1 60 40152 - 13/09/2011
Couplings : Standard : Three-phase transformer : Step-down Dyn11 - Step-up YNd1 single-phase transformer :Ii0 Specific : Three-single transformer, Leblanc three-two transformer, other couplings on request.
CONNEXION: Primary and secondary connesion on copper slots, by the upper side of the transformer.
STANDARD ACCESSORIES : Empty setting plugs : Three outputs on slots. Two earthing switches. Lifting lugs. Four rollers for 10 kVA and higher power rating transformers.
NOTE : Transformers mechanical and electrical characteristics are the same for step-down or step-up transformers. The tranformers are not reversible. Step-up transfrormers are built so that inrush currents are limited.
Single-phase transformer, TMAI type, with IP21 encolsure, fuse terminal 3200 V and locking.
CONSTRUCTION : Magnetical circuits with crystal made sheet metal, oriented, with low losses. Copper or aluminium windings, impregnated vacuum with a fungicide varnish, class H impregnation. Metallic flanges. Ironed chassis with rollers. Wooden terminals plate bakelised. Cooling Use Color : in natural air : NA. : use in dry, air conditioned rooms, at a room temperature of -15 C ; + 40C. : RAL 7035 gray.
STANDARDS AND TESTS : Conforms to NFC 17200 - NFC 52100 - CEI 76 standards. Other specifications on request. Routine tests U.T.E made on each transformer, specific tests on request..
Connexion plates
rollers Side panel dismantling (cables passage) Fixation by screw Baklite matter To be screwed on request Signaletic plate Firm plate LV side dismantling panel 3
CONNEXION : Primary and secondary connexions on copper plates, by the upper side of the transformer.
STANDARD ACCESSORIES : Voltage tapping adjustable out of voltage : +/- 2,5 % or +- 5% output on slots. Two earthing terminals. Lifting lugs. Four rollers for 10 kVA and higher power rating transformers. Naked presentation on frame : IP00.
OPTIONAL ACCESSORIES Painted sheet metal enclosure with natural airing upwards, IP 21. Connexion on pluggable terminals 3200 V or 5500 V. HRC fuses protection integrated above the protection envelop. Thermal protection by thermal probe integrated to windings, one or two thresholds protection. Tap changers +/- 2,5 % +/- 5%. Keyhole locking of the protection envelop and or pluggable terminals. NOTE : Transformers mechanical and electrical characteristics are the same for step-down or step-up transformers. The tranformers are not reversible. Step-up transfrormers are built so that inrush currents are limited.
ELECTRICAL CHARACTERISTICS
Power rating (kVA) Copper losses at 75C (W) Iron losses (W) Voltage drop (% ) at Cos = 0.83 CC tension (%) at 75C Empty current (%) 16 25 32 50 63 80 100 125 160 200 250 400 500 630
STANDARD ACCESSORIES : Voltage tapping adjustable out of voltage : +/- 2,5 % ou +- 5% sorties sur plages. Two earthing terminals. Lifting lugs. Four rollers for 10 kVA and higher power rating transformers. Naked presentation on IP00 frame.
OPTIONAL ACCESSORIES Painted sheet metal enclosure with natural airing upwards, IP 21. Connexion on pluggable terminals. HRC fuses protection integrated above the protection envelop. Thermal protection by thermal probe integrated to windings, one or two thresholds protection. Tap changers +/- 2,5 % +/- 5%. Keyhole locking of the protection envelop and or pluggable terminals. NOTE : Transformers mechanical and electrical characteristics are the same for step-down or step-up transformers. The tranformers are not reversible. Step-up transfrormers are built so that inrush currents are limited.
ELECTRICAL CHARACTERISTICS
Power rating (kVA) Copper losses at 75C (W) Iron losses (W) Voltage drop (% ) at Cos = 0.83 Cc tension (%) at 75C Empty current (%) 5 100 40 2.92 2.95 3.11 7,5 120 60 2.47 2.67 2.53 10 170 60 3.35 3.75 2.58 16 380 80 3.7 3.86 2.67 25 500 120 3.53 3.78 2.52 32 630 150 3.55 4 2.54 50 750 200 3.7 4 2.51
With constant improvements, the manufacturer may alter information without prior warning