You are on page 1of 2

Page 1

Flow Meter Site Investigation


Project: Location: Date/Time: Crew:
Omaha FM 3-1-10 / 14:10 ABM - WRS
MH#: Pipe Shape: Pipe Material: Pipe Size (in):
0692016 Circular Concrete 36
Site ID: Address: Site Quality: Basin:
6 133 Castelar Fair

Location Map Planar Description

Summary Description:

Site Hazards Measurements Site Conditions


Heavy Traffic? No Manhole Depth (ft): 12.75 Surcharge Evidence? Yes
Needed Traffic Attendants: No Manhole Dia. (in): 4.0 Depth of Surcharge (ft): 4
H2S: 0 O2: 20.9 MH Cover Size (in): 24.0 Depth of Debris (in): 7
LEL: 0 CO: 0 MH Cover Type: Vented Usable MH Steps? No
Describe potential hazards: Measured Flow Depth (in): 13 Meter: 2150
Velocity (fps): 0.25 Cellular Signal Strength: Full
Basic Hazards
Mounting Band Description: Antennae Install Considerations:

Scissor Possible

Other Comments: Permanent Power Available?

Velocity too slow for 2150 Yes


Sigma 910 Recommended
Page 2

Installation Sketch & Notes Pipe Cross Section

Depth (in) Width (in) Depth (in) Width (in)

SURFACE DOWN

INFLOW OUTFLOW