Round-wire winding The interturn voltages can add up to twice the interlayer voltage
U 2468
LV winding The standard low-voltage winding with its considerably reduced dielectric stresses is wound from single aluminum sheets with interleaved cast-resin impregnated berglass fabric (prepreg). The assembled coils are then oven-cured to form uniformly bonded solid cylinders that are impervious to moisture. Through the single-sheet winding design, excellent dynamic stability under short-circuit conditions is achieved. Connections are submerged arc-welded to the aluminum sheets and are extended either as aluminum or copper bars to the secondary terminals. Fire safety GEAFOL transformers use only ame-retardant and self-extinguishing materials in their construction. No additional substances, such as aluminum oxide trihydrate, which could negatively inuence the mechanical stability of the cast-resin molding material, are used. Internal arcing from electrical faults and externally applied ames do not cause the transformers to