You are on page 1of 137

CERT'D

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


APPR'D Eastern Region Branch ‫فرع المنطقة الشرقية‬
JA

JA

JA

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

RJP

RJP

RJP
REVISED AS PER SEC COMMENTS DATED 03.06.2009 ON REVISED CT CALCULATION.

REVISED AS PER SEC COMMENTS DATED 06.12.2009 ON REVISED CT CALCULATION.


REVISED AS PER BASE DESIGN REVIEW MEETING DATED 16.03.09 & 17.03.09
DESCRIPTION

380kV CT/VT SIZING CALCULATION


(CROSS BAY C#4)
URD
PG

PG
BY

03.04.2009

25.06.2009

17.12.2009
DATE
NO.

D
B

REVISIONS
DRAWN

BY:- RJP
DATE:- 20.12.08

CHECKED

BY:- JA

DATE:- 22.12.08

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT BY DATE

THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF 380kV CT SIZING CALCULATION
FOR ORDERING A T201 EE-086959 01 OF 50 D
MATERIALS UNTIL ABU-HADRIYAH 380/115kV BSP
CERTIFIED AND
DATED
KHURSANIYAH SAUDI ARABIA JOB ORDER NO. 3-083300.01 DWG.CONT.SHT. EE-086950

SEC-ERB CAD-E (2002/03)


DMS EXCEL
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380 kV CT/VT SIZING CALCULATION EA-086959
380/115 kV BSP

INDEX

SR. NO. DESCRIPTION SHEET NO.

1.0 GENERAL DESIGN CRITERIA FOR CT CALCULATION 1

1.1 SYSTEM DESIGN DATA 1

1.2
1.3 DESIGN BASIS AND REFERENCES FOR CT CALCULATION 1
1.3 CT LEAD RESISTANCE CALCULATION 2

2.0 CT CALCULATION FOR THE FOLLOWING CT's. 3


2.1 CT: 810 B1.C1 :- BF PROTECTION (RAICA) 3

2.2 CT: 810 B1.C2 :- OHL FEEDER SET-1 PROTECTION (REL 531) 5
2.3 CT: 810 B1.C3 :- OHL FEEDER SET-2 PROTECTION (7SA522) 12
16
2.4 CT: 810 B1.C4 :- METERING 14

2.5 CT: 810 F.C3 :- SPARE 15

2.6 CT: 810 F.C2 :- BUS-BAR PROTECTION MAIN-2 (MFAC14) 16

2.7 CT: 810 F.C1 :- BUS-BAR PROTECTION MAIN-1 (MCAG 14) 20

2.8 CT: 811 B1.C1 :- BF PROTECTION (RAICA) 24

2.9 CT: 811 B1.C2 :- OHL FEEDER SET-1 PROTECTION (RED 670) 25

2.10 CT: 811 B1.C3 :- OHL FEEDER SET-2 PROTECTION (MiCOM P546) 31

2.11 CT: 811 B1.C4 :- METERING 34

2.12 CT: 811 B2.C4 :- METERING 35


2.13 CT: 811 B2.C3 :- OHL FEEDER SET-2 PROTECTION (7SA522) 35

2.14 CT: 811 B2.C2 :-OHL FEEDER SET-1 PROTECTION (REL 531) 36

2.15 CT: 811 B2.C1 :- SPARE 36


2.16 CT: 812 F.C1 :- BUS-BAR PROTECTION MAIN-1 (MCAG 14) 37

2.17 CT: 812 F.C2 :- BUS-BAR PROTECTION MAIN-2 (MFAC14) 38

2.18 CT: 812 F.C3 :- SPARE 39

2.19 CT: 812 B2.C4 :- METERING 40

2.20 CT: 812 B2.C3 :- OHL FEEDER SET-2 PROTECTION (7SA522) 40

2.21 CT: 812 B2.C2 :- OHL FEEDER SET-1 PROTECTION (REL 531) 41

2.22 CT: 812 B2.C1 :- BF PROTECTION 41

ABU-HADRIYAH CONTRACT No.


BAY NUMBER: CROSS BAY C4 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380 kV CT/VT SIZING CALCULATION EA-086959
380/115 kV BSP

3.00 LINE VT SIZING CALCULATION 42

BUS-1 VT SIZING CALCULATION 47

BUS-2 VT SIZING CALCULATION 49


ATTACHMENTS:

ANNEXURE-1 CT REQUIREMENT OF RELAY


ANNEXURE-2 VA REQUIREMENT OF RELAY

ANNEXURE-3 SAUDI CABLE CATALOGUE


ANNEXURE-4 380kV GIS CT DATA FROM AREVA

ANNEXURE-4A 380kV GIS DATA SCHEDULE FROM AREVA

ANNEXURE-5 MANIFA SUBSTATION ELECTRICAL LAYOUT


ANNEXURE-6 380kV RELAYING & METERING ONE LINE DIAGRAM
ANNEXURE-7 LINE PARAMETER
ANNEXURE-8 380kV CVT DATA SCHEDULE
ANNEXURE-9 M&I METROSIL CATALOGUE

ABU-HADRIYAH CONTRACT No.


BAY NUMBER: CROSS BAY C4 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

1.0 GENERAL DESIGN CRITERIA FOR CT SIZING CALCULATION


1.1 System Design Data:
1.1.1 System Voltage in kV 380kV
1.1.2 380kV system X/R Ratio > 17 (As per 32-TMSS-02, sh. No. 31 of 53, Annexure-4A)
1.1.3 380kV Maximum 3 pahse fault level 63000 Amps
1.1.4 380kV Maximum P-E fault level 63000 : Amps
1.1.5 Design Fault level (CB Interr. capacity) 63kA (As per 32-TMSS-02, sh. No. 31 of 53, Annexure-4A)

1.2 DESIGN BASIS AND REFERENCES FOR CT CALCULATION :


1.2.1 CT secondary excitation limiting emf and other parameters of CT's are calculated
at adopted tap setting, as shown in relaying & metering one line diagram.
1.2.2 Lead length considered is 500 meters including safety margin.
Refer to the attached Abuhadriyah substation electrical layout (dwg. No. EA-009912).
Refer Annexure 5 sheet 2.
Thus we have ensured that assumed 500m length is not exceeded by any actual length.
500m is also used as basis for any future modifications for normal S/S life time of 35years.
1.2.3 Safety margin of 20% is considered for protection class CT and 25% for metering class CT in the formulae
for CT calculation as a general and where-ever applicable relay manufacturer's recommendation is followed.
1.2.4 CT specification is considered as per PTS 07EN307 part'F', Appendix-VII and GIS vendor data.
1.2.5 Zs (source Impedance) is calculated based on CB Interrupting capacity. The Line Impedance value will be added
to Zs to derive the fault current (PF & EF) at zone1 end for CT excitation limiting EMF calculation. Only one way
is considered for PF zone1 Ual calculation and 2 way CT lead length is considered for EF zone1 Ual calculation.
CT Calculation for close in fault is done for 3 phase fault level 63kA.
We also have assumed 3km long line in view of any future modifications in the 380kV system,
1.2.6 Annexure-1: CT requirement of relay
Annexure-2: VA burden requirement of relay
Annexure-3: Saudi cable catalogue for CT lead resistance calculation
Annexure-4: CT data from 380kV GIS vendor (TOSHIBA)
Annexure-4A: Data Schedule for 380kV GIS
Annexure-5: Abu-hadriyah substation electrical Layout drawing for CT/VT cable route length (dwg. No. EA-009912)
Annexure-6: 380kV Relaying & Metering one line diagram for cross bay C4.
Annexure-7: Line parameters
Annexure-8: 380kV GIS Data schedule-CCVT
Annexure-9: M&I Metrosil catalogue

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 1 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

1.3 CT LEAD RESISTANCE CALCULATION :


CT secondary lead size considered is 6 sq.mm.
0 0
6 sq.mm copper cable resistance at 20 C is 3.08 ohms/km.i.e Rdc at 20 C = 3.08 ohm/km (Refer Annexure-3)
Rdc at 75ºC = R20(1+α20(T2-T1)); α at 20ºC = 0.004,Where α= temperature co-efficient of resistance.

Hence, Rdc at 75ºC = 3.08(1+0.004(75-20));


= 3.76 ohm/km
Consider a distance from 380kV GIS CT to relay panel as per layout attached with considerable

(Refer Annexure-5) safe margin = 500 meter, Lead resistance calculated is,
= 3.76 x 0.5
= 1.88 ohms for 500 meters

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 2 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.0 CT CALCULATION AS PER RELAY/INSTRUMENT MANUFACTURER'S RECOMMENDATION


2.1 CT: 810 B1.C1

Protection : BF protection (50BF)


Core : CT: 810 B1.C1
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 3.1 Ohms at 2000A tap.
Knee point voltage, Vk Vk > 3700 V at 2000A tap
CT excitation current at 2000A tap in mA Ie < 75
Thermal rating factor 200%

Application : CB Fail Protection (50BF)


Relay Type / Make: "RAICA", ABB,(50BF)

CT CALCULATION:
2.1.1 CT Vk requirement:
For 2000 A
Vk Knee point voltage
IP = Nominal ( rated) CT primary Current = 2000 amps
T = Turn ratio = 1/2000
Is = Nominal ( rated) CT secondary Current = 1 amps
IF = Maximum short circuit current = 63000 amps
IF sec = CT Secondary short circuit current in Amps. = 31.5 amps
RCT = Internal CT secondary resistance = 3.1 ohms
RL = Lead Resistance =2 L x Rpkm / 1000 = 1.88 ohms
RL = Lead resistance of cable. = 1.88 Ohms
=For 6 sq.mm copper cable, RL= 0.00308 ohm/meter at 20ºC.
α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1)) RL = 1.88 ohms.
Consider length of cable = 500 meters.
RRAICA= Relay Burden (Refer Annexure-2, Sh. No. 6) = 0.15 VA
2 2
RRAICA= Relay resistance = RB / Is = (0.15/1 ) = 0.15 ohms

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 3 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

Note:
Maximum Relay burdens occur for 1ph-G fault when both phase & ground BFP O/C relay units are in series.
2x BFP Relay Fault Detectors = 0.30 Ohms
Total= 0.30 ohms Ground o/c relay [1ph-G loop]
0.15 ohms phase o/c relay [3ph]

BFP fault detectors come once main protection operates & initiate BFP. Worst case relay operation (fatest)
is ½ cycle & hence @ maximum peak during fully offset.
CT Requirement considering 20% margin.

General formulae:
Vkrequired > 1.2xOffset for DC x Ifsecondaryx (Connected burden)

Vkrequired > 1.2x2xIf x ( RCT + 2RL + 2x(RRAICA ))


> 1.2x2x31.5 x ( 3.1 + 3.76 + 2x(0.15))
> 541.296 Volts

Since CT rated knee point voltage is 3700V which is greater than 541.3 volts, CT is adequate.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 4 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.2 CT: 810 B1.C2

Protection : OHL feeder protection Set-1 (87L-1,21-1)


Core : CT: 810 B1.C2
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 3.1 Ohms at 2000A tap.
Knee point voltage, Vk Vk > 3700 V at 2000A tap
CT excitation current at 2000A tap in mA Ie < 75
Thermal rating factor 200%

Application : OHL feeder protection Set-1 (87L-1,21-1)


Relay Type / Make: "REL 531", ABB

2.2.1 Line Data: (Refer Annexure-7 attached)


Line length as per annexure attached = 44.485 km (Annexure-7)
Line parameter for Abu-hadriyah Al-fadhili line. Refer Annexure-7 for Line parameters.
Z1 = 0.00054+j 0.0098 p.u Base MVA = 100
Z0 = 0.00645+j 0.03112 p.u Base kV = 380
2
Base Impedance calculated = (BasekV ) = 1444 ohms
Base MVA

Base Current calculated = (Base MVA) = 151.9 amps


√3 x Base kV

Zline in ohms calculated; R1= 0.794 ohms


(Base Impedance x p.u Impedance) X1= 14.15 ohms
R0= 9.314 ohms
X0= 44.94 ohms

X/R = 17 Phase volt.= 219393.1 Volts


sin(tan-1(X/R)) = 0.998 Phase Curr.= 63000 Amperes
cos(tan-1(X/R)) = 0.059

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 5 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.2.2 Source impedance:


Xs = (Ph vol/Ph cu)xsin(tan-1(X/R)) Rs = (Ph vol/Ph cu)xcos(tan-1(X/R))
= 380000 x sin(tan-1(X/R)) = 380000 x cos(tan-1(X/R))
Sqrt.(3)x63000 Sqrt.(3)x63000
= 3.48 ohms = 0.20 ohms
Zs= 0.2 + j 3.48 ohms

2.2.3 Line impedance:


X1 full Line: Line length x Reactance value/km X0 full Line: Line length x Reactance value/km
= 14.1512 ohms = 44.93728 ohms
R1 full Line: Line length x Resistance value/km R0 full Line: Line length x Resistance value/km
= 0.7942 ohms = 9.3138 ohms
Z1 line = 0.7942 + j 14.15 ohms Z0 line = 9.3 + j 44.94 ohms

2.2.4 THREE PHASE FAULT CONDITION


Close in Fault
Fault current = 63 kA
X/R = 17
Source Imp. Z1=Z2=Z0 0.2
= + j 3.48 ohms

Through fault current at the end of the line:


For 44.485 Km line
Impedance calculated : (Rs + R1) + j(Xs+X1)
(Positive sequence) = (0.2+0.794) + j (3.48+14.15)
= 0.994+j17.63 ohms
ZT1 = 17.66 ohms
Phase fault current = Ph. Volt / Ph. Imp.
= 380000
Sqrt.(3)x17.63
= 12424.57 Amps
Phase fault X/R = 17.63
0.994
= 17.74

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 6 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

Fault current calculation at the end of zone1 fault i.e 80% of line length:
For 44.485 Km line
Impedance calculated : (Rs+0.8R1) + j(Xs+0.8X1)
(Positive sequence) = (0.2+0.635) + j (3.48+11.32)
= 0.84+j14.8
ZT1 = 14.82 ohms
Phase fault current = Ph. Volt / Ph. Imp.
= 380000
Sqrt.(3)x14.82
= 14800.04 Amps
Phase fault X/R = 14.82
0.835
= 17.75

2.2.5 SINGLE PHASE-GROUND FAULT CONDITION:


Through fault current at the end of the line:
For 44.485 Km line
Impedance calculated : (3Rs+2R1+R0) +
(Loop Impedance) j(3Xs+2X1+X0)
= 11.5+j83.79 ohms
ZT1 = 84.39 ohms
Earth fault current = Ph. Volt / Ph. Imp.
= 380000
Sqrt.(3)x84.39
I0 = 2599.62 Amps
Earth fault X/R = 83.79
11.5
= 7.29
3I0 = 7798.87 Amps

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 7 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

Fault current calculation at the end of zone1 fault i.e 80% of line length:
For 44.485 Km line
Impedance calculated : (3Rs+0.8x2R1+R0) +
(Loop Impedance) j(3Xs+0.8x2X1+X0)
= 9.32+j69.12 ohms
ZT1 = 69.75 ohms
Earth fault current = Ph. Volt / Ph. Imp.
= 380000
Sqrt.(3)x69.75
= 3145.62 Amps
Earth fault X/R = 69.12
9.32
= 7.42
3I0= = 9436.869326 Amps
2.2.6 CT Requirement : ( As per Annexure-1, Sh. No.20,21)

2
Eal > Ealreq = {I kmax x I sn} / Ipn x 0.5 x (RCT + RL + SR / Ir ) Equation-1
2
Eal > Ealreq = 2 x {Ikmax x I sn} / Ipn x (RCT + RL + SR / Ir ) Equation-2
2
Eal > Ealreq = 0.12 x f x Isn x(RCT + RL + SR / Ir ) Equation-3
2
Eal > Ealreq = (Imin sat x CT factor x Ir) / 100 x (RCT + RL + SR / Ir ) Equation-4
Where,
Ikmax = Maximum Primary fundamental frequency fault current for internal close-in faults (A)
Itfdb = Maximum Primary fundamental frequency fault current for external faults (A) that
passes through two CT's (A).
Here for one and half breaker scheme Ikmax is equal to Itfdb.
Ipn = The rated primary CT current (A)
Isn = The rated secondary CT current (A)
Ir = The rated current of the protection IED (A)
SR = The burden of IED 670 a current input channel (VA). SR = 0.25 VA/channel.
f= system frequeny in Hz.
Imin sat= Saturation detector min current ( 100 - 1000% Of Ir) and set at 500%
CT factor = set current scalling factor (0.4 - 1.0)

Where, For 2000 amps


Ealreq= Required secondary e.m.f.

Eal = Rated equivalent secondary e.m.f.= Vk = 3700 volts


I K max = Maximum short circuit current-Three phase = 63000 amps

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 8 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

Itfdb = Maximum Primary fault current for external faults (A) = 63000 amps
I pn = Nominal ( rated) CT primary Current = 2000 amps
I sn = Nominal ( rated) CT secondary Current = 1 amps
RCT = CT secondary winding resistance = 3.1 ohms
RB = Burden of relay = 0.25 ohms
RL = Lead resistance of cable.
=For 6 sq.mm copper cable, RL= 3.08 ohm/kmeter at 20ºC.
α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1)) RL 1.88
Consider length of cable = 500 meters. 2RL = 3.76 ohms
Ir = Protection terminal rated Current = 1 amps
f = System Frequency = 60 Hz
Imin Sat= Sat saturation detector min current

X/R = System ratio = 17


Tp = Primary time constant, (L/R)
L/R = (X/(2x 3.14x f )/R
.= ( 17 / 2x 3.14x 60) x 1000 = 45.09 msec
RTFR = Burden value for TFR (Refer Annexure-2,Sh. No.7) = 0.01 VA
Hence, total VA burden including TFR. = 0.26 VA

Voltage developed across CT as per ABB relay catalogue.


At 2000/1 A tap
Considering 20% margin

2
Eal > Ealreq = {I kmax x I sn} / Ipn x 0.5 x (RCT + RL + SR / Ir ) Equation-1

As per REL 531 relay requirement, the factor 0.5( for Tc less than 120ms) is replaced with 0.53 & 0.54
for primary time constant of 200ms and 300ms respectively.

Ealreq = 63000 x 1 x 0.5 x ( 3.1+ 1.88 + 0.27/1^2 ) = 82.5 volts


2000
With 20% extra margin Ealreq = 99.0 volts

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 9 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2
Eal > Ealreq = 2 x {Ikmax x I sn} / Ipn x (RCT + RL + SR / Ir ) Equation-2

As per REL 531 relay requirement, the factor 2 ( for Tc less than 120ms) is replaced with 2.32 & 2.5
for primary time constant of 200ms and 300ms respectively.

Ealreq = 63000 x 1 x 2 x ( 3.1+ 1.88 + 0.27/1^2 ) = 330.1 volts


2000
With 20% extra margin Ealreq = 396.1 volts

2
Eal > Ealreq = 0.12 x f x Isn x (RCT + RL + SR / Ir ) Equation-3

2
Ealreq = 0.12 x 50 x 1x(3.1+ 1.88 +0.27/1 ) = 31.4 volts

With 20% extra margin Ealreq = 37.7 volts

Eal > Ealreq = (Imin sat x CT factor x Ir) / 100 x (RCT + RL + SR / Ir 2 ) Equation-4

2
Ealreq = 500 x 1 x 1x(3.1+ 1.88 +0.27/1 ) = 26.2 volts
100
With 20% extra margin Ealreq = 31.4 volts

Since CT rated knee point voltage is 3700V which is greater than the required value,
the proposed CT is adequate.

The Voltage developed across the CT secondary for distance protection (21L) feature as per
ABB catalogue. (Refer Annexure-1 Sh. No. 22 )
Requirement -1
At 2000/1 A tap

Eal > Ealreq = {I kmax x I sn} / Ipn x a x (RCT + RL + SR / Ir 2 ) Equation-5


a' = 2 for primary time constant less than 50msec.
With 20% extra margin
Ealreq = 63000 x 1.2 x 2 x ( 3.1+ 1.88 + 0.27/1^2 ) = 538.3 volts
2000

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 10 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

Requirement -2
2
Eal > Ealreq = Ikzone1x 7 x (Isn / Ipn) x (RCT + RL + SR / Ir ) Equation-6
k' = 7 for primary time constant greater than 30 msec.
Ikzone1= Maximum primary fundamental fault current at the end of zone 1 reach.
Considering 80% of actual line length = 14800.04 Amps
(Refer above fault current calculation at the end of zone1 reach considering actual line length)
At 2000/1 A tap and with 20% extra margin
2
Ealreq = 14800 x 1.2 x 7 x ( 3.1+ 1.88 +0.27/1 ) = 442.58038 volts
2000
Since CT rated knee point voltage is 3700V which is greater than the required value,
the proposed CT is adequate.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 11 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.3 CT: 810 B1.C3

Protection : OHL feeder protn. -Set-2 (87L-2,21-2)


Core : CT: 810 B1.C3
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 3.1 Ohms at 2000A tap.
Knee point voltage, Vk Vk > 3700 V at 2000A tap
CT excitation current at 2000A tap in mA Ie < 75
Thermal rating factor 200%

Application : OHL feeder protection - Set-2 (87L-2,21-2)


Relay Type/make : ''7SA522 ", Siemens.

2.3.1 CT Calculation
Where For 2000 amps
Vk = Knee point voltage of CT 3700 Volts
RB = Resistance of relay 7SA522 = 0.05 ohms
Rr = Relay resistance
RCT = CT secondary winding resistance = 3.1 ohms
RL = Lead resistance of cable.
For 6 sq.mm copper cable, RL= 3.08 ohm/kmeter at 20ºC.
α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1)) RL = 1.88 ohms
Consider length of cable = 500 meters. 2RL= 3.76 ohms
IP = Nominal ( rated) CT primary Current = 2000 amps
IS = Nominal ( rated) CT secondary Current = 1 amps
ISCC max = Maximum short circuit current-Three phase = 63000 amps
VK CT knee point voltage specified = 3700 volts
X/R = System ratio = 17
If = Maximum value of through fault current for
stability ( multiple of Is) = I SCC max / IP = 31.50
( I f )x( X/R) = 535.5
Tp = Primary time constant, (L/R)
L/R = (X/(2x 3.14x f )/R
.= ( 17 / 2x 3.14x 60) x 1000 = 45.09 msec

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 12 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

The CT should meet the following Vk requirement as per Siemens publication.


( Refer Annexure-1 Sh. No. 24 )

Vk 1 > {Ktd(a)xIssc max(close-in fault)/1.3xIpn} x Isn x (RB + RCT +RL) For close-in fault
Vk 2 > {Ktd(b)xIssc max(zone-1 end fault)/1.3xIpn} x Isn x (RB + RCT +RL) For zone-1 end fault

Ktd(a) = 2' for primary time constants less than 50ms


Ktd(b) = 5' for primary time constants less than 50ms
Vk1 = Accuracy limiting voltage for close in fault in volts
Vk2 = Accuracy limiting voltage for end of zone 1 line fault in volts
IFZ1 = Maximum secondary fault current for end of zone 1 fault in amps.
Considering actual line length as a worst case, primary fault current (A) calculated is equal 14800.04
Amps. Hence, CT secondary fault current = 14800.04
2000
= 7.40 Amps.
RB = Relay burden

CT requirement for close-in fault condition:


Vk 1 > {Ktd(a)xIssc max(close-in fault)/1.3xIpn} x Isn x (RB + RCT +RL)

= {2 x 63000/1.3x2000} x (0.05 + 3.1 + 1.88) = 244 volts


Vk 2 with 20 % margin = 293 volts
Peak voltage = 413.7 Vpeak

CT requirement for zone1 fault condition:


Vk 2 > {Ktd(b)xIssc max(zone-1 end fault)/1.3xIpn} x Isn x (RB + RCT +RL)

= {5 x 14800/1.3x2000} x (0.05 + 3.1 + 1.88) = 143 volts


Vk 2 with 20 % margin = 172 volts
Peak voltage = 243.0 Vpeak

Since CT rated knee point voltage is 3700V which is greater than the required value,
the proposed CT is adequate.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 13 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.4 CT: 810 B1.C4

Protection : Metering
Core : CT: 810 B1.C4
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : 0.2
VA Burden 50 VA
Thermal rating factor 200%

Application : Metering
Burden Calculation (Refer Annexure-2)
a LCP
Ammeter 0.5 VA (Assumed)
b Revenue metering panel
ABB, ALPHA A3R 1E-04 VA ( Refer Annexure-1 Sh. No. 18 )
c Mosaic panel
Watt transducer, , AREVA, ISTAT300 1 VA ( Refer Annexure-1 Sh. No. 13 )
Var transducer, AREVA, ISTAT300 1 VA ( Refer Annexure-1 Sh. No. 13 )
Watt meter, PML ION6200 0.5 VA (Assumed)
Var meter PML ION6200 0.5 VA (Assumed)
d DSM 0.1 VA (Assumed)
Cabling loop (500 meters)
For 4 sq.mm copper cable, RL= 0.00461 ohm/meter at 20ºC.
α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1));
Consider length of wire = 500 meters. RL = 2.812 Ohms
2RL = 5.624 VA
Total connected burden, PBC = 9.224 VA
Considering 25% safe margin, connected VA equals to= 11.53 VA

CT Rated burden = 50VA

The total connected burden is less than the CT rated burden i.e 50VA. Hence the CT is adequate.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 14 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.5 CT: 810 F.C3

Protection : Spare
Core : CT: 810 F.C3
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 4.65 Ohms at 3000A tap.
Knee point voltage, Vk Vk > 5550 V at 3000A tap
CT excitation current at 3000A tap in mA Ie < 50
Thermal rating factor 200%

Application : Spare

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 15 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.6 CT: 810 F.C2

Protection : Bus-bar protection (87M2)


Core : CT: 810 F.C2
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 4.65 Ohms at 3000A tap.
Knee point voltage, Vk Vk > 5550 V at 3000A tap
CT excitation current at 3000A tap in mA Ie < 50
Thermal rating factor 200%

NOTE:
Typical bus-bar protection CT's core detail for adjacent cross bay's(3 nos. including future bays)
are shown below.

Protection : Bus-bar protection (87M2)


Core : Core 2
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 4.65 Ohms at 3000A tap.
Knee point voltage, Vk Vk > 5550 V at 3000A tap
CT excitation current at 3000A tap in mA Ie < 50
Thermal rating factor 200%

Application : Bus-Bar Protection-Main-2 (87M2)


Relay Type / Make: "MFAC14", AREVA (Setting range: 25V-325V)

2.6.1 CT Calculation

The setting voltage is determined by the following relationship. (Refer Annexure-1, Sh. No.11)
Vs > 1.2 x If x ( RCT + 2 x RL ) (20% additional margin is taken)
Where For 3000
IP = Nominal ( rated) CT primary Current 3000 amps
IS = Nominal ( rated) CT secondary Current 1 amps
IF = Maximum Fault Current = 63000 amps
If = CT secondary fault current = 21 amps
RCT = Internal CT secondary resistance 4.65 ohms

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 16 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

RL = Lead resistance of cable. = 1.88 Ohms


=For 6 sq.mm copper cable, RL= 0.00308 ohm/meter at 20ºC.
α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1)) RL = 1.88 ohms.
Consider length of cable = 500 meters.
Vk = Specified knee point voltage = 5550 Volts

Calculation of relay setting voltage:

Vs > 1.2 x If x ( RCT + 2 x RL )

Vs > 1.2 x 21 x (4.65 + 3.76 )


Vs > 211.932
Hence select Vs = 275 Vrms
Peak voltage = 388.91 Vpeak

Hence, select a metrosil with setting range 25V- 325V and set at 275 volts.

2.6.2 Metrosil requirement


For this relay Metrosil proposed by the manufacturer has the following parameters.
C = 900
β = 0.25
The current drawn by metrosil at relay setting voltage is given by formulae below.
Irms drawn= 0.52((√2xV')/C))1/β
where V' = voltage in (RMS Sine)
Metrosil recommended for 25-325V relay range @ 2kVrms
Irms drawn= 0.52x((√2x2000)/900)1/0.25
= 50.72 A rms

At voltage setting Vs = 275V, Metrosil draws about 18mA

%Error = (0.018 / Ifs ) x 100


= (0.018 / 21 ) x 100
= 0.086%
Error introduce by metrosil at voltage setting Vs = 275V is 0.086% only.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 17 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

Metrosil selection: (Refer Annexure-8)


To limit voltage to 2kVrms, select metrosil same as recommended by MFAC 14 for Vs = 275V
C = 900
β = 0.25
As per M&I materials catalogue attached, for the above 'C' and 'β' characteristics, the recommended
metrosil type is 600A/S1/S1088.
We recommend standard metrosil as per AREVA recommandation only as the relay & scheme is by AREVA.
CT secondary fault current calculated as above = 21 Amps.
Hence, Metrosil withstanding capability is greater than CT secondary current.

2.6.3 Determination of primary fault current setting:


At 3000/1 A tap
Taking Primary fault currrent setting as 1% of maximum fault current i.e 63000 Amps.
1% of bus-bar fault current = 630 amps
Primary Fault current setting Calculation
The primary operating current or fault setting calculated as Ip= { n Im+ Ir +IM+IV}xT

Ip = Primary fault setting


n = number of CTs in parallel including 3 future bays = 8.0
Im = exciting current of each CT at the relay circuit setting voltage 0.005 Amps
RMVTP31 = Resistance of CT supervision relay MVTP 31(Assumed) 90000.0 ohms
IV = Current in MVTP11 relay, (Vs/RMVTP31) 0.003 Amps
IM = current in metrosil at the relay circuit setting voltage 0.018 Amps
Ir = Relay operating current as per MFAC manual for setting range 25-325V 0.03 Amps
Where relay setting voltage is low then current in non linear resistor is ignored.
Primary fault setting (Ip) = {n Im+ Ir +IM+IV}xT

= 273.167
This current is too small as compared to 63kA i.e 0.43% of 63kA.
It is observed that the primary operating current is less than 630A.
Hence, an external shunt resistor (Rsh) needs to be connected inorder to get a primary operating current 630A.

Select shunt resistor to get primary operating current of say 742 Amps.
Ip = { nIe+ Ir +IM+(Vs/Rsh)+IV}xT

742 = {8x0.005+0.03+0.018+(275/Rsh)+0.003} x3000 0.156


The value of external shunt resistor required is calculated as Rsh = 1759.7 ohms

As per AREVA MCAG14 catalogue attached Annexure-2 sheet no. 4


Select a resistor 2700 ohms and set at 1760 ohms with the short time current rating (1 seconds) of 1.3 Amps.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 18 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.6.4 Shunt resistor Wattage calculation:


Current in shunt resistor at setting voltage Vs =275 Volts;= 275 = 0.16 Amps.
Shunt resistor Wattage = 0.16x0.16x1760 Watts. 1759.7
45.06 Watts.
Hence, select a shunt resistor of 50 watts.
Hence, Primary operating current calculated =
Primary fault setting (Ip) = {n Im+ Ir +IM+IV+IRsh}T

= 742.0 Amps.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 19 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.7 CT: 810 F.C1

Protection : Bus-bar protection (87M1)


Core : CT: 810 F.C1
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 4.65 Ohms at 3000A tap.
Knee point voltage, Vk Vk > 5550 V at 3000A tap

CT excitation current at 3000A tap in mA Iex < 50


Thermal rating factor 200%

NOTE:
Typical bus-bar protection CT's core detail for adjacent cross bay's(3 nos. including future bays)
are shown below.

Protection : Bus-bar protection (87M1)


Core : Core 1
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 4.65 Ohms at 3000A tap.
Knee point voltage, Vk Vk > 5550 V at 3000A tap

CT excitation current at 3000A tap in mA Ie < 50


Thermal rating factor 200%

Application : Bus-Bar Protection-Main-1 (87M1)


Relay Type / Make: "MCAG 14", AREVA (Setting range: 20%-80% of 1A)

2.7.1 CT Requirement
Where For 3000 A

Vk Knee point voltage = 5550 volts


Vs Setting Voltage
IP = Nominal ( rated) CT primary Current = 3000 amps
T = Turn ratio = 1/3000
Is = Nominal ( rated) CT secondary Current = 1 amps
IF = Maximum short circuit current = 63000 amps
If = CT secondary fault current in amps. = 21 amps

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 20 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

RCT = Internal CT secondary resistance = 4.65 ohms


RL = Lead resistance of cable. = 1.88 Ohms
=For 6 sq.mm copper cable, RL= 0.00308 ohm/meter at 20ºC.
α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1)) RL = 1.88 ohms.
Consider length of cable = 500 meters.
RB-MCAG =Relay Burden = 1.00 VA
RRMCAG = Relay resistance = RB / Is 2 = 1.00 ohms

The setting voltage Vs shall be calculated in order to ensure the stability of the protection in
regard with the maximum through fault current If . The setting voltage is determined by the following eqn.

Vs > 1.2 x If x ( RCT + 2 x RL ) (Refer Annexure-1, Sh.No.8)

Vs > 1.2 x 21 x (4.65 + 3.76 )

Vs > 211.932
Hence, select Vs same as Main-2 protection = 275 Vrms
Peak voltage = 388.91 Vpeak

2.7.2 Voltage Llimiting Resistor- Metrosiles: (Refer MCAG 14 sheet attached)


To establish the requirement for a Metrosil the peak voltage needs to exceed 3kV.
Hence V rms needs to be exceeded is equal to (Vpk/ root2) = 2.12 kV
1/2
VPK = ( 2 VK ( V f -VK))
Where VPK = Peak voltage of the voltage wave form.
Vf = If x Tx(RCT+2RL+Rsr+RRMCAG)

Where
Vf = Maximum voltage in absence of saturation = 28547.6 volts
VPK = 1/2
( 2x5550x (28547.6- 5550)) = 15977.28 volts
= 15.98 kVolts
VPK is 15.98kV which is more than 3kV hence Metrosiles are required.

Therefore select metrosil to limit the secondary voltage to 3kV peak.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 21 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

Metrosil requirement
For this relay Metrosil proposed by the manufacturer has the following parameters.
C = 900
β = 0.25
The current drawn by metrosil at relay setting voltage is given by formulae below.
Irms drawn= 0.52((√2xV')/C))1/β
where V' = voltage in (RMS Sine)
Metrosil recommended for 25-325V relay range @ 2kVrms
Irms drawn= 0.52x((√2x2000)/900)1/0.25
= 50.72 A rms

At voltage setting Vs = 275V, Metrosil draws about 18mA

%Error = (0.018 / Ifs ) x 100


= (0.018 / 21 ) x 100
= 0.387%
Error introduce by metrosil at voltage setting Vs = 275V is 0.086% only.

Metrosil selection: (Refer Annexure-9)


To limit voltage to 2kVrms, select metrosil same as recommended by MCAG14 for Vs = 275V
C = 900
β = 0.25
As per M&I materials catalogue attached, for the above 'C' and 'β' characteristics, the recommended
metrosil type is 600A/S1/S1088.
We recommend standard metrosil as per AREVA recommandation only as the relay & scheme is by AREVA.
CT secondary fault current calculated as above = 21 Amps.
Hence, Metrosil withstanding capability is greater than CT secondary current.

2.7.3 Determination of primary fault current setting:


Taking Primary fault currrent setting as 1% of maximum fault current i.e 63000 Amps.
1% of bus-bar fault current = 630 amps
Primary Fault current setting Calculation
The primary operating current or fault setting calculated as Ip= { n Im+ Ir +IM+IV}xT

Ip = Primary fault setting


n = number of CTs in parallel including 3 future bays = 8.0
Im = exciting current of each CT at the relay circuit setting voltage 0.005 Amps
RMVTP31 = Resistance of CT supervision relay MVTP 31(Assumed) 90000.0 ohms

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 22 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

IV = Current in MVTP11 relay, (Vs/RMVTP31) 0.003 Amps


IM = current in metrosil at the relay circuit setting voltage (Assumed) '= 0.018 Amps
Ir = Relay setting current 0.20 Amps
Where relay setting voltage is low then current in non linear resistor is ignored.
=
Primary fault setting (Ip) = { n Im+ Ir +IM+IV}xT

{(8x0.005)+0.2+0.018+0.003}x3000
= 783.2 Amps.

2.7.4 Determination of stabilising resistor Rsr: (Refer MCAG 14 Manual attached, Annex-1, Sh. No.10)
Relay circuit Voltage Vs = 275.00 Volts
Relay setting current, Is = 0.20 Amps
Relay burden at 275V setting is considered as 1VA,
Stabilising resistor required, Rsr = (Vs/Ir) - (Relay burden)/(Ir^2) Rs= = 1350.00 ohms
Select a resistor of range (0 -1500 ohms),0.31A continous,1.36A/3sec,1.8A/1sec as per MCAG 14 Manual.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 23 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.8 CT: 811 B1.C1

Protection : CB fail protection


Core : CT: 811 B1.C1
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 3.1 Ohms at 2000A tap.
Knee point voltage, Vk Vk > 3700 V at 2000A tap
CT excitation current at 2000A tap in mA Ie < 75
Thermal rating factor 200%

Application : CB Fail Protection (50BF)


Relay Type / Make: "RAICA", ABB,(50BF)
CT calculation same as CT: 810 B1.C1. Refer above CT: 810 B1.C1 for detailed calculation.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 24 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.9 CT: 811 B1.C2

Protection : OHL feeder protn. -Set-1 (87L-1,21-1)


Core : CT: 811 B1.C2
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 3.1 Ohms at 2000A tap.
Knee point voltage, Vk Vk > 3700 V at 2000A tap
CT excitation current at 2000A tap in mA Ie < 75
Thermal rating factor 200%

Application : OHL feeder protection Set-1 (87L-1,21-1)


Relay Type / Make: "RED 670", ABB
2.9.1 Line Data: (Refer Annexure-7 attached)
Line length as per annexure attached = 50 km
Z1 = 0.00055+j 0.0108 p.u Base MVA = 100
Z0 = 0.00545+j 0.0322 p.u Base kV = 380
2
Base Impedance calculated = (BasekV ) = 1444 ohms
Base MVA

Base Current calculated = (Base MVA) = 151.9 amps


√3 x Base kV

Zline in ohms calculated; R1= 0.794 ohms


(Base Impedance x p.u Impedance) X1= 15.6 ohms
R0= 7.87 ohms
X0= 46.5 ohms

X/R = 17 Phase volt.= 219393.1 Volts


sin(tan-1(X/R)) = 0.998 Phase Curr.= 63000 Amperes
cos(tan-1(X/R)) = 0.059
2.9.2 Source impedance:
Xs = (Ph vol/Ph cu)xsin(tan-1(X/R)) Rs = (Ph vol/Ph cu)xcos(tan-1(X/R))
= 380000 x sin(tan-1(X/R)) = 380000 x cos(tan-1(X/R))
Sqrt.(3)x63000 Sqrt.(3)x63000
= 3.48 ohms = 0.20 ohms
Zs= 0.2 + j 3.48 ohms

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 25 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.9.3 Line impedance:


X1 full Line: Line length x Reactance value/km X0 full Line: Line length x Reactance value/km
= 15.5952 ohms = 46.4968 ohms
R1 full Line: Line length x Resistance value/km R0 full Line: Line length x Resistance value/km
= 0.7942 ohms = 7.8698 ohms
Z1 line = 0.7942 + j 15.6 ohms Z0 line = 7.8698 + j 46.5 ohms

2.9.4 THREE PHASE FAULT CONDITION


Close in Fault
Fault current = 63 kA
X/R = 17
Source Imp. Z1=Z2=Z0 0.2
= + j 3.48 ohms

Through fault current at the end of the line:


1) For 50 Km line
Impedance calculated : (Rs + R1) + j(Xs+X1)
(Positive sequence) = (0.2+0.794) + j (3.48+15.6)
= 0.994+j19.08 ohms
ZT1 = 19.11 ohms
Phase fault current = Ph. Volt / Ph. Imp.
= 380000
Sqrt.(3)x19.11
= 11483.02 Amps
Phase fault X/R = 19.08
0.994
= 19.20

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 26 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

Fault current calculation at the end of zone1 fault i.e 80% of line length:
1) For 50 Km line
Impedance calculated : (Rs+0.8R1) + j(Xs+0.8X1)
(Positive sequence) = (0.2+0.635) + j (3.48+12.5)
= 0.84+j16
ZT1 = 16.02 ohms
Phase fault current = Ph. Volt / Ph. Imp.
= 380000
Sqrt.(3)x16.02
= 13693.21 Amps
Phase fault X/R = 15.98
0.835
= 19.14

2.9.5 SINGLE PHASE-GROUND FAULT CONDITION:


Through fault current at the end of the line:
1) For 50 Km line
Impedance calculated : (3Rs+2R1+R0) +
(Loop Impedance) j(3Xs+2X1+X0)
= 10.08+j88.12 ohms
ZT1 = 88.69 ohms
Earth fault current = Ph. Volt / Ph. Imp.
= 380000
Sqrt.(3)x88.69
I0 = 2473.58 Amps
Earth fault X/R = 88.12
10.08
= 8.74
3I0 = 7420.73 Amps

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 27 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

Fault current calculation at the end of zone1 fault i.e 80% of line length:
1) For 50 Km line
Impedance calculated : (3Rs+0.8x2R1+R0) +
(Loop Impedance) j(3Xs+0.8x2X1+X0)
= 8.18+j72.5 ohms
ZT1 = 72.96 ohms
Earth fault current = Ph. Volt / Ph. Imp.
= 380000
Sqrt.(3)x72.96
= 3007.03 Amps
Earth fault X/R = 72.50
8.18
= 8.86
3I0= = 9021.097278 Amps

2.9.6 CT Requirement : ( As per Annexure-1, Sh. No.2)

Eal > Ealreq = {I kmax x I sn} / Ipn x (RCT + RL + SR / Ir 2 ) Equation-1


2
Eal > Ealreq = 2 x {I tmax x I sn} / Ipn x (RCT + RL + SR / Ir ) Equation-2
2
Eal > Ealreq = Itfdb x (Isn / Ipn) x (RCT + RL + SR / Ir ) Equation-3
Where,
Ikmax = Maximum Primary fundamental frequency fault current for internal close-in faults (A)
Itfdb = Maximum Primary fundamental frequency fault current for external faults (A) that
passes through two CT's (A).
Here for one and half breaker scheme Ikmax is equal to Itfdb.
Ipn = The rated primary CT current (A)
Isn = The rated secondary CT current (A)
Ir = The rated current of the protection IED (A)
SR = The burden of IED 670 a current input channel (VA). SR = 0.25 VA/channel.

Where, For 2000 amps


Ealreq= Required secondary e.m.f.

Eal = Rated equivalent secondary e.m.f.= Vk = 3700 volts


I K max = Maximum short circuit current-Three phase = 63000 amps
Itfdb = Maximum Primary fault current for external faults (A) = 63000 amps
I pn = Nominal ( rated) CT primary Current = 2000 amps

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 28 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

I sn = Nominal ( rated) CT secondary Current = 1 amps


RCT = CT secondary winding resistance = 3.1 ohms
RB = Burden of relay = 0.25 ohms
RL = Lead resistance of cable.
=For 6 sq.mm copper cable, RL= 3.08 ohm/kmeter at 20ºC.
α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1)) RL 1.88
Consider length of cable = 500 meters. 2RL = 3.76 ohms
Ir = Protection terminal rated Current = 1 amps
f = System Frequency = 60 Hz
Imin Sat= Sat saturation detector min current

X/R = System ratio = 17


Tp = Primary time constant, (L/R)
L/R = (X/(2x 3.14x f )/R
.= ( 17 / 2x 3.14x 60) x 1000 = 45.09 msec
RTFR = Burden value for TFR (Refer Annexure-2,Sh. No.7) = 0.01 VA
Hence, total VA burden includong TFR = 0.26 VA

Voltage developed across CT as per ABB relay catalogue (Refer Annexure-1 Sh. No.2 )
At 2000/1 A tap
Considering 20% margin
2
Eal > Ealreq = {I kmax x I sn} / Ipn x (RCT + RL + SR / Ir ) Equation-1

Ealreq = 63000 x 1 x ( 3.1+ 1.88 + 0.26/1^2 ) = 224.3 volts


2000
With 20% extra margin Ealreq = 269.1 volts

Eal > Ealreq = 2 x {I tmax x I sn} / Ipn x (RCT + RL + SR / Ir 2 ) Equation-2

Ealreq = 63000 x 1 x 2 x ( 3.1+ 1.88 + 0.26/1^2 ) = 448.6 volts


2000
With 20% extra margin Ealreq = 538.3 volts

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 29 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

At 2000/1 A tap
2
Eal > Ealreq = Itfdb x (Isn / Ipn) x (RCT + RL + SR / Ir ) Equation-3

Ealreq = 63000 x 1x(3.1+ 1.88 +0.26/12 ) = 224.3 volts


2000
With 20% extra margin Ealreq = 269.1 volts

Since CT rated knee point voltage is 3700V which is greater than the required value,
the proposed CT is adequate.

The Voltage developed across the CT secondary for distance protection (21L) feature as per
ABB catalogue. (Refer Annexure-1 Sh. No. 3 )
Requirement -1
At 2000/1 A tap
2
Eal > Ealreq = {I kmax x I sn} / Ipn x a x (RCT + RL + SR / Ir ) Equation-5
a' = 2 for primary time constant less than 50msec.
With 20% extra margin
Ealreq = 63000 x 1.2 x 2 x ( 3.1+ 1.88 + 0.26/1^2 ) = 538.3 volts
2000

Requirement -2

Eal > Ealreq = Ikzone1x k x (Isn / Ipn) x (RCT + RL + SR / Ir 2 ) Equation-6


k' = 6 for primary time constant greater than 30 msec.
Ikzone1= Maximum primary fundamental fault current at the end of zone 1 reach.
At 2000/1 A tap and with 20% extra margin

Ealreq = 13693.21 x 1.2 x 6 x ( 3.1+ 1.88 +0.26/12 ) = 350.98 volts


2000
Since CT rated knee point voltage is 3700V which is greater than the required value,
the proposed CT is adequate.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 30 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.10 CT: 811 B1.C3

Protection : OHL feeder protn. -Set-2 (87L-2,21-2)


Core : CT: 811 B1.C3
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 3.1 Ohms at 2000A tap.
Knee point voltage, Vk Vk > 3700 V at 2000A tap
CT excitation current at 2000A tap in mA Ie < 75
Thermal rating factor 200%

Application : OHL feeder protection - Set-2 (87L-2,21-2)


Relay Type/make : ''MiCOM P546", Areva.
2.10.1 CT Calculation
Where For 2000 amps
Vk = Knee point voltage of CT 3700 Volts
RB = Resistance of relay P543 = 0.04 ohms
Rr = Relay resistance
RCT = CT secondary winding resistance = 3.1 ohms
RL = Lead resistance of cable.
For 6 sq.mm copper cable, RL= 3.08 ohm/kmeter at 20ºC.
α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1)) RL = 1.88 ohms
Consider length of cable = 500 meters. 2RL= 3.76 ohms
IP = Nominal ( rated) CT primary Current = 2000 amps
IS = Nominal ( rated) CT secondary Current = 1 amps
ISCC max = Maximum short circuit current-Three phase = 63000 amps
VK CT knee point voltage specified = 3700 volts
X/R = System ratio = 17
If = Maximum value of through fault current for
stability ( multiple of Is) = I SCC max / IP = 31.50
( I f )x( X/R) = 535.5

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 31 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

The CT should meet the following Vk requirement as per Areva publication.


( Refer Annexure-1 Sh. No. 5 - 6 )

Vk1 > K xI n x (RB + RCT +RL) (equation -1) for through fault condition
Vk 2 > KRPA xIFZ1 x (1+X/R)x(RB + RCT +RL+Rr) (equation -2) for zone1 fault condition
Vk3 > Kmax x IFmax x (RB + RCT +RL+Rr) (equation -3) for close-up fault

Vk1 = Accuracy limiting voltage for line through fault condition in volts
Vk2 = Accuracy limiting voltage for end of zone 1 line fault in volts
Vk2 = Accuracy limiting voltage for close in fault in volts
IFZ1 = Maximum secondary fault current for end of zone 1 fault in amps.
For 50kM line length , primary fault current (A) calculated is equal to = 13693.21
Amps. Hence, CT secondary fault current = 13693.21
2000
= 6.85 Amps.
KRPA = Fixed dimensioning factor for zone 1 fault and always = 0.6 (Refer Annex-1, Sh. No. 7)
Kmax = Fixed dimensioning factor for close in fault and always = 1.4 (Refer Annex-1, Sh. No. 7)
RB = Relay burden

Where K is dimensioning factor and depends upon the maximum value of through fault current(as a multiple of In)
and primary system X/R ratio.
For three end current differential schemes relay set at Is1=20%, Is2=2In, K1=30% and K2=100%,
K' is calculated as below. (Refer Annex-1, Sh. No. 6)
For through fault condition the fault current and X/R calculated above are
IF = 11483.02 Amps. (Primary); X/R = 19.20
CT secondary fault currect calculated = 5.74
If x X/R = 110.24
If, If x X/R < 1000xIn,
K> 40 + 0.35 x (If x X/R)
K> 40 + 0.35x(110.24)
K> 78.584
As per AREVA relay catalogue, K > 78.584

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 32 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

CT requirement for through fault condition:


Vk = K x I n x ( RB + RCT +2RL )

.= 78.584 x 1 x ( 0.04 + 3.1 + 3.76 ) = 542 volts


Vk with 20 % margin = 651 volts
Peak voltage = 920.2 Vpeak

CT requirement for zone1 fault condition:


Vk 2 > KRPA xIFZ1 x (1+X/R)x(RB + RCT +RL+Rr)

= 0.6 x6.85 x (1+19.14) x (0.04 + 3.1 + 1.88) = 415 volts


Vk 2 with 20 % margin = 498 volts
Peak voltage = 704.8 Vpeak

CT requirement for close-up fault condition:


Vk3 > Kmax x IFmax x (RB + RCT +RL+Rr)

= 1.4 x 63000/2000 x (0.04 + 3.1 + 1.88) = 221 volts


Vk 2 with 20 % margin = 266 volts
Peak voltage = 375.7 Vpeak

Since, the CT rated knee point voltage is greater than the calculated value, the proposed CT is adequate.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 33 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.11 CT: 811 B1.C4

Protection : Metering
Core : CT: 811 B1.C4
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : 0.2
VA Burden 50 VA
Thermal rating factor 200%

Application : Metering
Burden Calculation (Refer Annexure-2)
a LCP
Ammeter 0.5 VA (Assumed)
b Energy metering panel
NEXUS/1262 3.2 VA (Refer Annex-2, Sh. No. 8)
c Mosaic panel
Watt transducer, , AREVA, ISTAT300 1 VA (Refer Annex-2, Sh. No. 13)
Var transducer, AREVA, ISTAT300 1 VA (Refer Annex-2, Sh. No. 13)
Watt meter, PML ION6200 0.5 VA (Assumed)
Var meter PML ION6200 0.5 VA (Assumed)
d DSM 0.1 VA (Assumed)
Cabling loop (500 meters)
For 4 sq.mm copper cable, RL= 0.00461 ohm/meter at 20ºC.
α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1));
Consider length of wire = 500 meters. RL = 2.812 Ohms
2RL = 5.624 VA
Total connected burden, PBC = 12.42 VA
Considering 25% safe margin, connected VA equals to= 15.53 VA

CT Rated burden = 50VA

The total connected burden is less than the CT rated burden i.e 50VA. Hence the CT is adequate.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 34 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.12 CT: 811 B2.C4

Protection : Metering
Core : CT: 811 B2.C4
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : 0.2
VA Burden 50 VA
Thermal rating factor 200%

Application : Metering
CT calculation same as CT: 810 B1.C4. Refer above CT: 810 B1.C4 for detailed calculation.

2.13 CT: 811 B2.C3

Protection : OHL feeder protn. -Set-2 (87L-2,21-2)


Core : CT: 811 B2.C3
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 3.1 Ohms at 2000A tap.
Knee point voltage, Vk Vk > 3700 V at 2000A tap
CT excitation current at 2000A tap in mA Ie < 75
Thermal rating factor 200%

Application : OHL feeder protection - Set-2 (87L-2,21-2)


Relay Type/make : ''7SA522", Siemens.
CT calculation same as CT: 810 B1.C3. Refer above CT: 810 B1.C3 for detailed calculation.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 35 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.14 CT: 811 B2.C2

Protection : OHL feeder protn. Set-1 (87L-1,21-1)


Core : CT: 811 B2.C2
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 3.1 Ohms at 2000A tap.
Knee point voltage, Vk Vk > 3700 V at 2000A tap
CT excitation current at 2000A tap in mA Ie < 75
Thermal rating factor 200%

Application : OHL feeder protection Set-1 (87L-1,21-1)


Relay Type / Make: "REL 531", ABB
CT calculation same as CT: 810 B1.C2. Refer above CT: 810 B1.C2 for detailed calculation.

2.15 CT: 811 B2.C1

Protection : spare
Core : CT: 811 B2.C1
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 4.65 Ohms at 3000A tap.
Knee point voltage, Vk Vk > 5550 V at 3000A tap
CT excitation current at 3000A tap in mA Ie < 50
Thermal rating factor 200%

Application : spare

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 36 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.16 CT: 812 F.C1

Protection : Bus-bar protection (87M1)


Core : CT: 812 F.C1
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 4.65 Ohms at 3000A tap.
Knee point voltage, Vk Vk > 5550 V at 3000A tap

CT excitation current at 3000A tap in mA Iex < 50


Thermal rating factor 200%

NOTE:
Typical bus-bar protection CT's core detail for adjacent cross bay's(3 nos. including future bays)
are shown below.

Protection : Bus-bar protection (87M1)


Core : Core 1
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 4.65 Ohms at 3000A tap.
Knee point voltage, Vk Vk > 5550 V at 3000A tap

CT excitation current at 3000A tap in mA Ie < 50


Thermal rating factor 200%

Application : Bus-Bar Protection-Main-1 (87M1)


Relay Type / Make: "MCAG 14", AREVA (Setting range: 20%-80% of 1A)
CT calculation same as above for 87M1. Refer above CT: 810 F.C1 for detailed calculation.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 37 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.17 CT: 812 F.C2

Protection : Bus-bar protection (87M2)


Core : CT: 812 F.C2
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 4.65 Ohms at 3000A tap.
Knee point voltage, Vk Vk > 5550 V at 3000A tap

CT excitation current at 3000A tap in mA Iex < 50


Thermal rating factor 200%

NOTE:
Typical bus-bar protection CT's core detail for adjacent cross bay's(3 nos. including future bays)
are shown below.

Protection : Bus-bar protection (87M2)


Core : Core 2
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 4.65 Ohms at 3000A tap.
Knee point voltage, Vk Vk > 5550 V at 3000A tap

CT excitation current at 3000A tap in mA Ie < 50


Thermal rating factor 200%

Application : Bus-Bar Protection-Main-2 (87M2)


Relay Type / Make: "MFAC 14", AREVA (Setting range: 25V-325V)
CT calculation same as above CT: 810 F.C2. Refer above CT: 810 F.C2 for detailed calculation.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 38 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.18 CT: 812 F.C3

Protection : Spare
Core : CT: 812 F.C3
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 4.65 Ohms at 3000A tap.
Knee point voltage, Vk Vk > 5550 V at 3000A tap

CT excitation current at 3000A tap in mA Iex < 50


Thermal rating factor 200%

Application: Spare

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 39 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.19 CT: 812 B2.C4

Protection : Metering
Core : CT: 812 B2.C4
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : 0.2
VA Burden 50 VA
Thermal rating factor 200%

Application : Metering
CT calculation same as CT: 811 B1.C4. Refer above CT: 811 B1.C4 for detailed calculation.

2.20 CT: 812 B2.C3

Protection : OHL feeder protn. -Set-2 (87L-2,21-2)


Core : CT: 812 B2.C3
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 3.1 Ohms at 2000A tap.
Knee point voltage, Vk Vk > 3700 V at 2000A tap
CT excitation current at 2000A tap in mA Ie < 75
Thermal rating factor 200%

Application : OHL feeder protection - Set-2 (87L-2,21-2)


Relay Type/make : ''MiCOM P546", Areva.
CT calculation same as CT: 811 B1.C3. Refer above CT: 811 B1.C3 for detailed calculation.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 40 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

2.21 CT: 812 B2.C2

Protection : OHL feeder protn. Set-1 (87L-1,21-1)


Core : CT: 812 B2.C2
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms ) < 3.1 Ohms at 2000A tap.
Knee point voltage, Vk Vk > 3700 V at 2000A tap
CT excitation current at 2000A tap in mA Ie < 75
Thermal rating factor 200%

Application : OHL feeder protection Set-1 (87L-1,21-1)


Relay Type / Make: "RED 670", ABB
CT calculation same as CT: 811 B1.C2. Refer above CT: 811 B1.C2 for detailed calculation.

2.22 CT: 812 B2.C1

Protection : BF protection (50BF)


Core : CT: 812 B2.C1
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 3.1 Ohms at 2000A tap.
Knee point voltage, Vk Vk > 3700 V at 2000A tap
CT excitation current at 2000A tap in mA Ie < 75
Thermal rating factor 200%

Application : CB Fail Protection (50BF)


Relay Type / Make: "RAICA", ABB,(50BF)
CT calculation same as CT: 810 B1.C1. Refer above CT: 810 B1.C1 for detailed calculation.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 41 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

3 380kV VT SIZING CALCULATION

3.1 VT LEAD RESISTANCE CALCULATION :


VT secondary lead size considered is 4 sq.mm.

4 sq.mm copper cable resistance at 200C is 4.61 ohms/km.i.e Rdc at 200C = 4.61 ohm/km
Rdc at 75ºC = R20(1+α20(T2-T1)); α at 20ºC = 0.004,Where α= temperature co-efficient of resistance.

Hence, Rdc at 75ºC = 4.61(1+0.004(75-20));


= 5.62 ohm/km
Consider a distance from 380kV GIS CT to relay panel as per layout attached with considerable
safe margin = 500 meter, Lead resistance calculated is,
= 5.62 x 0.5
= 2.81 ohms for 500 meters

380kV ABU HADRIYAH- MANIFA LINE-2


CCVT Details :

Core-1 Core-2

VT Ratio : 380kV/√3/110V/√3-110V 380kV/√3/110V/√3-110V

Class : 0.2/3P 0.2/3P

VA Burden : 100 100

Vector group : Star-Star Star-Star

Voltage Factor : 1.2 Cont., 1.2 Cont.,

1.9 for 30 sec 1.9 for 30 sec

Calculation of VT burden :

Calculation of Lead burden:

RL = Lead resistance of wire.

For 4 sq.mm copper cable, RL= 0.00461 ohm/meter at 20ºC.

α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1)), RL= 2.81 ohms

Calculation of Lead current at rated burden :(IVT) = 0.1939 Amperes

Lead current is calculated considering Total VA burden.

Hence, Lead current calculated =100/63.5 = 0.19 Amperes

RB= Lead burden, 2xRLx (IVT^2) = 0.2112 VA

RB= (2 x 2.81 x 0.1939 x 0.1939)

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 42 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

Core-1 :

Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
FFR (98L) A811/A812 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

Line set-1 protection RED670 1 0.1 0.1 (Annexure-2 Sh. No.2)

Transient Fault Recorder TR2000 1 0.01 0.01 (Annexure-2 Sh. No.7)

FFR (98) (Meas.) for set-1 protection RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98) (Ref.) for set-2 protection RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98) (Ref.) for Energy meter RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98L2) (Ref.) for 25AR RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

DSM 1 0.2 0.2 Assumed

FFR (98) 25AR/A811 FOR AF-2 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

Total VA = 12.31 VA per phase

Hence, total required burden of VT (Meters/relays plus lead burden) = 12.52 VA

.= (VA Connected + VA Lead)

The Burden calculated considering 25% safety margin = 15.7 VA

Since, the connected burden is less than 100VA,the VT burden is adequate.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 43 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

Core-2:

Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
25MC/A811 KVAS100 1 0.02 0.02 (Annexure-2 Sh. No.10)

25MC/A812 KVAS100 1 0.02 0.02 (Annexure-2 Sh. No.10)

FFR (98L) (Meas.) A811/A812 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98) (Ref.) for set-1 protection RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98) (Meas.) for 67N-2 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

Line set-2 protection MICOMP546 1 0.02 0.02 (Annexure-2 Sh. No.3)

25AR / A812 KVAS100 1 0.02 0.02 (Annexure-2 Sh. No.10)

25AR / A811 KVAS100 1 0.02 0.02 (Annexure-2 Sh. No.10)

FFR (98L2) (Meas.) / 25AR RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98B2) (Meas.) / A812 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98) (Meas.) / A811 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

25AR / A811 FOR AF-2 KVAS100 1 0.02 0.02 (Annexure-2 Sh. No.10)

(27L2), Under voltage relay RAEDA1 3 4.4 13.2 (Annexure-2 Sh. No. 11)

Transducer Panel

Voltage transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No. 13)

Watt meter Watt transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No. 13)

Var meter Var transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No. 13)

Voltmeter, PML ION6200 1 0.5 0.5 Assumed

Wattmeter, PML ION6200 1 0.5 0.5 Assumed

VARmeter, PML ION6200 1 0.5 0.5 Assumed

Energy metering panel

Energy meter Nexus/1262 1 5+3.2 8.2 (Annexure-2 Sh. No. 8)

Under voltage relay RAEDA1 1 4.4 4.4 (Annexure-2 Sh. No. 11)

FFR (98) (Meas.) for revenue meter RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

LCP

Under voltage relay RAEDA1 1 4.4 4.4 (Annexure-2 Sh. No. 11)

Voltmeter ION6200 1 0.5 0.5 Assumed

Total VA = 46.62 VA per phase

Hence, total required burden of VT (Meters/relays plus lead burden) = 46.83 VA

.= (VA Connected + VA Lead)

The Burden calculated considering 25% safety margin = 58.5 VA

Since, the connected burden is less than 100VA,the provided VT burden is adequate.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 44 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

3.3 380kV ABU HADRIYAH- AL-FADHILI LINE-2


CCVT Details :

Core-1 Core-2

VT Ratio : 380kV/√3/110V/√3-110V 380kV/√3/110V/√3-110V

Class : 0.2/3P 0.2/3P

VA Burden : 100 100

Vector group : Star-Star Star-Star

Voltage Factor : 1.2 Cont., 1.2 Cont.,

1.9 for 30 sec 1.9 for 30 sec

Calculation of VT burden :

Calculation of Lead burden:

RL = Lead resistance of wire.

For 4 sq.mm copper cable, RL= 0.00461 ohm/meter at 20ºC.

α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1)), RL= 2.81 ohms

Calculation of Lead current at rated burden :(IVT) = 0.1954 Amperes

Lead current is calculated considering Total VA burden.

Hence, Lead current calculated =100/63.5 = 0.20 Amperes

RB= Lead burden, 2xRLx (IVT^2) = 0.2147 VA

RB= (2 x 2.81 x 0.1954 x 0.1954)

Core-1 :
Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
FFR 98-25AR/A811 FOR MAIN-2 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

Line set-1 protection REL 531 1 0.2 0.2 (Annexure-2 Sh. No.15)

Transient Fault Recorder TR2000 1 0.01 0.01 (Annexure-2 Sh. No.7)

FFR (98) (Meas.) for 67N-1 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98) (Ref.) for 67N-2 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98) (Ref.) for Energy meter RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98L2) (Ref.) for 25AR RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

DSM 1 0.2 0.2 Assumed

FFR (98L) (Ref.) for 25MC 810 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

Total VA = 12.41 VA per phase

Hence, total required burden of VT (Meters/relays plus lead burden) = 12.62 VA

.= (VA Connected + VA Lead)

The Burden calculated considering 25% safety margin = 15.8 VA

Since, the connected burden is less than 100VA,the VT burden is adequate.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 45 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

Core-2:

Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
25MC/A811 RASC 1 0.25 0.25 (Annexure-2 Sh. No.17)

25MC/A810 RASC 1 0.25 0.25 (Annexure-2 Sh. No.17)

FFR (98L) (Meas.) A810/A811 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98) (Ref.) for 67N-1 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98) (Meas.) for 67N-2 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

Line set-2 protection 7SA522 1 0.1 0.1 (Annexure-2 Sh. No.16)

25AR / A810 RASC 1 0.25 0.25 (Annexure-2 Sh. No.17)

25AR / A811 FOR MAIN-2 RASC 1 0.25 0.25 (Annexure-2 Sh. No.17)

27-L2 Under voltage relay RAEDA1 3 4.4 13.2 (Annexure-2 Sh. No. 11)

FFR (98B1) (Meas.) /A810 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

Transducer Panel

Voltage transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No.13)

Watt meter Watt transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No.13)

Var meter Var transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No.13)

Voltmeter PML 1 0.5 0.5 Assumed

Wattmeter PML 1 0.5 0.5 Assumed

VARmeter PML 1 0.5 0.5 Assumed

Revenue metering panel

Revenue meter ELESTER 1 0.0173 0.0173 (Annexure-2 Sh. No. 18)

Under voltage relay RAEDA1 1 4.4 4.4 (Annexure-2 Sh. No. 11)

FFR (98) (Meas.) for revenue meter RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

LCP
FVS-U-
Under voltage relay 1 4.4 4.4 Assumed
DC12
Voltmeter PML 1 0.5 0.5 Assumed

Total VA = 35.42 VA per phase

Hence, total required burden of VT (Meters/relays plus lead burden) = 35.63 VA

.= (VA Connected + VA Lead)

The Burden calculated considering 25% safety margin = 44.5 VA

Since, the connected burden is less than 100VA,the provided VT burden is adequate.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 46 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

3.4 380kV BUS1-VT (Refer Annexure-4A)

VT Details :

Core-1 Core-2

VT Ratio : 380kV/√3/110V/√3-110V 380kV/√3/110V/√3-110V

Class : 0.2/3P 0.2/3P

VA Burden : 100 100

Vector group : Star-Star Star-Star

Voltage Factor : 1.2 Cont., 1.2 Cont.,

1.9 for 30 sec 1.9 for 30 sec

Calculation of VT burden :

Calculation of Lead burden:

RL = Lead resistance of wire.

For 4 sq.mm copper cable, RL= 0.00461 ohm/meter at 20ºC.

α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1)), RL= 2.81 ohms

Calculation of Lead current at rated burden :(IVT) = 0.0945 Amperes

Lead current is calculated considering Total VA burden.

Hence, Lead current calculated =100/63.5 = 0.09 Amperes

RB= Lead burden, 2xRLx (IVT^2) = 0.0502 VA

RB= (2 x 2.81 x 0.0945 x 0.0945)

Core-1 :

Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
FFR (98B1) (Meas.) 25AR/810 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98B1) (Meas.) 25AR/807 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98B1)-25MC/A810 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

Total VA = 6 VA per phase

Hence, total required burden of VT (Meters/relays plus lead burden) = 6.05 VA

.= (VA Connected + VA Lead)

Considering 25% safety margin for any additional FFR relay required.

The Burden calculated considering 25% safety margin = 7.6 VA

Since, the connected burden is less than 100VA,the VT burden is adequate.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 47 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

Core-2:

Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
25MC/A804 RASC 1 0.25 0.25 (Annexure-2 Sh. No.17)

25MC/A807 KVAS100 1 0.02 0.02 (Annexure-2 Sh. No.10)

25MC/A810 RASC 1 0.25 0.25 (Annexure-2 Sh. No.17)

98B1-25MC/810 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

98B1-25AR/807 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

98B1-25AR/810 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

25AR / A807 RASC 1 0.25 0.25 (Annexure-2 Sh. No.17)

25AR / A810 RASC 1 0.25 0.25 (Annexure-2 Sh. No.17)

Transient Fault Recorder TR2000 1 0.01 0.01 (Annexure-2 Sh. No.7)

DSM 1 0.2 0.2 Assumed

Transducer panel

Voltage transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No.13)

Voltmeter PML 1 0.5 0.5 Assumed

LCC

Voltmeter PML 1 0.5 0.5 Assumed

Total VA = 8.33 VA per phase

Hence, total required burden of VT (Meters/relays plus lead burden) = 8.38 VA

.= (VA Connected + VA Lead)

Considering 25% safety margin for any additional FFR relay required.

The Burden calculated considering 25% safety margin = 10.5 VA

Since, the connected burden is less than 100VA,the provided VT burden is adequate.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 48 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

3.5 380kV BUS2-VT


VT Details : (Refer Annexure-4A)

Core-1 Core-2

VT Ratio : 380kV/√3/110V/√3-110V 380kV/√3/110V/√3-110V

Class : 0.2/3P 0.2/3P

VA Burden : 100 100

Vector group : Star-Star Star-Star

Voltage Factor : 1.2 Cont., 1.2 Cont.,

1.9 for 30 sec 1.9 for 30 sec

Calculation of VT burden :

Calculation of Lead burden:

RL = Lead resistance of wire.

For 4 sq.mm copper cable, RL= 0.00461 ohm/meter at 20ºC.

α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1)), RL= 2.81 ohms

Calculation of Lead current at rated burden :(IVT) = 0.0945 Amperes

Lead current is calculated considering Total VA burden.

Hence, Lead current calculated =100/63.5 = 0.09 Amperes

RB= Lead burden, 2xRLx (IVT^2) = 0.0502 VA

RB= (2 x 2.81 x 0.0945 x 0.0945)

Core-1 :
Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
FFR (98B2) (Meas.) 25AR/806 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98B2) (Meas.) 25AR/812 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

FFR (98B2)-25MC/A812 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

Total VA = 6 VA per phase

Hence, total required burden of VT (Meters/relays plus lead burden) = 6.05 VA

.= (VA Connected + VA Lead)

Considering 25% safety margin for any additional FFR relay required.

The Burden calculated considering 25% safety margin = 7.6 VA

Since, the connected burden is less than 100VA,the VT burden is adequate.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 49 of 50 3-083300.01
PROJECT: DOCUMENT TITLE: DOCUMENT NUMBER:
ABU-HADRIYAH 380/115 kV BSP 380 kV CT/VT SIZING CALCULATION EA-086959

Core-2:

Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
25MC/A806 RASC 1 0.25 0.25 (Annexure-2 Sh. No.17)

25MC/A809 RASC 1 0.25 0.25 (Annexure-2 Sh. No.17)

25MC/A812 KVAS100 1 0.02 0.02 (Annexure-2 Sh. No.10)

98B2-25MC/812 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

98B2-25AR/806 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

98B2-25AR/812 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)

25AR / A806 RASC 1 0.25 0.25 (Annexure-2 Sh. No.17)

25AR / A812 KVAS100 1 0.02 0.02 (Annexure-2 Sh. No.10)

Transient Fault Recorder TR2000 1 0.01 0.01 (Annexure-2 Sh. No.7)

DSM 1 0.2 0.2 Assumed

Transducer panel

Voltage transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No.13)

Voltmeter PML 1 0.5 0.5 Assumed

LCC

Voltmeter PML 1 0.5 0.5 Assumed

Total VA = 8.1 VA per phase

Hence, total required burden of VT (Meters/relays plus lead burden) = 8.15 VA

.= (VA Connected + VA Lead)

Considering 25% safety margin for any additional FFR relay required.

The Burden calculated considering 25% safety margin = 10.2 VA

Since, the connected burden is less than 100VA,the provided VT burden is adequate.

BAY NUMBER: Sheet No. ABU-HADRIYAH CONTRACT No.


CROSS BAY C4 50 of 50 3-083300.01
ANNEXURE-1
CT requirements of relay

Sr No. Description Make Type Page No.

1 Line differential protection main-1 ABB RED670 2

2 Line differential protection main-2 AREVA MICOMP546 5

3 Busbar differential protection AREVA MCAG14 8

4 Busbar differential protection AREVA MFAC14 11

5 CT circuit supervision relay AREVA MVTP11 15

6 Breaker failure protection relay ABB RAICA 16

7 Transient fault recorder ROCHESTER TR2000 17

8 Line differential protection main-1 ABB REL531 20

9 Line differential protection main-2 SIEMENS 7SA522 24

Annexure-: CT Requirement of Relay Page 1


Annexure-: CT Requirement of Relay Page 2
Annexure-: CT Requirement of Relay Page 3
Annexure-: CT Requirement of Relay Page 4
Annexure-: CT Requirement of Relay Page 5
Annexure-: CT Requirement of Relay Page 6
Annexure-: CT Requirement of Relay Page 7
Annexure-: CT Requirement of Relay Page 8
Annexure-: CT Requirement of Relay Page 9
Annexure-: CT Requirement of Relay Page 10
Annexure-: CT Requirement of Relay Page 11
Annexure-: CT Requirement of Relay Page 12
Annexure-: CT Requirement of Relay Page 13
Annexure-: CT Requirement of Relay Page 14
Annexure-: CT Requirement of Relay Page 15
Annexure-: CT Requirement of Relay Page 16
Annexure-: CT Requirement of Relay Page 17
Annexure-: CT Requirement of Relay Page 18
Annexure-: CT Requirement of Relay Page 19
Annexure-: CT Requirement of Relay Page 20
Annexure-: CT Requirement of Relay Page 21
Annexure-: CT Requirement of Relay Page 22
Annexure-: CT Requirement of Relay Page 23
Annexure-: CT Requirement of Relay Page 24
ANNEXURE-2
VA burden requirements of relay

Sr No. Description Make Type Page No.

1 Line differential protection main-1 ABB RED670 2

2 Line differential protection main-2 AREVA MICOMP546 3

3 Busbar differential protection AREVA MCAG4 4

4 CT circuit supervision relay AREVA MVTP11 5

5 Breaker failure protection relay ABB RAICA 6

6 Transient fault recorder ROCHESTER TR2000 7

7 Energy Meter Electro Ind. NEXUS1262 8

8 Fuse failure relay ABB RXBA4 9

9 Synchro check relay AREVA KVAS100 10

10 Undervoltage relay ABB RAEDA1 11

11 Line differential protection main-1 ABB REL531 12

12 Transducer AREVA ISTAT300 13

13 Line differential protection main-1 ABB REL531 14

14 Line differential protection main-2 SIEMENS 7SA522 16

15 Synchro check relay ABB RASC 17

16 Revenue Meter ELSTER A3 ALPHA 18

Annexure-: VA Requirement of Relay Page 1


Annexure-: VA Requirement of Relay Page 2
Annexure-: VA Requirement of Relay Page 3
Annexure-: VA Requirement of Relay Page 4
Annexure-: VA Requirement of Relay Page 5
Annexure-: VA Requirement of Relay Page 6
Annexure-: VA Requirement of Relay Page 7
Annexure-: VA Requirement of Relay Page 8
Annexure-: VA Requirement of Relay Page 9
Annexure-: VA Requirement of Relay Page 10
Annexure-: VA Requirement of Relay Page 11
Annexure-: VA Requirement of Relay Page 12
Annexure-: VA Requirement of Relay Page 13
Annexure-: VA Requirement of Relay Page 14
Annexure-: VA Requirement of Relay Page 15
Annexure-: VA Requirement of Relay Page 16
Annexure-: VA Requirement of Relay Page 17
Annexure-: VA Requirement of Relay Page 18
ANNEXURE-3
SAUDI CABLE CATALOGUE
ANNEXURE-4
380kV GIS CT DATA
Ref.No. NA40034-
NA40034-D020
Date : 9 May,
May, 2006
Rev.2 5 Aug. 2009
Rev.3 12 Aug.,2009
Rev.4 18 Aug.,2009

TECHNICAL SPECIFICATION FOR CT

Project : New 380/115kV ABU HADRIYAH BSP


Contract No. : 30531099/00
Specification : 380kV 63kA 3150/2000A GIS

1. Applicable Standard
- IEC 60044-1, IEC 60044-6

2. Ratings
- Symmetric short circuit (Ith) : 63kA rms
- Dynamic short circuit (Idyn) : 163.8kA peak
- Continuous thermal current rating factor : 2.0
1) GCB A810
Specification Type
Location Current Ratio Adopted Class Ual Rct Ial Burden Kssc K Rb
TAP @75℃
<3.1Ω
Bus-1 1 3000-2500-2000-1500- 50BF/A810
2000/1A TPS >3700V <75mA - 31.5 12.63 6.2 CT-1
1250-1000-750/1A
Side
<3.1Ω
2 3000-2500-2000-1500- AL-FADHILI
2000/1A TPS >3700V <75mA - 31.5 12.63 6.2 CT-1
1250-1000-750/1A LINE-2 SET-2
3 3000-2500-2000-1500-
1250-1000-750/1A
2000/1A TPS >3700V <3.1 Ω <75mA - 31.5 12.63 6.2 CT-1
AL-FADHILI
LINE-2 SET-1
4 3000-2500-2000-1500- AL-FADHILI
2500/1A 0.2 SF<5 - - 50VA - - -
1250-1000-750/1A LINE-2 MET.
Bus-2 1 3000-2500-2000-1500-
1250-1000-750/1A
3000/1A TPS >5550V <4.65Ω <50mA - 21 18.95 9.3 CT-1 87B1/M1
Side
<4.65Ω
2 3000-2500-2000-1500- 87B1/M2
3000/1A TPS >5550V <50mA - 21 18.95 9.3 CT-1
1250-1000-750/1A
<4.65Ω
3 3000-2500-2000-1500- SPARE
3000/1A TPS >5550V <50mA - 21 18.95 9.3 CT-1
1250-1000-750/1A

NOTE:
1. CT-2 TYPE: Present design - 3000/1A Tap Rct<6.7ohm --- The CT is CT-2 type. If the CT will be used 2000/1A tap, Rct will be <4.65 ohm,
not <3.1ohm.
2. CT-1 TYPE: Present design - 2000/1A Tap Rct<3.1ohm --- The CT is CT-1 type. If the CT will be used 3000/1A tap, Rct will be <4.7ohm,
not <6.7ohm.
2) GCB A811
Specification Type
Location Current Ratio Adopted Class Ual Rct Ial Burden Kssc K Rb
TAP @75℃
<3.1Ω
Bus-1 1 3000-2500-2000-1500- 50BF/A811
2000/1A TPS >3700V <75mA - 31.5 12.63 6.2 CT-1
1250-1000-750/1A
Side
<3.1Ω
2 3000-2500-2000-1500- MANIFA
2000/1A TPS >3700V <75mA - 31.5 12.63 6.2 CT-1
1250-1000-750/1A LINE-2 SET-1
3 3000-2500-2000-1500-
1250-1000-750/1A
2000/1A TPS >3700V <3.1 Ω <75mA - 31.5 12.63 6.2 CT-1
MANIFA
LINE-2 SET-2
4 3000-2500-2000-1500- MANIFA
3000/1A 0.2 SF<5 - - 60VA - - -
1250-1000-750/1A LINE-2 MET.
Bus-2 1 3000-2500-2000-1500-
1250-1000-750/1A
3000/1A TPS >5550V Ω
<4.65 <50mA - 21 18.95 9.3 CT-1 SPARE
Side
<3.1Ω
2 3000-2500-2000-1500- AL-FADHILI
2000/1A TPS >3700V <75mA - 31.5 12.63 6.2 CT-1
1250-1000-750/1A LINE-2 SET-1
3 3000-2500-2000-1500-
1250-1000-750/1A
2000/1A TPS >3700V <3.1 Ω <75mA - 31.5 12.63 6.2 CT-1
AL-FADHILI
LINE-2 SET-2
4 3000-2500-2000-1500- AL-FADHILI
2500/1A 0.2 SF<5 - - 50VA - - -
1250-1000-750/1A LINE-2 MET.
NOTE:
1. CT-2 TYPE: Present design - 3000/1A Tap Rct<6.7ohm --- The CT is CT-2 type. If the CT will be used 2000/1A tap, Rct will be <4.65 ohm,
not <3.1ohm.
2. CT-1 TYPE: Present design - 2000/1A Tap Rct<3.1ohm --- The CT is CT-1 type. If the CT will be used 3000/1A tap, Rct will be <4.7ohm,
not <6.7ohm.
3) GCB A812
Specification Type
Location Current Ratio Adopted Class Ual Rct Ial Burden Kssc K Rb
TAP @75 ℃
<4.65Ω
Bus-1 1 3000-2500-2000-1500- 87B2/M1
3000/1A TPS >5550V <50mA - 21 18.95 9.3 CT-1
1250-1000-750/1A
Side
<4.65Ω
2 3000-2500-2000-1500- 87B2/M2
3000/1A TPS >5550V <50mA - 21 18.95 9.3 CT-1
1250-1000-750/1A
<4.65Ω
3 3000-2500-2000-1500- SPARE
3000/1A TPS >5550V <50mA - 21 18.95 9.3 CT-1
1250-1000-750/1A
<3.1Ω
Bus-2 1 3000-2500-2000-1500- 50BF/A812
2000/1A TPS >3700V <75mA - 31.5 12.63 6.2 CT-1
1250-1000-750/1A
Side
<3.1Ω
2 3000-2500-2000-1500- MANIFA
2000/1A TPS >3700V <75mA - 31.5 12.63 6.2 CT-1
1250-1000-750/1A LINE-2 SET-1
3 3000-2500-2000-1500-
1250-1000-750/1A
2000/1A TPS >3700V <3.1 Ω <75mA - 31.5 12.63 6.2 CT-1
MANIFA
LINE-2 SET-2
4 3000-2500-2000-1500- MANIFA
3000/1A 0.2 SF<5 - - 60VA - - -
1250-1000-750/1A LINE-2 MET.

NOTE:
1. CT-2 TYPE: Present design - 3000/1A Tap Rct<6.7ohm --- The CT is CT-2 type. If the CT will be used 2000/1A tap, Rct will be <4.65 ohm,
not <3.1ohm.
2. CT-1 TYPE: Present design - 2000/1A Tap Rct<3.1ohm --- The CT is CT-1 type. If the CT will be used 3000/1A tap, Rct will be <4.7ohm,
not <6.7ohm.
ANNEXURE-4A
380kV GIS DATA SCHEDULE FROM TOSHIBA
ANNEXURE-5
SUBSTATION ELECTRICAL LAYOUT-PLAN
PROJECT: ABU-HADRIYAH CONTRACT No.
ABU-HADRIYAH 380/115 kV BSP 3-083300.01

ABUHADRIYAH 380/115kV BSP


TITLE: CT LEAD ROUTE LENGTH CALCULATION
DRAWING REFERENCE: ABU-HADRIYAH SUBSTATION ELECTRICAL LAYOUT -EA-009912

LENGTH MEASURED LENGTH AFTER TERMINATION LENGTH SELECTED


SR.NO. FROM BAY NO. TO RELAY PANEL
IN METERS (WITH 30% MARGIN) IN METERS IN METERS
1.0 CROSS BAY C4 RP 250 325 500
2.0 CROSS BAY C3 RP 230 299 400
3.0 CROSS BAY C2 RP 210 273 350

NOTE: CT LEAD LENGTH IS CONSIDERED AS 500 METERS ON CONSIDERABLY SAFER SIDE TO ACOUNT FOR ANY CIRCUIT
CHANGES IN FUTURE. HENCE, CT LEAD LENGTH IS ESTIMATED AS 500 METERS FOR ALL BAYS CT SIZING CALCULATION.
ANNEXURE-6
RELAYING & METERING ONE LINE DIAGRAM
ANNEXURE-7
LINE PARAMETERS
ANNEXURE-8
M&I METROSIL CATALOGUE
ANNEXURE-9
380kV CVT DATA SCHEDULE