Transactions on Power Systems, Vol. 6, No.

3, August 1991

975

RADIAL DISTRIBUTION TEST FEEDERS

IEEE Distribution Planning Working Group Report

Abstract - Many computer programs are


available
for
the analysis
of
radial
distribution feeders. Because of the wide
variation of the assumptions made in the
development of the programs, there is a need
for benchmark systems for comparison testing
of the various programs. This paper presents
the complete data for three four-wire wye and
one three-wire delta radial
distribution
feeders.
Kevwords: distribution system analysis, test
systems, computer programs.

Load Models
Loads can be connected at a bus (spot load)
or assumed to be uniformly distributed along
a line section (distributed load). Loads can
be three-phase (balanced and unbalanced) or
single-phase.
Three-phase loads can
be
connected in wye or delta while single phase
loads can be connected line-to-neutral or
line-to-line.
All loads can be modeled as
constant kW and kVAr, constant impedance (Z)
or constant current (I).
Table 1 lists the numeric codes that will
used to describe the various loads.

be

INTRODUCTION
Table 1

In
recent years many
digital
computer
programs have been developed for the analysis
of unbalanced three-phase radial distribution
feeders. The programs use a wide variety of
iterative techniques and range from very
simple with many simplifying assumptions made
for
line
and
load
models
to
very
sophisticated with little if any simplifying
assumptions. With so many different programs
available there is a need for benchmark test
various
feeders so that the results of
programs can be compared.
This paper presents the complete data for
three four-wire wye and one three-wire delta
radial distribution feeders. No results will
be given for any of the feeders. It is hoped
that developers of distribution
analysis
programs will use these test systems to test
their programs and to present results in
future papers.
BASIC DATA
The following data will be common
three systems:

Load Model Codes


Code No.
1
2
3

4
5

Connection
WYe
WYe
WYe
Delta
Delta
Delta

Model
Constant kW, kVAr
Constant I
Constant Z
Constant kW, kVAr
Constant I
Constant Z

Single-phase loads connected


line-to-line
will be assigned code numbers 4,5 or 6.
All of the load data will be given in kW and
kVAr per phase. For constant impedance and
constant current loads, the kW and kVAr given
are assumed at rated voltage (1.0 per unit).
For wye connected loads, Phases 1, 2 and 3
will
be
connected a-n,
b-n
and
c-n
respectively and delta connected loads will
be connected a-b, b-c and c-a respectively.
Only non-zero bus loads will be given in the
various feeder load tables. All other bus
loads are assumed to be zero.

for all

The systems described in this paper were


approved by the IEEE Distribution Planning
Working
Group
during
the
1990
Power
Engineering Society's Winter Meeting.
The
paper
was written by W.
H.
Kersting,
Professor of Electrical Engineering at New
Mexico State University, Las Cruces, NM.

9 1 WM 2 7 0 - 9 PWRS A paper recommended and approved


by the IEEE Power System Engineering Committee of
the IEEE Power Engineering Society for presentation
at the IEEE/PES 1 9 9 1 Winter Meeting, New York,
New York, February 3 - 7 , 1991. Manuscript submitted
March 5, 1990; made available for printing
November 30, 1990.

Shunt Capacitor
Shunt capacitor banks may be three-phase wye
or delta connected and single-phase connected
line-neutral or line-line. The capacitors are
modeled as constant susceptance and specified
as nameplate rated kVAr.
Overhead Spacinu Models
The Spacing ID numbers and type for
lines are summarized in Table 2.

overhead

Table 2

Overhead Line Spacings


Spacinq ID
500
505

510

0885-8950/91/0700-0975$01.00 0 1991 IEEE

~~

Type
Three-phase, 4 wire
Two-phase, 3 wire
Single-phase, 2 wire

976

Figure 1 shows the spacing distances between


the
phase
conductors and
the
neutral
conductor for the Spacing ID numbers used for
the overhead lines.

1
I

Voltage Level
desired voltage (on a
120 volt base ) to be held at the
regulating point.

2.

Bandwidth
the voltage level tolerance
usually assumed to be 2 volts.

3.

Compensator R and X Settings


the
equivalent resistance and reactance
to the regulating point calibrated
in volts.

4.

PT Ratio
turns ratio of the potential
transformer feeding the compensator
circuit.

5.
ID #500

ID #505

Figure 1

ID #510

AA
ACSR

500,000

AA

336,400

ACSR
ACSR
AA
ACSR
CU

4/0

2/0
1/ 0
1/ 0
#2
#2
#4

#lO
#I2
# 14

AA

ACSR
ACSR
CU
CU
CU

CT Rating - the primary current rating


of the current transformer feeding
the compensator circuit.

The 123 bus test feeder is characterized by:


1.

Table 3

556,500

IEEE 123 BUS RADIAL DISTRIBUTION FEEDER

Table 3 lists the characteristics of the


various conductors that are used in the four
test feeders.

1,000,000

Overhead Line Spacings

Conductor Data

Conductor Type

1.

Res.
Dia.
fohm/mi.l
finl
0.105
1.150
0.186
0.927
0.206
0.813
0.306
0.721
0.592
0.563
0.769
0.414
1.120
0.398
0.607
0.368
1.540
0.292
1.690
0.316
2.550
0.257
5.903
0.102
9.375
0.081
14.872
0.064

GMR
fftl
0.03680
0.03110
0.02600
0.02440
0.00814
0.01250

698
730
483
530
340
230
0.00446 230
0.01113 310
0.~0883 156
0.00418 180
0.00452 140
0.00331
80
0.00262
75
0.00208
20

Line Section Data


Each test feeder will have a table of "Line
Section Data". The data will consist of the
bus terminations of each line section (BUS A
and BUS B), the length of the line section
and a configuration code (CONFIG.CODE).
The
line data has been sorted on BUS A so there
is no significance in the order in which the
data appears or whether BUS A or BUS B is
closer to the source. Each system will have
a "Table of Configuration Codes1' that will
describe
the
conf@uration
code.
The
configuration
code is a
unique
number
assigned to describe the spacing model (Table
2), the phasing (left to right) and the phase
and neutral conductors.
Voltase Recrulators
Voltage regulators are assumed to be "steptype" and can be connected in the substation
or out on the feeder. The regulators can be
three-phase or single-phase. Tap positions
will be determined by the compensator circuit
settings described by:

Load Types
a. All spot loads
b. Wye and delta connected
c. Mixture of constant kW,kVAR,
constant Z and constant I.

2.

Line Types
a. Three-phase overhead (all
combinations of a ,b ,c)
b. Two-phase overhead
(Combinations of a,b,c)
c. Single-phase overhead
(a-n, b-n and c-n)
d. Three-phase underground

3.

Voltage Regulators
a. Three-phase, gang operated
b. Three single-phase, wye connected
c. Two single-phase, open wye connected
d. Single-phase, line-to-neutral
connected

4.

Shunt Capacitors
a. Three-phase
b. Single-phase

5.

Substation
a. Three-phase short circuit MVA and
angle at the high voltage terminals
of the substation transformer.
b. Substation transformer ratings and
impedance.
c. Substation transformer output
voltages

6.

Motor
a. Step-down transformer
b . Starting kVA and power factor given
c. Running power factor

The circuit diagram (not to scale) for


feeder is shown in Figure 2.

this

Figure 2
The
substation
feeder is rated:

transformer serving

123 Bus Circuit Diagram


this
Table 4

5,000 kVA
115 delta-4.16 grounded wye kV
Z = 1.0 + j8.0 %

IEEE 123 BUS RADIAL DISTRIBUTION SYSTEM


LINE SECTION DATA

The three-phase short circuit MVA on the 115


kV bus of the substation is 1100 MVA at an
angle of 82 degrees.
The output voltages from the transformer are
balanced three-phase of 0.98 per unit.
150 horsepower induction motor is located
Bus 610. The starting kVA is assumed to
be 6 times rated kVA at a 0.4 lagging power
factor. The running power factor is 0.8 lag.
A

at

Table 4 gives the Line Section Data for


system.

this

BUS A BUS B
1
1
1
3
3
5
7

2
3
7
4
5
6

8
8

12

13
14
34
18
152
11

13
13
13
14

8
9

LENGTH CONFIG.
(FT.)
CODE
175.0
250.0
300.0
200.0
325.0
250.0
200.0
225.0
225.0
300.0
425.0
150.0
825.0
0.0
250.0

10
11
1
11
11
11
1
10
9

1
9
11
2
506
9

978
Table 4
(continued)

Table 4

(continued)
IEEE 1 2 3 BUS RADIAL DISTRIBUTION SYSTEM
LINE SECTION DATA
BUS A BUS B
14
15
15
18
18
18
19
21
21
23
23
25
25
26
26
27
28
29
30
31
34
35
35
36
36
38
40
40
42
42
44
44
45
47
47
49
50
52
53
54
54
55
57
57
58
60
60
60
61
62
63
64
65
67
67
67
68
69
70
72
72
73
74
76
76
77
78

10
16
17
19
21
135
20
22
23
24
25
26
28
27
31
33
29
30
250
32
15
36
40
37
38
39
41
42
43
44
45
47
46
48
49
50

51
53
54
55
57
56
58
60
59
61
62
160
610
63
64
65
66
68
72
97
69
70
71
73
76
74
75
77
86
78
79

IEEE 1 2 3 BUS RADIAL DISTRIBUTION SYSTEM


LINE SECTION DATA

LENGTH CONFIG.
CODE
(FT.1
250.0
375.0
350.0
250.0
300.0
0.0
325.0
525.0
250.0
550.0
275.0
350.0
200.0
275.0
225.0
500.0
300.0
350.0
200.0
300.0
100.0
650.0
250.0
300.0
250.0
325.0
325.0
250.0
500.0
200.0
200.0
250.0
300.0
150.0
250.0
250.0
250.0
200.0
125.0
275.0
350.0
250.0
250.0
750.0
250.0
550.0
250.0
0.0
0.0
175.0
350.0
425.0
325.0
200.0
275.0
250.0
275.0
325.0
275.0
275.0
200.0
350.0
400.0
400.0
700.0
100.0
225.0

BUS
A

BUS
A

78
80
81
81
82
84
86
87
87
89
89
91
91
93
93
95
97
97
98
99
100
101
101
102
103
105
105
106
108
108
109
110
110
112
113
135
150
152
160
197

80
81
82
84
83
85
87
88
89
90
91
92
93
94
95
96
98
197
99
100
450
102
105
103
104
106
108
107
109
350
110
111
112
113
114
35
1
52
67
101

LENGTH CONFIG.
CODE
(FT. 1

9
11

11
9
2
506
9
10
2
11
2

7
2
7
11
9

2
2
2
11
11
8
1
9
10
10
11
1
10
1

9
1

9
4
4
4
4
1
1
1
3
1
10
3
10
5
12
506
3
12
12
12
12
9
3
3
9
9
9
11
3
11

475.0
175.0
250.0
675.0
250.0
475.0
450.0
175.0
275.0
250.0
225.0
300.0
225.0
275.0
300.0
200.0
275.0
0.0
550.0
300.0
800.0
225.0
275.0
325.0
700.0
225.0
325.0
575.0
450.0
1000.0
300.0
575.0
125.0
525.0
325.0
375.0
400.0
400.0
350.0
250.0

6
6
6
11
6
11
6
9
6
10
6
11
6
9
6
10
3
506
3
3
3
11
3
11
11
10
3
10
9
3
9
9
9
9
9
4
1
1
6
3

Table 5 gives the Overhead Line Configuration


Codes for this system.
Table 5

IEEE 1 2 3 BUS RADIAL DISTRIBUTION SYSTEM


OVERHEAD LINE CONFIGURATIONS
CONF
ID PHASING
1

2
3
4
5
6
7
8
9

11

10
11

6
3
6
6

A
C
B
C
B
A
A
A
A
B
C

_I--

B
A
C
B
A
C
C
B
N
N
N

C
B
A
A
C
B
N
N

N
N
N
N
N
N

PHASE
COND
ACSR
336,400
336,400
336,400
336,400
336,400
336,400
336,400
336,400
1/ 0
1/ 0
1/0

26/7
26/7
26/7
26/7
26/7
26/7
26/7
26/7

NEUTRAL
COND SPACING
ACSR
ID
4/0 6 / 1
4/0 6 / 1
4/0 6 / 1
4/0 6 / 1
4/0 6 / 1
4/0 6 / 1
4/0 6 / 1
4/0 6 / 1
1/0
1/0
1/0

500
500
500
500
500
500
505
505
510
510
510

T-

---

979

Addition Configuration Codes are:

512

Table 7

Three-phase
underground
1 ine
consisting
of three
1/0
copper
concentric
neutral
cables.
The
cables are spaced 6 inches apart on a
below
horizontal plane 40 inches
ground.
The
concentric
neutral
consists of 10-#14 copper conductors.
The outside diameter of the cable
(over the concentric neutral) is 0.97
inches.

506

3 -

a three-phase zero impedance switch


a

three-phase transformer rated:


150 kVA
4160 wye
480 delta volt
Z = 1.27 + j 2.72 %.

Table 6 gives the Shunt Capacitor


this system.

Data

for

Table 6

IEEE 123 BUS RADIAL DISTRIBUTION FEEDER


SHUNT CAPACITORS
BUS
NO.

PHASE A

PHASE B

KVAR

83
200.00
88
50.00
90
92
Total ***
250.00

***

Table 7
system

PHASE C

KVAR

KVAR

200.00

200.00

50.00

50.00
250.00

gives the Bus Load

250.00
Data

for

this

Table 7
IEEE 123 BUS RADIAL DISTRIBUTION SYSTEM
BUS LOADS AS K W AND KVAR
BUS LOAD
NO. MDL.
1
2
4
5

6
7
9
10
11
12
16
17
19
20
22
24
28
29
30
31
32
33
34
35
37
38

1
1

1
2
3
1
1
2
3
1
1
1
1
2
3
1
2
3
1
1
1
2
3
4
3
2

PH-1

PH-1

PH-2

PH-2

PH-3

PH-3

KW

KVAR

KW

KVAR

KW

KVAR

38.47
0.00
0.00
0.00
0.00
19.23
38.47
19.23
38.47
0.00
0.00
0.00
38.47
38.47
0.00
0.00
38.47
38.47
0.00
0.00
0.00
38.47
0.00
38.47
38.47
0.00

19.22
0.00
0.00
0.00
0.00
9.61
19.22
9.61
19.22
0.00
0.00
0.00
19.22
19.22
0.00
0.00
19.22
19.22
0.00
0.00
0.00
19.22
0.00
19.22
19.22
0.00

0.00
19.23
0.00
0.00
0.00

0.00
9.61
0.00
0.00
0.00

0.00

0.00

0.00

0.00
0.00
0.00
19.23
0.00
0.00
0.00
0.00
38.47
0.00
0.00
0.00

0.00
0.00
0.00
9.61
0.00
0.00
0.00
0.00
19.22
0.00
0.00
0.00

0.00
0.00
38.47
19.23
38.47
0.00
0.00
0.00

0.00
0.00

0.00
0.00
0.00
0.00

0.00

0.00
0.00
0.00
0.00
19.23

0.00
0.00

0.00
9.61

0.00
0.00
38.47
19.23
0.00
0.00
0.00
38.47
0.00
0.00
38.47
19.23
19.23
0.00
38.47
0.00
0.00
0.00

0.00
19.22
9.61
19.22
0.00
0.00
0.00
0.00
0.00
19.22
9.61
0.00
0.00
0.00
19.22
0.00
0.00
19.22
9.61
9.61
0.00
19.22
0.00
0.00
0.00

(continued)
IEEE 123 BUS RADIAL DISTRIBUTION SYSTEM
BUS LOADS AS K W AND KVAR
BUS LOAD
NO. MDL.
39
41
42
43
45
4
47
4
49
50
51
52
53
55
56
58
59
6
62
63
6
65
66
68
69
70
71
73
74
75
76
77
I9
8
82
83
84
85
86
87
88

1
1
1
3
2
6 1
2
8 3
1
1
1
1
1
3
1
2
1
0 1
3
1
4 2
6
1
1
1
1
1
1

3
1
5
1
3
1
1
1
1
1

90
92
94
95
96
98
99
100
102
103
104
106
107
109
111
112
113
114
*Total*

1
1
1
2
1
1
1

1
1
1
3
1
1
1
1
1
1
1
2
3
1

PH-1

PH-1

PH-2

PH-2

PH-3

PH-3

KW

KVAR

KW

KVAR

KW

KVAR

0.00
19.23
0.00
0.00
0.00
0.00
34.19
68.38
34.19
38.47
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
38.47
0.00
0.00
68.38
76.93
0.00
0.00
0.00
0.00
38.47
38.47
38.47
68.38
0.00
0.00
0.00
0.00
19.23
19.23
38.47
0.00
0.00
0.00
0.00
38.47
0.00
0.00
0.00
0.00
0.00
38.47
19.23
38.47
38.47
0.00
0.00
0.00
0.00
0.00
0.00
0.00

0.00
9.61
0.00
0.00
0.00
0.00
26.46
52.91
26.46
19.22
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
19.22
0.00
0.00
52.91
38.44
0.00
0.00
0.00
0.00
19.22
19.22
19.22
52.91
0.00

0.00
0.00
19.23
0.00
19.23
19.23
34.19
68.38
34.19
0.00
19.23
38.47
38.47
19.23
0.00
0.00
0.00
19.23
0.00
38.47
0.00
34.19
0.00
19.23
38.47
19.23
38.47
0.00
0.00
0.00
102.57
0.00
38.47
0.00
38.47
0.00
0.00
0.00
0.00
0.00
38.47
0.00
0.00
38.47
0.00
0.00
38.47
0.00
0.00
0.00
0.00
0.00
0.00
0.00
38.47
19.23
19.23
38.47
19.23

0.00
0.00
9.61
0.00
9.61
9.61
26.46
52.91
26.46
0.00
9.61
19.22
19.22
9.61
0.00
0.00
0.00
9.61
0.00
19.22
0.00
26.46
0.00
9.61
19.22
9.61
19.22
0.00
0.00
0.00
79.37
0.00
19.22
0.00
19.22
0.00
0.00
0.00
0.00
0.00
19.22
0.00
0.00
19.22
0.00
0.00
19.22
0.00
0.00
0.00
0.00
0.00
0.00
0.00
19.22
9.61
9.61
19.22
9.61

19.23
0.00
0.00
38.47
0.00
0.00
34.19
68.38
68.38
0.00
0.00
0.00
0.00
0.00
19.23
19.23
19.23
0.00
0.00
0.00
76.93
34.19
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
68.38
38.47
0.00
38.47
0.00
0.00
0.00
0.00
19.23
38.47
0.00
38.47
0.00
0.00
19.23
19.23
0.00
38.47
0.00
0.00
0.00
0.00
38.47
38.47
0.00
0.00
0.00
0.00
0.00

9.61
0.00
0.00
19.22
0.00
0.00
26.46
52.91
52.91
0.00
0.00
0.00
0.00
0.00
9.61
9.61
9.61
0.00
0.00
0.00
38.44
26.46
0.00
0.00
0.00
0.00
0.00
0.00

0.00
0.00
52.91
19.22
0.00
19.22
0.00
0.00
0.00
0.00
9.61
19.22
0.00
19.22
0.00
0.00
9.61
9.61
0.00
19.22
0.00
0.00
0.00
0.00
19.22
19.22
0.00
0.00
0.00
0.00
0.00

0.00
0.00
0.00
9.61
9.61
19.22
0.00
0.00
0.00
0.00
19.22
0.00
0.00
0.00

0.00
0.00
19.22
9.61
19.22
19.22
0.00
0.00

0.00
0.00
0.00
0.00
0.00

l**l*****l**ltt***I***l.**;;*****~********;;**;;***;;;;;;**

1369.85 759.43

888.98

519.17 1119.8

634.49

980

The voltage regulator data for the system is


as follows:

5.

Substation
a. Three-phase short circuit MVA and
angle at the high voltage terminals
of the substation transformer.
b. Substation transformer ratings and
impedance.
c. Substation transformer output
voltages

6.

In-line
autotransformer
converting
feeder voltage from 24.9 kV to 4.16 kV.

Regulator Id: 1
Bus A: 150
Bus B:
1
Bandwidth Setting: 2.0 volts
Three-phase, wye connected, compensator
monitoring Phase A
Phase A
PT Ratio
CT Rating
R-Setting
X-Setting
Voltage Level

20.0

700.0
3.0
7.5

The circuit diagram (not to scale) for


feeder is shown in Figure 3.

this

120.0
.............................................

Regulator Id: 2
Bus A:
9
Bus B: 14
Bandwidth Setting: 1.0 volts
Single-phase connected to Phase A

"B

Phase A
PT Ratio
CT Rating
R-Setting
X-setting
Voltage Level

20.0
50.0

0.4
0.4

120.0

Regulator Id: 3
Bus A: 25
Bus B: 26
Bandwidth Setting: 1.0 volts
Two single-phase connected A-N and C-N
PT Ratio
CT Rating
R-Setting
X-setting
Voltage Level

Phase A

Phase C

20.0
50.0
0.4
0.4
120.0

20.0
50.0
0.6
0.4
120.0

Regulator Id: 4
Bus A: 160
Bus B:
67
Bandwidth Setting: 2.0 volts
Three single-phase connected in wye
PT Ratio
CT Rating
R-Setting
X-setting
Voltage Level

Phase A

Phase B

20.0
300.0
0.6
1.3
124.0

20.0
300.0
1.4
2.6
124.0

Phase C
20.0

300.0
0.2

1.4
124.0

.............................................

Figure 3
IEEE 34 BUS RADIAL DISTRIBUTION FEEDER

The 34 bus test feeder is characterized by:


1.

2.

Load Types
a. Spot and distributed loads
b. All wye connected
c. All constant kW,kVAr
Line Types
a. Three-phase overhead
b. Single-phase overhead
(a-n, b-n and c-n)

3.

Voltage
Regulators
regulators wye connected

4.

Shunt Capacitors

34

Bus Circuit Diagram

The
substation transformer
feeder is rated:

serving

2 ,500 kVA
345 delta-24.9 grounded wye kV
z 3: 1.0 + j8.0 %

The three-phase short circuit MVA on the 345


kV bus of the substation is 1800 MVA at an
angle of 85 degrees.
The output voltages from the transformer
balanced three-phase of 1.03 per unit.

single-phase

- balanced three-phase

this

are

Table 8 gives the Line Section Data for this


system.

98 1

Table 8

T a b l e 10

IEEE 34 BUS RADIAL DISTRIBUTION SYSTEM


LINE SECTION DATA
BUS
A

BUS
B

800
802
806
808
808
812
814
816
816
818
820
824
824
828
830
832
832
834
834
836
836
842
844
846
850
852
854
854
858
858
860
8 62
888

802
806
808
810
812
814
850
818
824
820
822
826
828
830
854
858
888
860
842
840
862
844
846
848
816
832
856
852
864
834
836
838
890

IEEE 34 BUS RADIAL DISTRIBUTION FEEDER


SHUNT CAPACITORS

LENGTH CONFIG.
CODE
(FT.1
2580.0
1730.0
32230.0
5840.0
37500.0
29730.0
10.0
1710.0
10210.0
48150.0
13740.0
3030.0
840.0
20440.0
520.0
4900.0

301
301
301
303
301
301
301
302
301
302
302
303
301
301
301
301
55
301
301
301
301
301
301
301
301
301
303
301
302
301
301
304
300

0.0

2020.0
280.0
860.0
280.0
1350.0
3640.0
530.0
310.0
10.0
23330.0
36830.0
1620.0
5830.0
2680.0
4860.0
10560.0

B
B
A
B
A

A C N
A C N
N
N
N

1/ 0
#2 6/1
#4 6/1
#4 6/1
#2 6/1

844
848

100.00
150.00

100.00
150.00

100.00
150.00

250.00

250.00

Total

........................

gives the Bus Load Data

for this

IEEE 34 BUS RADIAL DISTRIBUTION SYSTEM


BUS LOADS AS K W AND KVAR
BUS LOAD
NO. MDL.
860
840
844
848
890
** Total

PH-1

PH-1

PH-2

PH-2

PH-3

PH-3

KW

KVAR

KW

KVAR

KW

KVAR

15.94
7.09
106.83
15.57
21.62

19.91
8.86
133.44
19.45
27.00

15.94
7.09
106.83
15.57
21.62

167.05

208.66

167.05

19.91
8.86
133.44
19.45
27.00

19.91 15.94
7.09
8.86
133.44 106.83
19.45 15.57
27.00 21.62

1
1
1
1

t*****titt*b*****b**t*t***l*t*.***tt*...*bb**

208.66 167.05

208.66

Table 12 gives the Line Section Distributed


Loads.
T a b l e 12

500

500
510
510
510

IEEE 34 BUS RADIAL DISTRIBUTION FEEDER


LINE SECTION DISTRIBUTED LOADS
BUS BUS LOAD
A B MDL.
802
808
818
820
816
824
824
828
854
832
858
858
834

806
810
820
822
824
826
828
830
856
858
864
834

836
862
842
844
846

840
838
844
846
848

860
860 836

Addition Configuration Codes are:


55

KVAR

PHASE C

T a b f e 11

NEUTRAL
COND SPACING
ACSR
ID
1/0
#2 6/1
#4 6/1
#4 6/1
#2 6/1

WAR

Table 11
system.

Table 9

300
301
302
303
304

PHASE B

250.00

IEEE 34 BUS RADIAL DISTRIBUTION SYSTEM


OVERHEAD LINE CONFIGURATIONS
PHASE
COND
ACSR

PHASE A
KVAR

***

Table 9 gives the Overhead Line Configuration


Codes or this system.

CONF
ID PHASING

BUS
NO.

In-line three-phase grounded wye


grounded wye connected autotransformer
rated:
150 kVA
24.9 delta
4.16 wye kV
Z = 1.90 + j4.08 per unit

1
1

1
1
1

1
1
1
1
1
1
1
1
1
1
1
1
1

PH-1

PH-1

K W KVAR
0.00
0.00
33.90
135.53
0.00
0.00
0.00
6.18

0.00
6.68
0.63
3.99
15.66
27.37
17.49
27.61
9.12
0.00

0.00
0.00
17.52
70.07
0.00
0.00
0.00
3.20
0.00
3.45
0.33
2.06
8.09
14.15
9.04
14.27
4.71
0.00

PH-2

PH-2

PH-3

PH-3

K W KVAR K W

KVAR

31.22 16.14 26.07


15.88 8.21 0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.39
0.20
0.00
41.93 21.68 0.00
0.00 0.00
2.78
0.00
0.00 0.00
3.71
1.92 0.00
1.08 0.56
5.35
0.00 0.00
0.00
12.55 6.49 12.82
20.86 10.78 111.15
10.55 5.45 42.05
21.81 11.27 0.00
0.00 0.00
0.00
0.00 0.00
0.00
24.59 12.71 22.23

13.48
0.00
0.00
0.00
0.00
0.00
1.44
0.00
0.00
2.77
0.00
6.63
57.46
21.74
0.00
0.00
0.00
11.49

Table 10 gives the Shunt Capacitor


this system.

Data

for

The voltage regulator data for the feeder


as follows:

is

982

Regulator Id: 1
Bus A: 814
Bus B: 850
Bandwidth Setting: 2.0 volts
Three single-phase connected in wye
Phase A
120.0

PT Ratio
CT Rating
R-Setting
X-Setting
Voltage Level

Phase B
120.0
100.0
7.4
4.2
124.0

100.0

4.2
6.2
124.0

b.
c.
Phase C
120.0
100.0
9.6

4.6
124-0

-____-_^__--__--__---------------------------

Phase A
120.0
100.0
2.1
1.2
124.0

Phase B
120 * 0
100.0
2.1
1.2
124.0

and

6. Motor
a. step-down transformer
b. Starting kVA and power factor given
c. Running power factor
The
substation
feeder is rated:

Regulator Id: 2
Bus A: 852
Bus B: 832
Bandwidth Setting: 2.0 volts
Three single-phase connected in wye
PT Ratio
CT Rating
R-Setting
X-Sett ing
Voltage Level

Substation transformer ratings


impedance.
Substation transformer output
voltages

transformer

serving

this

5,000 kVA
115 delta-4.16 grounded wye kV
Z = 1.0 + j8.0 %
Phase C
120.0
100.0
2.1
1.2
124.0

IEEE 13 BUS RADIAL DISTRIBUTIO# FEEDER


The circuit diagram (not to scale) for
feeder is shown in Figure 4 .

this

The three-phase short circuit MVA on the 115


kV bus of the substation is 1100 MVA at an
angle of 82 degrees.
The output voltages from the transformer
balanced three-phase of 1.00 per unit.

are

A 500 horsepower induction motor is located


at Bus 34. The starting kVA is assumed to be
6 times rated kVA at a 0 . 4
lagging power
factor. The running power factor is 0.8 lag.
Table 13 gives the Line Section Data for this
system.
T a b l e 13

IEEE 13 BUS RADIAL DISTRIBUTION SYSTEM


LINE SECTION DATA
BUS
A

32
33
33
45
50
52

Figure 4

71
71
71
75
84
92

- 13 Bus Circuit Diagram

The 13 bus test feeder is characterized by:


1. Load Types
a. Spot and distributed loads
b. Wye and delta connected
c. Mixture of constant kW,kVAR,
constant Z and constant I.

BUS
B

LENGTH
(FT.)

CONFIG.
CODE

45
32
34
46
32
84
32
84
150
92
911
71

500.0
500.0

503
502
507
503
501
509
501
504
501
508

0.0

300.0
2000.0
800.0
2000.0
300.0
1000.0
500.0
300.0

505
506

0.0

Table 14 gives the Overhead Line Configuration


Codes for this system.
Table 14

2. Line Types
a. Three-phase overhead & underground
b. Single-phase overhead & underground

3. Voltage
Regulators
regulators wye connected
4.

IEEE 13 BUS RADIAL DISTRIBUTION SYSTEM


OVERHEAD LINE CONFIGURATIONS

single-phase

shunt Capacitors
a. Balanced three-phase
b. Single-phase

5. Substation
a. Three-phase short circuit W A and
angle at the high voltage terminals
of the substation transformer.

CONF
ID
501
502
503
504
505

PHASING
B
C
C
A
C

A
A
B
C
N

C N
B N
N
N

PHASE
COND
ACSR
556,500 26/7
4/0 6/1

NEUTRAL
COND SPACING
ACSR
ID
4/0

6/1

I/ 0

4/0 6/1
I/ 0

1/ 0
1/ 0

1/ 0
1/ 0

500
500
505
505
510

Table 17

Additional Configuration Codes are:


506
507

IEEE 13 BUS RADIAL DISTRIBUTION SYSTEM


BUS LOADS AS KW AND KVAR

Three-phase, zero impedance switch


Step
down
rated:

three-phase

transformer

32 71
*TOT&

500 kVA
4160 delta - 480 wye volts
Z = 1.1 + j2.0%

PH-1 PH-1
KW KVAR
16.48

A
single-phase
l
(
0
copper
tape
shielded conductor with a separate 1/0
copper bare peutral. The cable and
bare neutral are buried 40 inches
below ground with a 1.0 inch spacing
between centers.

9.45

PH-2 PH-2 PH-3 PH-3


KW KVAR KW KVAR

66.40 38.06 116.97

67.05

**8*8tli88t8**88***88888*88*88*8**l.****8*******88***8*

16.48

underground
508 - Three-phase
1ine
consisting of three 250,000 CM, AL
concentric
neutral
cables.
The
cables are spaced 6 inches apart on a
horizontal
plane 40 inches
below
ground.
The
concentric
neutral
consists of 13-#14 copper conductors.
The outside diameter of the cable
(over the concentric neutral) is 1.28
inches.
509

BUS BUS LOAD


A B MDL

9.45

66.40 38.06 116.97

67.05

The voltage regulator data for the feeder


as follows:

is

Regulator Id: 1
Bus A: 50
Bus B: 32
Bandwidth Setting: 2.0 volts
Three single-phase connected in wye
PT Ratio
CT Rating
R-Setting
X-Setting
Voltage Level

Phase A
20.0
700.0
3.0
9.0
122.0

Phase B
20.0
700.0
3.0
9.0
122.0

Phase C
20.0
700.0
3.0
9.0
122.0

IEEE 37 BUS DELTA RADIBL DISTRIBUTION FEEDER

Table 15 gives the Shunt Capacitor Data


this system.

for
The circuit diagram (not to scale) for
feeder is shown in Figure 5.

this

Table 15

IEEE 13 BUS RADIAL DISTRIBUTION FEEDER


SHUNT CAPACITORS
BUS
NO.

PHASE A

75
911

200.00

***

KVAR

Total . . .
200.00

PHASE B
KVAR

PHASE C
KVAR

200.00

200.00
100.00

. . . . . . . . . . . . . . . . . .

200.00

Table 16 gives the Bus Load


system.

300.00
Data

for

this

Table 16
IEEE 13 BUS RADIAL DISTRIBUTION SYSTEM
BUS LOADS AS KW AND KVAR
BUS LOAD
NO. MDL.

PH-1
KW

34
45
46
52
71
75
92
911
*Total

42.63 20.18
0.00
0.00

1
1
6
3
4
1
5
2

0.00

PH-1
KVAR

0.00

127.90 85.79
383.70 219.95
486.02 189.07
0.00 0.00
0.00 0.00

PH-2
KW
0.00

PH-2
KVAR
0.00

170.53
230.22
0.00
383.70
68.21

125.09
131.97
0.00
219.95
60.55

0.00
0.00

0.00
0.00

PH-3
KW

PH-3
KVAR

0.00
0.00
0.00

0.00
0.00

0.00
383.70
289.91
170.53
170.53

.:-

0.00
0.00
219.95
212.65
151.38
80.74

8*8*8*88*8888*88*88*i**8***888*8**88*88***88**88***88*:8

1040.25 514.99

Table
Loads.

852.66

537.56 1014.67

17 gives the Line Section

664.72

Distributed

Figure 5

37 BUS Delta Circuit Diagram

984

T a b l e 18

The 37 bus delta test feeder is characterized


by :
1.

2.

IEEE 37 BUS DELTA RADIAL DISTRIBUTION SYSTEM


LINE SECTION DATA

Load Types
a. Delta connected spot loads
b. Mixture of constant kW,kVAR,
constant 2 and constant I.

Line Types
underground

All

three-phase

(conthued)

voltage
Regulators
single-phase
regulators open-delta connected

4.

No Shunt Capacitors

5.

Substation
a. Three-phase short circuit MVA and
angle at the high voltage terminals
of the substation transformer.
b. Substation transformer ratings and
impedance.
c. Substation transformer output
voltages

6.

Motor
a. Step-down transformer
b. Starting kVA and power factor given
c. Running power factor

2 ,500 kVA
230 delta-4.8 delta
Z = 2.0 + j8.0 %

BUS
B

LENGTH
(FT.)

CONFIG.
COPE

8
9
9
10
10
11
11
13
14
20
20
27
30
33
34
34
37
38
44
44
75
99

32
31
8
35
36
41
40
4
18
7
6
44
9
34
37
10
38
11
28
29
9

320.0
600.0
320.0
200.0
1280.0
400.0
200.0
520.0
520.0
920.0
600.0
280.0
200.0
560.0
640.0
520.0
400.0

325
323
323
325
325
323
325
323
325
325
323
325
323
323
323
325
323
323
325
325
10
321

delta

3.

The
substation transformer
feeder is rated:

BUS
A

serving

this

400.0

200.0
280.0
1.0
1850.0

Table
19
gives
the
Underground
Configuration Codes for this system.

Line

kV
T a b l e 19

The three-phase short circuit MVA on the 230


kV bus of the substation is 1100 MIA at an
angle of 82 degrees.
The output voltages from the transformer
balanced three-phase of 1.00 per unit.

IEEE 37 BUS DELTA RADIAL DISTRIBUTION SYSTEM


UNDERGROUND LINE CONFIGURATIONS
PHASE
COND

are

A 500 horsepower induction motor is located


at Bus 75. The starting kVA is assumed to be
6 times rated kVA at a 0.4 lagging power
factor. The running power factor is 0.8 lag.
Table 18 gives the Line Section Data for this
system.

CONF
ID
PHASING
321
322
323
325

A
A
A
A

B C
B C
B C
B C

AA

1000 KCM
500 KCM
2/0
#2

CONCENTRIC
NEUTRAL
COPPER
20
16
7
10

#lo
#12
#14
#14

SPACING
ID #
321
322
323
325

Table 20 gives the phase spacings for the


underground configurations.

T a b l e 18

T a b l e 20

IEEE 37 BUS DELTA RADIAL DISTRIBUTION SYSTEM


LINE SECTION DATA
BUS
A

BUS
B

LENGTH
(FT.)

CONFIG.
CODE

1
2
2
2
3
3
4
4
5
5
6
7
7
8

2
5
13
3
27
30
14
20
42
12
25
24
22
33

960.0
400.0
360.0
1320.0
240.0
600.0
80.0
800.0
320.0
240.0
280.0
760.0
120.0
320.0

322
325
323
322
325
323
325
323
325
325
325
325
325
323

IEEE 37 BUS DELTA RADIAL DISTRIBUTION SYSTEM


UNDERGROUND LINE SPACING
SPACING
ID
321
322
323
325

A-B
B-C
C-A
(Inch) (Inch) (Inch)
2.074
1.603
1.146
1.030

2.074
1.603
1.146
1.030

2.060
1.570
1.120
0.970

Additional Configuration Codes are:


10

Three-phase
500 kVA

transformer rated:

4,800 delta
480 delta volts
= 0.85 + jl.81 %

985

Table 21 gives the Bus Load


system.

Data

for this

Table 21
IEEE 37 BUS DELTA RADIAL DISTRIBUTION SYSTEM
BUS LOADS AS K W AND KVAR
BUS LOAD
NO. MDL

PH-1

PH-1

PH-2

PH-2

PH-3

PH-3

KW

KVAR

KW

KVAR

KW

KVAR

69.74 350.75
1
4
140.47 69.74 140.47
0.00
84.11
0.00
0.00
0.00
12
4
0.00
84.11
0.00
13
4
0.00 0.00
10.44
0.00
14
5
16.82 8.35
21.03
0.00
0.00
0.00
18
6
84.11 41.76
0.00
84.11
0.00
0.00
0.00
20
4
69.74
21.03
22
5
0.00 0.00 140.47
0.00
20.88
42.06
24
6
0.00 0.00
0.00
42.06
20.88
25
4
0.00 0.00
0.00 0.00
0.00
0.00
42.06
21
4
20.88
42.06
42.06
28
4
42.06 20.88
0.00
0.00
0.00
29
5
4B.06 20.88
0.00 0.00
0.00
0.00
84.11
30
6
41.76
0.00
0.00
84.11
31
6
0.00
0.00
0.00
42.06
0.00
0.00
32
4
0.00
0.00
0.00
33
5
84.11 41.76
0.00
42.06
34
4
0.00
0.00
0.00
0.00
0.00
84.11
0.00 0.00
35
4
20.88
0.00
0.00
0.00
42.06
36
6
37
5
140.47 69.74
0.00
0.00
0.00
0.00
0.00
38
4
126.17 62.64
0.00
0.00
84.11
40
4
0.00
0.00
0.00
42.06
0.00 0.00
0.00
0.00
41
5
0.00
42
6
8.41 4.18
84.11
41.76
4 4 4
42.06 20.88
0.00
0.00
0.00
*Total * * * * * * * i * * * t * * * i i * * t I . * * . i * * * t * * . . * * t . l * * * * * * * * * *
726.74 360.81 638.43 316.% 1086.74

174.!5
41.76
41.76
0.00
0.00
41.76
10.44
0.00
0.00
20.88
20.88
0.00
41.76
0.00
20.88
0.00
20.88
41.76
0.00
0.00
0.00
41.76
20.88
0.00
0.00
539.55

The voltage regulator data for the feeder


as follows:

is

Regulator Id: 1
Bus A: 99
Bus B: 1
Bandwidth Setting: 2.0 volts
Two single-phase connected in open-delta
compensator controlled
Phase A
PT Ratio
CT Rating
R-Setting
X-setting
Voltage Level

Phase C

40.0

40.0

350.0

350.0
1.0
0.4
122.0

0.2
0.9

122.0
CONCLUSIONS

The
complete data
for
four
radial
distribution feeders has been
presented.
Developers of radial distribution analysis
programs are encouraged to use these feeders
to test their programs and to compare the
results with the results from other programs.

W. H. Kerstinq (SM'64-Fellow'89) was born in


Santa Fe, New Mexico. He received the BSEE
degree from New Mexico State University and
the MSEE degree from Illinois Institute of
Technology.
He joined the faculty at New Mexico
State University in 1962 and is currently
Professor of Electrical Engineering and
Director of the Electric Utility Management
Program at New Mexico State University.
Prior to joining NMSU, he was employed as a
distribution engineer by El Paso Electric
Company.
Prof. Kersting is a member of Eta Kappa
Nu and Tau Beta Pi. He has been an active
member of the IEEE Power Engineering
Society's
Power Engineering Education
Committee serving as Chairman of the
committee and several subcommittees.