻟﻬﺏ ﻓﻲ ﺍﻟﻤﻜﺎﻥ )ﻤﺜل ﺤﺭﻴﻕ ﺍﻟﻜﺎﺒﻼﺕ( ﺃﻥ ﻨﺴـﺘﺨﺩﻡ ﺃﺠﻬﺯﺓ‬
‫ﻜﺸـﻑ ﺍﻟﺩﺨﺎﻥ‪.‬‬
‫ﻴﻔﻀل ﻓﻲ ﺤﺎل ﺤﻤﺎﻴﺔ ﻤﻜﺎﻥ ﻟﺘﺨﺯﻴﻥ ﺍﻟﺴـﻭﺍﺌل ﺍﻟﻘﺎﺒﻠﺔ ﻟﻼﺸـﺘﻌﺎل ﺃﻭ ﻤﻭﺍﺩ‬ ‫•‬
‫ﺒﻼﺴـﺘﻴﻜﻴﺔ ﺃﻥ ﻨﺴـﺘﺨﺩﻡ ﺃﺠﻬﺯﺓ ﺍﻟﻜﺸـﻑ ﺫﺍﺕ ﺍﻟﻔﻭﺍﺼﻡ ﺍﻟﻤﻨﺼﻬﺭﺓ‪.‬‬
‫ﻓﻲ ﺒﻌﺽ ﺍﻷﺤﻴﺎﻥ ﻴﻔﻀل ﺍﺴـﺘﺨﺩﺍﻡ ﺃﻜﺜﺭ ﻤﻥ ﻨﻭﻉ ﻤﻥ ﺃﺠﻬﺯﺓ ﺍﻟﻜﺸـﻑ‬ ‫•‬
‫ﻟﺤﻤﺎﻴﺔ ﻤﻨﻁﻘﺔ ﻭﺍﺤﺩﺓ‪.‬‬
‫ﺇﻥ ﺯﻴﺎﺩﺓ ﺍﺭﺘﻔﺎﻉ ﺍﻟﺴـﻘﻑ ﺃﻭ ﻭﺠﻭﺩ ﻋﻭﺍﺌﻕ ﻓﻲ ﺍﻟﺴـﻘﻑ ﻴﻤﻜﻥ ﺃﻥ ﻴﺅﺜﺭ‬ ‫•‬
‫ﻋﻠﻰ ﻋﻤل ﺃﺠﻬﺯﺓ ﺍﻟﻜﺸـﻑ ﻤﻥ ﺤﻴﺙ ﺯﻴﺎﺩﺓ ﺍﻟﻭﻗﺕ ﺍﻟﻼﺯﻡ ﻟﺘﻔﻌﻴﻠﻬﺎ‪.‬‬
‫ﻓﻲ ﺤﺎل ﺍﺴـﺘﺨﺩﺍﻡ ﺃﺠﻬﺯﺓ ﻜﺸـﻑ ﺤﺭﺍﺭﻴﺔ ﻴﺠﺏ ﺍﻻﻨﺘﺒﺎﻩ ﻟﻤﺠﺎل ﺩﺭﺠﺔ‬ ‫•‬
‫ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﻤﺤﻴﻁﺔ ﺍﻟﻤﺫﻜﻭﺭ ﻓﻲ ﻤﻭﺍﺼﻔﺎﺕ ﺠﻬﺎﺯ ﺍﻟﻜﺸـﻑ )ﻤﻌﺘﻤﺩ ﻤﻥ ﻗﺒل‬
‫ﺃﺤﺩ ﺍﻟﻬﻴﺌﺎﺕ ﺍﻟﺩﻭﻟﻴﺔ( ﺤﻴﺙ ﺃﻥ ﻤﻌﻅﻡ ﺃﺠﻬﺯﺓ ﺍﻟﻜﺸـﻑ ﺘﻌﻤل ﺒﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ‬
‫ﺃﺩﻨﻰ ﻤﻥ ‪ 50‬ﺩﺭﺠﺔ ﻤﺌﻭﻴﺔ‪.‬‬
‫ﻓﻲ ﺤﺎل ﺍﺴـﺘﺨﺩﺍﻡ ﺃﺠﻬﺯﺓ ﻜﺸـﻑ ﺤﺭﺍﺭﻴﺔ ﻴﺠﺏ ﺍﻻﻨﺘﺒﺎﻩ ﺇﻟﻰ ﺃﻥ ﻓﺭﻕ ﺩﺭﺠﺔ‬ ‫•‬
‫ﺍﻟﺤﺭﺍﺭﺓ ﺒﻴﻥ ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﻤﺤﻴﻁﺔ ﻭﺤﺭﺍﺭﺓ ﺘﻔﻌﻴل ﺠﻬﺎﺯ ﺍﻟﻜﺸـﻑ ﻋﺎﺩﺓ ﻤﺎ ﻴﻜﻭﻥ‬
‫‪ 30‬ﺩﺭﺠﺔ ﻤﺌﻭﻴﺔ‪.‬‬
‫ﻻ ﻴﻨﺼﺢ ﺒﺎﺴـﺘﺨﺩﺍﻡ ﺃﺠﻬﺯﺓ ﻜﺸـﻑ ﺤﺭﺍﺭﻴﺔ ﺘﻔﺎﻀﻠﻴﺔ ﻓﻲ ﺍﻷﻤﺎﻜﻥ ﺍﻟﺘﻲ‬ ‫•‬
‫ﺘﺘﻐﻴﺭ ﻓﻴﻬﺎ ﺩﺭﺠﺔ ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﻤﺤﻴﻁﻴﺔ ﺒﺸـﻜل ﺴـﺭﻴﻊ ﻭﻜﺒﻴﺭ‪.‬‬
‫ﻴﻤﻜﻥ ﺍﺴـﺘﺨﺩﺍﻡ ﺃﺠﻬﺯﺓ ﻜﺸـﻑ ﺍﻟﺩﺨﺎﻥ ﻓﻲ ﺒﻴﺌﺔ ﺘﺼل ﻓﻴﻬﺎ ﺴـﺭﻋﺔ ﺍﻟﺭﻴﺎﺡ‬ ‫•‬
‫ﺇﻟﻰ ‪ 5‬ﻤﺘﺭ‪/‬ﺜﺎﻨﻴﺔ ﻜﺤﺩ ﺃﻗﺼﻰ‪.‬‬
‫ﻴﺠﺏ ﻤﺭﺍﻋﺎﺓ ﺍﺨﺘﻴﺎﺭ ﺃﺠﻬﺯﺓ ﻜﺸـﻑ ﻤﻨﺎﺴـﺒﺔ ﻓﻲ ﺍﻷﻤﺎﻜﻥ ﺍﻟﻤﻌﺭﻀﺔ‬ ‫•‬
‫ﻟﻼﻫﺘﺯﺍﺯﺍﺕ‪.‬‬
‫ﻴﻤﻨﻊ ﺍﺴـﺘﺨﺩﺍﻡ ﺃﺠﻬﺯﺓ ﺍﻟﻜﺸـﻑ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻲ ﺍﻷﻤﺎﻜﻥ ﺫﺍﺕ ﺍﻟﺒﻴﺌﺔ ﺍﻟﻘﺎﺒﻠﺔ‬ ‫•‬
‫ﻟﻼﻨﻔﺠﺎﺭ‪.‬‬
‫ﻴﺠﺏ ﺘﺠﻨﺏ ﺃﻤﺎﻜﻥ ﺍﻟﺘﺭﻜﻴﺏ ﻷﺠﻬﺯﺓ ﺍﻟﻜﺸـﻑ ﻭﺍﻟﺘﻲ ﻗﺩ ﺘﺴـﺒﺏ ﺤﺼﻭل‬ ‫•‬
‫ﺇﻨﺫﺍﺭﺍ" ﻜﺎﺫﺒﺎ" )ﻨﺘﻴﺠﺔ ﻷﺸـﻌﺔ ﺍﻟﺸـﻤﺱ ﺍﻟﻤﺒﺎﺸـﺭﺓ ﻤﺜﻼ"(‪.‬‬
‫ﻋﻨﺩ ﺍﺴـﺘﺨﺩﺍﻡ ﺃﺠﻬﺯﺓ ﻜﺸـﻑ ﺍﻟﺩﺨﺎﻥ ﻟﺘﻔﻌﻴل ﺍﻟﻨﻅﺎﻡ ﻴﺠﺏ ﻀﺒﻁ ﺘﺤﻜﻡ‬ ‫•‬
‫ﺍﻟﻨﻅﺎﻡ ﺒﺤﻴﺙ ﻴﻔﻌل ﻨﺘﻴﺠﺔ ﺇﺸـﺎﺭﺘﻴﻥ ﻤﻥ ﺠﻬﺎﺯﻴﻥ ﻤﺨﺘﻠﻔﻴﻥ ﻓﻲ ﻨﻔـﺱ ﺍﻟﻤﻨﻁﻘﺔ‬
‫ﻭﻴﻨﺼﺢ ﺒﺄﻥ ﻴﻭﻀﻊ ﺠﻬﺎﺯ ﻭﺍﺤﺩ ﻟﻜل ‪ 25‬ﻤﺘﺭ ﻤﺭﺒﻊ ﻤﻥ ﺃﺭﻀﻴﺔ ﺍﻟﻤﻜﺎﻥ‬
‫ﺍﻟﻤﺤﻤﻲ‪.‬‬

‫‪30‬‬
‫• ﻴﺠﺏ ﺃﻥ ﻻ ﻴﺯﻴﺩ ﺍﻟﺒﻌﺩ ﺒﻴﻥ ﺠﻬﺎﺯ ﺍﻟﻜﺸـﻑ ﻭﺃﻱ ﺠﺩﺍﺭ ﻓﻲ ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﻤﺤﻤﻴﺔ‬
‫ﻋﻥ ‪ 3‬ﻤﺘﺭ‪.‬‬
‫• ﻴﺠﺏ ﺃﻥ ﻻ ﻴﺯﻴﺩ ﺍﻟﺒﻌﺩ ﺒﻴﻥ ﺠﻬﺎﺯ ﺍﻟﻜﺸـﻑ ﻭﺴـﻘﻑ ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﻤﺤﻤﻴﺔ ﻋﻥ‬
‫‪ 30‬ﺴـﻡ‪.‬‬
‫• ﻴﺠﺏ ﺃﻥ ﻻ ﻴﺯﻴﺩ ﺍﻟﺒﻌﺩ ﺒﻴﻥ ﺠﻬﺎﺯﻱ ﻜﺸـﻑ ﻋﻥ ‪ 6‬ﻤﺘﺭ‪.‬‬

‫ﺠﻬﺎﺯ ﺍﻟﺘﺄﺨﻴﺭ ﺍﻟﺯﻤﻨﻲ‪:‬‬

‫ﺇﻥ ﺠﻬﺎﺯ ﺍﻟﺘﺄﺨﻴﺭ ﺍﻟﺯﻤﻨﻲ ﺠﺯﺀ ﺭﺌﻴﺴـﻲ ﻤﻥ ﺍﻟﻨﻅﺎﻡ ﻤﻬﻤﺘﻪ ﺘﺄﺨﻴﺭ ﺒﺩﺀ ﻋﻤل ﺍﻟﻨﻅﺎﻡ‬
‫ﻟﻔﺘﺭﺓ ﺯﻤﻨﻴﺔ ﺘﻀﻤﻥ ﺘﻨﺒﻴﻪ ﻭﺇﺨﻼﺀ ﺍﻷﺸـﺨﺎﺹ ﺍﻟﻠﺫﻴﻥ ﻗﺩ ﻴﺘﻭﺍﺠﺩﻭﺍ ﻓﻲ ﻤﻨﻁﻘﺔ‬
‫ﺍﻟﺤﺭﻴﻕ ﻋﻨﺩ ﺤﺩﻭﺜﻪ‪.‬‬

‫ﻭﻴﺠﺏ ﺃﻥ ﻻ ﻴﻘل ﺯﻤﻥ ﺍﻟﺘﺄﺨﻴﺭ ﻋﻥ ‪ 10‬ﺜﻭﺍﻥ ﻭﺃﻥ ﻻ ﻴﺯﻴﺩ ﻋﻥ ‪ 30‬ﺜﺎﻨﻴﺔ ﻭﺫﻟﻙ ﺘﺒﻌﺎ"‬
‫ﻟﻁﺒﻴﻌﺔ ﺍﻟﻤﻜﺎﻥ ﻭﻋﺩﺩ ﺍﻷﺸـﺨﺎﺹ ﺍﻟﻤﺤﺘﻤل ﻭﻁﺭﻕ ﺍﻹﺨﻼﺀ‪.‬‬

‫ﺠﻬﺎﺯ ﺍﻹﻨﺫﺍﺭ‪:‬‬

‫ﻴﺠﺏ ﺃﻥ ﻴﺤﺘﻭﻱ ﺍﻟﻨﻅﺎﻡ ﻋﻠﻰ ﺃﺠﻬﺯﺓ ﺇﻨﺫﺍﺭ ﻜﺎﻓﻴﺔ ﻹﻋﻼﻡ ﺠﻤﻴﻊ ﺍﻷﺸـﺨﺎﺹ‬
‫ﺍﻟﻤﺘﻭﺍﺠﺩﻴﻥ ﻓﻲ ﺍﻟﻤﻨﻁﻘﺔ ﺒﻭﻗﻭﻉ ﺤﺭﻴﻕ ﻓﻴﻬﺎ ﻭﻴﺠﺏ ﺃﻥ ﻴﺤﻘﻕ ﺠﻬﺎﺯ ﺍﻹﻨﺫﺍﺭ ﻤﺎ ﻴﻠﻲ‪:‬‬

‫ﻴﺠﺏ ﺃﻥ ﻴﺒﺩﺃ ﺠﻬﺎﺯ ﺍﻹﻨﺫﺍﺭ ﺒﺎﻟﻌﻤل ﻓﻭﺭ ﺍﻜﺘﺸـﺎﻑ ﺍﻟﺤﺭﻴﻕ ﻤﻥ ﻗﺒل ﺃﺠﻬﺯﺓ‬ ‫•‬
‫ﺍﻟﻜﺸـﻑ‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﻴﻜﻭﻥ ﺍﻹﻨﺫﺍﺭ ﺫﺍ ﻁﺒﻴﻌﺔ ﺜﻨﺎﺌﻴﺔ ﺴـﻤﻌﻴﺔ ﻭﺒﺼﺭﻴﺔ‪.‬‬ ‫•‬
‫ﻴﺠﺏ ﺃﻥ ﻴﺴـﺘﻤﺭ ﺍﻹﻨﺫﺍﺭ ﻋﻠﻰ ﻤﺩﺍﺨل ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﻤﻐﻤﻭﺭﺓ ﺒﺎﻟﻐﺎﺯ ﻟﻤﺩﺓ ‪30‬‬ ‫•‬
‫ﺩﻗﻴﻘﺔ ﻋﻠﻰ ﺍﻷﻗل ﺒﻌﺩ ﻏﻤﺭ ﺍﻟﻤﻨﻁﻘﺔ ﺒﺤﻴﺙ ﻴﻨﺒﻪ ﺇﻟﻰ ﺨﻁﺭ ﺩﺨﻭل ﺍﻟﻤﻨﻁﻘﺔ ﻗﺒل‬
‫ﻋﻤﻠﻴﺔ ﺍﻟﺘﻬﻭﻴﺔ ﻭﻁﺭﺩ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ﺒﻌﺩ ﺇﻁﻔﺎﺀ ﺍﻟﺤﺭﻴﻕ‪.‬‬
‫ﻴﺠﺏ ﺃﻥ ﺘﺨﺘﻠﻑ ﻨﻭﻋﻴﺔ ﺍﻹﻨﺫﺍﺭ ﺍﻟﺼﻭﺘﻲ ﻋﻥ ﺃﻱ ﺇﻨﺫﺍﺭ ﺼﻭﺘﻲ ﺁﺨﺭ ﻗﺩ ﻴﻜﻭﻥ‬ ‫•‬
‫ﻤﺴـﺘﻌﻤﻼ" ﻷﻏﺭﺍﺽ ﺃﺨﺭﻯ ﻓﻲ ﻨﻔـﺱ ﺍﻟﻤﻨﻁﻘﺔ‪.‬‬
‫ﻴﻔﻀل ﺇﻀﺎﻓﺔ ﻜﺒﺴـﺔ ﻴﺩﻭﻴﺔ ﻟﺘﻔﻌﻴل ﻨﻅﺎﻡ ﺍﻹﻨﺫﺍﺭ ﻋﻨﺩ ﻓﺸـل ﺍﻟﻨﻅﺎﻡ ﺍﻵﻟﻲ‪.‬‬ ‫•‬

‫‪31‬‬
‫ﻜﺒﺴـﺎﺕ ﺘﻌﻁﻴل ﺍﻟﻨﻅﺎﻡ ﻴﺩﻭﻴﺎ"‪:‬‬

‫ﻴﺠﺏ ﺃﻥ ﺘﺯﻭﺩ ﺠﻤﻴﻊ ﺍﻷﻨﻅﻤﺔ ﺒﻜﺒﺴـﺎﺕ ﻴﺩﻭﻴﺔ ﻟﺘﻌﻁﻴل ﻋﻤﻠﻴﺔ ﺘﺤﺭﻴﺭ ﺍﻟﻐﺎﺯ ﻀﻤﻥ‬
‫ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﻤﺤﻤﻴﺔ ﻤﻴﻜﺎﻨﻴﻜﻴﺎ" ﺨﻼل ﻓﺘﺭﺓ ﺍﻟﺘﺄﺨﻴﺭ ﻋﻠﻰ ﺃﻥ ﺘﺴـﺘﺨﺩﻡ ﻫﺫﻩ ﺍﻟﻜﺒﺴـﺔ ﻓﻲ‬
‫ﺤﺎل ﺍﻹﻨﺫﺍﺭ ﺍﻟﻜﺎﺫﺏ ﺃﻭ ﺍﻟﺴـﻴﻁﺭﺓ ﺍﻟﻤﻜﺎﻨﻴﺔ ﻋﻠﻰ ﺍﻟﺤﺭﻴﻕ‪ ،‬ﻭﺘﻭﻀﻊ ﻫﺫﻩ ﺍﻟﻜﺒﺴـﺎﺕ‬
‫ﺒﺸـﻜل ﻭﺍﻀﺢ ﻭﻋﻨﺩ ﻤﺨﺎﺭﺝ ﺍﻟﻤﻨﺎﻁﻕ ﺍﻟﻤﺤﻤﻴﺔ ﻭﻓﻲ ﻤﻜﺎﻥ ﺘﻭﻀﻊ ﻤﻜﻭﻨﺎﺕ ﺍﻟﻨﻅﺎﻡ‬
‫ﺍﻷﺴـﺎﺴﻴﺔ )ﺃﺴﻁﻭﺍﻨﺎﺕ‪ ،‬ﻨﻅﺎﻡ ﺘﺤﻜﻡ(‪ .‬ﻭﻴﺠﺏ ﺃﻥ ﻻ ﺘﻌﻁل ﻫﺫﻩ ﺍﻟﻜﺒﺴـﺎﺕ ﻋﻤل ﺃﻱ‬
‫ﻤﻥ ﺃﺠﻬﺯﺓ ﺍﻟﻜﺸـﻑ ﺃﻭ ﺍﻹﻨﺫﺍﺭ‪.‬‬

‫‪32‬‬
‫ﺘﻔﺘﻴـﺵ ﺍﻟﻨﻅﺎﻡ‬

‫ﺇﻥ ﻤﻥ ﺃﻫﻡ ﺍﻟﻭﺍﺠﺒﺎﺕ ﺍﻟﻤﺘﺭﺘﺒﺔ ﻋﻠﻰ ﺍﻷﺸـﺨﺎﺹ ﺍﻟﻤﺨﻭﻟﻴﻥ ﻭﺍﻟﻤﺩﺭﺒﻴﻥ ﻋﻠﻰ ﺘﺸـﻐﻴل‬
‫ﻭﺍﺴـﺘﺜﻤﺎﺭ ﺍﻟﻨﻅﺎﻡ ﺍﻟﻘﻴﺎﻡ ﺒﺎﻟﺘﻔﺘﻴـﺵ ﻭﺍﻟﺘﺄﻜﺩ ﻤﻥ ﺠﺎﻫﺯﻴﺔ ﻋﻤل ﺠﻤﻴﻊ ﻤﻜﻭﻨﺎﺕ ﺍﻟﻨﻅﺎﻡ‬
‫ﻭﺒﺸـﻜل ﺩﻭﺭﻱ‪.‬‬

‫ﺍﻟﺘﻔﺘﻴـﺵ ﺍﻟﻴﻭﻤﻲ‪:‬‬

‫ﻴﻌﺘﺒﺭ ﺍﻟﺘﻔﺘﻴـﺵ ﺍﻟﻴﻭﻤﻲ ﻟﻠﻨﻅﺎﻡ ﻤﻥ ﺍﻷﻋﻤﺎل ﺍﻟﺭﻭﺘﻴﻨﻴﺔ ﻭﺍﻟﺒﺴـﻴﻁﺔ ﺤﻴﺙ ﻴﻌﺘﻤﺩ ﻋﻠﻰ‬
‫ﺇﺠﺭﺍﺀ ﻓﺤﺹ ﺒﺼﺭﻱ ﻟﻤﻜﻭﻨﺎﺕ ﺍﻟﻨﻅﺎﻡ ﺒﺤﺜﺎ" ﻋﻥ ﺃﻱ ﻤﺅﺸـﺭ ﻴﻔﻴﺩ ﺒﺎﺤﺘﻤﺎل ﺤﺩﻭﺙ‬
‫ﻋﻁل ﻤﺎ ﻓﻲ ﺍﻟﻨﻅﺎﻡ‪ ،‬ﻭﻻ ﻴﺴـﺠل ﻫﺫﺍ ﺍﻟﺘﻔﺘﻴـﺵ ﻓﻲ ﺴـﺠل ﺨﺎﺹ ﺒﻪ‪.‬‬

‫ﺍﻟﺘﻔﺘﻴـﺵ ﺍﻷﺴـﺒﻭﻋﻲ‪:‬‬

‫ﺍﻟﺘﻔﺘﻴـﺵ ﺍﻷﺴـﺒﻭﻋﻲ ﻟﻠﻨﻅﺎﻡ ﻋﻤﻼ" ﺃﻜﺜﺭ ﺘﻌﻘﻴﺩﺍ" ﺒﻘﻠﻴل ﻤﻥ ﺍﻟﺘﻔﺘﻴـﺵ ﺍﻟﻴﻭﻤﻲ‪ ،‬ﺇﻻ‬
‫ﺃﻨﻪ ﻴﺠﺏ ﺍﻟﻘﻴﺎﻡ ﺒﻪ ﻭﺘﺴـﺠﻴل ﺍﻟﻤﻼﺤﻅﺎﺕ ﻓﻲ ﺴـﺠل ﺨﺎﺹ ﺒﺎﻟﺘﻔﺘﻴـﺵ‬
‫ﺍﻷﺴـﺒﻭﻋﻲ‪ .‬ﻭﻴﺸـﻤل ﺍﻟﺘﻔﺘﻴـﺵ ﺍﻷﺴـﺒﻭﻋﻲ ﺍﻷﻋﻤﺎل ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬
‫• ﻓﺤﺹ ﺃﺠﻬﺯﺓ ﻜﺸـﻑ ﺍﻟﺤﺭﻴﻕ‪.‬‬
‫• ﻓﺤﺹ ﻜﻤﻴﺔ ﺍﻟﻐﺎﺯ ﺍﻟﻤﻭﺠﻭﺩﺓ ﻓﻲ ﺃﺴـﻁﻭﺍﻨﺎﺕ ﺍﻟﻨﻅﺎﻡ ﻭﻓﻲ ﺤﺎل ﻨﻘﺼﺎﻥ ﻫﺫﻩ‬
‫ﺍﻟﻜﻤﻴﺔ ﺒﻤﻘﺩﺍﺭ ‪ %10‬ﻴﺠﺏ ﺘﺒﺩﻴل ﺍﻷﺴـﻁﻭﺍﻨﺔ ﻓﻭﺭﺍ" ﻭﺇﻴﺠﺎﺩ ﺴـﺒﺏ‬
‫ﺍﻟﺘﺴـﺭﺏ‪.‬‬
‫• ﻓﺤﺹ ﻭﻀﻌﻴﺎﺕ ﺍﻟﺼﻤﺎﻤﺎﺕ‪.‬‬
‫• ﻓﺤﺹ ﻤﺼﺎﺩﺭ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻤﻭﺼﻭﻟﺔ ﺒﺎﻟﻨﻅﺎﻡ‪.‬‬

‫ﺍﻟﺘﻔﺘﻴـﺵ ﺍﻟﺸـﻬﺭﻱ‪:‬‬

‫ﻴﺴـﺠل ﻫﺫﺍ ﺍﻟﺘﻔﺘﻴـﺵ ﻓﻲ ﺴـﺠل ﺨﺎﺹ ﻭﻴﺸـﻤل ﺇﻀﺎﻓﺔ ﺇﻟﻰ ﺃﻋﻤﺎل ﺍﻟﺘﻔﺘﻴـﺵ‬
‫ﺍﻷﺴـﺒﻭﻋﻲ ﺍﻷﻋﻤﺎل ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬
‫ﻯ ﻭﺘﺠﻬﻴﺯﺍﺕ ﺍﻹﺨﻼﺀ )ﺇﻥ ﻭﺠﺩﺕ(‪.‬‬ ‫• ﻓﺤﺹ ﻤﺨﺎﺭﺝ ﺍﻟﻁﻭﺍﺭ ْ‬
‫• ﻓﺤﺹ ﻨﻅﺎﻡ ﺍﻹﻨﺫﺍﺭ ﺍﻟﻤﺭﺌﻲ ﻭﺍﻟﻤﺴـﻤﻭﻉ‪.‬‬
‫• ﻓﺤﺹ ﺠﻬﺎﺯ ﺍﻟﺘﺄﺨﻴﺭ ﺍﻟﺯﻤﻨﻲ ﻟﻠﻨﻅﺎﻡ‪.‬‬
‫• ﻓﺤﺹ ﻓﻭﻫﺎﺕ ﻨﻔﺙ ﺍﻟﻐﺎﺯ‪.‬‬
‫• ﻓﺤﺹ ﺃﻱ ﺘﺠﻬﻴﺯﺍﺕ ﺇﻀﺎﻓﻴﺔ ﻓﻲ ﺍﻟﻨﻅﺎﻡ‪.‬‬

‫‪33‬‬
‫ﻤﺨﻁﻁ ﺼﻨﺩﻭﻗﻲ ﻟﻨﻅﺎﻡ ﺇﻁﻔﺎﺀ ﺒﻐﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪CO2‬‬

‫‪34‬‬
‫ﻤﻼﺤﻅـﺔ ﻫـﺎﻤـﺔ‬
‫ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﺠﻤﻴﻊ ﻤﻜﻭﻨﺎﺕ ﺍﻟﻨﻅﺎﻡ ﺍﻟﺘﺎﻟﻴﺔ ﻤﺼﺎﺩﻕ ﻋﻠﻰ ﻤﻼﺌﻤﺘﻬﺎ‬
‫ﻟﻼﺴـﺘﻌﻤﺎل ﻓﻲ ﺃﻨﻅﻤﺔ ﻏﺎﺯ ﺜﺎﻨﻲ ﺃﻭﻜﺴﻴﺩ ﺍﻟﻜﺭﺒﻭﻥ ‪ CO2‬ﻤﻥ ﻗﺒل ﺠﻬﺎﺕ‬
‫ﺩﻭﻟﻴﺔ ﻤﻌﺘﻤﺩﺓ‪:‬‬

‫ﺃﺠﻬﺯﺓ ﺍﻟﺘﺤﻜﻡ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﺍﻷﻭﺘﻭﻤﺎﺘﻴﻜﻴﺔ‬ ‫•‬


‫ﺃﺠﻬﺯﺓ ﺍﻟﺘﺤﻜﻡ ﺍﻷﻭﺘﻭﻤﺎﺘﻴﻜﻴﺔ ﻏﻴﺭ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‬ ‫•‬
‫ﺠﻤﻴﻊ ﺼﻤﺎﻤﺎﺕ ﺍﻟﻀﻐﻁ ﺍﻟﻌﺎﻟﻲ‬ ‫•‬
‫ﺃﺠﻬﺯﺓ ﺍﻟﺘﺤﻜﻡ ﺍﻟﻴﺩﻭﻴﺔ‬ ‫•‬
‫ﺃﺠﻬﺯﺓ ﺍﻟﺘﺄﺨﻴﺭ ﺍﻟﺯﻤﻨﻲ‬ ‫•‬
‫ﺼﻤﺎﻤﺎﺕ ﺍﻷﺴـﻁﻭﺍﻨﺎﺕ‬ ‫•‬
‫ﺼﻤﺎﻤﺎﺕ ﻋﺩﻡ ﺍﻟﺭﺠﻭﻉ‬ ‫•‬
‫ﻤﻘﺎﻴﻴـﺱ ﺍﻟﻀﻐﻁ‬ ‫•‬
‫ﻤﻨﻅﻤﺎﺕ ﺘﻔﻌﻴل ﺼﻤﺎﻤﺎﺕ ﺍﻷﺴـﻁﻭﺍﻨﺎﺕ‬ ‫•‬
‫ﺃﺠﻬﺯﺓ ﺍﻹﻴﻘﺎﻑ ﺍﻟﻁﺎﺭﻯﺀ‬ ‫•‬
‫ﻓﻭﻫﺎﺕ ﻨﻔﺙ ﺍﻟﻐﺎﺯﺍﺕ‬ ‫•‬
‫ﺍﻷﻨﺎﺒﻴﺏ ﻭﺍﻟﻭﺼﻼﺕ ﺍﻟﻤﺭﻨﺔ‬ ‫•‬
‫ﺃﺠﻬﺯﺓ ﻜﺸـﻑ ﺍﻟﺤﺭﻴﻕ‬ ‫•‬
‫ﺍﻟﺼﻤﺎﻤﺎﺕ ﺍﻟﻤﺴـﺘﺨﺩﻤﺔ ﻓﻲ ﺍﻟﻨﻅﺎﻡ‬ ‫•‬
‫ﻤﺜﺒﺘﺎﺕ ﺍﻷﻨﺎﺒﻴﺏ‬ ‫•‬

‫‪35‬‬