Driver Manual
(Supplement to the FieldServer Instruction Manual)

FS-8700-14 GE Mark IV Speedtronic

APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after April 2010

Driver Version: Document Revision:

1.00 7

FS-8700-14 GE Mark IV Speedtronic

Table of Contents

TABLE OF CONTENTS
1 2 3 4 5 GE Mark IV Speedtronic Description .............................................................................................................. 3 Driver Scope of Supply ................................................................................................................................... 3 2.1 Supplied by FieldServer Technologies for this driver .....................................................................................3 Hardware Connections ................................................................................................................................... 4 Data Array Parameters ................................................................................................................................... 5 Configuring the FieldServer as a GE Mark IV Speedtronic Passive Client ........................................................ 6 5.1 Client Side Connection Descriptions ..............................................................................................................6 5.2 Client Side Node Descriptors .........................................................................................................................7 5.3 Client Side Map Descriptors...........................................................................................................................7 5.3.1 FieldServer Related Map Descriptor Parameters ...................................................................................7 5.3.2 Driver Related Map Descriptor Parameters ...........................................................................................7 5.3.3 Map Descriptor Example. .......................................................................................................................8

Appendix A. Reference .......................................................................................................................................... 9 Appendix A.1. Driver Point List ..................................................................................................................................9

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

FS-8700-14 GE Mark IV Speedtronic Driver Manual

Page 3 of 13

GE MARK IV SPEEDTRONIC DESCRIPTION

The GE Mark IV Speedtronic driver allows the FieldServer to receive status data from Speedtronic devices over either RS-232 or RS-485 using GE Mark IV Speedtronic protocol. The Driver acts as a Passive Client and receives status data from Speedtronic devices. Note that only Digital values are supported. Max Nodes Supported FieldServer Mode Passive Client Nodes 1-10 (max) Comments The max number of nodes is limited by the amount of physical ports on the FieldServer.

2 2.1

DRIVER SCOPE OF SUPPLY Supplied by FieldServer Technologies for this driver


Description UTP Cable (7-Foot) For RS-232 Use RJ45 To DB25F Connection Adapter (8915-04) Driver Manual.

FieldServer Technologies PART # FS-8915-10 FS-8917-09 FS-8700-14

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

FS-8700-14 GE Mark IV Speedtronic Driver Manual

Page 4 of 13

HARDWARE CONNECTIONS

Configure the GE Mark IV Speedtronic according to manufacturers instructions The FieldServer is connected to the GE Mark IV Speedtronic as shown below.

P1

GE MKIV Speedtronic #1

FieldServer
R2 GE MKIV Speedtronic #10 Connection pinouts to be inserted

(408)-262-2299

GE MARK IV SPEEDTRONIC CONNECTION DIAGRAM


BASE NAME: FILE NAME: DATE: 01/05/03 BY: MF

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

FS-8700-14 GE Mark IV Speedtronic Driver Manual

Page 5 of 13

DATA ARRAY PARAMETERS

Data Arrays are protocol neutral data buffers for storage of data to be passed between protocols. It is necessary to declare the data format of each of the Data Arrays to facilitate correct storage of the relevant data. Section Title Data_Arrays Column Title Data_Array_Name

Function Provide name for Data Array Provide data format. Each Data Array can only take on one format. Number of Data Objects. Must be larger than the data storage area required by the Map Descriptors for the data being placed in this array.

Data_Array_Format

Legal Values Up to 15 alphanumeric characters FLOAT, BIT, UInt16, SInt16, Byte. 1-10, 000

Data_Array_Length

Example // Data Arrays Data_Arrays Data_Array_Name GE_Status_Data

, Data_Array_Format , Byte

, Data_Array_Length , 253

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

FS-8700-14 GE Mark IV Speedtronic Driver Manual

Page 6 of 13

CONFIGURING THE FIELDSERVER AS A GE MARK IV SPEEDTRONIC PASSIVE CLIENT

For a detailed discussion on Fieldserver configuration, please refer to the Fieldserver Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See .csv sample files provided with the FieldServer). This section documents and describes the parameters necessary for configuring the Fieldserver to communicate with GE Mark IV Speedtronic devices. The configuration file tells the Fieldserver about its interfaces, and the routing of data required. In order to enable the Fieldserver for GE Mark IV Speedtronic communications, the driver independent Fieldserver buffers need to be declared in the Data Arrays section, the destination device addresses need to be declared in the Client Side Nodes section, and the data required from the servers needs to be mapped in the Client Side Map Descriptors section. Details on how to do this can be found below. Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

5.1

Client Side Connection Descriptions

Section Title Connections Column Title Port Protocol Baud* Parity* Data_Bits* Stop_Bits* Poll_Delay* Example //

Function Specify which port the device is connected to the Fieldserver Specify protocol used Specify baud rate Specify parity Specify data bits Specify stop bits Time between internal polls

Legal Values P1-P8, R1-R2


1

GE MKIV 300; 1200; 2400; 4800; 9600; 19200; 28800; 38400 Even 8 1 0-32000s, 1.0s

Client Side Connections

Connections Port , Protocol P1 , GE MKIV

, Baud , 9600

, Parity , Even

, Poll_Delay , 0.100s

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

FS-8700-14 GE Mark IV Speedtronic Driver Manual

Page 7 of 13

5.2

Client Side Node Descriptors

Section Title Nodes Column Title Node_Name Protocol Port Example

Function Provide name for node Specify protocol used Specify which port the device is connected to the Fieldserver

Legal Values Up to 32 alphanumeric characters GE MKIV 2 P1-P8, R1-R2

// Client Side Nodes Nodes Node_Name GE_Node_1

, Protocol , GE MKIV

, Port , P1

5.3

Client Side Map Descriptors

5.3.1 FieldServer Related Map Descriptor Parameters


Column Title Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Function Name of this Map Descriptor Name of Data Array where data is to be stored in the Fieldserver Starting location in Data Array Function of Client Map Descriptor Legal Values Up to 32 alphanumeric characters One of the Data Array names from Section 4. 0 to (Data_Array_Length-1) as specified in Section 4. Passive

5.3.2 Driver Related Map Descriptor Parameters


Column Title Node_Name Length Address Function Name of Node to fetch data from Length of Map Descriptor Starting address of read block Legal Values One of the Node names specified in Section 5.2 253 1

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

FS-8700-14 GE Mark IV Speedtronic Driver Manual

Page 8 of 13

5.3.3 Map Descriptor Example.


// Client Side Map Descriptors Map_Descriptors Map_Descriptor_Name Status_Data_1

, Data_Array_Name , GE_Status_Data

, Data_Array_Offset ,0

, Function , Passive

, Node_Name , GE_Node_1

, Address ,1

, Length , 253

Use any descriptive name.

Received status data will be stored in this data array. Must be previously declared in Section 4.

Received data will be stored in the data array starting at this offset. Use zero to store data from the very first data array location.

This driver can only be used as a passive client listening for Speedtronic status data.

This Map Descriptor will only respond to the node settings defined under the Section 5.2.

The starting address of received data to be stored must always start at 1 for this driver, since received data is always a complete dump of all statuses.

The length of the data this Map Descriptor will store. The complete status dump from the Speedtronic is 253 bytes long.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

FS-8700-14 GE Mark IV Speedtronic Driver Manual

Page 9 of 13

Appendix A. Reference

Appendix A.1. Driver Point List


Byte No. Signal Description Zero Pt. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Maximum Units Bytes

Miscellaneous Points 1 TIME 2 TIME 3 TIME 4 TIME 5 TIME 6 TIME 7 TIMR-01 11 TIMR-02 15 CNTR-01 19 CNTR-02 23 CNTR-03 27 CNTR-04 31 CNTR-05 Integer Points 35 TTX01-1 37 TTX01-2 39 TTX01-3 41 TTX01-4 43 TTX01-5 45 TTX01-6 47 TTX01-7 49 TTX01-8 51 TTX01-9 53 TTX01-10 55 TTX01-11 57 TTX01-12 59 TTX01-13 61 TTX01-14 63 TTX01-15 65 TTX01-16 67 TTX01-17 69 TTX01-18 71 TTXC 73 CTIF-1 75 CTIF-2 77 CTDA-1 79 CTDA-2 81 TTWS1FI1 83 TTWS1FI2 85 TTWS1FO1 87 TTWS1FO2 89 TTWS1FA1 91 TTWS1FA2

SECONDS MINUTES HOUR DAY MONTH YEAR TOTAL FIRED HOURS MANUALLY INIT STARTS PEAK FIRED HOURS TOTAL STARTS FAST LOAD STARTS FIRED STARTS TRIPS EXHAUST TEMPERATURE TC = 1 EXHAUST TEMPERATURE TC = 2 EXHAUST TEMPERATURE TC = 3 EXHAUST TEMPERATURE TC = 4 EXHAUST TEMPERATURE TC = 5 EXHAUST TEMPERATURE TC = 6 EXHAUST TEMPERATURE TC = 7 EXHAUST TEMPERATURE TC = 8 EXHAUST TEMPERATURE TC = 9 EXHAUST TEMPERATURE TC = 10 EXHAUST TEMPERATURE TC = 11 EXHAUST TEMPERATURE TC = 12 EXHAUST TEMPERATURE TC = 13 EXHAUST TEMPERATURE TC = 14 EXHAUST TEMPERATURE TC = 15 EXHAUST TEMPERATURE TC = 16 EXHAUST TEMPERATURE TC = 17 EXHAUST TEMPERATURE TC = 18 EX TEMP AVG LOW'S - HIGH AND LOW REJECTED COMP INLET FLANGE TEMP 1 COMP INLET FLANGE TEMP 2 COMP DISCHARGE TEMP 1 COMP DISCHARGE TEMP 2 TURB WHEELSPACE TEMP 1ST STG FWD INNER TURB WHEELSPACE TEMP 1ST STG FWD INNER TURB WHEELSPACE TEMP 1ST STG FWD OUTER TURB WHEELSPACE TEMP 1ST STG FWD OUTER TURB WHEELSPACE TEMP 1ST STG AFT OUTER TURB WHEELSPACE TEMP 1ST STG AFT OUTER

59 59 24 9 12 99 9999999.9 9999999.9 9999999.9 9999999.9 9999999.9 9999999.9 9999999.9 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F

1 1 1 1 1 1 4 4 4 4 4 4 4 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

FS-8700-14 GE Mark IV Speedtronic Driver Manual


Byte No. 93 95 97 99 101 103 105 107 109 111 113 115 117 119 121 123 125 127 129 131 133 135 137 139 141 143 145 147 149 151 153 155 157 159 161 163 165 167 169 171 173 175 177 179 181 183 185 187 189 Signal TTWS2FO1 TTWS2FO2 TTWS2AO1 TTWS2AO2 TTWS3FO1 TTWS3FO2 TTWS3AO1 TTWS3AO2 TTXSPL TTXSP1 TTXSP2 LTTH1 LTB1D LTB2D LTBT1D BTLG1 BTLG2 BTLG3 BTLG4 BTLG5 BTGJ11 BTGJ21 BB1 BB2 BB4 BB5 BB7 BB8 BB9 BB-MAX PN TNH TNR FSR1 FSR2 CPD FPCI TTRXB CSRGV CSGV FOROUT FO FSROUT FSG FPRG FSGR DW SVL SFL Description TURB WHEELSPACE TEMP 2ND STG FWD INNER TURB WHEELSPACE TEMP 2ND STG FWD INNER TURB WHEELSPACE TEMP 2ND STG AFT OUTER TURB WHEELSPACE TEMP 2ND STG AFT OUTER TURB WHEELSPACE TEMP 3RD STG FWD INNER TURB WHEELSPACE TEMP 3RD STG FWD INNER TURB WHEELSPACE TEMP 3RD STG AFT OUTER TURB WHEELSPACE TEMP 3RD STG AFT OUTER COMBUSTION MONITOR ALLOWABLE SPREAD COMBUSTION MONITOR ACTUAL SPREAD 1 COMBUSTION MONITOR ACTUAL SPREAD 2 LUBE TEMP TURBINE HEADER, GT/GG LUBE TEMP NO. 1 TURB. BRG. DRAIN LUBE TEMP NO. 2 TURB. BRG. DRAIN LUBE TEMP NO. 1 THRUST BRG. DRAIN BEARING METAL TEMP LEAD GEAR =1 BEARING METAL TEMP LEAD GEAR =2 BEARING METAL TEMP LEAD GEAR =3 BEARING METAL TEMP LEAD GEAR =4 BEARING METAL TEMP LEAD GEAR =5 BEARING METAL TEMP GEN. JOURNAL =1 BEARING METAL TEMP GEN. JOURNAL =2 VIBRATION TRANSDUCER = 1 VIBRATION TRANSDUCER = 2 VIBRATION TRANSDUCER = 4 VIBRATION TRANSDUCER = 5 VIBRATION TRANSDUCER = 7 VIBRATION TRANSDUCER = 8 VIBRATION TRANSDUCER = 9 VIBRATION MAX SELECT TURBINE STARTING DEVICE SPEED TURBINE SPEED HP SPEED CONTROL REFERENCE LIQUID FUEL STROKE REF. FROM FUEL SPLITTER GAS FUEL STROKE REF. FROM FUEL SPLITTER COMPRESSOR DISCHARGE PRESSURE INTERVALVE PRESSURE SPEED BIASED TEMPERATURE CONTROL REF. VIGV REFEENCE ANGLE INLET GUIDE VANE ANGLE (SCALED) LIQUID FUEL FLOW REFERENCE LIQUID FUEL FLOW GAS CONTROL VALVE POSITION REFERENCE GAS CONTROL VALVE LVDT POSITION GAS RATIO VALVE CONTROL PRESS REF. SPEED RATIO VALVE CALIBR. POS. GENERATOR LOAD SYSTEM LINE VOLTAGE SYSTEM LINE FREQUENCY Zero Pt. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0.00 0 0.00 Maximum 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 8 8 8 8 8 8 8 8 125 125 125 100 100 2048 2048 2048 100 100 10 64 10 100 10 10 204.80 150 62.50

Page 10 of 13
Units DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F IN/SEC IN/SEC IN/SEC IN/SEC IN/SEC IN/SEC IN/SEC IN/SEC % SPEED % SPEED % SPEED % % PSI PSI DEG F DEGR DEGR V DC m/SEC V DC % V DC V DC MW V RMS HZ Bytes 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

FS-8700-14 GE Mark IV Speedtronic Driver Manual


Byte No. 191 193 195 197 199 201 203 205 207 207 Signal DVAR DDUMP1 DDUMP2 DDUMP3 DDUMP4 DDUMP5 DDUMP6 DDUMP7 DDUMP8 DDUMP8 Description GENERATOR LOAD VARS (SCALED) Zero Pt. 0.00 0 0 0 0 0 0 0 0 0 Maximum 204.80 32768 32768 32768 32768 32768 32768 32768 32768 32768

Page 11 of 13
Units MVAR CNT1S CNT1S CNT1S CNT1S CNT1S CNT1S CNT1S CNT1S CNT1S Logic One 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Bytes 2 2 2 2 2 2 2 2 2 2 Bytes 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8

SPARE POINT SEQUENCING)

(OPT.

WRITTEN

TO

BY

Byte No. Signal Logic points 0 L30D-SD 1 L30D-SU 2 L30D-RUN 3 L30D-RSZ 211 4 L30D-RSZ 5 L30D-STG 6 L30D-CRN 7 L63SUF 1 0 1 2 3 212 4 5 6 7 0 1 2 3 213 4 5 6 7 0 1 2 3 214 4 5 6 7 0 1 215 2 3

Description NORMAL DISPLAY MESSAGE "SHUTDOWN STATUS" NORMAL DISPLAY MESSAGE "STARTUP STATUS" NORMAL DISPLAY MESSAGE "RUN STATUS" NORMAL DISPLAY MESSAGE "NOT READY TO START" NORMAL DISPLAY MESSAGE "READY TO START" NORMAL DISPLAY MESSAGE "STARTING" NORMAL DISPLAY MESSAGE "CRANKING" STARTUP FSR FIRING FUEL COMMAND STARTUP FSR WARMUP FUEL COMMAND NORMAL DISPLAY MESSAGE "ACCELERATING" NORMAL DISPLAY MESSAGE "FULL SPEED NO LOAD" NORMAL DISPLAY MESSAGE "SYNCHRONIZING" NORMAL DISPLAY MESSAGE "SPINNING RESERVE" NORMAL DISPLAY MESSAGE "LOADING" NORMAL DISPLAY MESSAGE "FAST LOADING" NORMAL DISPLAY MESSAGE "PRESELECTED LOAD" NORMAL DISPLAY MESSAGE "BASE LOAD" NORMAL DISPLAY MESSAGE "PEAK LOAD" NORMAL DISPLAY MESSAGE "PART LOAD" NORMAL DISPLAY MESSAGE "UNLOADING" NORMAL DISPLAY MESSAGE "FIRED SHUTDOWN" NORMAL DISPLAY MESSAGE "COASTING DOWN" NORMAL DISPLAY MESSAGE "ON COOLDOWN" NORMAL DISPLAY MESSAGE "OFF COOLDOWN" OFF MODE SELECTED CRANK MODE SELECTED FIRE MODE SELECTED AUTO MODE SELECTED REMOTE MODE SELECTED NORMAL DISPLAY MESSAGE "START SELECT" NORMAL DISPLAY MESSAGE "STOP SELECT" PRE-SELECTED LOAD COMMAND BASE LOAD COMMAND PEAK LOAD COMMAND FSR SHUTDOWN CONTROL FSR STARTUP CONTROL

Logic Zero 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

FS-8700-14 GE Mark IV Speedtronic Driver Manual


Byte No. Signal Logic points 4 5 6 7 0 1 2 3 216 4 5 6 7 0 1 2 3 217 4 5 6 7 0 1 2 3 218 4 5 6 7 0 1 2 3 219 4 5 6 7 0 1 2 3 220 4 5 6 7 0 1 221 2 3 4 Description FSR ACCELERATION CONTROL HP SPEED FSR TEMPERATURE CONTROL FSR SPEED DROOP CONTROL FSR SPEED ISOCH CONTROL MIN FSR LOGIC FSR MANUAL CONTROL SEQUENCE IN PROGRESS 10V CONTROL MESSAGE - MAXIMUM ANGLE 10V CONTROL MESSAGE - TEMPERATURE CONTROL 10V CONTROL MESSAGE - MANUAL CONTROL NORMAL DISPLAY MESSAGE "VOLTAGE MATCHING" AUXILIARY TO FAST LOAD START SIGNAL WATER WASH SELECTED FUEL LINE PURGE IN PROGRESS MASTER PROTECTIVE SIGNAL NORMAL SHUTDOWN TURBINE COMPLETE SEQUENCE HP ZERO SPEED SIGNAL MINIMUM SPEED SIGNAL (APPR 20%) ACCELERATING FUEL SPEED SIGNAL (APPR 40%) HP OPERATING SPEED SIGNAL FLAME DETECTED CHANNEL =1 FLAME DETECTED CHANNEL =2 FLAME DETECTED CHANNEL =3 FLAME DETECTED CHANNEL =4 GENERATOR BREAKER CLOSURE SPARE POINT (OPT. WRITTEN TO BY SEQUENCING) Logic Zero 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Page 12 of 13
Logic One 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Bytes 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8

SPARE POINT (OPT. WRITTEN TO BY SEQUENCING)

SPARE POINT (OPT. WRITTEN TO BY SEQUENCING)

SPARE POINT (OPT. WRITTEN TO BY SEQUENCING)

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

FS-8700-14 GE Mark IV Speedtronic Driver Manual


Byte No. Signal Logic points 5 6 7 Byte No. Annunciator Alarms 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 Description Logic Zero 0 0 0 Description ALARM 0-7 ALARM 8-15 ALARM 16-23 ALARM 24-31 ALARM 32-39 ALARM 40-47 ALARM 48-55 ALARM 56-63 ALARM 64-71 ALARM 72-79 ALARM 80-87 ALARM 88-95 ALARM 96-103 ALARM 104-111 ALARM 112-119 ALARM 120-127 ALARM 128-135 ALARM 136-143 ALARM 144-151 ALARM 152-159 ALARM 160-167 ALARM 168-175 ALARM 176-183 ALARM 184-191 ALARM 192-199 ALARM 200-207 ALARM 208-215 ALARM 216-223 ALARM 224-231 ALARM 232-239 ALARM 240-247 ALARM 248-255 LogicZero 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 LogicOne FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF

Page 13 of 13
Logic One 1 1 1 Bytes 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Bytes 1/8 1/8 1/8