Professional Documents
Culture Documents
Case study - 1
Professor Charles Q. Su
( PhD, Fellow IET, SM IEEE, CIGRE A2 )
Prof. Charles Q. Su
Prof. Charles Q. Su
Ron E James & Q. Su Condition Assessment of HV Insulation in Power System Equipment - IET Power and Energy Series No.53, April 2008
Prof. Charles Q. Su
Prof. Charles Q. Su
Prof. Charles Q. Su
Ts 0
We arout period
Prof. Charles Q. Su
Background
There are over 3,700 km of 6.6kV cables in a utility. The average failure rate from 2000 - 2004 was 30 cables per year. Serious consequences: 1. In-service failures of 6.6kV cables cause local blackout. 2. Due to the time of failure (e.g. at mid-night) and the possible bad weather conditions at failure (e.g. thunder storm), restoration of power supply is difficult and could take many hours. There was an urgent need to reduce the in-service failures.
Prof. Charles Q. Su
21 25 yrs 22kV Cable Length : 4,948.379 km 16 20 yrs 11 15 yrs 6 10 yrs < = 5 yrs
6% (288.551 km) 13% (668.678 km) 25% (1,218.271 km) 34% (1,694.035 km) 22% (1,078.844 km)
> 30 yrs 0.07% (2.682 km) 26 30 yrs 6.6kV Cable Length : 3,768.647 km 21 25 yrs 16 20 yrs 11 15 yrs 6 10 yrs < = 5 yrs 15% (583.758 km) 0.35% (13.109 km) 9% (323.093 km) 14% (541.152 km) 25% (954.976 km) 36% (1,349.877 km)
20
40
60
80
100 (%)
Prof. Charles Q. Su
Year
76 47%
Joint
Year
Average 28 years
Implication: Cable joint can fail at any time due to mainly poor workmanship, as well as bad quality of materials and insulation ageing
The Petroleum Institute Prof. Charles Q. Su
15
Prof. Charles Q. Su
Effectiveness of Megger Test Detect the leakage caused by terminal contamination (surface crapping resistance) Water seepage to the joint Insulation deterioration (ageing), especially paper/oil cables
16
Prof. Charles Q. Su
For example:
Water tree contamination (before electric tree is established)
Bubbles and unbridged cracks in XLPE or epoxy insulation
17
Prof. Charles Q. Su
Also, in this utility a number of 6.6kV cables of high megger reading failed in the past.
18
Prof. Charles Q. Su
Case (2)
A 66kV XLPE cable under a bus stop failed; It was found that the failure was due to an early damage caused by sinking an earthing rod; Lost about 1/3 of the XLPE insulation
19
Prof. Charles Q. Su
A close look
20
Prof. Charles Q. Su
A surprise
It was found that the bus stop was built five years before the failure. So, after the bad damage, the poor cable survived five more years before its insulation broke down;
More surprisingly .
Its insulation resistance was measured three times during the five years, always giving high megger readings!
21
Prof. Charles Q. Su
Why megger tests could not detect the incipient fault (damage)?
XLPE insulation has a very large volume resistivity of 1016 .cm. The damage did not bridge the insulation. Water trees do not affect insulation resistance before electric treeing is established across the electrodes.
22
Prof. Charles Q. Su
10
Comparison of megger readings between phases; Trend analysis; Stability of insulation resistance reading under dc high voltage. Add polarisation index measurement in the analysis (PI = R10min / R1min)
23
Prof. Charles Q. Su
Prof. Charles Q. Su
11
These test voltages and time are in line with the new IEEE Standard on VLF tests IEEE Std 400.2TM 2004. The IEEE/EPRI/CEA and other world engineering bodies recommended test level for MV extruded cables is two to three times line to ground voltage for 15-60 minutes.
Prof. Charles Q. Su
12
50
Number of failures
28
Prof. Charles Q. Su
540
97
100%
18%
29
Prof. Charles Q. Su
13
2003
2004
2005
2006
Why Cable Still Fails after Passing VLF Test? Total Circuits Tested Failed During VLF Tests Failed in Service after VLF Tests
540
97
20
100%
18%
3.7%
31
Prof. Charles Q. Su
14
18 16 14 12 10 8 6 4 2 0 XLPE
2 1 17
PILC
Joint
32
Prof. Charles Q. Su
25 20
Year
15 10 5 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
33
Prof. Charles Q. Su
15
34
Prof. Charles Q. Su
Cable sheath
XLPE insulation
Conductor
16
Voltage
50Hz 0.1Hz Cos-rectangular 0.1Hz Sine
17
Year
5 PILC
4 XLPE
3 Joints
Ave Age = 30
Ave Age = 22
Ave Age = 6
39
Prof. Charles Q. Su
18
40
Prof. Charles Q. Su
41
Prof. Charles Q. Su
19
42
Prof. Charles Q. Su
43
Prof. Charles Q. Su
20
TEST VOLTAGES FOR 6.6KV AND 22KV XLPE CABLES Selection consideration: Recommended by standards From utilities experiences
Prof. Charles Q. Su
Prof. Charles Q. Su
21
AC 50/60Hz test voltage and time are determined by agreement between the purchaser and the contractor
EUROPEAN STANDARD
(for PE and XLPE cables from 6kV to 36kV)
Frequency 0.1 Hz 50 Hz
Test voltage
(rms)
3 x Uo 2 x Uo
European Standard for cable after laying test CENELEC HD 620 S1 AND 621 S1 15 European countries signed the harmonization document 620 S1 and 621 S1 in 1996
22
VLF test voltage and duration adopted by some utilities in North America
Age of cable Test voltage (RMS) 6.6kV Newly installed 1~10 years old 10~30 years old 12kV (3.1Uo) 9.5kV(2.5Uo) 6.5kV(1.7Uo) 22kV 38kV (3.0Uo) 32kV (2.5Uo) 22kV (1.7Uo)
Note:
5
8 15 25 35
10 (14) - 3.5Uo
13 (18) 2.8Uo 20 (28) 2.3Uo 31 (44) 2.15Uo 44 (62) 2.2Uo
7 (10) 2.4Uo
10 (14) 2.2Uo 16 (22) 1.85Uo 23 (33) 1.6Uo 33 (47) 1.6Uo
23
RECOMMENDATIONS
(for 6.6kV and 22kV cable after laying tests) Insulation resistance test at 5kV - Purpose: detect poor workmanship and joint/terminal insulation leakage VLF tests at 2Uo RMS for 60 minutes - Purpose: flush-out insulation defects. If failed during VLF test, after repair the cable should be VLF tested again regardless of the insulation resistance. If necessary*, oscillating wave and PD mapping tests could be carried out at the following peak voltages: 1 Uo, 1.5 Uo and 2 Uo. - Purpose: detect and locate defective joints and insulation weakness
* Criteria of PD level to be determined
Prof. Charles Q. Su
Prof. Charles Q. Su
24
DC component in AC leakage current - water tree detection Propagation characteristic spectroscopy - LV pulse attenuation versus frequency - For insulation ageing detection - Can apply to in-service cables AC superposition test (101Hz) - Detect the 1 Hz component - Detect water tree
Prof. Charles Q. Su
SUGGESTIONS
Apply VLF tests to old PILC cables (age>20) For XLPE cables
if 200M<M<1000M and the ratio between the highest and lowest phases is <5, dont do VLF test. If M>1000M, dont do VLF test. If age > 15, dont do VLF test.
58
Prof. Charles Q. Su
25
CONCLUSIONS
VLF Test has been successful in reducing 6.6kV cable failures and should be used according to the total insulation condition of the cable and joint assets. Review the test procedure and failures every two years. Some defects, especially those in cable joints, could be detected by PD mapping, during either VLF or OW tests.
59
Prof. Charles Q. Su
Case study - 2
60
Prof. Charles Q. Su
26
Background
A new installation of transformer and cable termination The failure of yellow phase terminal occurred only 10 days after commissioning The failure caused an explosion and fire The transformer/cable terminal box was destroyed The transformer was significantly damaged About a quarter of the city was blackout
61
Prof. Charles Q. Su
Case study - 3
Three 230kV Cables Failed After Only 3 Years Operation - Caused by a Design Problem
Professor Charles Q. Su
( PhD, Fellow IET, SM IEEE, CIGRE A2 )
62
Prof. Charles Q. Su
27
Background
230kV 2000 mm2 XLPE cable, circuit length 7.2 km Installed in the middle of 2000 by a consortium of three manufacturers
63
Prof. Charles Q. Su
Background
cont
64
Prof. Charles Q. Su
28
Questions
Are the failures due to mechanical damage? Are they isolated failures? If not due to cable damages, what are the possible root causes? How to prevent the recurrence of the type of failures
65
Prof. Charles Q. Su
Case study - 4
66
Prof. Charles Q. Su
29
Background
Failures of two 230kV XLPE cable joints during HV ac commissioning tests. The cable and joints were made by different manufacturers. The cable joints were rubber pre-moulded joints. Cable Joint A: circuit I, Red phase, joint bay 5/6: PDs were detected under 1.1Uo, PD inception voltage 120kV (0.9 Uo). In Red phase, circuit II, joint bay 2/3: The joint failed at 27kV (0.2 Uo) during HV ac tests.
67
Prof. Charles Q. Su
69
Prof. Charles Q. Su
30