You are on page 1of 4

Doc. No.

Ver: 1.09 Rev:0

EST3 ECP
FS-8700-39

DESCRIPTION

The EST3 External Communications Protocol (ECP) driver allows the FieldServer to transfer data to and from EST devices over RS-232 or RS-485 (with converter) serial ports using the EST3 ECP protocol. In the EST application the FieldServer always emulates a Client. Gateway Type II and Type III formats are supported. The FieldServer makes use of the following ECP Services: Read Operations: Report Service Delta Service Write Operations: Command Service All read points are continually updated using the Report Service; response times are enhanced using Delta Service broadcasts by the EST3 panel. Note: FieldServer also offers a Remote Serial Port option by which a PC-based EST3 ECP client (e.g. Fireworks) can remotely access a Gateway Type III panel via Ethernet (TCP/IP). Fieldserver Mode Client Server Nodes 1 0 Comments Each FieldServer port can connect to only 1 EST3 panel The EST3 ECP driver cannot be used as a Server

FORMAL DRIVER TYPE

Serial Client Only

COMPATIBILITY MATRIX
Compatible with this driver Yes Yes Yes Yes Yes Yes

FieldServer Model FS-X2010 FS-X2011 FS-X25 FS-X30 FS-X40 ProtoCessor

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 1 of 4

Doc. No.

Ver: 1.09 Rev:0

EST3 ECP
FS-8700-39

CONNECTION INFORMATION
RS-232, RS-485 9600; 19200 (as determined by EST3 panel) 8 1 None Yes

Connection type: Baud Rates: Data Bits: Stop Bits: Parity: Multidrop Capability:

DEVICES TESTED
Tested (FACTORY, SITE) Factory

Device EST3 panel

CONNECTION CONFIGURATIONS

AUDIO IN

AUDIO OUT

N E T W O R K

COM 1

COM 2

RTS 1

RTS 2

EST3 ECP TB2

RX 1

RX 2

TX 1

TX 2

A+

B+

A-

B-

N A N A N A N A

3 TX

2 RX

Blue/white
5 GN D

Orange/White Brown

FS-8917-16

FieldServer Part # 8917-16 Pigtail for RJ45 Port

Connect to one of the RS-232 Ports on the FieldServer


8 1

Pinouts
Model 8051 Function RX TX GND FS-8917-16 Pin 2 Pin 3 Pin 5 EST3 ECP TB2 TX 2 RX 2 COM 2

FieldServer

P1

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 2 of 4

Doc. No.

Ver: 1.09 Rev:0

EST3 ECP
FS-8700-39

7 7.1

COMMUNICATIONS FUNCTIONS - SUPPORTED FUNCTIONS AT A GLANCE: Data Types and Commands Supported

The following commands may be sent using the EST3 Command Service. EST3 Object Type Relay Led ServGroup GuardPtrl ChkInGrp AltMessage AmpPower AudMsg Reset PanelSil AlarmSil Drill GAInhibit Set Time Set Date Reboot Evacuate AltSensitiv MCmsg Partition Cmd List Input Zone Card AndGroup Matrix TimeCtrl Instruction Text EST3 Commands Activate, Restore, Enable, Disable Activate, Restore, Enable, Disable Activate, Restore, Enable, Disable Activate, Restore, Enable, Disable Activate, Restore, Enable, Disable Activate, Restore Activate, Restore, Enable, Disable Activate, Restore Activate, Restore Activate, Restore Activate, Restore Activate, Restore Activate, Restore Activate, Restore Activate, Restore Activate, Restore Activate, Restore Activate, Restore Activate, Restore Activate, Restore, Enable, Disable Activate, Restore Enable, Disable Enable, Disable Enable, Disable Activate, Restore,Enable, Disable Enable, Disable Enable, Disable Enable, Disable

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 3 of 4

Doc. No.

Ver: 1.09 Rev:0

EST3 ECP
FS-8700-39

7.2

Read Operations supported

The EST3 ECP driver makes use of the Report Service to read the current state of EST3 points. It also updates the current state if Delta Service reports are received, which are unsolicited broadcasts initiated by the EST3 panel when a point changes. FieldServer as a Client EST3 Report Service (polled) All panel points IO Status Status values are able to be decoded and stored as Alarm, Trouble, Supervisory, Monitor or as Others. It is now possible to configure the category that an event is placed in. The Driver can be configured to provide Relay confirmation status. The Driver can be configured to provide the acknowledge state of a point and can acknowledge it. Sensitivity Report: The Driver can be configured to store dirtiness as value*10 for system sensor devices and the actual value for other devices (The Panel sends % values for other devices). EST3 Delta Service (unsolicited) All panel points Delta message status values are optionally decoded and stored as Alarm, Trouble, Supervisory, Monitor or as Others. EST3 Date and Time Service The FieldServer can be configured to synchronize its clock with Panel or the FieldServer can set the Panels clock

UNSUPPORTED FUNCTIONS AND DATA TYPES


Reason not required to date not required to date not required to date not required to date not required to date not required to date Reason not required to date not required to date not required to date not required to date not required to date

EST3 Command Stay Conditional Away Conditional Stay Update Status Remove Bypass Bypass

EST3 Service Panel State Service Protocol Encapsulation Service Access Event Service Partition Reset Service Command Logging Service

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 4 of 4

You might also like