SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - August 2004)

SAIC NUMBER DATE APPROVED QR NUMBER


SAUDI ARAMCO INSPECTION CHECKLIST
Fence and Gate Components Receiving Inspection- Types I -
SAIC-M-1001 18-May-05 CIVIL-
V Fences
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

A General Fence Components Receiving Inspection

Saudi Aramco Security Fencing Type I shall be used for all facilities SAES-M-006
A1
where security is of concern. Sec. 4.3

Use of Reclaimed material is not permitted unless written approval is SAES-M-006


A2
obtained. Sec. 4.2

Galvanized fabric and hardware shall be used for all inland locations 12-SAMSS-021
A3
(more than 1.5 km from the sea). Sec. 4.1.1

Vinyl-clad fabric, barbed wire, tension wire, tie wire and gate infilling shall
SAES-M-006
A4 be used on all locations within 1.5 km from the sea.
Sec. 4.5
(12-SAMSS-022, Sec 4.1.1)

Types of Saudi Aramco fencing and their appurtenances:


Fence Height Top Brace Post Barbed Wire Number Continuous
Type Fabric Rail For Each Number of of Barbed Concrete
(mm) Line Post Arms Wires Anchor SAES-M-006
A5 I 2.4m Yes Yes 2 6 Yes Sec. 4.9
II 2.4m Yes Yes 2 6 No Table 1
III 2.4m No No 2 6 No
IV 2.4m No No 1 3 No
V 2.4m No No 0 0 No

B Gates and Components Receiving Inspection

Applicable Gate Sizes:


Fence Gate Walk/ Width Overall Gate Frame Gate Post
Type Type Drive opening Height Extensions O.D.(mm)
SAES-M-006
I,II,III,IV,V A Walk 1.2m 2.45m No 73
B1 Sec. 4.10
B Drive 4.0m 2.8m Yes 102
Table 2
I,II,III,IV C Drive 7.3m 2.8m Yes 102
V D Drive 4.0m 2.45m No 102
E Drive 7.3m 2.45m No 102

Gates shall be framed with 48mm O.D. steel pipe, Schedule 40, ASTM 12-SAMSS-021 &
B2
A53 as the framing material. 022 Sec. 4.8.1.a

12-SAMSS-021 &
B3 Gates shall have welded or bolted construction.
022 Sec. 4.8.1.b

12-SAMSS-021 &
B4 Gates shall have 10 mm diameter adjustable diagonal tension rods.
022 Sec. 4.8.1.c

Gates shall have 50mm mesh chain link, 3.75mm diameter link vinyl-clad 12-SAMSS-021 &
B5
galvanized as specified on the Purchase Order and/or Drawings. 022 Sec. 4.8.1.d

12-SAMSS-021 &
B6 Gate hinges shall be able to swing 900 either way from a closed position.
022 Sec. 4.8.1.e

Page 1 of 4
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Fence and Gate Components Receiving Inspection- Types I -
SAIC-M-1001 18-May-05 Civil
V Fences
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Gates shall have fittings for 35mm diameter plunger rod on each leaf of 12-SAMSS-021 &
B7
the gate. 022 Sec. 4.8.1.f

Gates shall be equipped with attachments for padlocking, the padlock to 12-SAMSS-021 &
B8
be accessible from both sides of the gate. 022 Sec. 4.8.1.g

Gates shall be equipped with 35mm diameter plunger rod for each gate 12-SAMSS-021 &
B9
leaf; as an alternative to only a single plunger rod. 022 Sec. 4.8.1.h

Gate leaves shall be equipped with a plunger rod receiver and open-gate 12-SAMSS-021 &
B10
holders. 022 Sec. 4.8.1.i

Where required, gate frame extensions shall extend 300mm above the 12-SAMSS-021 &
B11
gate frame. 022 Sec. 4.8.1.j

Where gates exceed 1.2m in width, additional vertical framing members


12-SAMSS-021 &
B12 shall connect the top and bottom horizontal members dividing the leaves
022 Sec. 4.8.1.k
into panels between 900mm and 1550mm's in width.

C Fence Post Receiving Inspection

Post Lengths: Length of Posts (mm)


Fence Type: I II III IV V
Walk Gate 3400 3400 3400 3400 3400
Drive Gate 3900 3900 3900 3900 3900 SAES-M-006
C1 Line 3400 3400 3400 3400 3400 Sec. 4.11
Corner/End 3400 3400 3400 3400 3400 Table 3
Brace 2900 2900 2900 2900 2900
Post Lengths (Heights) are subject to a + 12mm tollerance; They include
975 mm for embedment in the footings.

All tubular steel posts shall be as specified in the purchase order or on


the IFC Drawings, shall be schedule 40 seamless mild steel pipe, hot dip
galvanized with 400g/m2 of zinc. Table 2 - Post Diameters
Classification Nominal Post Size (inches) O.D. mm 12-SAMSS-021 &
C2 Brace and Rails 1.25" 41 022 Sec. 4.6.1
Line Posts 2.0" 60 Table 2
Corner/End Posts 2.5" 73
Single Gates 1.2m wide 2.5" 74
Double Gates 4-8.0m wide 3.5" 102

All Posts shall be supplied with moisture excluding top caps or extension 12-SAMSS-021 &
C3
arms as specified in the purchase order or IFC Drawings. 022 Sec. 4.6.3

All Posts shall be supplied with the necessary holes drilled for the 12-SAMSS-021 &
C4
appropriate fittings. 022 Sec. 4.6.2

D Fencing Fabric and Fittings Receiving Inspection

Table 1 - Fencing Fabric Wire Type:


Coating Type Size O.D. Galv./Coating Min. Breaking Strength
12-SAMSS-021 &
D1 Plain Galvanized 3.75mm 366g/m 2 zinc 5740 N(1290lbs)
2
022, Sec. 4.1.1
PVC Fusion Bonded 3.75mm 85.4g/m +0.2mm PVC 5340 N(1200lbs)
Extruded Vinyl 4.88mm 85.4g/m2+0.5mm Vinyl 5340 N(1200lbs)
Wire fencing fabrics shall be 2.400 meter high, have a 50mm diamond
mesh, the top and bottom selvages shall be machine twisted with the 12-SAMSS-021 &
D2
wire cut to form a barbed wire finish, Vinyl Clad or Galvanized, meeting 022, Sec. 4.1.1
SAMS Number 12-679-440 or 12-679-410; Standard roll lengths 15m.

Page 2 of 4
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Fence and Gate Components Receiving Inspection- Types I -
SAIC-M-1001 18-May-05 Civil
V Fences
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Galvanized Tension wire shall be used top and bottom in type III, IV and
V fencing and at the bottom only for type II fencing; shall be SAMS
12-SAMSS-021
D3 Number 12-711-585, having a 3.75mm nominal wire diameter,
Sec. 4.4
galvanized with 244g/m2 of zinc.
(SASD AB-036677, AE-036882 to 036884 & AE-036904)
Vinyl-Clad Galvanized Tension wire shall be used top and bottom in type
III, IV and V fencing and at the bottom only for type II fencing; shall be
12-SAMSS-022
D4 SAMS Number 12-711-585, having a 3.75mm nominal wire diameter,
Sec. 4.4
galvanized with 244g/m2 of surface area with additional PVC or Vinyl
coating. (SASD AB-036677, AE-036882 to 036884 & AE-036904)
Galvanized Tie Wire 2.65mm diameter shall be provided in 250mm
lengths + 10mm long, with 244 g/m 2 galvanization, meeting SAMS 12-SAMSS-021
D5
number 12-711-600. Sec. 4.5
(SASD AB-036677, AE-036882 to 036884 & AE-036904)

Vinyl-Clad Tie Wire 2.65mm diameter shall be provided in 250mm


lengths + 10mm long, with 85.4 g/m 2 galvanization, with a top coating of
12-SAMSS-022
D6 either 0.2mm (8mil) of fusion bonded PVC or 0.5mm (20mil) of extruded
Sec. 4.5
Vinyl; SAMS number 12-711-600.
(SASD AB-03667, AE-036882 to 036884 & AE-036904)

Lock wires in lenghts 460mm long, annealed and galvanized with a


12-SAMSS-021 &
D7 25mm diameter hook on one end, for securing barbed wires to extension
022, Sec. 4.3
arms in fence types I, II, III and V shall be ASTM A641.

Barbed wire for fence types I, II, III, IV and V shall consist of consist of
two twisted strands of not lighter than 2.5mm nominal diameter wire, with
four barbs (points) of not lighter than 2mm nominal diameter wire,
spaced 125mm + 20mm apart. Galvanized barbed wire shall have 12-SAMSS-021 &
D8
2 022, Sec. 4.2
244g/m of zinc coating; Galanized and Coated wire shall have 85.4
2
gr/m zinc coating with either 0.20mm (8mil) of fusion bonded PVC or
0.5mm (20mil) of Vinyl jacketing.

All fittings shall be galvanized pressed steel or wrought iron or malleable 12-SAMSS-021 &
D9
iron. 022, Sec. 4.7.1

Attachment of fittings shall be with galvanized carriage bolts with nuts,


12-SAMSS-021 &
D10 except for post extension arms where galvanized machine bolts shall be
022, Sec. 4.7.2
used.

12-SAMSS-021 &
D11 All gate fittings shall be compatible with the gates supplied.
022, Sec. 4.7.3

REMARKS:

REFERENCE DOCUMENTS:
1- SAES-M-006 -- Saudi Aramco Security and General Purpose Fencing, 30 November 2003
2- 12-SAMSS-021 -- Saudi Aramco Security and General Purpose Fencing(Galvanized), 30 November 2003
3- 12-SAMSS-022 -- Saudi Aramco Security and General Purpose Fencing(Vinyl-Clad Galvanized), 30 November 2003
4- AA-036678 -- Saudi Aramco Security and General Purpose Fencing Post and Fabric Details, 01 January 1990
5- AB-036677 -- Saudi Aramco Security and General Purpose Fencing, An Overview (Architectural), 02 March 1990
6- AB-036679 -- Saudi Aramco Security and General Purpose Fencing Gate Details, 04 February 1990

Page 3 of 4
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Fence and Gate Components Receiving Inspection- Types I -
SAIC-M-1001 18-May-05 Civil
V Fences
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
7- AC-036680 -- Saudi Aramco Security and General Purpose Fencing Footing Details, 01 March 1997
8- AE-036881 -- List of Material for Saudi Aramco Security Fencing, 01 October 1993
9- AE-036882 -- List of Material for Saudi Aramco Type II Fencing, 01 October 1993
10- AE-036883 -- List of Material for Saudi Aramco Type III Fencing, 11 October 1993
11- AE-036884 -- List of Material for Saudi Aramco Type IV Fencing, 12 October 1993
12- AE-036904 -- List of Material for Saudi Aramco Type V Fencing, 01 November 1990

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:
*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Page 4 of 4