These instructions show how NPS 24kV switch disconnectors with epoxy resin insulators can be mounted as transformer or line disconnectors in one or two pole substations. Line disconnector or horizontal mounting is demonstrated foremost. Also other mounting alternatives are possible. The crossarm is 80 x 80 mm or 100 x 100 mm RHS-beam.
Do not attempt to handle, install, use or service this product before reading this installation guide.
This product is intended to be installed, operated and maintained by qualified personel, thoroughly trained and knowledgeable with the regards of the hazards involved. This publication is written only for such qualified persons and is not intended to be a substitute for adequate training and experience in the safety procedures for this device. Warning Detailed descriptions of standard repair procedures, safety principles, and service operations are not included. It is important to note that this document contains some warnings and cautions against some specific service methods that could cause personal injury to service personnel, or could damage equipment or render it unsafe. These warnings do not cover every conceivable method in which service (whether or not recommended by ABB) may be performed. Secondly, ABB cannot predict or investigate all potential hazards resulting from all conceivable service methods. Anyone using service procedures or tools, whether or not recommended by ABB, must satisfy himself thoroughly that neither personal safety nor equipment safety will be jeopardized by the service method or tools selected. All information contained in this manual ris based on the latest product information available at the time of printing. The right is reserved to make changes at any time without notice.
Safety Notices Must always follow the directions in the manual and good engineering practice. Dangerous voltage can cause electric shock and burns. Do not perform any activity described in this document with the switch energized. ALWAYS follow your companys or countrys Safety procedures before performing any work on this equipment. NPS outdoor switch disconnector should be installed only within the design limitation. All the activities listed on this document it must be performed with the switch completely de-energized, isolated, grounded and out of service. Must be observed appropriate guidance given in the manuals for all operations performed on the apparatus.
Dimensions drawing
Transformer disconnector, vertical mounting, single pole installation. 1950 min. 300 max. 640 min. 300
UEKE 3_1
Transformer disconnector, vertical mounting, double pole installation. 1900 200 A min. 300 600
UEKE 3_1
A
NPS switch 24kV with epoxy insulators 3
Line disconnector, horizontall mounting, single pole installation. 460 260 720
60
UEKE 3_1
750
Crossarm
80 x 80 mm 100 x 100 mm
(14 mm *)
56 mm
(14 mm *)
(14 mm *) 56 mm
56 mm
M8 15 Nm
M12 50 Nm
6. (Mount the operating lever, two pole mounting) Tighten the screws
M12 50 Nm
Before tightening the screws: a) Push the contact arm upwards. b) Push the spring support downwards. c) Check the mechanical function.
min. 10
M8 20 Nm ~5
6 1
4 5 7 8
3
With mounting equipment OJUP-ZK 9
14 13 10 11 12
M12 35 Nm
M12 35 Nm
Join the upper rod to the lever (cut the rod if needed)
750
Fix the rod guides Note. No bending stress on the rod isolator
14 NPS switch 24kV with epoxy insulators
750
max . 12
Installation guide of manual operating device or motor operating device comes with the operating device.
min. 10 ~5 ~
max . 12
min. 10 ~5 ~
) 0* 20 n. mi
) 0* 20 n. mi
min. 35
55 Nm max. 5
min. 320
min. 320 min. 360 min. 360 min. 320 min. 360 min. 360 min. 320 min. 320 min. 360 min. 360
min. 320
min. 320
control lever
(160 )
(160 ) (160 )
min . 27 0 180
DETAIL 80 1A
0
180 18 DETAIL A
min . 27 0
min . 27 0 min . 27 0
DETAIL A DETAIL A
90
UEKE 3
DETAIL B 90
90 90
DETAIL B
NPS switch 24kV with epoxy insulators 17
DETAIL B DETAIL B
min. 320
min. 360 min. 360 min. 320 min. 320 min. 360 min. 360
min. 320
control lever
(160 )
min . 27 0
160
DETAIL A
DETAIL A
R110
control cabinet
min. 320
min. 320
min. 360
min. 360
min. 320
min. 320
min. 320
min. 360
min. 320
min. 270
min. 270
(160)
180 180
control lever control lever control lever
180
R222 R222
control cabinet control cabinet
R222
control cabinet
DETAIL B DETAIL B
DETAIL B
NPS switch 24kV with epoxy insulators 19
For more information please contact: ABB Sp. z o.o. Branch in Przasnysz 59 Leszno Str. 06-300 Przasnysz, Poland Phone: +48 29 75 33 000 Fax: +48 29 75 33 327 www.abb.pl
We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB.