6.1 INTRODUCTION
Whenever the values of voltage or current in a power
circuit are too high to permit convenient direct
connection of measuring instruments or relays, coupling
is made through transformers. Such 'measuring'
transformers are required to produce a scaled down
replica of the input quantity to the accuracy expected
for the particular measurement; this is made possible by
the high efficiency of the transformer. The performance
of measuring transformers during and following large
instantaneous changes in the input quantity is
important, in that this quantity may depart from the
sinusoidal waveform. The deviation may consist of a
step change in magnitude, or a transient component
that persists for an appreciable period, or both. The
resulting effect on instrument performance is usually
negligible, although for precision metering a persistent
change in the accuracy of the transformer may be
significant.
However, many protection systems are required to
operate during the period of transient disturbance in the
output of the measuring transformers that follows a
system fault. The errors in transformer output may
abnormally delay the operation of the protection, or
cause unnecessary operations. The functioning of such
transformers must, therefore, be examined analytically.
It can be shown that the transformer can be represented
by the equivalent circuit of Figure 6.1, where all
quantities are referred to the secondary side.
1/1 Rp Lp Rs Ls
Ze Burden
When the transformer is not 1/1 ratio, this condition can voltage drops are made small, and the normal flux
be represented by energising the equivalent circuit with an density in the core is designed to be well below the
ideal transformer of the given ratio but having no losses. saturation density, in order that the exciting current may
be low and the exciting impedance substantially
constant with a variation of applied voltage over the
6.1.1 Measuring Transformers desired operating range including some degree of
Voltage and current transformers for low primary voltage overvoltage. These limitations in design result in a VT for
or current ratings are not readily distinguishable; for a given burden being much larger than a typical power
higher ratings, dissimilarities of construction are usual. transformer of similar rating. The exciting current, in
Nevertheless the differences between these devices lie consequence, will not be as small, relative to the rated
principally in the way they are connected into the power burden, as it would be for a typical power transformer.
circuit. Voltage transformers are much like small power
transformers, differing only in details of design that
6.2.1 Errors
control ratio accuracy over the specified range of output.
Current transformers have their primary windings The ratio and phase errors of the transformer can be
connected in series with the power circuit, and so also in calculated using the vector diagram of Figure 6.2.
series with the system impedance. The response of the
The ratio error is defined as:
transformer is radically different in these two modes of
operation. ( K nV s )
× 100%
Vp
C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s
0.25 - 1.0 x rated burden at 0.8pf as possible. A short circuit on the secondary circuit
Accuracy 0.05 - Vf x rated primary voltage wiring will produce a current of many times the rated
class voltage ratio error phase displacement
(%) (%) output and cause excessive heating. Even where primary
3P +/- 3.0 +/- 120 fuses can be fitted, these will usually not clear a
6P +/- 6.0 +/- 240 secondary side short circuit because of the low value of
Table 6.2: Additional limits for protection voltage transformers.
primary current and the minimum practicable fuse rating.
6.2.5 Construction
6.2.2 Voltage Factors
The construction of a voltage transformer takes into
The quantity Vf in Table 6.2 is an upper limit of operating account the following factors:
voltage, expressed in per unit of rated voltage. This is
important for correct relay operation and operation a. output – seldom more than 200-300VA. Cooling is
under unbalanced fault conditions on unearthed or rarely a problem
impedance earthed systems, resulting in a rise in the b. insulation – designed for the system impulse
voltage on the healthy phases. voltage level. Insulation volume is often larger
Voltage factors, with the permissible duration of the than the winding volume
maximum voltage, are given in Table 6.3. c. mechanical design – not usually necessary to
withstand short-circuit currents. Must be small to
Voltage factor Time Primary winding connection/system fit the space available within switchgear
C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s
Vf rating earthing conditions
Three-phase units are common up to 36kV but for higher
Between lines in any network.
1.2 continuous Between transformer star point and voltages single-phase units are usual. Voltage
earth in any network transformers for medium voltage circuits will have dry
1.2 continuous Between line and earth in an type insulation, but for high and extra high voltage
1.5 30 s effectively earthed network
systems, oil immersed units are general. Resin
1.2 continuous Between line and earth in
a non-effectively earthed neutral system encapsulated designs are in use on systems up to 33kV.
1.9 30 s Figure 6.3 shows a typical voltage transformer.
with automatic earth fault tripping
1.2 continuous Between line and earth in an isolated
neutral system without automatic earth fault
1.9 8 hours tripping, or in a resonant earthed system
without automatic earth fault tripping
Table 6.3: Voltage transformers: Permissible duration
of maximum voltage
voltage equal to three times the zero sequence voltage of If a voltage is suddenly applied, an inrush transient will
the system will be developed. occur, as with power transformers. The effect will,
however, be less severe than for power transformers
because of the lower flux density for which the VT is
A B C
designed. If the VT is rated to have a fairly high voltage
factor, little inrush effect will occur. An error will appear
in the first few cycles of the output current in proportion
to the inrush transient that occurs.
When the supply to a voltage transformer is interrupted,
the core flux will not readily collapse; the secondary
winding will tend to maintain the magnetising force to
Residual sustain this flux, and will circulate a current through the
voltage burden which will decay more or less exponentially,
possible with a superimposed audio-frequency
oscillation due to the capacitance of the winding.
Figure 6.4: Residual voltage connection
Bearing in mind that the exciting quantity, expressed in
ampere-turns, may exceed the burden, the transient
current may be significant.
In order to measure this component, it is necessary for a
zero sequence flux to be set up in the VT, and for this to
be possible there must be a return path for the resultant
C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s
n
6.2.7 Transient Performance S
a
Transient errors cause few difficulties in the use of N
conventional voltage transformers although some do
occur. Errors are generally limited to short time periods
following the sudden application or removal of voltage Figure 6.5: Schematic diagram of typical cascade
from the VT primary. voltage transformer
The conventional type of VT has a single primary winding, the normal value using a relatively inexpensive
the insulation of which presents a great problem for electromagnetic transformer. The successive stages of
voltages above about 132kV. The cascade VT avoids this reasoning are indicated in Figure 6.6.
these difficulties by breaking down the primary voltage
in several distinct and separate stages.
The complete VT is made up of several individual C1 C1
transformers, the primary windings of which are
connected in series, as shown in Figure 6.5. Each L
magnetic core has primary windings (P) on two opposite C2 Zb C2 Zb
C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s
Figure 6.6: Development of capacitor
winding, which is a fraction of the total according to the voltage transformer
number of stages. The individual transformers are
mounted on a structure built of insulating material, There are numerous variations of this basic circuit. The
which provides the interstage insulation, accumulating inductance L may be a separate unit or it may be
to a value able to withstand the full system voltage incorporated in the form of leakage reactance in the
across the complete height of the stack. The entire transformer T. Capacitors C1 and C2 cannot conveniently
assembly is contained in a hollow cylindrical porcelain be made to close tolerances, so tappings are provided for
housing with external weather-sheds; the housing is ratio adjustment, either on the transformer T, or on a
filled with oil and sealed, an expansion bellows being separate auto-transformer in the secondary circuit.
included to maintain hermetic sealing and to permit Adjustment of the tuning inductance L is also needed;
expansion with temperature change. this can be done with tappings, a separate tapped
inductor in the secondary circuit, by adjustment of gaps
in the iron cores, or by shunting with variable
6.3 CAPACITOR VOLTAGE TRANSFORMERS capacitance. A simplified equivalent circuit is shown in
The size of electromagnetic voltage transformers for the Figure 6.7.
higher voltages is largely proportional to the rated
voltage; the cost tends to increase at a disproportionate C L Rp Rs
rate. The capacitor voltage transformer (CVT) is often
more economic. • 6•
This device is basically a capacitance potential divider. Zb
Vi Ze
As with resistance-type potential dividers, the output
voltage is seriously affected by load at the tapping point.
The capacitance divider differs in that its equivalent
source impedance is capacitive and can therefore be L - tuning inductance
compensated by a reactor connected in series with the Rp - primary winding resistance (plus losses)
Ze - exciting impedance of transformer T
tapping point. With an ideal reactor, such an Rs - secondary circuit resistance
arrangement would have no regulation and could supply Zb - burden impedance
C - C1 + C2 (in Figure 6.6)
any value of output.
Figure 6.7: Simplified equivalent circuit
A reactor possesses some resistance, which limits the of capacitor voltage transformer
output that can be obtained. For a secondary output
voltage of 110V, the capacitors would have to be very
large to provide a useful output while keeping errors It will be seen that the basic difference between Figure
within the usual limits. The solution is to use a high 6.7 and Figure 6.1 is the presence of C and L. At normal
secondary voltage and further transform the output to frequency when C and L are in resonance and therefore
cancel, the circuit behaves in a similar manner to a and the capacitance of the potential divider together
conventional VT. At other frequencies, however, a form a resonant circuit that will usually oscillate at a
reactive component exists which modifies the errors. sub-normal frequency. If this circuit is subjected to a
Standards generally require a CVT used for protection to voltage impulse, the resulting oscillation may pass
conform to accuracy requirements of Table 6.2 within a through a range of frequencies. If the basic frequency of
frequency range of 97-103% of nominal. The this circuit is slightly less than one-third of the system
corresponding frequency range of measurement CVT’s is frequency, it is possible for energy to be absorbed from
much less, 99%-101%, as reductions in accuracy for the system and cause the oscillation to build up. The
frequency deviations outside this range are less increasing flux density in the transformer core reduces
important than for protection applications. the inductance, bringing the resonant frequency nearer
to the one-third value of the system frequency.
The result is a progressive build-up until the oscillation
6.3.1 Voltage Protection of Auxiliary Capacitor
stabilizes as a third sub-harmonic of the system, which
If the burden impedance of a CVT were to be short- can be maintained indefinitely. Depending on the values
circuited, the rise in the reactor voltage would be limited of components, oscillations at fundamental frequency or
only by the reactor losses and possible saturation, that is, at other sub-harmonics or multiples of the supply
to Q x E2 where E2 is the no-load tapping point voltage frequency are possible but the third sub-harmonic is the
and Q is the amplification factor of the resonant circuit. one most likely to be encountered.
This value would be excessive and is therefore limited by
The principal manifestation of such an oscillation is a rise
a spark gap connected across the auxiliary capacitor. The
C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s
voltage on the auxiliary capacitor is higher at full rated in output voltage, the r.m.s. value being perhaps 25%-
output than at no load, and the capacitor is rated for 50% above the normal value; the output waveform
continuous service at this raised value. The spark gap will would generally be of the form shown in Figure 6.8.
be set to flash over at about twice the full load voltage.
The effect of the spark gap is to limit the short-circuit
current which the VT will deliver and fuse protection of
the secondary circuit has to be carefully designed with this
point in mind. Facilities are usually provided to earth the
Amplitude
Z=21.2Ω
IsRs
E=6350V 300/5A Burden
10VA
IsXs Es
C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s
(a) Physical arrangement Iq
Ir
Z=21.2Ω 0.2Ω Ip
Vs
'Ideal'
CT
E=6350V r=300/5 j50Ω 150Ω 0.4Ω θ
Is
a. the secondary current will not be affected by This is the difference in magnitude between Ip and Is and is
change of the burden impedance over a equal to Ir, the component of Ie which is in phase with Is.
considerable range 6.4.1.2 Phase Error
b. the secondary circuit must not be interrupted while This is represented by Iq, the component of Ie in
the primary winding is energised. The induced quadrature with Is and results in the phase error .
secondary e.m.f. under these circumstances will be The values of the current error and phase error depend on
high enough to present a danger to life and insulation the phase displacement between Is and Ie, but neither
c. the ratio and phase angle errors can be calculated current nor phase error can exceed the vectorial error Ie.
easily if the magnetising characteristics and the It will be seen that with a moderately inductive burden,
burden impedance are known resulting in Is and Ie approximately in phase, there will
be little phase error and the exciting component will Class Current error at Phase displacement Composite error at
result almost entirely in ratio error. rated primary at rated current rated accuracy limit
current (%) (minutes) primary current (%)
A reduction of the secondary winding by one or two 5P +/-1 +/-60 5
turns is often used to compensate for this. For example, 10P +/-3 10
in the CT corresponding to Figure 6.9, the worst error due Standard accuracy limit factors are 5, 10, 15, 20, and 30
to the use of an inductive burden of rated value would Table 6.5: Protection CT error limits for classes 5P and 10P
be about 1.2%. If the nominal turns ratio is 2:120,
removal of one secondary turn would raise the output by
0.83% leaving the overall current error as -0.37%. Even though the burden of a protection CT is only a few
For lower value burden or a different burden power VA at rated current, the output required from the CT may
factor, the error would change in the positive direction to be considerable if the accuracy limit factor is high. For
a maximum of +0.7% at zero burden; the leakage example, with an accuracy limit factor of 30 and a
reactance of the secondary winding is assumed to be burden of 10VA, the CT may have to supply 9000VA to
negligible. No corresponding correction can be made for the secondary circuit.
phase error, but it should be noted that the phase error Alternatively, the same CT may be subjected to a high
is small for moderately reactive burdens. burden. For overcurrent and earth fault protection, with
elements of similar VA consumption at setting, the earth
fault element of an electromechanical relay set at 10%
6.4.2 Composite Error would have 100 times the impedance of the overcurrent
elements set at 100%. Although saturation of the relay
C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s
C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s
Exciting voltage (IIe) in place of three phase CT's whose secondary windings
are residually connected. In this way the CT magnetising
Figure 6.11: Definition of knee-point
of excitation curve
current at relay operation is reduced by approximately
three-to-one, an important consideration in sensitive
earth fault relays where a low effective setting is
Design requirements for current transformers for general required. The number of secondary turns does not need
protection purposes are frequently laid out in terms of to be related to the cable rated current because no
knee-point e.m.f., exciting current at the knee-point (or secondary current would flow under normal balanced
some other specified point) and secondary winding conditions. This allows the number of secondary turns to
resistance. Such current transformers are designated be chosen such as to optimise the effective primary pick-
Class PX. up current.
Core-balance transformers are normally mounted over a
cable at a point close up to the cable gland of switchgear
6.4.5 CT Winding Arrangements
or other apparatus. Physically split cores ('slip-over'
A number of CT winding arrangements are used. These types) are normally available for applications in which
are described in the following sections. the cables are already made up, as on existing
6.4.5.1 Wound primary type switchgear.
This type of CT has conventional windings formed of 6.4.5.4 Summation current transformers • 6•
copper wire wound round a core. It is used for auxiliary The summation arrangement is a winding arrangement
current transformers and for many low or moderate ratio used in a measuring relay or on an auxiliary current
current transformers used in switchgear of up to 11kV transformer to give a single-phase output signal having
rating. a specific relationship to the three-phase current input.
6.4.5.2 Bushing or bar primary type 6.4.5.5 Air-gapped current transformers
Many current transformers have a ring-shaped core, These are auxiliary current transformers in which a small
sometimes built up from annular stampings, but often air gap is included in the core to produce a secondary
consisting of a single length of strip tightly wound to voltage output proportional in magnitude to current in
form a close-turned spiral. The distributed secondary the primary winding. Sometimes termed 'transactors'
winding forms a toroid which should occupy the whole and 'quadrature current transformers', this form of
perimeter of the core, a small gap being left between current transformer has been used as an auxiliary
start and finish leads for insulation. component of unit protection schemes in which the
Such current transformers normally have a single outputs into multiple secondary circuits must remain
concentrically placed primary conductor, sometimes linear for and proportioned to the widest practical range
permanently built into the CT and provided with the of input currents.
6.4.6 Line Current CT’s 10mm. As its name implies the magnetic behaviour
tends to linearisation by the inclusion of this gap in the
CT’s for measuring line currents fall into one of three types.
magnetic circuit. However, the purpose of introducing
6.4.6.1 Overdimensioned CT’s more reluctance into the magnetic circuit is to reduce
Overdimensioned CT’s are capable of transforming fully the value of magnetising reactance. This in turn reduces
offset fault currents without distortion. In consequence, the secondary time-constant of the CT, thereby reducing
they are very large, as can be deduced from Section the overdimensioning factor necessary for faithful
6.4.10. They are prone to errors due to remanent flux transformation. Figure 6.12 shows a typical modern CT
arising, for instance, from the interruption of heavy fault for use on MV systems.
currents.
6.4.6.2 Anti-remanence CT’s 6.4.7 Secondary Winding Impedance
This is a variation of the overdimensioned current As a protection CT may be required to deliver high values
transformer and has small gap(s) in the core magnetic of secondary current, the secondary winding resistance
circuit, thus reducing the possible remanent flux from must be made as low as practicable. Secondary leakage
approximately 90% of saturation value to approximately reactance also occurs, particularly in wound primary
10%. These gap(s) are quite small, for example 0.12mm current transformers, although its precise measurement
total, and so the excitation characteristic is not is difficult. The non-linear nature of the CT magnetic
significantly changed by their presence. However, the circuit makes it difficult to assess the definite ohmic
resulting decrease in possible remanent core flux value representing secondary leakage reactance.
C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s
instruments is largely independent of the rated value of when the primary current is suddenly changed. The
current. This is because the winding of the device has to effects are most important, and were first observed in
develop a given number of ampere-turns at rated connection with balanced forms of protection, which
current, so that the actual number of turns is inversely were liable to operate unnecessarily when short-circuit
proportional to the current, and the impedance of the currents were suddenly established.
winding varies inversely with the square of the current
6.4.10.1 Primary current transient
rating. However, electromechanical or static earth-fault
relays may have a burden that varies with the current The power system, neglecting load circuits, is mostly
tapping used. inductive, so that when a short circuit occurs, the fault
current that flows is given by:
Interconnection leads do not share this property,
however, being commonly of standard cross-section Ep
ip =
regardless of rating. Where the leads are long, their R 2 + ω 2 L2
resistance may be appreciable, and the resultant burden
will vary with the square of the current rating. For
example a CT lead run of the order of 200 metres, a [ sin ( ωt + β − α ) + sin ( α − β ) e − ( R L) t
] …Equation 6.1
typical distance for outdoor EHV switchgear, could have where:
a loop resistance of approximately 3 ohms.
Ep = peak system e.m.f.
The CT lead VA burden if a 5A CT is used would be 75VA,
R = system resistance
to which must be added the relay burden (up to of
perhaps 10VA for an electromechanical relay, but less L = system inductance
C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s
than 1VA for a numerical relay), making a total of 85VA.
β = initial phase angle governed by instant
Such a burden would require the CT to be very large and
of fault occurrence
expensive, particularly if a high accuracy limit factor
were also applicable. α = system power factor angle
With a 1A CT secondary rating, the lead burden is = tan-1 ωL/R
reduced to 3VA, so that with the same relay burden the The first term of Equation 6.1 represents the steady state
total becomes a maximum of 13VA. This can be provided alternating current, while the second is a transient
by a CT of normal dimensions, resulting in a saving in
quantity responsible for displacing the waveform
size, weight and cost. Hence modern CT’s tend to have
asymmetrically.
secondary windings of 1A rating. However, where the
primary rating is high, say above 2000A, a CT of higher Ep
secondary rating may be used, to limit the number of R + ω 2 L 2 is the steady state peak current I .
2
8
KR b I s
= T = 0.06s
ω ...Equation 6.4
4
The transient flux is given by:
α
KR b I s L
= KR b I s ∫ e − (
R L) t
B dt = 0 0.05 0.1 0.15 0.2
0
R ...Equation 6.5 Time (seconds)
Hence, the ratio of the transient flux to the steady state T - time constant of primary circuit
value is:
Figure 6.13: Response of a CT of
wL X
= = infinite shunt impedance to transient asymmetric
B
R R primary current
A
resistance values.
Since a CT requires a finite exciting current to maintain
The CT core has to carry both fluxes, so that: a flux, it will not remain magnetised (neglecting
hysteresis), and for this reason a complete representation
Ê Xˆ
= + = Á1 + ˜ of the effects can only be obtained by including the
C A B A
Ë R¯
...Equation 6.6 finite inductance of the CT in the calculation. The
The term (1+X/R) has been called the 'transient factor' response of a current transformer to a transient
(TF), the core flux being increased by this factor during asymmetric current is shown in Figure 6.14.
the transient asymmetric current period. From this it can
be seen that the ratio of reactance to resistance of the
1.0
power system is an important feature in the study of the
behaviour of protection relays. 0.9
- 1
T1
0.8 e
Alternatively, L/R is the primary system time constant T,
so that the transient factor can be written: 0.7 -1
e T
ωL 0.6
=1 + = 1 + ωT Ie
R 0.5
C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s
would be expected from linear theory.
T1 = CT secondary circuit time constant Le/Rb When the exponential component drives the CT into
I1 = prospective peak secondary current saturation, the magnetising inductance decreases,
causing a large increase in the alternating component ie.
6.4.10.2 Practical conditions
The total exciting current during the transient period is
Practical conditions differ from theory for the following of the form shown in Figure 6.15 and the corresponding
reasons: resultant distortion in the secondary current output, due
a. no account has been taken of secondary leakage or to saturation, is shown in Figure 6.16.
burden inductance. This is usually small compared
with Le so that it has little effect on the maximum
transient flux
b. iron loss has not been considered. This has the
Exciting current
secondary
then be made for the extent of each chord
The above theory is sufficient, however, to give a good
insight into the problem and to allow most practical Time
0
issues to be decided.
Secondary current
d. the effect of hysteresis, apart from loss as Residual flux = 0
discussed under (b) above, is not included. Resistive burden
Power system T.C. = 0.05s
Hysteresis makes the inductance different for flux
build up and decay, so that the secondary time Figure 6.16: Distortion in secondary current
constant is variable. Moreover, the ability of the due to saturation
The presence of residual flux varies the starting point of CT will cost more. This fact should be weighed against
the transient flux excursion on the excitation the convenience achieved; very often it will be found
characteristic. Remanence of like polarity to the that the tests in question can be replaced by alternative
transient will reduce the value of symmetric current of procedures.
given time constant which the CT can transform without
severe saturation; conversely, reverse remanence will
greatly increase the ability of a CT to transform transient 6.5 NOVEL INSTRUMENT TRANSFORMERS
current. The preceding types of instrument transformers have all
If the CT were the linear non-saturable device considered been based on electromagnetic principles using a
in the analysis, the sine current would be transformed magnetic core. There are now available several new
without loss of accuracy. In practice the variation in methods of transforming the measured quantity using
excitation inductance caused by transferring the centre optical and mass state methods.
of the flux swing to other points on the excitation curve
causes an error that may be very large. The effect on
measurement is of little consequence, but for protection 6.5.1 Optical Instrument Transducers
equipment that is required to function during fault The key features of a freestanding optical instrument
conditions, the effect is more serious. The output current transducer can be illustrated with the functional
is reduced during transient saturation, which may diagram of Figure 6.17.
prevent the relays from operating if the conditions are
near to the relay setting. This must not be confused with
C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s
fit optical sensing devices as an integral part of the field, it plays the role of the ‘odd’ polariser. Changes in
insulator. Additionally, the non-linear effects and the magnetic or electric field in which the optical sensor
electromagnetic interference problems in the secondary is immersed are monitored as a varying intensity of the
wiring of conventional VT’s and CT’s are minimised. probing light beam at the light detector. The light output
intensity fluctuates around the zero-field level equal to
Optical transducers can be separated in two families:
50% of the reference light input. This modulation of the
firstly the hybrid transducers, making use of
light intensity due to the presence of varying fields is
conventional electrical circuit techniques to which are
converted back to time-varying currents or voltages.
coupled various optical converter systems, and secondly
the ‘all-optical’ transducers that are based on A transducer uses a magneto-optic effect sensor for
fundamental, optical sensing principles. optical current measuring applications. This reflects the
fact that the sensor is not basically sensitive to a current
6.5.1.1 Optical sensor concepts
but to the magnetic field generated by this current.
Certain optical sensing media (glass, crystals, plastics) Although ‘all-fibre’ approaches are feasible, most
show a sensitivity to electric and magnetic fields and commercially available optical current transducers rely
that some properties of a probing light beam can be on a bulk-glass sensor. Most optical voltage transducers,
altered when passing through them. One simple optical on the other hand, rely on an electro-optic effect sensor.
transducer description is given here in Figure. 6.18. This reflects the fact that the sensor used is sensitive to
Consider the case of a beam of light passing through a the imposed electric field.
pair of polarising filters. If the input and output 6.5.1.2 Hybrid transducers
polarising filters have their axes rotated 45° from each
C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s
The hybrid family of non-conventional instrument
other, only half the light will come through. The
transducers can be divided in two types: those with
reference light input intensity is maintained constant
active sensors and those with passive sensors. The idea
over time. Now if these two polarising filters remain
behind a transducer with an active sensor is to change
fixed and a third polarising filter is placed in between
the existing output of the conventional instrument
them, a random rotation of this middle polariser either
transformer into an optically isolated output by adding
clockwise or counter-clockwise will be monitored as a
an optical conversion system (Figure 6.18). This
varying or modulated light output intensity at the light
conversion system may require a power supply of its
detector.
own: this is the active sensor type. The use of an optical
When a block of optical sensing material (glass or isolating system serves to de-couple the instrument
crystal) is immersed in a varying magnetic or electric transformer output secondary voltages and currents
'Odd' polariser
input output
polariser polariser
optical optical
fibre fibre sensing
light • 6•
detector
in out
light source
45° 90°
optical
zero field level
1.0 sensing 1.0
medium
+
0.5 0.5
0 0
t t
reference modulated
light input light input
intensity intensity
Figure. 6.18: Schematic representation of the concepts behind the optical sensing of varying electric and magnetic fields
from earthed or galvanic links. Thus the only link that analysing circuitry. In sharp contrast with a
remains between the control-room and the switchyard is conventional free-standing instrument transformer, the
a fibre optic cable. optical instrument transformer needs an electronic
interface module in order to function. Therefore its
Another type of hybrid non-conventional instrument
sensing principle (the optical material) is passive but its
transformer is achieved by retrofitting a passive optical
operational integrity relies on the interface that is
sensing medium into a conventional ‘hard-wire
powered in the control room (Figure 6.21).
secondary’ instrument transformer. This can be termed
as a passive hybrid type since no power supply of any
'Floating'
kind is needed at the secondary level. electrode
electrode
element is either located free in the magnetic field (Figure
6.19(a)) or it can be immersed in a field-shaping magnetic
‘gap’ (Figure 6.19(b)). In the case of a voltage-sensing
device (Figure 6.20) the same alternatives exist, this time Light
for elements that are sensitive to electric fields. The AC line path
voltage Electro-optic
possibility exists of combining both sensors within a sensor
single housing, thus providing both a CT and VT within a
single compact housing that gives rise to space savings
within a substation.
Reference
(b) 'Field shaping' type electrode Optical fibres
I AC line current
In all cases there is an optical fibre that channels the AC/DC source
probing reference light from a source into the medium Figure 6.21: Novel instrument transducer concept
and another fibre that channels the light back to requiring an electronic interface in the control room
Insulator
column
AC line current
Fibre junction box I
Light in
Sensor #1 Fibre
optic
Sensor #2 cables Optical fibres
C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s
Light out
Fibre
sensing element
Similar to conventional instrument transformers there are Although ‘all-optical’ instrument transformers were first
‘live tank’ and ‘dead tank’ optical transducers. Typically, introduced 10-15 years ago, there are still only a few in
current transducers take the shape of a closed loop of light- service nowadays. Figure 6.24 shows a field installation
transparent material, fitted around a straight conductor of a combined optical CT/VT.
carrying the line current (Figure 6.22). In this case a bulk-
glass sensor unit is depicted (Figure 6.22(a)), along with an
‘all-optical’ sensor example, as shown in Figure 6.22(b).
Light detectors are basically very sensitive devices and the
sensing material can thus be selected in such a way as to
scale-up readily for larger currents. ‘All-optical’ voltage
transducers however do not lend themselves easily for
extremely high line voltages. Two concepts using a 'full-
voltage' sensor are shown in Figure 6.23.
• 6•
Conductor
Figure 6.23: Optical voltage transducer concepts, Figure 6.24: Field installation of a combined
using a ‘full-voltage’ sensor optical CT/VT
6.5.2 Other Sensing Systems of insulation material. In most cases the Rogowski coil
will be connected to an amplifier, in order to deliver
There are a number of other sensing systems that can be
sufficient power to the connected measuring or
used, as described below.
protection equipment and to match the input impedance
6.5.2.1 Zero-flux (Hall Effect) current transformer of this equipment. The Rogowski coil requires
In this case the sensing element is a semi-conducting integration of the magnetic field and therefore has a
wafer that is placed in the gap of a magnetic time and phase delay whilst the integration is completed.
concentrating ring. This type of transformer is also This can be corrected for within a digital protection relay.
sensitive to d.c. currents. The transformer requires a The schematic representation of the Rogowski coil sensor
power supply that is fed from the line or from a separate is shown in Figure 6.27.
power supply. The sensing current is typically 0.1% of the
current to be measured. In its simplest shape, the Hall
Electrical to optical
effect voltage is directly proportional to the magnetising converter/transmitter
current to be measured. For more accurate and more I
Burden
sensitive applications, the sensing current is fed through
a secondary, multiple-turn winding, placed around the
magnetic ring in order to balance out the gap magnetic Optical
field. This zero-flux or null-flux version allows very fibres
accurate current measurements in both d.c. and high-
frequency applications. A schematic representation of
Current transformer
C u r r e n t a n d Vo l t a g e T r a n s f o r m e r s
Air core
toroidal coil
i
Electrical to optical
converter
V
i
Optical
fibres
Sensing current
Sensing element