Super Solution
North American Edition
Super Solution
Overview Main characteristics Accessories Technical information Mounting & connection Characteristics curves
Contents
>>>
Super Solution
Circuit breakers
For protection of power distribution
MCCB
The circuit breaker will supply more stable, reliable, upgraded systems to customer with high breaking capacity.
Susol MCCB
Simplified product range
AF: 125AF, 250AF, 400AF, 800AF Ampere Range: 15A ~ 800A
Standards
High performance
Ultimate breaking capacity (kA rms) Icu: Max 65kA @480VAC
World class with UL489, CE approvals FTU: Fixed thermal & Magnetic unit ATU: Adjustable thermal & Magnetic unit Variable accessories FMU: Adjustable thermal, Fixed magnetic unit MCS: Molded Case Switch Electrical auxiliaries Extended rotary handle Flange handle Locking devices
MCCB
8 Models in 4 Frames
Susol TD and TS circuit breakers are rated from 15 through 800 amperes and are available in four frame sizes.
TD125U
In 15~125A Icu: 35kA(NU), 65kA(HU) 90(W) x 164(H) x 86mm(D)
TS800NU
TS400NU
TS250HU
TS250NU
TD125HU
TD125NU
65kA
35kA
MCCB Accessories
A complete range of convenient internal and external accessories for Susol TD and TS series
Circuit breaker Flange handle (Cable operating handle) Extended rotary handle Locking devices (Removable, Fixed) Mechanical interlock device Accessories device (AL, AX, UVT, SHT) Trip units
MCCB
Trip units
Susol TS series circuit breakers provide several kinds of protection function according to selected trip unit and thanks to interchangeable trip unit concept, user can change the trip unit easily and rapidly.
* Only available in factory
Im=2500A
Ir Im
250A
40 3P
Motor Protection
- MTU: Magnetic only trip unit
TS250MTU
1848 1584 1320
Im
220A
3P
3P
15
20
32 40
50
60
80 100 128 150 160 175 200 225 250 300 350 400 500 600 700 800 FTU
Thermal-magnetic (Interchangeable)
FMU ATU
MCS
MCCB
Internal accessories
Simplicity
The range of internal accessories of TD & TS series circuit breakers is characterized by common use regardless of frame size and is allowing reduction of stocks.
Internal accessories
Common use to all Susol TD and TS circuit breakers
Electrical auxiliaries that are installed internally are common from 15A to 800A.
Alarm Switch (AL)
Alarm switches offer provisions for immediate audio or visual indication of a tripped breaker due to overload, short-circuit, operation of shunt trip, or undervoltage trip conditions, operation of push button. They are particularly useful in automated plants where operators must be signaled about changes in the electrical distribution system. This switch features a closed contact when the circuit breaker is tripped automatically. In other words, this switch does not function when the breaker is operated manually. Its contact is open when the circuit breaker is reset.
MCCB
External accessories
Convenience
Wide range of external accessories provides convenient solution for easy installation.
External accessories
Locking device
Fixed padlock Removable padlock Key lock device on direct handle
MCCB
Main characteristics
A-1. Overview
Range of Susol products Overview of TD/TS family Marking and configuration Overview of trip units Switching mechanism Degree of protection
A-1-1 A-1-3 A-1-5 A-1-7 A-1-9 A-1-10
125AF
250AF
Susol switch-disconnectors
TS250U
A-1-1
400AF
800AF
TS800U
Susol switch-disconnectors
TS800U
A-1-2
TD series
TD125U
Frame size Rated current In No. of Poles Rated operational voltage, Ue AC UL interrupting rating AC 50/60Hz 240 V 480 V 600 V Reference standard Trip unit (Thermal-Magnetic) Fixed-thermal, Fixed-magnetic Adjustable-thermal, Fixed-magnetic Adjustable-thermal, Adjustable-magnetic (3Pole) Molded Case Switch Variable accessories AX AL SHT UVT Extended rotary handle Flange handle Locking devices (Removable, Fixed) Mechanical interlock device Mechanical life Electrical life @600V AC Weight 3-Pole Basic dimension, WHD 3-Pole [operations] [operations] [lbs/kg] [inch/m]
4,000 4,000 2.65/1.2 3.546.463.39/0.901.640.86
[AF] [A]
125 15, 20, 30, 40, 50, 60, 80, 100, 125 2, 3
[V] [kA]
NU 50 35 10
A-1-3
TS series
TS250U
250 150, 160, 175, 200, 225, 250 2, 3 600 NU 50 35 10 UL 489 HU 100 65 14 NU 50 35 10
TS400U
400 300, 350, 400 2, 3 600 HU 100 65 14 UL 489 NU 50 35 10
TS800U
800 500, 600, 700, 800 2, 3 600 HU 100 65 14 UL 489
A-1-4
Rated frequency
Standard
Manufacturer
Utilization category
A-1-5
Model (Rating and breaking capacity) TS: Series 250: Max. Ampere rating NU: Normal (Standard) HU: High Standardized characteristics: Ui: Rated insulation voltage Uimp: Impulse withstand voltage Ue: Rated operational voltage Icu: Ultimate breaking capacity Ics: Service breaking capacity
125AF NU TD125NU
250AF TS250NU
400AF TS400NU
800AF TS800NU
HU
TD125HU
TS250HU
TS400HU
TS800HU
NU
50kA
50kA
50kA
50kA
HU
100kA
100kA
100kA
100kA
Upstream connections Fixing hole Certificate plate Indication of closed (I/ON) position
Brand name
Operating handle
Indication of open (O/OFF) position Company logo "push to trip" button Rating of trip unit Trip unit
A-1-6
On TD100U to TS800U circuit breakers, the thermal-magnetic trip units are interchangeable and may be rapidly fitted to the circuit breakers.
It is therefore easy to change the protection of a given circuit following a modification in an uninstallation.
Ampere ratings
MCCB frame type Rated current, In[A] Thermal magnetic release Type of trip unit TD125U FTU 15, 20, 30, 40, 50, 60, 80, 100, 125 150, 175, 200, 225, 250 300, 350, 400 FMU 32, 40, 48, 64, 80, 100 128, 160, 200 ATU MCS 15, 20, 30, 40, 50, 60, 80, 100, 125 150, 160, 175, 200, 225, 250 300, 350, 400
TS250U
TS400U
240, 320
240, 320
TS800U
Fixed thermal, Fixed magnetic Adjustable thermal, Fixed magnetic Adjustable thermal, Adjustable magnetic Molded case switch
A-1-7
FTU
Fixed-thermal, fixed-magnetic
TS250 FTU
Im=2500A
Thermal magnetic trip unit
FMU
Adjustable-thermal, fixed-magnetic
7 6 5
8 9 10
MCS
FTU FMU ATU
3P
A-1-8
Switching mechanism
Double contactor structure
Optimize
Repulsion force Shape of contactor Induce easily the arc mobility to grid direction Rapidly redeploy the arc from moving contactor Prevent contact tip from erosion Open speed & contact force
ON position
Unvarying contact force regardless of over travel Open speed of moving contact is rapid by optimized cam curve regardless of trip signal Function of trip free
Optimized cam curve
Force
Unvarying contact
Fig. 3 ON position
Angle
Stability of endurance
600.0
4.00E+06
3.00E+06
1.20E+07
1.60E+07
2.00E+07
Life
TRIP position Enables tripping mechanically from outside, for confirming the operation of the accessory switches and the manual resetting function
Fig. 5 TRIP position
A-1-9
Degree of protection
The table indicates the degrees of protection guaranteed by Susol TD and TS circuitbreakers according to several type of installation. Basically, the fixed parts are always preset with IP20 degree of protection.
IP65 degree of protection can be obtained with the circuit-breaker installed in a switchboard fitted with an extended rotary handle operating mechanism transmitted on the compartment door.
Type
Degree of protection
IP
NEMA type
IP40
1, 3R,12 4X
Wire
IP40
1, 3R,12 4X
Wire
A-1-10
A-2-17
TD series
TD125U
Frame size No. of Poles Maximum voltage ratings Switch ampere ratings Magnetic override Short circuit withstand ratings 120V AC 240V AC 480V AC 600V AC Catalog number of wire connector Dimensions Shipping weight [V AC] [A] [A] [AF] 125 3 600 125 1250 100kA 100kA 65kA 14kA LSCA1 Same as MCCB Same as MCCB
A-2-1
TS series
TS250U
250
TS400U
400 3
TS800U
800
600 400 4000 100kA 65kA 20kA LSCA4 Same as MCCB Same as MCCB
A-2-2
Function
Protection of power distribution Overload protection: Thermal protection with a fixed or adjustable threshold Short-circuit protection: Magnetic protection with a fixed or adjustable pick-up Protection of the fourth pole 4P3T type (neutral unprotected) 4P4T type 50% (neutral protection at 0.5In) 4P4T type 100% (neutral protection at 1In)
Operation
Trip bar
ATU
Thermal magnetic types Time-Delay operation An overcurrent heats and warps the bimetal to actuate the trip bar by the bimetal characteristic. Instantaneous operation If the overcurrent is excessive, the armature is attracted and the trip bar actuated by electromagnetic force.
Bimetal
Armature
Ratings
Ratings(A) at 40 TD125U TS250U TS400U TS800U In 15 20 30 40 Thermal magnetic trip units(FTU/FMU/ATU) 50 60 TD125U to TS800U 80 100 125 150 160 175 200 225 250 300 350 400 500 600 700 800
A-2-3
Im=2500A
Ir Im
Adjustable thermal, fixed magnetic trip units FMU Adjustable thermal 40A ... 800A rated currents Adjustable : 0.8~1In Fixed magnetic 400A ... 8000A tripping currents Applicable to TD125U ... TS800U frames
Adjustable thermal, adjustable magnetic trip units ATU Adjustable thermal 150A ... 800A rated currents Adjustable : 0.8~1In Adjustable magnetic 500A ... 8000A tripping currents Adjustable : 5~10In Applicable to TS250U ... TS800U frames
TS250 ATU
0.8
0.9 1
Ir Im
7 6 5
8 9 10
A-2-4
Configuration
Trip unit identification
Ratings (A), In at 40C Number of pole Short circuit protection (magnetic) Setting current, Im
TD125FTU
Im=1250A
Ir Im
125A
TD125U FMU
t
0.9 0.8 1
TD125FMU
0.8
Im=1250A
125A
0 Ir Im I
A-2-5
Characteristics
Thermal magnetic trip units(FTU/FMU) ... TD125U Rating(A) at 40 In TD125U 15 20 30 40 50 60 80 100 125
Overload protection(thermal) Current setting(A) Ir FTU FMU Fixed Adjustable 0.8, 0.9, 1In (3 settings)
Short - circuit protection(magnetic) Current setting(A) Im FTU FMU Fixed 400A Fixed 400A Fixed 10In Fixed 10In
A-2-6
Setting details
Thermal overload protection
Trip unit type Setting Ir TD125U FTU TD125U FMU Fixed 0.8 0.9 1 15 15 20 20 30 30 Trip unit rating, In (A) 40 40 32 36 40 50 50 40 45 50 60 60 48 54 60 80 80 64 72 80 100 100 80 90 100 125 125 100 112.5 125
A-2-7
Ratings (A), In at 40C Number of pole Short circuit protection (magnetic) Setting current, Im
TS250U FMU
Im=2500A
Ir Im
TS250U ATU
t
7 6 5
8 9 10
0 Ir Im
A-2-8
Short - circuit protection(magnetic) Current setting(A) Im FTU FMU ATU Fixed 10In Fixed 10In Adjustable 5, 6, 7, 8, 9, 10In (6 settings)
TS250U
FMU
Trip unit function - FMU: Adjustable thermal, fixed magnetic unit MCCB frame type - TS250U: TS250NU, TS250HU
TS250U
ATU
Trip unit function - ATU: Adjustable thermal, adjustable magnetic unit MCCB frame type - TS250U: TS250NU, TS250HU
A-2-9
In 10 In 5 In 0.9 In Adjustable In In In 6 7 8 9
In 10 In 5 In 1.0 In Adjustable In In In 6 7 8 9
In 10
A-2-10
Configuration
Trip unit identification
Ratings (A), In at 40C Number of pole Short circuit protection (magnetic) Setting current, Im
TS400U FMU
TS400 FTU
Im=4000A
Ir Im
400A
0.9 0.8 1
Ir
Im
TS400FMU
0.9 0.8 1 Ir Im
400A
Im=4000A TS400U ATU
t
0.9 0.8 1
8 9
TS400ATU
0.9 0.8 1 Ir Im 6 5 7 8 9 10
0 Ir Im
400A
10
A-2-11
Characteristics
Thermal magnetic trip units(FTU/FMU/ATU) ... TS400U Rating(A) at 40 In TS400U Overload protection(thermal) Current setting(A) Ir FTU FMU ATU In=Ir (Fixed) Adjustable 0.8, 0.9, 1In (3 settings) Adjustable 0.8, 0.9, 1In (3 settings) 300 350 400
Short - circuit protection(magnetic) Current setting(A) Im FTU FMU ATU Fixed 10In Fixed 10In Adjustable 5, 6, 7, 8, 9,10In(6 settings)
A-2-12
Setting details
Thermal overload protection
Trip unit type Setting Ir TS400U FTU TS400U FMU Fixed 0.8 0.9 1 TS400U ATU 0.8 0.9 1 300 300 240 270 300 240 270 300 Trip unit rating, In (A) 350 350 400 400 320 360 400 320 360 400
In 5 In 0.8 In Adjustable In In In 6 7 8 9
In 10 In 5 In 0.9 In Adjustable In In In 6 7 8 9
In 10 In 5 In 1.0 In Adjustable In In In 6 7 8 9
In 10
A-2-13
Configuration
Trip unit identification
TS800FTU
Im=8000A
Ir Im
TS800U FMU
800A
t
0.9 0.8 1
TS800FMU
0.9 0.8 1 Ir Im
Ir
Im
Im=8000A
800A
TS800U ATU
t
0.9 0.8 1
TS800ATU
0.9 0.8 1 Ir Im 6 5 7 8 9 10
0 Ir Im
800A
A-2-14
Characteristics
Thermal magnetic trip units(FTU/FMU/ATU) ... TS800U Rating(A) at 40 In TS800U Overload protection(thermal) Current setting(A) Ir FTU FMU ATU Fixed Adjustable 0.8, 0.9,1In (3 settings) Adjustable 0.8, 0.9,1In (3 settings) 500 600 700 800
Short - circuit protection(magnetic) Current setting(A) Im FTU FMU ATU Fixed 10In Fixed 10In Adjustable 5, 6, 7, 8, 9, 10In (6 settings)
A-2-15
Setting details
Thermal overload protection
Trip unit type Setting Ir TS800U FTU TS800U FMU Fixed 0.8 0.9 1 TS800U ATU 0.8 0.9 1 500 500 400 450 500 400 450 500 Trip unit rating, In (A) 600 600 480 540 600 480 540 600 700 700 800 800 640 720 800 640 720 800
In 5 In 0.9 In Adjustable In In In In 6 7 8 9 10
In 5 In 1.0 In Adjustable In In In In 6 7 8 9 10
A-2-16
The Molded case switch are different from the circuit-breakers in the absence of the conventional protection unit. They keep the overall dimensions, connection systems and accessories unchanged from the
corresponding circuit-breakers. Installation standards require upstream protection. However, thanks to their high-set magnetic release, TD125U ... TS800U MCS are self protected.
TD series
TD125U
Frame size Conventional thermal current, Ith No. of poles Rated operational voltage, Ue Rated operational current, Ie Rated impulse withstand voltage,Uimp Rated insulation voltage, Ui Rated short-circuit making capacity, Icm Rated short-time withstand current, Icw 1s 3s 20s Isolation behavior Trip unit (release) Molded case switch Connection fixed front-connection rear-connection plug-in front-connection rear-connection Mechanical life Electrical life @415 V AC Basic dimensions, WHD (front connection) Weight (front connection) Reference standard 2-pole 3-pole 2-pole 3-pole [operations] [operations] [mm] [mm] [kg] [kg] MCS [kV] [V] [kA peak] [A rms] [A rms] [A rms] AC DC [V] [V] [AF] [A] 125 125 2, 3 600
A-2-17
TS series
TS250U
250 250 2, 3 600
TS400U
400 400 2, 3 600
TS800U
800 800 2, 3 600
A-2-18
A-3. Accessories
Electrical auxiliaries
Undervoltage release, UVT Shunt release, SHT Auxiliary switch (AX), Alarm switch (AL) and Fault alarm switch (FAL) Possible configuration of electrical auxiliaries
A-3-1 A-3-2 A-3-3 A-3-4
Rotary handles
Rotary handles
A-3-5
Locking devices
Removable locking device Fixed locking device
A-3-7 A-3-8
Interlock
Mechanical interlocking device
A-3-9
Accessories
Electrical auxiliaries
The following devices are installed into all TD & TS circuit breakers regardless of frame size. And, the electrical auxiliaries can be easily installed in the accessory compartment of the circuit breakers which is cassette type.
UVT
Range of tripping voltage: 0.35 ~ 0.7Vn MCCB making is possible voltage: 0.85Vn (exceed) Frequency (only AC): 45Hz ~ 65Hz
Technical data
Control voltage (V) AC/DC 24V Power consumption AC/DC 48V AC/DC 110~130V AC 200~240V/DC 250V AC 380~440V AC 440~480V Max.opening time (ms) Tightening torque of terminal screw Transformer operating voltage (V) - Drop (Circuit breaker trips) - Rise (Circuit breaker can be switched on) 0.7~1.35Vn ~0.85Vn 0.64 1.09 0.73 1.21 1.67 1.68 Consumption AC (VA) DC (W) 0.65 1.10 0.75 1.35 50 8.2kgfcm mA 27 23 5.8 5.4 3.8 3.5 TD125U, TS250U, TS400U, TS800U Applicable MCCBs
8.2kgfcm
A-3-1
Accessories
Electrical auxiliaries
SHT
Technical data
Control voltage (V) DC 12V Power consumption AC/DC 24V AC/DC 48V AC/DC 110~130V AC 220~240V/DC250V AC 380~500V Max.opening time (ms) Tightening torque of terminal screw 0.58 1.22 1.36 1.80 1.15 Consumption AC (VA) DC (W) 0.36 0.58 1.23 1.37 1.88 50 8.2kgfcm mA 30 24 25 10.5 7.5 2.3 TD125U, TS250U, TS400U, TS800U Applicable MCCBs
8.2kgfcm
Click
A-3-2
Accessories
Electrical auxiliaries
AX
This switch features a closed contact when the circuit breaker is tripped automatically. In other words, this switch does not function when the breaker is operated manually. Its contact is open when the circuit breaker is reset.
Contact operation
MCCB
AL
ON
AXa1 AXc1 AXb1
OFF
AXc1
TRIP
AXa1 AXb1
Position of AX Position of AL
AXa1 AXb1
Technical data
Conventional thermal current Ith Rated operational current Ie with rated operational voltage Ue - Altemating current 50/60Hz AC 125V 250V 500V - Direct current DC 30V 125V 250V 5A Voltage Resistance 5 3 4 0.4 0.2 Ie Inductance 3 2 3 0.4 0.2 TD125U, TS250U, TS400U, TS800U
A-3-3
Accessories
Electrical auxiliaries
TD125U
TS250U
TS400U
TS800U
AX AX AX AL
*FAL
AX AX AX
AL AL
SHT/ UVT
A-3-4
Accessories
Rotary handles
Extended handles
The rotary handle operating mechanism is available in either the direct version or in the extended version on the compartment door.
TS800U
Flange Handle
The flange hanle is operated by cable and can be applied on the compartment door. This device is designed to easily installed and operated for its own flexibility And, also can be selected various length (4 types) at each frames.
TS800U
A-3-5
Accessories
Locking devices
The locking device for the toggle handle can be installed in 2-pole and 3-pole circuit-breakers. Maximum three (3) padlocks with shackle diameters ranging from 0.2~0.3inch(5~8mm) may be used. (Padlocks are not supplied)
Cover Aux.
Pad-lock
0.2~0.3inch (5~8mm)
1.2inch (30mm)
Padlock dimensions
A-3-6
Accessories
Locking devices
0.2~0.3inch (5~8mm)
How to use
The locking device for the toggle handle is designed to be easily attached to the front of circuit-breaker. Please set the toggle handle in the position of On or Off. Install the lock device onto the front of auxiliary cover of circuit breaker. Folding the wings of lock device as shown in picture 3. The padlock to be used shall be that which is commercially available with the nominal dimension. (1.2inch (30mm), nominal dimension, 0.2~0.3inch (5~8mm) diameter)
1.2inch (30mm)
Padlock dimensions
TD125U
TS250U ~ TS800U
A-3-7
Accessories
Interlock
The front interlocking plate allows installation of a padlock in order to fix the position. (possibility of locking in the O-O position as well) This mechanical interlocking device is very useful and simple for consisting of manual source-changeover system.
Operation
Frame type TD125U
TS400U
3-pole 4-pole
TS800U
3-pole 4-pole
A-3-8
Protective coordination
Discrimination & Cascading Cascading, network 220/240V Cascading, network 380/415V Cascading, network 480/500V Protection discrimination table, Discrimination Type 2 Coordination according to IEC60947-4-1
A-4-15 A-4-16 A-4-19 A-4-22 A-4-25 A-4-31
Technical information
Temperature derating
A derating of the rated operational current of the Susol TD and TS molded case circuit breaker is necessary if the ambient temperature is greater than 40C. Namely, when the ambient temperature is greater than 40C, overload-protection characteristics are
slightly modified. Electronic trip units are not affected by variations in temperature. But, the maximum permissible current in the circuit breaker depends on the ambient temperature.
A-4-1
Technical information
Power dissipation / Resistance
8.83 10.05
AF Rating (A) Fixed MCCB R (m ) Watt single pole Watt three poles 150 0.62 13.95 41.85 160 0.62 15.87 47.62
TS250U (2P & 3P) 175 0.52 15.93 47.78 200 0.52 20.80 62.40 225 0.25 12.66 37.97 250 0.25 15.79 47.38
AF Rating (A) Fixed MCCB R (m ) Watt single pole Watt three poles 300 0.30 26.82 80.46
TS400U(2P & 3P) 350 0.30 36.75 110.25 400 0.30 47.68 143.04
AF Rating (A) Fixed MCCB R (m ) Watt single pole Watt three poles 500 0.49 122.50 367.50
TS800U (2P & 3P) 600 0.49 176.40 529.20 700 0.12 58.80 176.40 800 0.12 76.80 230.40
Power dissipated per pole (P/pole): Watts (W). Resistance per pole (R/pole): Milliohms (m) (measured cold). Total power dissipation is the value measured at In, 50/60 Hz, for a 3 pole or 4 pole circuit breaker (Power= 3I2R)
A-4-2
Technical information
Application Primary use of transformer
Application for transformer protection
Transformer excitation surge current may possibly exceed 10 times rated current, with a danger of nuisance tripping of the MCCB. The excitation surge current will vary depending upon the supply phase angle at the time of switching, and also on the level of core residual magnetism. So, its recommended to select proper circuit breakers according to the continuous current carrying capacity of transformer. It requires to consider separately whether transformer is single phase or three phase. The below table indicates the proper molded case circuit breaker suitable for each transformer.
AC240V
Capacity of 3 phase transformer (kVA) Capacity of single phase transformer (kVA) Breaking capacity (kA) (sym) Frame (A) 125 250 400 800 Below 1500 Below 300 50 TD125NU TS250NU TS400NU TS800NU TD125HU TS250HU TS400HU TS800HU 100 Below 1500 Below 2000 -
AC480V
Capacity of 3 phase transformer (kVA) Breaking capacity (kA) (sym) Frame (A) 125 250 400 800 TD125NU TS250NU TS400NU TS800NU Below 2000 35 TD125HU TS250HU TS400HU TS800HU 65 Below 3000
A-4-3
Technical information
Application Primary use of transformer
Application for transformer protection (MCCBs for Transformer-Primary Use)
Transformers are used to change in the supply voltage, for both medium and low voltage supplies. The choice of the protection devices should be considered transient insertion phenomena, during which the current may reach values higher than the rated full load current; the phenomenon decays in a few seconds. The peak value of the first half cycle may reach values of 15 to 25 times the effective rated current. For a protective device capable of protecting these units this must be taken into account. Manufacturers data and tests have indicated that a protective device feeding a transformer must be capable of carrying the following current values without tripping.
A-4-4
Technical information
Application Protection of lighting & heating circuits
In the lighting & heating circuits, switchingsurge magnitudes and times are normally not sufficient to cause serious tripping problems. But, in some cases, such as incandescent lamps, mercury arc lamps, metal halide and sodium vapour, or other large starting-current equipment, the proper selection should be considered. Upon supply of a lighting installation, for a brief period an initial current exceeding the rated current (corresponding to the power of the lamps) circulates on the network. This possible peak has a value of approximately 1520 times the rated current, and is present for a few milliseconds; there may also be an inrush current with a value of approximately 1.53 times the rated current, lasting up to some minutes. The correct dimensioning of the switching and protection devices must take these problems into account. Generally, it is recommended to make the maximum operating current not to exceed 80% of the related current.
AC220V
The maximum operating current (A) 12 16 24 32 40 48 64 80 100 120 140 160 180 200 240 280 320 400 480 560 640 The rated Breaking capacity (kA) current of sym MCCB (A) 15 20 30 40 50 60 80 100 125 150 175 200 225 250 300 350 400 500 600 700 800 TS800NU TS800HU TS400NU TS400HU TS250NU TS250HU TD125NU TD125HU 50 100
A-4-5
Technical information
Application Protection of lighting & heating circuits
AC480V
The maximum operating current (A) 12 16 24 32 40 48 64 80 100 120 140 160 180 200 240 280 320 400 480 560 640 The rated Breaking capacity (kA) current of sym MCCB (A) 15 20 30 40 50 60 80 100 125 150 175 200 225 250 300 350 400 500 600 700 800 TS800NU TS800HU TS400NU TS400HU TS250NU TS250HU TD125NU TD125HU 35 65
A-4-6
Technical information
Application Protection of resistance welding circuits
Short circuit protection for resistance welding devices can be obtained by applying molded case circuit breaker properly. These breakers permit normally high welding currents, but trip instantaneously if a short circuit develops. It's recommended to select proper circuit breaker according to the characteristics of welding devices as the follow table.
Applied circuit breaker (MCCB 2P) 240V (Single phase) 415V (Single phase)
15
35
TD125NU/HU 125A
TD125NU/HU 50A
30
65
TS250NU/HU 150A
TD125NU/HU 125A
55
140
TS250NU/HU 250A
TD125NU/HU 125A
A-4-7
Technical information
Application Use of circuit-breakers for capacitor banks
Application for protection of capacitor circuit
C
Capacitor circuit
In order to reduce system losses (less than 0.5W/kvar in low voltage) and voltage drops in the power distribution system, reactive power compensation or power factor correction is generally undertaken. As a result, the power fed into the system is used as active power and costs will be saved through a reduction in Examples of equipment which consume reactive energy are all those receivers which require magnetic fields or arcs in order to operate, such as: - Asynchronous motors: An asynchronous motor is a large consumer of inductive reactive energy. The amount of reactive power consumed is between 20% and 25% of the rated power of the motor (depending on its speed). - Power Transformers: Power transformers are normally always connected. This means that reactive energy is always consumed. Also, as a consequence of its inductive nature, the reactive energy increases when the transformer is loaded. - Discharge lamps, Resistance-type soldering machines, Dielectric type heating ovens, Induction heating ovens, Welding equipments, Arc furnaces
the capacitive and inductive power factors. The compensation can be carried out by the fixed capacitors and automatic capacitor banks. However, the disadvantages of installing capacitors are sensitivity to over-voltages and to the presence of nonlinear loads.
L1 L2 L3 1 2 3 4 5 6 Breaker
1 2
3 4
5 Contactor 6
O/L
At the instant of closing a switch to energize a capacitor, the current is limited only by the impedance of the network upstream of the capacitor, so that high peak values of current will occur for a brief period, rapidly falling to normal operating values. According to the relevant standards IEC 60831-1/IEC 70, capacitors must function under normal operating conditions with the current having a RMS value up to 1.3 times the rated current of the capacitor. Additionally, a further tolerance of up to 15% of the real value of the power must be taken into consideration. The maximum current with which the selected circuit-breaker can be constantly loaded, and which it must also be able to switch, is calculated as follows: Maximum expected rated current = Rated current of the capacitor bank1.5 (RMS value)
T1
T2 T3 C M Motor
L1 L2 L3 1 2 3 4 5 6 Breaker
1 2
3 4
5 Contactor 6 O/L
T1
T2 T3 C M Motor
L1 L2 L3 1 2 3 4 5 6 Breaker 1 2 3 4 5 6 Breaker
1 2
3 4
5 Contactor 6 O/L C
T1
T2 M
T3
Motor
A-4-8
Technical information
Application Using circuit-breakers in DC networks
Susol circuit-breakers for protection of power distribution with thermal overload and magnetic short-circuit trip units are suitable for usage in Circuit-breaker selection criteria The followings are the most important criteria for selection of suitable circuit breaker for DC networks. The rated current determines the rating and size of the circuit-breaker (Equipment) Setting range of the trip values Thermal overload protection: Same setpoints as in 50/60Hz circuits DC networks. The circuit-breakers with electronic overcurrent releases are not suitable for DC networks. The rated voltage determines the number of poles in series necessary for breaking The maximum short-circuit current at the connection point determines the breaking capacity Instantaneous short-circuit protection: The response threshold increases by maximum 40%.
The following wiring diagrams are recommended since the current must flow through all current paths in order to conform to the thermal tripping characteristic curve.
-(N) +(P) -(N) +(P)
Load
Load
Model TD125NU TS250NU TS400NU Thermal magnetic TS800NU TD125HU TS250HU TS400HU TS800HU
Trip unit
Applicable to DC circuits
50
65
85
A-4-9
Technical information
Application Circuit breakers for 400Hz networks
When circuit breakers are used at high frequencies, the breakers in many cases require to be derated as the increased resistance of the copper sections resulting from the skin effect produced by eddy currents at 400Hz. Standard production breakers can be used with alternating currents with frequencies other than 50/60 Hz (the frequencies to which the rated performance of the device refer, with alternating current) as appropriate derating coefficients are applied.
Multiplier factors (K1, K2) Trip unit K1 (Thermal trip units) 0.8 0.8 0.8 0.8 K2 (Magnetic trip units) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
TD125NU, TD125HU
0.8 0.8 0.8 FTU FMU ATU 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
TS250NU, TS250HU
TS400NU, TS400HU
TS800NU, TS800HU
A-4-10
Technical information
Application Protection of several kinds of loads
Application for protection of several kinds of loads
It requires to select proper circuit breakers according to the characteristics of loads when they are installed to protect several kinds of loads. It's needed to consider the maximum operating current and the capacity of loads in total so as to select the rated current of breakers.
IW IM + IL Choose the low value among two formulas: Ib 3IM + IL. and Ib 2.5IW Iw 1.25IM + IL Its permitted to select the above value only if IW (above 100A) isnt subject to the rated current of circuit breaker. IW 1.1IM + IL
The rated current of breakers as the main circuit of 3 phase inductive loads (AC 220V)
Capacity of loads In total (below kW) 3 4.5 6.3 8.2 12 15.7 19.5 23.2 30 37.5 45 52.5 63.7 75 86.2 97.5 112.5 125 150 175
1kw 1.3405hp Capacity of the highest motor (HP/ A) The maximum operating current 1.00 2.01 2.95 4.96 7.37 10.0 14.7 20.1 24.8 29.4 40.2 49.6 60.3 73.7 100. 120. 5 0 5 5 0 0 9 1 0 2 3 53 64 (below A) 4.8 8 11.1 17.4 26 34 48 65 79 93 125 160 190 230 310 360
15 20 30 40 50 75 90 100 125 150 175 200 250 300 350 400 450 500 600 700
20 40 40 50 80 100 100 125 160 200 200 250 300 400 400 500 500 700 700 800
30 40 40 50 80 100 100 125 160 200 200 250 300 400 400 500 500 700 700 800
30 40 40 50 80 100 100 125 160 200 200 250 300 400 400 500 500 700 700 800
50 50 50 80 100 100 125 160 200 200 250 300 400 400 500 500 700 700 800
80 80 80 100 100 125 160 200 200 250 300 400 400 500 500 700 700 800
100 100 100 100 125 160 200 200 250 300 400 400 500 500 700 700 800
125 125 125 160 200 200 250 300 400 400 500 500 700 700 800
160 160 160 160 200 200 250 300 400 400 500 500 700 700 800
200 200 200 200 200 250 300 400 400 500 500 700 700 800
200 250 250 250 250 300 400 400 500 500 700 700 800
300 300 400 300 400 300 400 400 400 400 400 500 500 500 500 700 700 700 700 800 800
A-4-11
Technical information
Application Protection of several kinds of loads
The rated current of breakers as the main circuit of 3 phase inductive loads (AC 440V)
Capacity of loads In total (below kW) 3 4.5 6.3 8.2 12 15.7 19.5 23.2 30 37.5 45 52.5 63.7 75 86.2 97.5 112.5 125 150 175 200 250 300 Capacity of the highest motor (HP/ A) 1kw 1.3405hp The maximum operating 1.00 2.95 10.0 14.7 20.1 24.8 29.4 40.2 49.6 60.3 73.7 100. 120. 147. current 5 2.01 0 4.96 7.37 5 5 0 0 9 1 0 2 3 53 64 45 (below A) 4.8 8 11.1 17.4 26 34 48 65 79 93 125 160 190 230 310 360 220 7.5 10 15 20 25 38 45 50 63 75 88 100 125 150 175 200 225 250 300 350 400 500 600 20 20 20 40 40 50 50 80 80 20 20 20 40 40 50 50 80 80 20 20 20 40 40 50 50 80 80 40 40 40 40 50 50 80 80 40 40 40 50 50 80 80 50 50 50 50 80 80 80 80 80 80 80 80 100 80 100 125 80 100 125
100 100 100 100 100 100 100 100 100 125 160 100 100 100 100 100 100 100 100 100 125 160 200 125 125 125 125 125 125 125 125 125 125 160 200 250 160 160 160 160 160 160 160 160 160 160 160 200 250 250 200 200 200 200 200 200 200 200 200 200 200 200 250 250 200 200 200 200 200 200 200 200 200 200 200 200 250 300 400 250 250 250 250 250 250 250 250 250 250 250 250 250 300 400 400 500 250 250 250 250 250 250 250 250 250 250 250 250 250 300 400 400 500 300 300 300 300 300 300 300 300 300 300 300 300 300 300 400 400 500 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 500 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 500 700 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 800 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 800
Notes) The above mentioned technical data is defined under the usage conditions as follows ; 1. The circuit breaker is tripped within 10seconds in 600% of the current of the fully operating loads. 2. The start-up input current is set within 1700% of the current of the fully operating loads. 3. The capacity of highest motor is also applied when several loads starts up simultaneously.
A-4-12
Technical information
Protective coordination Discrimination & Cascading
The primary purpose of a circuit protection system is to prevent damage to series connected equipment and to minimize the area and duration of power loss. The first consideration is whether an air circuit breaker or molded case circuit breaker is the most suitable. The next is the type of system to be used. The two major types are: Discrimination and cascading.
Discrimination
Main breaker Comtinuous supply
According to IEC60947-2, the discrimination Total discrimination (total selectivity) Over-current discrimination where, in the presence of two over-current protective devices in series, the protective device on the Partial discrimination (partial selectivity) Over-current discrimination where, in the presence of two over-current protective devices in series, the protective device on the No discrimination In case of a fault, main and branch circuit
can be defined as follows. load side effects the protection without causing the other protective device to operate.
Branch breaker
Healthy circuit
Short-circuit point
load side effects the protection up to a given level of over-current, without causing the other protective device to operate. breakers open.
Main breaker
Branch breaker
Cascading
This is an economical approach to the use of circuit breakers, whereby only the main (upstream) breaker has adequate interrupting capacity for the maximum available fault current. The MCCBs downstream cannot handle this maximum fault current and rely on the opening of the upstream breaker for protection. The advantage of the cascade back-up approach is that it facilitates the use of low cost, low fault level breakers downstream, thereby offering savings in both the cost and size of equipment. As Susol TD & TS circuit breakers have a very considerable current limiting effect, they can be used to provide this cascade back-up protection for downstream circuit breakers.
Fault point
A-4-13
Technical information
Protective coordination Cascading, network 240V
Complementary technical information
Main: Susol UL TD Branch: Susol UL TD, TS
TD125NU 50 TD125HU 100 75 75 75 75 TS250NU 50 TS250HU 100 75 75 75 75 Main breaker Branch breaker Rated breaking capacity (kArms) TD125NU TD125HU Susol TS250NU TD & TS TS250HU TS400NU TS400HU TS800NU TS800HU 50 100 50 100 50 100 50 100
Main breaker Branch breaker Rated breaking capacity (kArms) TD125NU TD125HU Susol TS250NU TD & TS TS250HU TS400NU TS400HU TS800NU TS800HU 50 100 50 100 50 100 50 100
TS400NU 50 -
TS400HU 100 75 75 75 75 -
TS800NU 50 --
TS800HU 100 75
75 75 75 -
A-4-14
Technical information
Protective coordination Cascading, network 480V
Complementary technical information
Main: Susol UL TD Branch: Susol UL TD, TS
TD125NU 35 TD125HU 65 50 50 50 50 TS250NU 35 TS250HU 65 50 50 50 50 Main breaker Branch breaker Rated breaking capacity (kArms) TD125NU TD125HU Susol TS250NU TD & TS TS250HU TS400NU TS400HU TS800NU TS800HU 35 65 35 65 35 65 35 65
Main breaker Branch breaker Rated breaking capacity (kArms) TD125NU TD125HU Susol TS250NU TD & TS TS250HU TS400NU TS400HU TS800NU TS800HU 35 65 35 65 35 65 35 65
TS400NU 35 -
TS400HU 65 50 50 50 50 -
TS800NU 35 -
TS800HU 65 50 50 50 50 -
A-4-15
Technical information
Protective coordination Cascading, network 600V
Complementary technical information
Main: Susol UL TD Branch: Susol UL TD, TS
TD125NU 10 TD125HU 14 12 12 TS250NU 10 TS250HU 18 14 16 14 16 Main breaker Branch breaker Rated breaking capacity (kArms) TD125NU TD125HU Susol TS250NU TD & TS TS250HU TS400NU TS400HU TS800NU TS800HU 10 14 10 18 14 20 18 25
Main breaker Branch breaker Rated breaking capacity (kArms) TD125NU TD125HU Susol TS250NU TD & TS TS250HU TS400NU TS400HU TS800NU TS800HU 10 14 10 18 14 20 18 25
TS400NU 14 12 12 -
TS400HU 20 15 17 15 19 17 19 -
TS800NU 18 14 16 14 16 -
TS800HU 25 17 19 17 21 19 22 21 -
A-4-16
Technical information
Protective coordination Protection discrimination table, Discrimination
Complementary technical information
Main: TD125U (Thermal magnetic)
Branch breaker Main breaker Rating (A) 15 15 20 30 40 N 50 60 80 Susol TD & TS 100 Trip unitsThermal magnetic 125 15 20 30 40 H 50 60 80 100 125 150 160 N Susol TD & TS H 175 200 225 Trip unitsThermal magnetic 250 150 160 175 200 225 250 1.25kA 0.5kA 0.5kA 0.5kA 0.63kA 0.8kA 0.5kA 0.5kA 0.63kA 0.8kA 0.5kA 0.63kA 0.8kA 0.63kA 0.8kA 0.63kA 0.8kA 0.8kA 2kA 2kA 2kA 2kA 2kA 2kA T T 50kA 50kA 50kA 50kA 50kA 50kA 20 30 TD125NU/HU Trip units-Thermal magnetic 40 50 60 80 100 125 2kA 2kA 2kA 2kA 2kA 2kA 1.25kA 150 2kA 2kA 2kA 2kA 2kA 2kA 2kA 0.5kA 0.5kA 0.5kA 0.63kA 0.8kA 0.5kA 0.5kA 0.63kA 0.8kA 0.5kA 0.63kA 0.8kA 0.63kA 0.8kA 0.63kA 0.8kA 0.8kA
1.6kA 1.6kA
1.25kA 1.25kA T T 50kA 50kA 50kA 50kA 50kA 50KA T T 50kA 50kA 50kA 50kA 50kA 50kA
A-4-17
Technical information
Protective coordination SCCR according to UL489
MCCB
Motor hp (kW) 0.49 (0.37) 0.737 (0.55) 1.005 (0.75) 1.474 (1.1) 2.01 (1.5) 2.95 (2.2) 4.02 (3) 4.959 (3.7) 5.36 (4) 7.37 (5.5) 10.05 (7.5) 12.06 (9) 13.41 (10) 14.745 (11) 20.11 (15) A 1.8 Type TD125U
2.75
TD125U
15
MC-32
MT-32
2.5-4
3.5
TD125U
15
MC-32
MT-32
2.5-4
4.4
TD125U
15
MC-40
MT-63
4-6
6.1
TD125U
15
MC-40
MT-63
5-8
8.7
TD125U
15
MC-40
MT-63
9-13
11.5
TD125U
15
MC-40
MT-63
9-13
13.5
TD125U
15
MC-40
MT-63
12-18
14.5
TD125U
15
MC-40
MT-63
12-18
20
TD125U
20
MC-40
MT-63
16-22
27
TD125U
30
MC-40
MT-63
24-36
32
TD125U
40
MC-85
MT-95
28-40
35
TD125U
40
MC-85
MT-95
28-40
39
TD125U
40
MC-85
MT-95
34-50
52
TD125U
60
MC-85
MT-95
45-65
A-4-18
Technical information
Protective coordination SCCR according to UL489
MCCB
Motor hp (kW) 0.49 (0.37) 0.737 (0.55) 1.005 (0.75) 1.474 (1.1) 2.01 (1.5) 2.95 (2.2) 4.02 (3) 4.959 (3.7) 5.36 (4) 7.37 (5.5) 10.05 (7.5) 12.06 (9) 13.41 (10) 14.745 (11) 20.11 (15) 24.80 (18.5) 29.49 (22) 33.51 (25) A 1.03 1.6 2 2.6 3.5 5 6.6 7.7 8.5 11.5 15.5 18.5 20 22 30 37 44 52 Type TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U
Contactor Type MC-9 MC-9 MC-9 MC-32 MC-32 MC-40 MC-40 MC-40 MC-40 MC-40 MC-40 MC-40 MC-40 MC-40 MC-85 MC-85 MC-85 MC-85
Thermal overload relay Type MT-32 MT-32 MT-32 MT-32 MT-32 MT-63 MT-63 MT-63 MT-63 MT-63 MT-63 MT-63 MT-63 MT-63 MT-95 MT-95 MT-95 MT-95 Setting range (A) 1-1.6 1-1.6 1.6-2.5 2.5-4 2.5-4 4-6 5-8 6-9 7-10 9-13 12-18 16-22 16-22 16-22 24-36 28-40 34-50 45-65
A-4-19
Technical information
Protective coordination SCCR according to UL489
MCCB
Motor hp (kW) 0.49 (0.37) 0.737 (0.55) 1.005 (0.75) 1.474 (1.1) 2.01 (1.5) 2.95 (2.2) 4.02 (3) 4.959 (3.7) 5.36 (4) 7.37 (5.5) 10.05 (7.5) 12.06 (9) 14.745 (11) 20.11 (15) 24.80 (18.5) 29.49 (22) 33.51 (25) A 0.6 0.9 1.1 1.5 2 2.8 3.8 4.4 4.9 6.6 8.9 10.6 11.5 14 17.3 21.3 25.4 Type TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U TD125U
Contactor Type MC-9 MC-9 MC-9 MC-9 MC-32 MC-32 MC-32 MC-40 MC-40 MC-40 MC-40 MC-85 MC-85 MC-85 MC-85 MC-85 MC-85
Thermal overload relay Type MT-32 MT-32 MT-32 MT-32 MT-32 MT-32 MT-32 MT-63 MT-63 MT-63 MT-63 MT-95 MT-95 MT-95 MT-95 MT-95 MT-95 Setting range (A) 0.4-0.63 0.63-1 1-1.6 1-1.6 1.6-2.5 2.5-4 2.5-4 4-6 4-6 5-8 7-10 9-13 9-13 12-18 16-22 18-25 24-36
A-4-20
Technical information
How to calculate short-circuit current value Various short-circuit
The purpose of calculating short circuit values Selection of circuit breakers, fuse. Adjusting metering devices Consideration for mechanical resistance Consideration for thermal resistance Various value of short-circuit current should be applied to the tests for upper factors. Symmetrical current for AC and asymmetrical current for DC are used for classifying short circuit current. Their differences should be essentially considered in the basic step of making network plan. Symmetrical short-circuit current real value Short-circuit current is composed of AC and DC as it shows on <Fig.1>. The short-circuit which indicates the real value of AC is called as symmetrical short-current real value, l (rms)sym. This current is the essential factor of selecting MCCB, ACB, fuse.
AC+ DC (asymmetrical short-circuit current) DC AC
3-phases average asymmetrical shortcircuit current real value: l (rms)ave Each phase is different in its input current value in 3 phases circuit. So that AC rate for 3 phases is different. This value is the average of asymmetrical short-circuit current of 3 phases. And with symmetrical short-circuit current real value and short-circuit power factor, we can achieve the value, and 3-phases average asymmetrical short circuit current real value is calculated with this formula. l (rms)ave= (rms)sym l Maximum asymmetrical short-circuit current instantaneous value: lmax Each phase has different instantaneous current value. And when asymmetrical short-circuit current shows its maximum instantaneous value, the current value is called as maximum asymmetrical short-circuit current instantaneous value. This current is to test the mechanical strength of serial equipments. And with symmetrical short-circuit current real value and short-circuit power factor, we can achieve the value, and maximum asymmetrical short-circuit current instantaneous value is calculated with this formula. lmax= (rms)sym l
Maximum asymmetrical short-circuit current real value: l (rms)asym The short-circuit which indicates the real value of DC is called as asymmetrical short-circuit current real value. And this current value is changeable upon the short-circuit closing phase. This current value is treated for checking the thermal resistant strength of wrings, CT and etc. With symmetrical short-circuit current real value and short-circuit power factor, we can achieve the value, from <Fig.5>. and maximum asymmetrical short-circuit current real value is calculated with this formula. l (rms)asym= (rms)sym l
Network impedance for calculating shortcircuit current value Bellows should be considered for the calculation as the impedance components affecting circuit to trouble spot from shortcircuit power. a. Primary part impedance of incoming transformer Its calculated from the shortcircuit current data which is provided by power supplier. Calculated value can be regarded as reactance. b. Impedance of incoming transformer Its amount is upon the capacity of transformer and primary voltage. Generally this impedance can be regarded as reactance and refer to <Table.4>, <Table.5>.
A-4-21
Technical information
How to calculate short-circuit current value Various short-circuit
c. Reactance of motor Motor works as generator and supply short circuit current in the condition of an accident circuit such as <Fig.2>. Generation factor of firm motor should be considered in a low voltage circuit where a circuit breaker operates quickly and in a high voltage circuit for the selection of fuse. Reactance of motor can be regarded in the range of 25% normally. d. Distribution impedance Impedance of cable and busduct do control short-circuit remarkably in low voltage network. Refer to <Table.5>, <Table.6>. e. Others MCCB, ACB CT are equipments for the network of low voltage. The impedance of these equipment which is calculated from short-circuit current value should be considered. Generally, the impedance of those equipment is that of rated current (normal condition), if operators apply that impedance value, bigger reactance value may be applied to calculated short-circuit current value.
Interphase voltage Between RS Between ST 400V 30kW Short-circuit
A-4-22
Technical information
How to calculate short-circuit current value With percent impedance
Ohm formula (), percent impedance formula (%), unit formula (per unit) can be applied to calculate short-circuit current value. Ohm formula [] Short-circuit current value is calculated by converting into ohm value [] Percent impedance formula (%) Each impedance is converted into the impedance of base value and base voltage. And the required amount for electric demand should be shown as percent unit. And apply that value in ohm formula. Unit formula The base value equals 1.0. and all value of network shows in the way of decimal system. Applying any of upper calculation formulas to achieve short-circuit current value, it shows equal value. To select a certain formula for doing it, operator can select one of those formula which is proper to oneself. Below is percent impedance formula. Finding base value The rated current of transformer shall be the base value. Base capacity PB= PT kVA Base voltage VB= VT V Base current IB= IT = PT 103 A 3VT V V = PB103 PT103
2 B 2 T
Converting impedance into base value a. Primary part impedance of transformer: %X1 PB %X1= 100 % Q103
Q: Primary part short-circuit capacity
b. Impedance of transformer: %ZT It generally indicates as percent impedance. If base capacity is equal to transformer capacity, %ZT can be used as it is. When base capacity is not equal to transformer capacity, convert values by this formula. PT PB = %ZT %ZB
%: value converted by base value
1phase transformer should converted into the value of 3 phase transformer, And the percent impedance is equal to 3 2 calculated urgent value. c. Reactance of motor: %Xm Transformer capacity shows the value in kW, so it is converted into unit, kVA. (kVA value) 1.5(Output of motor, kW) %Xm= 25% Converting it from base capacity PB PM = %Xm %Xm
(Converting formula for different capacity)
d. Impedance of busduct, cable Cable: Area of cross-section & length Busduct: Rated current In <Fig.5>, <Fig.6> ZC = ( per each unit length)(length) [] Convert this value into % value. %ZC = ZC ZB
(% converting formula)
A-4-23
Technical information
How to calculate short-circuit current value
Preparing a impedance map Prepare impedance map according to the impedance value from (2). Various electricity suppliers like source, motor have same electric potential in impedance map. As you find it on <Fig.4> (a), extend it from the unlimited bus to fault point, draw impedance map.
Calculating impedance Calculate impedance as <Fig.4 (b)> in impedance map < Fig.4 (a)> %Z = %R + j %X %Z = (%R)2+ (%X)2
Calculating various short-circuit current value IF (3) = IF (rms)sym (3) = = P B10 3 100 3VB%Z IB 100 A %Z
Calculate various short-circuit current value with values from <Fig.5> like , , %R short-circuit power factor cos = %Z 3 phases average asymmetrical real value IF (rms)ave= (rms)sym IF Maximum average asymmetrical real value IF (rms)asym=IF (rms)sym Maximum asymmetrical instantaneous value IFmax= (rms)sym IF
A-4-24
Technical information
How to calculate short-circuit current value With a simple formula
For its special cases, calculating exact value should be needed, in the other hand, for the practical use, we recommend simple formula. Finding a base value It shall be the rated current of transformer. PB= PT [kVA] VB= VT [V] IB= IT [A] VTB [] ZB= PT103
Ref 1) Calculation in the random voltage E Voltage line which is mostly close to E shall be selected to calculate it . i.e. in case of 220V, (200V line value)200/220 Ref 2) Calculation for a certain impedance Zt (%) Impedance line which is mostly close to Zt (%) shall be selected to calculate it. i.e. 420V, Zt= 4.5% %Z=4% Line value (or 5% line) 4 (or 5)/4.5 Ref 3) When the value is out of lines or over 200VA or below 100kA, multiply 10 times to the calculated values. <Fig.7> Transformer capacity and short-circuit current <Fig.6> Base value
Short-circuit current from incoming circuit Disregard the impedance value of primary part of transformer. Calculate short-circuit current value according to <Fig.7>. (If the impedance value of primary part of transformer is considered, calculate the current value as below formula) IA (R)= IB (%RT)2+ (%X1+%XT)2 PB 100 [%] Q103 100 A
Short-circuit current to motor IA (M)= 4 (Rated current of motor) Symmetrical short-circuit current at point A IA= IA (R)+IA (M) Decreasing coefficient caused by busduct IA Obtaining the value of 10VT Calculate decreasing coefficient from <Fig.10> Decreasing short-circuit current by reactance When theres 1phase transformer in a certain circuit, calculate it in the base of reactance. Regarding the reactance as pre-impedance at source part at point of <Fig.8>, EB XC = 3 IC Reactance C~D: XD[] (impedance of 1 T)
%X1 =
A-4-25
Technical information
How to calculate short-circuit current value
Calculating the value of XD/XC and decreasing coefficient d from the reactance of <Fig.9>. Current at point D ID=dIC Impedance of 1 phase transformer XD= X (1) 1 2 a. Short-circuit current at EC voltage base ID (rms)sym3= dIC (rms)sym3 b. Short-circuit current at ED voltage base ID (rms)sym3= dIC (rms)sym3EC/ED
Coefficient d for cables ID Calculating the value of 10VT Decreasing coefficient b value is calculated from <Fig.13>. For insulator drawn wrings, we can find the value directly from <Fig.13>. Calculating symmetrical short-circuit current real value IF (rms)sym= bID[D] Various short-circuit current In case of having short-circuit current power factor, find , , from <Fig.5>, If not find 3 values from <Table.1> 3 phases short-circuit asymmetrical current average value IF IF (rms)ave= (rms)sym Maximum asymmetrical real value IF (rms)ave= (rms)sym IF Maximum asymmetrical instantaneous value IF (rms)ave= (rms)sym IF
<Table.2> , , values when short circuit power factor value is not definite.
Symmetrical short-circuit real value (A) Variables Maximum asymmetrical real value 3 phases short-circuit asymmetrical current average value Maximum asymmetrical instantaneous value
2.4110-4 1.31210-4 2.7410-4 0.75110-4 1.0210-4 1.26710-4 0.60710-4 0.9110-4 1.09410-4 0.41210-4 0.7210-4 0.83010-4 0.31510-4 0.6010-4 0.67810-4 0.26110-4 0.51610-4 0.57810-4 0.22110-4 0.44910-4 0.50010-4
2000 61252 0.12910-4 0.7910-4 0.80010-4 <Fig.10> Decreasing coefficient of general busduct (Cu)
A-4-26
Technical information
How to calculate short-circuit current value Calculation example
Calculation1) Short-circuit current value will be achieved by simple formula and percent impedance formula for <Fig.13>
<Fig.13>
Percent impedance formula (1) Base value PB = 750kVA VB = 420V IB = 1031A ZB = 0.237 (2) Each impedance a. Reactance at primary part of transformer %X1= 750 100= 0.075 % 1000103 e. Impedance of cable Converting impedance of whole metal tube [2100mm2 10m] % %RC1= 0.0001810 1 100= 0.38 0.237 2 1 %XC1= 0.0001310 100= 0.27 % 0.237 2 [125mm2 20m] % %RC2= 0.0001420 100= 1.18 0.237 %XC2= 0.0001320 100= 1.09 % 0.237 [250mm2 50m] % %RC3= 0.0000750 100= 1.47 0.237 %XC3= 0.0001350 100= 2.74 % 0.237 [14mm2 30m] % %RC4= 0.0001330 100= 16.45 0.237 %XC4= 0.0001530 100= 1.88 % 0.237
b. Impedance of transformer %RT= 1.4% %XT= 4.8% c. 1Tr impedance %RT1 = 1.15750 20 1.68750 %XT1 = 20 1 = 21.6 % 2 1 = 31.5 % 2
d. Reactance of transformer 750 1201.5 750 %Xm2 = 1401.5 750 %Xm3 = 1001.5 750 %Xm4 = 1151.5 %Xm1 = 25= 104 % 25= 89 % 25= 125 % 25= 108.7 %
A-4-27
Technical information
How to calculate short-circuit current value
(3) Preparing a impedance map Connect short-circuit supplier to the unlimited bus.
IF2 (rms)sym is short-circuit current. Therefore, convert it into 1 phase short-circuit current. 3 IF2 (rms)1sym= 7989 = 6919 A 2 39.06 = 0.72 cos2= 54.2
Unlimited bus
(6) Various short-circuit current Calculate from <Fig.5>. , , a. Fault point F1 cos1= 0.422 1.05 1.3 1.74 = = = IF1 (rms)ave= 1.0316900= 17407 A IF1 (rms)asym= 1.0516900= 17745 A IF1max= 1.7416900= 29406 A b. Fault point F2 cos2= 0.72 1.0 1.48 = = IF21 (rms)asym= 1.06919 A IF21max= 1.486919= 10240 A
<Fig.14>
Simple calculation formula (1) Base value PB = 750kVA VB = 420V IB = 1031A ZB = 0.237
<Fig.15>
a. Fault point F1
b. Fault point F2
(2) Short-circuit current of incoming circuit Disregard the impedance of primary part of transformer In <Fig.7> IA (R)= 20500 A (3) Short-circuit current of motor Sum of motor capacity= (120+140+100+115)1.5= 713 kVA IA (M) = 713 3420 4= 3920 A
%Z1=
(2.57)2+ (5.53)2
%Z2=
= 6.1[%]
= 54.2[%]
(5) Calculation of asymmetrical short-circuit current a. Fault point F1 1031 IF1 (rms)sym = 6.1 100= 16900 A 2.57 = 0.422 cos1 = 6.1 b. Fault point F2 (1 phase circuit) 1031 IF2 (rms)sym = 100= 1902 A (at 100V) 54.2 = 1031 100 420 = 7989 A (at 420V) 54.2 100
A-4-28
Technical information
How to calculate short-circuit current value Calculation example
(5) Decreasing short-circuit current for cable a. At point F1 2100mm2 10m 2100mm2 10m= 100mm2 5m IA 2024420 = = 29.1 10420 10E Coefficient b= 0.935 Short-circuit current value at point C Ic (rms)sym= 0.93524420= 22850 A 125mm2 20m IC 2022850 = = 108.9 10420 10E IF1 (rms) sym= 0.785244850= 17940 A b. At point F1 14mm2 30m IC 3024420 = = 174.4 10420 10E Coefficient b= 0.249 ID (rms)3sym= 0.2424420= 6080 A Decreasing by the reactance (1Tr)dp Convert the value of %X of 1Tr to base capacity XD= 7502/20= 75% Impedance of primary part at 1Tr XA = IB 1031 100 = 100[%] 6080 ID (6) Various short-circuit current Find , , from <Table.1> a. At point F1 1.25 1.13 2.17 = = = IF1 (rms)ave= 1.1317940= 20272 A IF1 (rms)asym= 1.2517940= 22425 A IF1max= 2.1717940= 38930 A b. At point F2 1.13 = 1.94 = IF21 (rms)asym= 1.137076= 7945 A IF21max= 1.947076= 13727 A
<Table.2> Comparison of short-circuit
Fault point
Symmetrical short-circuit current real value 3 phases average asymmetrical current real value Maximum asymmetrical current real value Percent impedance calculation value Simple formula calculation value Percent impedance calculation value Simple formula calculation value Percent impedance calculation value Simple formula calculation value
F1
F2
Convert XD to equivalent 3 phases, and XD/2 75026080 = = 2.21 XA 2021031100 Coefficient d of <Fig.9> d= 0.32 IF2 (rms)3sym= 0.326080=1945 A (400V) = 0.326080420/100 = 817 [A] (100V) IF2 (rms)1 sym= 8171 3 = 7076 A 2
A-4-29
Technical information
How to calculate short-circuit current value
Short-circuit current at point B: ISB a) Impedance Map Serial sum of impedance Ztot= 0.25+0.01+8= 8.26 %
B M 100kW M 200kW Tr2 100kVA 3.3kV/220V Z4=2.5% 20kWu=8.5% cos=0.8 1000kVA Z5=1.0% M 1000kVA Z5=1.0%
b) Short-circuit current ISC = 2118 A 33.3 kV 10008.26 Breaking capacity of breaker [MVA] MVA= 3 short-circuit current [kA] line to line voltage[kV] ISB= Short-circuit current at point C: ISC a) Impedance Map 1000 kVA 1000100
<Fig.16>
(1) Calculate rated current at each point Rated current InA at point A InA= 500 kVA 1000 36.6 kV 1000 Rated current InB at point B InB= 100 kVA 1000 33.3 kV 1000 InC= 20 kW 1000 3220 V 0.850.8 = 43.7 A
= 77.2 A
(2) Put 1000k VA for base capacity and calculate short-circuit current at each point. Short-circuit current ISA at point A a) Impedance Map
b) Short-circuit current ISC ISC= 1000 kVA 1000100 = 8055 A 3220 V 32.58 %
Incoming 25%
Calculation formula
Z=0.25(%)
Rated current In =
Short-circuit current Is =
Breaking capacity of breaker [MVA] MVA= 3 short-circuit current[kA] line to line voltage[kV]
A-4-30
Technical information
How to calculate short-circuit current value Combination of transformer and impedance
<Table. 3> Combination of transformer and impedance
Transformer Impedance 3 phases transformer 6.3kV/210V Oil Tr. 6.3kV/210V Mold Tr. 20kV/420V Mold Tr. 20kV/420V Oil Tr. XT[%] ZT[%] RT[%] XT[%]
Transformer capacity (VA) ZT[%] RT[%] XT[%] ZT[%] RT[%] XT[%] ZT[%] RT[%] 20 2.19 1.94 1.03 30 2.45 1.92 1.53 4.7 2.27 4.12 50 2.47 1.59 1.89 4.7 1.94 4.28 75 2.35 1.67 1.66 4.4 1.56 4.11 100 2.54 1.65 1.96 4.6 1.5 4.24 150 2.64 1.64 2.07 4.2 1.29 4.0 200 2.8 1.59 2.31 4.5 1.17 4.35 300 3.26 1.46 2.92 4.5 1.2 4.33 500 3.61 1.33 3.36 4.7 0.08 4.69 5.0 1.56 750 4.2 1.55 3.9 6.0 0.8 5.95 5.0 1.40 1000 5.0 1.35 4.82 7.0 0.7 6.96 5.0 1.26 1500 5.1 1.22 4.95 7.0 0.6 6.97 5.5 1.2 2000 5.0 1.2 4.85 7.5 0.65 7.47 5.5 1.1
ZT[%] RT[%] XT[%] ZT[%] RT[%] XT[%] 14.9 14.0 14.8 13.6 11.0 8.87 7.70 5.75 5.08 5.05 4.03 4.55 4.29 3.26 2.72 2.33 2.04 1.90 14.9 14.0 14.8 13.6 11.0 8.85 7.68 5.69 4.97 4.92 3.93 4.50 4.22 3.18 2.81 2.18 1.82 1.60 0.268 0.503 0.523 0.494 0.558 0.562 0.571 0.619 1.05 1.16 0.904 0.637 0.768 0.725 0.775 0.823 0.937 1.02
0.00031
0.00026
2.5 2.37 2.57 2.18 2.05 2.27 2.48 3.39 3.15 2.23 4.19
2.07 1.84 1.76 1.58 1.47 1.46 1.49 1.31 1.31 1.28 1.09
1.40 1.49 1.87 1.50 1.42 1.74 1.98 3.13 2.87 2.96 4.03
0.00022
<Remark1> At 60Hz, the reactance multiply 2 times itself, so 1/2 reactance of primary part can achieve IB. <Remark2> When the cable is parallelly 2 or 3ea, reactance and resistance can be calculated in the condition of 1/3 and 1/3 length cable.
A-4-31
Technical information
How to calculate short-circuit current value Various short-circuit
<Table.6> Impedance sample of bus and busduct (50Hz)
Ampere rating (A) 600 800 1000 1200 1350 1500 1600 2000 2500 3000 3500 4000 4500 5000 50Hz R 1.257 0.848 0.641 0.518 0.436 0.378 0.360 0.286 0.218 0.180 0.143 0.126 0.120 0.095 X 0.323 0.235 0.185 0.152 0.129 0.113 0.107 0.084 0.065 0.054 0.042 0.038 0.036 0.028 Z 1.297 0.879 0.667 0.540 0.454 0.394 0.375 0.298 0.228 0.188 0.149 0.131 0.125 0.099 R 1.385 0.851 0.645 0.523 0.443 0.386 0.367 0.293 0.221 0.184 0.146 0.129 0.122 0.098 60Hz X 0.387 0.282 0.222 0.183 0.155 0.135 0.128 0.101 0.078 0.064 0.051 0.045 0.043 0.034 Z 1.438 0.896 0.682 0.554 0.469 0.409 0.389 0.310 0.235 0.195 0.155 0.136 0.130 0.103
[10-4/m]
[10-4/m]
Z 1.078 0.879 0.606 0.468 0.384 0.384 0.328 0.273 0.192 0.164 0.143 0.126 0.109 0.096 0.091 0.077
A-4-32
Technical information
How to calculate short-circuit current value Calculation example
Using a certain graph, you can find and calculate the short-circuit current value which is at one position of network. No matter the condition of network is different, you can do the calculation through adjusting variables. Graph note P coordinatesTransformer capacity (kVA) Is 1 coordinatesShort-circuit current value (kA) Is 2 coordinatesShort-circuit current value affected cable condition (kA) Line - % impedance of transformer (%) Line - Length of cable (m) Line - Square mm of cable (mm2) Line - Is2 (kA)
Remark) line shows the length of hard vinyl cable (600V IV)
How to calculate short-circuit current value (1) 3 phases transformer Short-circuit current value at (A) where it is just below transformer. At P coordinates, find the coordinates value (g) of the cross point (f) which is from transformer capacity (e) and A line. Disregard primary part impedance of transformer. Find the short-circuit current value at Point B, C which are considered cable impedance. At short-circuit current g (kA) of Is 1 coordinates, find the value (h) of B line Move (h) to parallel direction of Is, and find the cross point (i) to C line. Move (i) to parallel direction of Is2, and find the cross point value (j) to D line (g), finally find (k) of Is2
(2) 1 phase transformer Short-circuit current value where it is just below transformer. Find the value as same as that of 3 phase transformer and multiply it 3 times. (gkA) Find the short-circuit current value where it is considered cable impedance. Multiply 2/3 times to g of Is coordinates Find the Is2 value as same as that of 3 phase transformer and multiply it 3/2 times.
Remark 1. Its not considered the transformer contribution. Multiply 4 times the rated current of transformer in cases. 2. The real short-circuit current value is littler lower that its calculated value by the way we suggest because we take the rated voltage as AC200V, 400V. So the current value should be calculated in the consideration of stability 3. The calculated value is symmetrical real value.
A-4-33
Technical information
A-4-34
Technical information
How to calculate short-circuit current value Calculation graph
(1) Short-circuit current value at point A (ISA) At P coordinates, find (f) which is the point which is to match transformer capacity 500kVA and A line. Then move (f) to Is1 (2) Short-circuit current value at point B (ISB) Find value h of B line (20mm) at g (= 29kA) of Is1 coordinates Move h parallely to the direction of Is1, and find value I at the cross point with C line (200mm) direction and finally find (g). ISA= 29kVA (g)
Move I parallely to the direction of Is2, and find value j at the cross point with D line (g= 29kA) ISB= 19kA (k)
B length of cable
A-4-35
Technical information
(3) Short-circuit current value at point C (ISC) Find Is1 coordinates value (19kA) of short-circuit current value k (= 19kA) at Point B. and find cross point m between 19kA and B line. Move m parallely to the direction of Is1 coordinates, and find the cross point n at C line (30mm). Move n parallely to the direction of Is1 and find the cross point p of Is2with D line. Isc= 10kA (g)
A-4-36
Susol TD and TS circuit-breakers can be directly connected to the mounting plate. If busbars or terminals are used to connect the circuit breaker on the back of the mounting plate, the appropriate safety clearances must be observed.
TS250U
TS400U
TS800U
2Pole:4EA(M5L16) 2Pole:4EA(M8L20) 3Pole:6EA(M5L16) 3Pole:6EA(M8L20) Torque: Max 78kgfcm Torque: Max 147kgfcm
A-5-1
Conductor (mm)
23
M820
22
>8
10 22
10 25
25
Max 147kgfcm
TS400U
30 M10L30 15 26.1
12
51
15 3745 19
12
3745
26
=
50
=
50
=
50
Max 630kgfcm
A-5-2
When installing a circuit breaker, safety clearances must be kept between the breaker and panels, bars and other protection devices installed nearby. These safety clearances are depend on the ultimate breaking capacity and are defined by tests carried out in accordance with standard IEC 60947-2.
When a short circuit interruption occur, high temperatures pressures are present in and above the arc chambers of the circuit-breaker. In order to allow the pressure to be distributed and to prevent fire and arcing or short-circuit currents, safety clearances are required.
A(mm) 415V TD125NU TD125NH TS250UN TS250UH TS400UN TS400UH TS800UN TS800UH 35 35 35 35 60 60 100 100 240V
A A
30 30 30 30 50 50 80 80
F
C1: Minimum distance for superimposed circuit breakers (from lower circuit breaker to uninsulated part of terminal of upper circuit breaker) C: C1+ the dimension of exposed conducting part (The dimension of exposed conduct)
C1(mm) 415V TD125NU TD125NH TS250UN TS250UH TS400UN TS400UH TS800UN TS800UH 35 35 35 35 60 60 100 100 240V 30 30 30 30 50 50 80 80
C1
C1
A-5-3
C1
D: Insulated length of main terminal of circuit breaker D1: Connection by ring terminal after taping (Larger than the dimension of exposed conducting part) D2: Connection by bar after taping D3: Connection by ring terminal using insulation barrier (Larger than the dimension of exposed conduct D4: Connection by bar using insulation barrier
D1 (mm) The dimension of exposed conduct + 20 TD125NU TD125NH TS250UN TS250UH TS400UN TS400UH TS800UN TS800UH
50
Note) If uninsulated conductors are used for connection, please insulate by taping to the point where the conductors overlap with the insulation barrier or to the root of the circuit breaker.
E(mm) 415V TD125NU TD125NH TS250UN TS250UH TS400UN TS400UH TS800UN TS800UH 25 25 25 25 20 20 45 45 240V 15 15 15 15 15 15 20 20
A-5-4
A-5-5
TD125U TS250U
35 35
M475
25 2 90 90
35
TS400U
60 M575
20
90 90
60
TS600U
100 M6100
45 90 90
100
Note) In case of using long or short terminal covers, no need to consider on minimum center distance for two horizontally installed circuit-breakers.
A-5-6
Current-limiting curves
240V 480V 600V
A-6-11 A-6-12 A-6-13
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TD125U
FTU FMU 15~125A
FTU:Ir=1In FMU:Ir=0.8~1In
In:15A -> Im=400A In:20A -> Im=400A In:30A -> Im=400A In:40A -> Im=400A
0.5
0.8 1
5 6 7 8 10
20
30
40 50
70
100
200
300
A-6-1
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS250U
FTU FMU 150~250A
FTU:Ir=1 In FMU:Ir=0.8~1In
FTU/FMU:Im=10In
A-6-2
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS250U
ATU 160~250A
ATU:Ir=0.8~1In
ATU:Im=5~10In
0.5
A-6-3
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS400U
FTU FMU 300~400A
FTU:Ir=1 In FMU:Ir=0.8~1In
FTU/FMU:Im=10 In
A-6-4
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS400U
ATU 300~400A
ATU:Ir=0.8~1In
ATU:Im=5~10 In
A-6-5
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS800U
FTU FMU 500~800A
FTU:Ir=1 In FMU:Ir=0.8~1In
FTU/FMU:Im=10In
A-6-6
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS800U
ATU 500~800A
ATU:Ir=0.8~1In
ATU:Im=5~10 In
A-6-7
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TD125U
MCS 125A
TS250U
MCS 250A
Thermal withstand
TS400U
MCS 400A
TS800U
MCS 800A
MCS Type 125A:1250A 250A:2500A 400A:4000A 800A:8000A
0.1
A-6-8
Characteristics curves
Specific let-through energy curves
240V
Thermal stress
A-6-9
Characteristics curves
Specific let-through energy curves
480V
Thermal stress
A-6-10
Characteristics curves
Specific let-through energy curves
600V
Thermal stress
A-6-11
Characteristics curves
Current-limiting curves
240V
Peak current
A-6-12
Characteristics curves
Current-limiting curves
480V
Peak current
A-6-13
Characteristics curves
Current-limiting curves
600V
Peak current
A-6-14
A-7. Dimensions
TD125U TS250U TS400U TS800U Flange handle Extended rotary handle Mechanical interlocking device
MIT13, MIT23, MIT33, MIT43
A-7-1 A-7-2 A-7-3 A-7-4 A-7-5 A-7-6 A-7-7
A-7-8
Overall dimensions
TD125U
Dimensions : inch [mm]
1.496 (38)
2.362 (60)
0.964 (24.5)
0.196 (5)
0.629 (16)
3.937 (100)
7.007 (178)
Terminal section
4.318 (109.7)
Conductor
2.5 (63.5)
0.69 (17.5)
1.259 (32)
4.921 (125)
A-7-1
1.102 (28)
2.677 (68)
Overall dimensions
TS250U
Dimensions : inch [mm]
0.81 (20.45)
1.496 (38)
2.362 (60)
0.192 (4.9)
6.456 (164)
0.578 (14.7)
Terminal section
Conductor
2.519 (64)
A-7-2
Overall dimensions
TS400U
Dimensions : inch [mm]
3.267 (83)
2.795 (71)
4.015 (102)
1.496 (38)
0.314(8)
11.496 (292)
6.353 (166)
1.082 (27.5)
Terminal section
Conductor
7.874 (200)
0.885 (22.5)
A-7-3
Overall dimensions
TS800U
Dimensions : inch [mm] 5.846 (148.5) 5.511 (140) 8.267 (210) 3.149 (80) 2.125 (54) 4.566 (116) 3.543 (90)
3.279 (83.3)
0.433 (11)
1 (25.4)
2.125 (54)
7.818 (198.6)
16.85 (428)
1.862 (47.3)
4.685 (119)
Terminal section
Conductor
10.944 (278)
4.566 (116)
A-7-4
Overall dimensions
TD125U
Dimensions : inch [mm] 14.5 (368.3) Min 14.5(368.3) Max 26.5(673.1)-Shaft 24inch
Panel drilling
Way of installation
4.21 (107)
2.68 (68)
(5
.5
A-7-5
0.
21
0.433 (11)
0.531 (13.5)
17 0. 7 . (4 5)
2. 01 1) (5
Overall dimensions
TS250U
Dimensions : inch [mm] 14.54 (369.3) Min 14.54 (369.3) Max 26.54 (674.1)-Shaft 24inch
Panel drilling
Way of installation
0.
17
1.39 (35.3)
7 (4 .5
1.38 (35)
)
4.90 (124.4)
2.68 (68)
2.0
0.79 (20)
1( 51 )
0 .23 6( 6)
0.433 (11)
A-7-6
Overall dimensions
TS400U
15.93 (404.6) Min 15.93 (404.6) Max 27.93 (709.4)-Shaft 24inch Dimensions : inch [mm]
Panel drilling
Way of installation
1.39 (35.3)
0. 17 7
1.83 (46.5)
(4 .5 )
7.87 (200)
2.68 (68)
2.
1.39 (35.4)
01 (5 1)
A-7-7
.27
6 (7
0.433 (11)
Overall dimensions
TS800U
17.42 (442.5) Min 15.93 (404.6) Max 27.93 (709.4)-Shaft 24inch Dimensions : inch [mm]
Panel drilling
0.
Way of installation
2.22 (56.3)
17
(4
2.76 (70)
.5 )
10.94 (278)
2.68 (68)
0.57 (14.5)
2.0
1(
51
(7 )
0.
27
0.433 (11)
A-7-8
Overall dimensions
TD125U
Dimensions : inch [mm]
0.433 (11) 4.251 (108) 4.685 (119) 1.18 (30) 4.212 (107)
Panel drilling
Way of installation
E MAX F "UP"
Enclosure 60 cable 17 17 17 17 16 14 11 6 31 31 28 28 26 26 24 21
F "DOWN"
A-7-9
Overall dimensions
TS250U
Dimensions : inch [mm]
2.5 (63.5)
1.377 (35)
4.921 (125)
Panel drilling
Way of installation
E MAX F "UP"
F "DOWN"
Enclosure 60 cable
A-7-10
Overall dimensions
TS400U
Dimensions : inch [mm]
1.83 (46.5) 0.433 (11) 7.874 (200) 4.251 (108) 4.685 (119)
Panel drilling
E MAX F "UP"
Way of installation
F "DOWN"
Enclosure 60 cable
A-7-11
Overall dimensions
TS800U
Dimensions : inch [mm]
2.755 (70)
10.944 (278)
Panel drilling
E MAX
Way of installation
F "UP"
Enclosure 60 cable 17 17 17 17 16 14 11 6 31 31 28 28 26 26 24 21
F "DOWN"
A-7-12
Overall dimensions
Mechanical interlocking device
MIT13, MIT23, MIT33, MIT43
[mm]
5~8mm
30mm
A-7-13
Overall dimensions
Mechanical interlocking device
Mounting dimension for MIT
[mm]
C
E(mm) 30 35 46.5 70
A-7-14
S u p e r
S o l u t i o n
HEAD OFFICE
Yonsei Jaedan Severance Bldg. 84-11, 5ga, Namdaemun-ro, Jung-gu, Seoul 100-753, Korea Tel. (82-2)2034-4870 Fax. (82-2)2034-4713 http://www.lsis.biz
Cheong-Ju Plant
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku, Cheong Ju, 361-720, Korea Tel. (82-43)261-6001 Fax. (82-43)261-6410
Specifications in this catalog are subject to change without notice due to continuous products development and improvement.
080601 / STAFF
2008.6 LS Industrial Systems Co.,Ltd. All rights reserved.