Switch-onto-fault protection If switched onto a fault, instantaneous tripping can be effected. If the internal control function is used (local, via binary input or via serial interface), the manual closing function is available without any additional wiring. If the control switch is connected to a circuit-breaker bypassing the internal control function, manual detection using a binary input is implemented.
Busbar
52
I>>, I>>>
Feeder earthed 50 & Typical feeder Manual close (356 > m close) 7SJx, 7SAx
Directional comparison protection (cross-coupling) Cross-coupling is used for selective protection of sections fed from two sources with instantaneous tripping, that is, without the disadvantage of time coordination. The directional comparison protection is suitable if the distances between the protection stations are not signicant and pilot wires are available for signal transmission. In addition to the directional comparison protection, the directional coordinated overcurrent-time protection is used for complete selective backup protection. If operated in a closed-circuit connection, an interruption of the transmission line is detected.
Substation A Bus 52
52
Substation B Bus 52
Substation C 52 Bus 52
Substation D 52 Bus
7SJ62/ 63/64 50
7SJ62/ 63/64 50
7SJ62/ 63/64 50
7SJ62/ 63/64 50
7SJ62/ 63/64 50
7SJ62/ 63/64 50
52 Blocking bus
50 7SJ80 *) Pickup 52 50
*) Alternatives: 7SJ60 Blocking signal Non-directional fault detection Direction of fault (67)
50 7SJ80 *) Pickup
Distribution feeder with reclosers General notes: The feeder relay operating characteristics, delay times and auto-reclosure cycles must be carefully coordinated with downstream reclosers, sectionalizers and fuses. The 50 / 50N instantaneous zone is normally set to reach out to the rst main feeder sectionalizing point. It has to ensure fast clearing of close-in faults and prevent blowing of fuses in this area (fuse saving). Fast auto-reclosure is initiated in this case. Further time-delayed tripping and reclosure steps (normally two or three) have to be graded against the recloser. The overcurrent relay should automatically switch over to less sensitive characteristics after long breaker interruption times in order to enable overriding of subsequent cold load pickup and transformer inrush currents.
Infeed
52
52
I>>, I>, t
I E >>, I E >, t
I2 >, t
46
50/51 50N/51N
79
Recloser
Sectionalizers
Fuses