EMERSON SMPS MAKE :NETSURE 701IG4

HOW TO SET THE BATTERY PARAMETERS??

START

FOLLOWING 
PRESS ENTER KEY
SCREEN 
APPEARS

SETTINGS
ALARM
BATT
A.C
D.C
RECT
SYS
1. PRESS BACK BUTTON TO COME OUT OF 
THE PREVIOUS SCREEN.
2.USE UP KEY AND DOWN KEY TO SCROLL 
THE DATA IN THE PRESENT SCREEN
3.USE RIGHT KEY AND LEFT KEY TO CHANGE
 THE PARAMETER OF THE PRESENT SCREEN
4.PRESS ENTER KEY TO SET THE DATA.
GO TO BATT 5. USE UP OR DOWN KEY TO SET THE 
SETTING AND  PASS WORD AND THEN PRESS ENTER.
PRESS ENTER 6.IF THE DATA IS SET AND NOT PRESSING 
THE ENTER KEY THE DATA WILL NOT BE SAVED.
7.IF ANY DOUBTS PLEASE FEEL FREE TO ASK.
8. NOTE EACH SMPS HAS ITS OWN WAY OF
 SETTING THE DATA.

ENTER
PASSWORD
123456
FOLLOWING 
SCREEN 
APPEARS

BATT SELECTION PRESS ENTER
LVD SETTING
CHARGE
BATTERY TEST
TEMP COMP

BATT SELECTION
BATT MODE:AUTO
BAT FUSE:2
CAPACITY:600AH
TYPE:1
SHUNT:YES
SHUNT COEFF:300A/75mv

SHUNT COEFF  CHECK SHUNT 
SET THE BATT
SHOULD BE THE  YES OR NO IT 
CAPACITY
ACTUAL SHOULD BEYES
RATING OF THE 
SMPS

PRESS ENTER

LVD SETTING
LLVDENABLE:Y
BLVDENABLE:Y
LVDMODE:
VOLTAGE SET LLVD AND 
LVDVOLTAGE: BLVD AS 
LLVD:45.0V RECOMMENDED 
BLVD:44.00V BY HBL
CHARGE SETTING

FOLLOWING 
SCREEN 
PRESS ENTER APPEARS

CHARGE
FLOAT:54.5V SET FLOAT AND
BOOST:55.9V BOOST VOLTAGE
LIMIT:0.150C10  AS PER 
OVER:0.300C10 PSA SETTINGS
START BOOST
AUTOMATIC:Y SET THE CHARGING
CYCLIC:N CURRENT AS PER THE AH
AUTOMATIC BOOST CAPACITY OF THE BATTERY
CURR: 0.060C10
CAPACITY:80%
CONSTANT BOOST
CURR:0.010C10 SET OVER CHARGING
DURATION 180MIN CURRENT AS RECOMMENDED
CYCLIC BOOST
INTERVAL:2400H
DURATION:720MIN
BOOST LIMIT
TIME:1080MIN IN BOOST SETTING SET 
CLRBATT RECD:N AUTOMATIC : Y
Y MEANS YES

IN AUTOMATIC BOOST THE 
CONDITION FOR SMPS TO GO 
EXTRA TIME IN BOOST MODE WITH
TO BOOST LOGIC ARE 
CURRENT LIMIT, WITH SET C.L AND
1, DURING DISCHARGE IF 
TIME, IT REMAINS IN BOOST MODE
THE BATTERY DRAIN (AH) 
BEFORE GOING TO FLOAT MODE
GREATER THAN THE SET 
VALUE OR CHARGING 
CURRENT GOES MORE THAN
THE SET CURRENT LIMIT 

THE OTHER PARAMETERS 
CYCLIC BOOST AND BOOST
LIMIT WILL BE IN ACTIVE 
WHEN CYCLIC IS SET “N”
BATTERY TEST

FOLLOWING 
SCREEN 
APPEARS

PRESS ENTER

ALL ARE 
FACTORY SET
PARAMETERS
TEST END VOLTAGE:45.2V
TEST END TIME:300MIN
TEST END CAP:0.700C10
TIME TEST ENABLE
SHORT TEST ENABLE:Y
ALARM CURRENT:10A  WE CAN DO BATTERY 
SHORT TEST CYCLE:720AH DISCHARGE BY SETTING 
DURAT:5MIN THE PARAMETER AS 
STABLE TEST ENABLE:N RECOMMENDED
CURRENT:9999A

SET THE CONFIG TO
BATTERY MODE IF 
TEMP COMP
TEMP IN BTS IS 
UNDER CONTROL OR SET THE ROOM
SET IT NONE TEMP

PRESS ENTER
SET THE mV DROP
PER DEG IN TEMP
RAISE

TEMP1 CONFIG:NONE SET THE BAT OVER
TEMP 2 CONFIG:NONE TEMP AS 
CENTER TEMP: 27 C RECOMMENDED
TEMP COMP COEFF:
72mV/C/STR
BATTERY TEMP ALARM SET THE BAT HIGH
BAT OVER: 40C TEMP AS 
BAT HIGH:39C RECOMMENDED
BAT LOW: 5C

SET THE BAT LOW
TEMP AS 
RECOMMENDED