You are on page 1of 4

ABU HAORIYAH· 380/115kV BSP GIS

CUSTOMER: SAUDI ELECTRICITY COMPANY. SEC. EOA.


EXPANSION PROJECT.
CONTRACT NO. : 30733178/00 NATIONAL CONTRACTING COMPANY
SUBSTATION: 380/115kV BSP ABU HADRIYAH LTO. AL KHOBAR.
TYPE FORM: 420kVGIS
BAYNo. C4. AL FADHILI LINE 2.

CONTACT RESISTANCE MEASUREMENT.


Measurement of the main contact resistance with DC voltage drops method. (100A DC)
Measurement of the resistance of each assembled unit with insulated earthing terminal.

Resistance(IJO) Ambient
Phase A Phase B Phase C Temp.oC
I Rs/Rs20 265/262.2 303/299.8 360/356.2 22.9
I Rf20 239 277 323 20

Rs : Site test value


Rs20: Site test valu at 20 DC
Rf20: Routine test valu at 20 DC
Rf20=Rs*( 1/0.004+20)/( 1/0.004+ts)
t. ;Ambient temprature at site

Name: MUHAMMAD KASHIF

Signature:

Date: tJ' / D t /2b II


Signature :

Date: \ '\ \~\


v
~
\, cffi/il
TOSHIBA CORPORATION SAUDI ELECTRICTY COMPANY. CSD. EOA
-Measurement of the resistance by DC voltage drop method
-Test current 100A DC
-Resistance value in table is a value corrected into 20 "C

Single line diagram

Measuring Resistance( f..L Q)


Icy® parts A B C
GAS-AIR B'I CD~® 27 33 37
Criteria 22 .......
32 27 .......
39 32 .......
47
®~@ 80 84 110
Criteria 63 .......
93 67 .......
99 87 .......
130
®~® 20 26 52
Criteria l4~22 .-- ..-
CV~® 112 127 134
Criteria --- ... ..-
® .......
® 917 853 794
Criteria 729 .......
1093 681 .......
1021 631 .......
946

~ Industrial Services
~ewed 0 Witnessed
d ~UN ,~Z ~:' ?Jii.i
ITS{Jl-03 T. IWABUCHI
®
ABU HAORIYAH - 380/115kV BSP GIS
CUSTOMER: SAUDI ELECTRICITY COMPANY. SEC. EOA. PROJECT:
EXPANSION PROJECT.
CONTRACT NO. : 30733178/00 NATIONAL CONTRACTING COMPANY
CONTRACTOR:
SUBSTATION: 380/115kV BSP ABU HADRIYAH LTD. AL KHOBAR.
TYPE FORM: 420kVGIS
BAYNo. C3. GCB A807. RATING: 380kV 3150A. 63kA 1see. 60Hz

CONTACT RESISTANCE MEASUREMENT.


Measurement of the main contact resistance with DC voltage drops method. (100A DC)
Measurement of the resistance of each assembled unit with insulated earthing terminal.

Resistance(~O) Ambient
No. Measurement point Result
Phase A Phase B Phase C Temp.oC
1 - 2 Rs/Rs20 17/16.86 19/18.80 19/18.80 22.2 OK
1
1 - 2 Rf20 35 49 63 20 OK

2 3 - 4 Rs/Rs20 110/108.48 121/119.32 134/132.14 23.8 OK

Note 1 : The measurement 1 made directly from the GCB contact


Note 2: The measurement 2 made through earthing switch K818 & K819 after new A807 GCB installation.

Criteria: Rf20x1.2 ~ Rs20 Rs : Site test value


Rs20: Site test valu at 20°C
Rf20: Routine test valu at 20°C
Rf20=Rs*( 1/0.004+20)/( 1/0.004+ts)
t. ;Ambient temprature at site

TEST EQUIPMENT USED : PROGRAMMA MOM 690.

TESTED BY WITNESSED BY
Name: BENNYJACOB N,me' MUHAMMADKASH~

Signature: •
::t:a:tu~6 /01/20 If ~ Date: D~\0\\ "}.e\ I
TOSHIBA CORPORATION SAUDI ELECTRICTY COMPANY. CSD. EOA
-Measurement of the resistance by DC voltage drop method
-Test current 100A DC
-Resistance value in table is a value corrected into 20 'C
Single line diagram

04 side
~
Resistance(.u 0Xat 20'C)
I C3 I Measuring
parts A B C
a>-® 35 49 63
Criteria 30-43 37-55 53........
79

CT
GC8
AB08
CT

®
CT
GC8
1.801
CT

DS

8USl

)[GIB
GAS-AIR 8' R
Industrial Services
eviewed 0 Witnessed
:s:t= APR20 2010
ITS J -03 T. IWA6UCHI

You might also like