DESIGN OF LONG COLUMN COL.

N0:- C1

Load on a column P= 400 KN SUMMERY


Width of column b= 200 mm LOAD- 400 KN
Depth of column D= 400 mm SIZE:-
Effective length of column Leff= 2700 mm WIDTH:- 200
Ratio Leff / b <12 short column 13.5 >12 DEPTH:- 400
Reduction factor Cr=1.25-(Leff./48/b) Cr= 0.969 BAR:- 6 14
Charecteristic strength of reinfo. fy= 415 N/mm2
Carecteristic strength of concrete fck= 20 N/mm2
Area of concrete Ac= b x D Ac= 80000 sqmm
Ultimate load on column 1.5xP Pu= 600 KN
Net load on col Pu(net)= Pu/Cr Pu(net)= 619 KN
Pu(Net) = 0.4*fck*Ac +0.67*fy*Asc
Area of longitudinal steel required
Asc= (Pu - 0.4*fck*Ac)/ (0.67*fy) Asc= -76 sqmm
check for min. reinforcement
Asc (min.) = 0.004*b*D/100 Asc(min) = 320 sqmm
PROVIDE 6 BAR 14 Asc(pro) = 923 sqmm
AREA PROVIDED OK

DESIGN OF LONG COLUMN COL. N0:- C2

Load on a column P= 500 KN SUMMERY


Width of column b= 200 mm LOAD- 500 KN
Depth of column D= 500 mm SIZE:-
Effective length of column Leff= 2700 mm WIDTH:- 200
Ratio Leff / b <12 short column 13.5 >12 DEPTH:- 500
Reduction factor Cr=1.25-(Leff./48/b) Cr= 0.969 BAR:- 8 14
Charecteristic strength of reinfo. fy= 415 N/mm2
Carecteristic strength of concrete fck= 20 N/mm2
Area of concrete Ac= b x D Ac= 100000 sqmm
Ultimate load on column 1.5xP Pu= 750 KN
Net load on col Pu(net)= Pu/Cr Pu(net)= 774 KN
Pu(Net) = 0.4*fck*Ac +0.67*fy*Asc
Area of longitudinal steel required
Asc= (Pu - 0.4*fck*Ac)/ (0.67*fy) Asc= -94 sqmm
check for min. reinforcement
Asc (min.) = 0.004*b*D/100 Asc(min) = 400 sqmm
PROVIDE 8 BAR 14 Asc(pro) = 1231 sqmm
AREA PROVIDED OK

42
DESIGN OF LONG COLUMN COL. N0:- C3

Load on a column P= 575 KN SUMMERY


Width of column b= 200 mm LOAD- 575 KN
Depth of column D= 500 mm SIZE:-
Effective length of column Leff= 2700 mm WIDTH:- 200
Ratio Leff / b <12 short column 13.5 >12 DEPTH:- 500
Reduction factor Cr=1.25-(Leff./48/b) Cr= 0.969 BAR:- 10 14
Charecteristic strength of reinfo. fy= 415 N/mm2
Carecteristic strength of concrete fck= 20 N/mm2
Area of concrete Ac= b x D Ac= 100000 sqmm
Ultimate load on column 1.5xP Pu= 862.5 KN
Net load on col Pu(net)= Pu/Cr Pu(net)= 890 KN
Pu(Net) = 0.4*fck*Ac +0.67*fy*Asc
Area of longitudinal steel required
Asc= (Pu - 0.4*fck*Ac)/ (0.67*fy) Asc= 324 sqmm
check for min. reinforcement
Asc (min.) = 0.004*b*D/100 Asc(min) = 400 sqmm
PROVIDE 10 BAR 14 Asc(pro) = 1539 sqmm
AREA PROVIDED OK

DESIGN OF LONG COLUMN COL. N0:- C4

Load on a column P= 680 KN SUMMERY


Width of column b= 200 mm LOAD- 680 KN
Depth of column D= 600 mm SIZE:-
Effective length of column Leff= 2700 mm WIDTH:- 200
Ratio Leff / b <12 short column 13.5 >12 DEPTH:- 600
Reduction factor Cr=1.25-(Leff./48/b) Cr= 0.969 BAR:- 12 14
Charecteristic strength of reinfo. fy= 415 N/mm2
Carecteristic strength of concrete fck= 20 N/mm2
Area of concrete Ac= b x D Ac= 120000 sqmm
Ultimate load on column 1.5xP Pu= 1020 KN
Net load on col Pu(net)= Pu/Cr Pu(net)= 1053 KN
Pu(Net) = 0.4*fck*Ac +0.67*fy*Asc
Area of longitudinal steel required
Asc= (Pu - 0.4*fck*Ac)/ (0.67*fy) Asc= 334 sqmm
check for min. reinforcement
Asc (min.) = 0.004*b*D/100 Asc(min) = 480 sqmm
PROVIDE 12 BAR 14 Asc(pro) = 1846 sqmm
AREA PROVIDED OK
43
DESIGN OF LONG COLUMN COL. N0:- C5

Load on a column P= 800 KN SUMMERY


Width of column b= 200 mm LOAD- 800 KN
Depth of column D= 700 mm SIZE:-
Effective length of column Leff= 2700 mm WIDTH:- 200
Ratio Leff / b <12 short column 13.5 >12 DEPTH:- 700
Reduction factor Cr=1.25-(Leff./48/b) Cr= 0.969 BAR:- 12 16
Charecteristic strength of reinfo. fy= 415 N/mm2
Carecteristic strength of concrete fck= 20 N/mm2
Area of concrete Ac= b x D Ac= 140000 sqmm
Ultimate load on column 1.5xP Pu= 1200 KN
Net load on col Pu(net)= Pu/Cr Pu(net)= 1238 KN
Pu(Net) = 0.4*fck*Ac +0.67*fy*Asc
Area of longitudinal steel required
Asc= (Pu - 0.4*fck*Ac)/ (0.67*fy) Asc= 424 sqmm
check for min. reinforcement
Asc (min.) = 0.004*b*D/100 Asc(min) = 560 sqmm
PROVIDE 12 BAR 16 Asc(pro) = 2412 sqmm
AREA PROVIDED OK

DESIGN OF LONG COLUMN COL. N0:- C6

Load on a column P= 800 KN SUMMERY


Width of column b= 200 mm LOAD- 800 KN
Depth of column D= 700 mm SIZE:-
Effective length of column Leff= 2700 mm WIDTH:- 200
Ratio Leff / b <12 short column 13.5 >12 DEPTH:- 700
Reduction factor Cr=1.25-(Leff./48/b) Cr= 0.969 BAR:- 14 16
Charecteristic strength of reinfo. fy= 415 N/mm2
Carecteristic strength of concrete fck= 20 N/mm2
Area of concrete Ac= b x D Ac= 140000 sqmm
Ultimate load on column 1.5xP Pu= 1200 KN
Net load on col Pu(net)= Pu/Cr Pu(net)= 1238 KN
Pu(Net) = 0.4*fck*Ac +0.67*fy*Asc
Area of longitudinal steel required
Asc= (Pu - 0.4*fck*Ac)/ (0.67*fy) Asc= 424 sqmm
check for min. reinforcement
Asc (min.) = 0.004*b*D/100 Asc(min) = 560 sqmm
PROVIDE 14 BAR 16 Asc(pro) = 2813 sqmm
AREA PROVIDED OK