CABLES SPECIFICATION REQUIREMENT AS PER CONTRACT WITH MCD


Cross -linked Polyethelene(XPLE) power cables or 1.1 grade power or control cable. Cables will be Galvanized Steel wire/Strip armoured type(IS 3975) 1.1 KV grade PVC insulated,PVC sheathed Power cables shall be electrical grade aluminium conductor as per IS 8130.IS1554 1.1 KV grade PVC insulated,PVC sheathed control cables will have annealed high conductivity copper wire. 1.1 KV grade PVC insulated,PVC sheathed Power cables shall have armour when the diameter exceeds 13 mm. Polyethylene insualted special twisted pair shielded cable shall provide balanced signal transmission with good noise immunity.The conductors shall be stranded tinned copper wire. The pilot wire protection cable will be manufactured as per IS 1554 (part1)

Electrical IS Code required

S.No.

IS CODE
1 IS 335 2 IS 694 3 IS 1180 4 IS 1416

IS CODE SPECIFICATION
New Insulating Coils PVC Insulated cables for working voltages up to and including 1100 V (All of 2 Parts) Outdoor type three-Phase distribution transformers up to and including 100 KVA and 11 KV Safety Transformer Specification for pVC insulated(heavy duty) electric cables Part 1 For working up to 1100 KV Part 2 For working voltages from 3.3 KV up to and including 11 KV. (All of 5 parts) Power transformers Specification for fillings and accessories for power transformer. (ALL of 5 parts) Recommended current ratings for cables. (All of 2 parts) Specifications for flexible cables for lift & other flexible connections. Guide for loading of oil immersed transformers. (All of 3 parts) Cross linked polyethylene insulated thermoplastic sheathed cables Part 1 for working voltages up to 7 including 1100V Part 2 For working voltages from 3.3 kV upto 7 including 33 kV Part 3 for working voltages from 66kV up to & including 220kV. Part 1 Elastomer insulated cables for working voltages up to & including 1100 kV. All of 3 parts Code of Practice for selection, installation & maintanance of tranforms Part 1 Selection Part 2 Installation Part 3 Maintance Application guide for power transformers. (All of 64 parts) Methods of test for cables. Specification for dry type transformers. Methods of calculation for maximum external diameter of cables for indoor installation. Part 1 Multicore & symmetrical pair/ quad cables for digital communications part 2 Generic Specification.

5 6 7 8

IS 1554 IS 2026 IS 3639 IS 3961

9 IS 4289 10 IS 6600

11 IS 7078 12 IS 9968

13 14 15 16

IS 10028 IS 10561 IS 10610 IS 11171

17 IS 11892

18 IS 14493

Power distribution boards


The Power distribution boards(PDBs) shall conform IS 5578,IS 8623,IS11353& IS13947.They enclosure will be IP54 and will be fabricated from 1.6/2 mm thick CRCA sheets An Enclosure of 250 mm height shall be reserved at the top for TP busbars.Similarily an enclosure of 250 mm height shall be reserved at the bottom.The bus bar shall be aluminium alloy conforming to IS 5082. Fuse Switch distribution boards conformimg to IS 13947 Non-Deteriorating HRC fuses having rupture capacity not less than 50 KA rms at 415 V AC conformimg to IS 13702(part1& 2) MCCB distribution boards,the incoming switches shall be of load break AC23 category conformimg IS 139479(part 3) with breaking capacity 50 KA The contactor shall be sturdy construction with double break silver tripped contacts conforming to IS 13647(part4/Sec 1)

LIGHTING TRANSFORMERS
The lighting transformers shall be 1-phase dry type (AN) for supplying 240V, 1-phase power to DP lighting distribution boards from 415V, 3-phase , 3-wire , 50HZ supply. The units shall be designed, manufactured & tested as per IS 2036 and IS 11171.

MINIATURE CIRCUIT BREAKER


The lighting distribution boards with outgoing miniature circuit breaker shall be suitable for 240V, 1phase system generally conforming to IS 8623 & IS 13947 as applicable.

LT electrical power distribution standards


IS 1293 IS 1416 IS 2026 IS 5578 Plug & socket outlets of 250 volt & rated current up to 16 amps. safety transformers (All of 5 parts) Power Transformers Guide for marking of insulated conductors

IS 8623 IS 11171 IS 11353

(All of 3 parts) Specification for low voltage switchgear & control gear Part 1 Requirements for type tested & partially type tested assemblies Part 2 particular requirements of bulbar trunking system (Busway) Part 3 Particular requirements of equipments where unskilled persons have access for their use. Specification of dry type Tansformers Guide for uniform system of marking & identification of conductors & appratus terminals. (All of 2 Parts) Residual current operated circuit breaker for household & similar uses Part 1 Circuit breakers without integral over current protection (RCCB's) Part 2 breakers with integral over current protection (RCVOs) (all of 4 parts) Low voltage fuses for voltages not exceeding 1000 V AC or 1500 V DC. (All of 5 parts) Specification for low voltages switchgear & control gear assemblies Parts 1 General rule Part 2 Circuit breaker Part 3 switches, disconnectors & combination units Part 4 Contractors & motor starters Part 5 Control circuit devices & switching elements

IS 12640 IS 13703

IS 13947