23 ATC WIRE & CONDUIT ILLUSTRATION

120vAC
Notes:
Power
Minimum 3/4" EMT conduit and 20% spare capacity
Label junction boxes ATC
Conduit & Box for vertical riser
and "Primary/Building"
communications cable DDC
Plenum rated wire above ceilings (typical secondary
Panel communications), fastened with wire ties every 24
inches, fasten to the structure every 6 feet in a
Cable Trough workman like manner to avoid a conflict with electrical
or HVAC installations

Conduit & Box for vertical


Use conduit above
riser and "Primary/Building"
inaccessible ceilings
communications cable

VAV VAV VAV VAV

Plaster ceiling

T T T T Stub out 6" and use


DDC bushings at end of
conduits
Panel
Conduit & Box in the wall
to the thermostat.