System parameters
Rated voltage Short-circuit current Normal current Load ow Protection functions Selectivity Measuring
Neutral earthing Cable/overhead line Overvoltage protection Power quality Redundancy Tripping times Metering
When an accessible compartment in a panel is opened, other panels must be shut down, i.e. at least one more only the connection compartment is accessible, while busbar and other panels remain energized any accessible compartment except the busbar can be open while busbar and other panels remain energized the connection (cable) compartment can remain energized while any other accessible compartment can be open except busbar and connections and busbar and other panels remain energized
LSC 2B
Service location
Ambient conditions
Altitude Air humidity Switching rate Availability Personal protection Work instructions Maintenance Laws Company regulations
Sector-specic application
Switching duties Busbar transfer Operation Working Inspection Standards Association guidelines
Access features Opening for normal operation and maintenance, e.g., fuse replacement
Type of construction Access is controlled by the construction of the switchgear, i.e., integrated interlocks prevent impermissible opening. Access control via a suitable procedure (work instruction of the operator) combined with a locking device (lock). Access only with tool for opening; special access procedure (instruction of the operator).
Regulations
Opening for normal operation or maintenance, e.g., fuse replacement Opening not for normal operation and maintenance, e.g., cable testing
Tool-based
Not accessible
Large cable cross sections or several parallel cables must be connected for high normal currents; the panel connection must be designed accordingly. Assigned conguration criteria for switchgear Rated current of busbar(s) and feeders Number of cables per phase in the panel (parallel cables) Current transformer ratings
Opening not possible not intended for operator; opening can destroy the compartment. This applies generally to the gas-lled compartments of gas-insulated switchgear. Because the switchgear is maintenance-free and climate-independent, access is neither required nor possible.
The notation IAC A FLR, and contains the abbreviations for the following values: IAC A Internal Arc Classication Distance between the indicators 300 mm, i.e., installation in rooms with access for authorized personnel; closed electrical service location. Access from the front (F), from the sides (L = Lateral) and from the rear (R). Test current = Rated short-circuit breaking current (in kA) Arc duration (in s)
FLR I t