PRODUCT LEAFLET

DRY TYPE TRANSFORMER


Single-phase, three-single, three-two and three-phase transformers 1.1 kV to 7.2 kV classes

1 60 40152 - 13/09/2011

Dry Type Transformers


Transformers meant to be installed in a dry and air conditioned room or in a PTI AUGIER type substation.
ELECTRICAL CHARACTERISTICS : Power rating and type : Single-phase : TMAI : 5 - 7.5 - 10 - 16 - 25 - 32 - 50 kVA Three-single : TTMAI : 16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 kVA Three-two : TTBAI : 16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 kVA Three-phase : TTAI : 16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 - 200 250 - 400 - 500 - 630 kVA Insulation voltage : 1.1 kV - 3.6 kV - 7.2 kV Primary voltage : Every voltage compatible with insulation voltages above. Usually standard voltages are : 230 V - 400 V - 950 V - 3200 V - 5500 V and 6600 V. Secondary load voltage : 230 V - 400 V - 950 V - 3200 V - 5500 V and 6600 V.

Couplings : Standard : Three-phase transformer : Step-down Dyn11 - Step-up YNd1 single-phase transformer :Ii0 Specific : Three-single transformer, Leblanc three-two transformer, other couplings on request.

Manufacturing specifications on request : Inrush current transformer reduced or very reduced.

CONNEXION: Primary and secondary connesion on copper slots, by the upper side of the transformer.

STANDARD ACCESSORIES : Empty setting plugs : Three outputs on slots. Two earthing switches. Lifting lugs. Four rollers for 10 kVA and higher power rating transformers.

NOTE : Transformers mechanical and electrical characteristics are the same for step-down or step-up transformers. The tranformers are not reversible. Step-up transfrormers are built so that inrush currents are limited.

Single-phase transformer, TMAI type, with IP21 encolsure, fuse terminal 3200 V and locking.

CONSTRUCTION : Magnetical circuits with crystal made sheet metal, oriented, with low losses. Copper or aluminium windings, impregnated vacuum with a fungicide varnish, class H impregnation. Metallic flanges. Ironed chassis with rollers. Wooden terminals plate bakelised. Cooling Use Color : in natural air : NA. : use in dry, air conditioned rooms, at a room temperature of -15 C ; + 40C. : RAL 7035 gray.

STANDARDS AND TESTS : Conforms to NFC 17200 - NFC 52100 - CEI 76 standards. Other specifications on request. Routine tests U.T.E made on each transformer, specific tests on request..

Dry type transformer, naked presentation on frame

Connexion plates

Tap changer MV side view

LV side dismantle panel Fixation by screw

Lifting lugs Connexion plates

Dry type transformer With IP21 enclosure

rollers Side panel dismantling (cables passage) Fixation by screw Baklite matter To be screwed on request Signaletic plate Firm plate LV side dismantling panel 3

Three-phase dry Type Transformers TTAI


ELECTRICAL CHARACTERISTICS : Power rating: 16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 - 200 - 250 - 400 - 500 - 630 kVA Insulation voltage : 1.1 kV - 3.6 kV - 7.2 kV Primary voltage : Every voltage compatible with insulation voltages above. Usually standard voltages are : 230 V - 400 V - 950 V - 3200 V - 5500 V and 6600 V. Secondary load voltage : 400 V - 950 V - 3200 V - 5500 V and 6600 V. Couplings : Step-down Dyn11 - Step-up YNd1, other couplings on request.

CONNEXION : Primary and secondary connexions on copper plates, by the upper side of the transformer.

STANDARD ACCESSORIES : Voltage tapping adjustable out of voltage : +/- 2,5 % or +- 5% output on slots. Two earthing terminals. Lifting lugs. Four rollers for 10 kVA and higher power rating transformers. Naked presentation on frame : IP00.

OPTIONAL ACCESSORIES Painted sheet metal enclosure with natural airing upwards, IP 21. Connexion on pluggable terminals 3200 V or 5500 V. HRC fuses protection integrated above the protection envelop. Thermal protection by thermal probe integrated to windings, one or two thresholds protection. Tap changers +/- 2,5 % +/- 5%. Keyhole locking of the protection envelop and or pluggable terminals. NOTE : Transformers mechanical and electrical characteristics are the same for step-down or step-up transformers. The tranformers are not reversible. Step-up transfrormers are built so that inrush currents are limited.

ELECTRICAL CHARACTERISTICS
Power rating (kVA) Copper losses at 75C (W) Iron losses (W) Voltage drop (% ) at Cos = 0.83 CC tension (%) at 75C Empty current (%) 16 25 32 50 63 80 100 125 160 200 250 400 500 630

350 100 3.3 3.4 1

470 180 3 3.2 0.7

550 200 3.07 3.4 0.8

800 250 3.14 3.5 0.9

1000 1100 250 3.4 4 0.7 380 3 3.5 0.8

1350 1400 450 3.2 4 0.9 450 3 4 0.6

2000 500 3.4 4 0.7

2300 550 3.2 4 0.5

2800 650 3.15 4 0.5

4200 900 3.5 4 0.8

5600 1250 3.5 4.5 0.6

7300 1500 3.5 5 0.7 4

TTAI Dry Transformers


SIZES-WEIGHT (mm) - PRESENTATION ON IP00 FRAME - STEP DOWN TRANSFORMER
Power rating (kVA) A B C D E Weight (kg) 16 636 400 611 380 295 155 25 750 480 670 510 400 270 32 825 500 718 510 400 310 50 825 500 718 510 400 345 63 840 520 734 520 400 365 80 930 530 809 580 440 450 100 930 530 809 580 440 465 125 950 530 836 590 440 525 160 980 530 858 610 440 600 200 1000 570 889 650 465 700 250 1096 660 1086 690 520 940 400 1240 660 1134 770 520 1185 500 1400 830 1300 870 520 1450 630 1600 900 1650 900 520 1800

Protection degree IP00

SIZES-WEIGHT (mm) - PRESENTATION WITH IP21 ENCLOSURE - STEP DOWN TRANSFORMER


Power rating (kVA) A B C D E Weight (kg) 16 850 550 900 380 295 185 25 960 630 970 510 400 300 32 1040 650 1020 510 400 350 50 1040 650 1030 510 400 400 63 1050 660 1040 520 400 405 80 1140 660 1100 580 440 535 100 1140 660 1100 580 440 565 125 1160 660 1140 590 440 630 160 1190 680 1200 610 440 750 200 1220 720 1200 650 465 900 250 1310 810 1390 690 520 1150 400 1550 810 1500 770 520 1450 500 1610 980 1600 870 520 1700 630 1810 1050 1950 900 520 2050

Protection degree IP21

Single-phase Dry Type Transformers TMAI


ELECTRICAL CHARACTERISTICS : Power rating: 5 - 7,5 - 10 - 16 - 25 - 32 - 50 kVA Insulation voltage : 1.1 kV - 3.6 kV - 7.2 kV Primary voltage : Every voltage compatible with insulation voltages above. Usually standard voltages are : 230 V - 400 V - 950 V - 3200 V. Secondary load voltage : 230 V - 950 V - 3200 V. Couplings : Standard : single-phase transformer : Ii0 CONNEXION : Primary and secondary connexions on copper plates, by the upper side of the transformer.

STANDARD ACCESSORIES : Voltage tapping adjustable out of voltage : +/- 2,5 % ou +- 5% sorties sur plages. Two earthing terminals. Lifting lugs. Four rollers for 10 kVA and higher power rating transformers. Naked presentation on IP00 frame.

OPTIONAL ACCESSORIES Painted sheet metal enclosure with natural airing upwards, IP 21. Connexion on pluggable terminals. HRC fuses protection integrated above the protection envelop. Thermal protection by thermal probe integrated to windings, one or two thresholds protection. Tap changers +/- 2,5 % +/- 5%. Keyhole locking of the protection envelop and or pluggable terminals. NOTE : Transformers mechanical and electrical characteristics are the same for step-down or step-up transformers. The tranformers are not reversible. Step-up transfrormers are built so that inrush currents are limited.

ELECTRICAL CHARACTERISTICS
Power rating (kVA) Copper losses at 75C (W) Iron losses (W) Voltage drop (% ) at Cos = 0.83 Cc tension (%) at 75C Empty current (%) 5 100 40 2.92 2.95 3.11 7,5 120 60 2.47 2.67 2.53 10 170 60 3.35 3.75 2.58 16 380 80 3.7 3.86 2.67 25 500 120 3.53 3.78 2.52 32 630 150 3.55 4 2.54 50 750 200 3.7 4 2.51

TMAI Dry Transformers


SIZES-WEIGHT (mm) - PRESENTATION ON IP00 FRAME
Power rating (kVA) A B C D E Weight (kg) 5 320 320 372 45 7,5 400 390 560 72 10 400 390 494 320 218 84 16 540 400 632 300 230 140 25 600 400 652 315 245 190 32 630 450 710 270 270 230 50 650 460 749 270 270 265

Protection degree IP00

SIZES-WEIGHT (mm) - PRESENTATION WITH IP21 ENCLOSURE


Power rating(kVA) A B C D E Weight (kg) 5 380 344 532 56 7,5 424 414 570 83 10 424 414 600 320 218 98 16 570 450 830 300 230 160 25 630 460 850 315 245 220 32 670 550 960 270 270 270 50 700 570 1020 270 270 310

Protection degree IP121