Fire Department Fire Apparatus Service or Acceptance Test

Manufacturer: Emergency One Unit No. 1 Manufacturers Model: Pumper 44 (Typhoon) Engine Make: Cummins Model: ISL 400 Pump Make: Hale Model: QMAX150-23 Model Yr.: 2002 Department: Manufacturers Serial No. 123456 BHP 400 at 2200 Stages: 2 Torque: 1200 200 PSI 10 : 1 2.28 : 1 D 1050 My Fire Department VIN: 4EN6AAA8021003456 RPM 2330 Ft Lbs at 1300

Counter Ratio: Gear Ratio: Engine to Pump Transmission Gear Used Test Requirements (in GPM) Run by: Howard Sykes

150 PSI 10 : 1 2.28 : 1 D 1500

250 PSI 10 : 1 2.28 : 1 D 750

Tested at: Their Fire Department, Any Street, Durham, NC Date: Air temp: 81 Pressure: 30.15 Water temp: 78 Counter Speed Checked Readings Taken From: Veedee Root 6611 Suction Size: 6 inches Length 16 feet Lift: 3.33 feet 1250 Dry Vacuum test: 8 inch drop in 5 minutes Time to obtain suction: 33 seconds (water flow) Tank flow test: seconds GPM Tip Size: 1.5 Pitot: 58 0 gallons flowed at: 508 Tank flow test: 1.5 Tip size 58 Pitot pressure 700 GPM maximum flow rate measured with a HOSE LAYOUT: Two lines of 2-50 sections + two 1-50 sections 2.5 hose Digital Counter Start Stop 130 131 132 132 134 659 132 8
Engine Counter Pump Speed
Pump Pressure Appar. Gauge Pump Pressure Test Gauge

Tip Size:

2 1/2

Pitot

Time 15:11 15:16 15:21 15:26 15:31

Speed from App. Tach. counter Speed

Suction Pressure

Net Pump Pressure

Pitot Reading

2964 2987 3010 3010 3055

1300 1310 1320 1320 1340

1325 1329 1326 1324 1333 6637 1327

149 149 149 149 152 748 150

145 145 145 145 145 725 145


Relief Valve Test

5.5 5.5 5.5 5.5 5.5 28 6

150.5 150.5 150.5 150.5 150.5 753 151 10

81 81 81 81 81

GPM 1506 1506 1506 1506 1506

Total Average Relief Valve Test

15025 6590 3005 1318 psi increase at 150 psi

405 7530 81 1506 psi increase at 90 psi

10% Overload test Digital Counter Time 15:42 15:47 Start Stop 138 136

Engine Counter Pump Speed

Speed from App. Tach. counter Speed

Pump Pressure Appar. Gauge

Pump Pressure Test Gauge

Suction Pressure

Net Pump Pressure

Pitot Reading

3146 3101

1380 1360

1374 1373

170 165

162 162

4 4

166 166

81 81

GPM 1506 1506

HOSE LAYOUT: Two lines of 2-50 sections + one 1-50 2.5 hose Digital Counter Time 15:56 16:01 16:06 Start Stop 149 142 146
Engine Counter Pump Speed Speed from App. Tach. counter Speed
Pump Pressure Appar. Gauge Pump Pressure Test Gauge

Tip Size:

2 1/8
Net Pump Pressure Pitot Reading

Pitot

Suction Pressure

3397 3238 3329

1490 1420 1460

1506 1469 1464

194 190 190

198 198 198

4 4 4

202 202 202

64 64 64

GPM 1056 1056 1056

Total Average Relief Valve Test

437 146 15

9964 4370 3321 1457 psi increase at 200 psi

4439 1480

574 191

594 198

12 4

606 202

192 64

3168 1056

HOSE LAYOUT: Two lines of 2-50 sections 2.5 hose Digital Counter Time 16:15 16:20 16:25 Start Stop 167 167 170
Engine Counter Pump Speed Speed from App. Tach. counter Speed
Pump Pressure Appar. Gauge Pump Pressure Test Gauge

Tip Size:

1 3/4
Net Pump Pressure Pitot Reading

Pitot

Suction Pressure

3808 3808 3876

1670 1670 1700

1662 1662 1669

253 255 255

250 250 250

3 3.5 3.5

253 253.5 253.5

68 68 68

GPM 750 750 750

Total Average Relief Valve Test

504 168 15

11491 5040 3830 1680 psi increase at 250 psi

4993 1664

763 254

750 250

10 3

760 253

204 68

2250 750

FINAL RESULTS 150 psi 1. 2. 3. 4. 5. 6. 7. 8. 9. Average Nozzle Pressure Gallons Per Minute Pump Stage (Par/Ser) Avg. Pump Press. (App. Gauge) Avg. Pump Press. (Test Gauge) Suction Pressure Average Net Pump Press. Avg. RPM Engine: Counter Avg. RPM Engine: App Tach 81 1506 Volume 150 145 6 151 1318 1327 3005 200 psi 64 1056 Volume 191 198 4 202 1457 1480 3321 250 psi 68 750 Pressure 254 250 3 253 1664 1664 3830

10. Avg. RPM Pump

Signature of Person Running Test

Title of Person Running Test

09/14/03 Date

re Department 4EN6AAA8021003456 Governed RPM RPM

09/14/03

gallon booster tank seconds (water flow) ze: 1.5 Pitot: 58 Pitot pressure 81

REMARKS

crease at 90 psi

REMARKS

64

REMARKS

68

REMARKS

Fire Department Fire Apparatus Service or Acceptance Test


Pump rated capacity:
1500

Date of test:

9/14/03

Manufacturer: Emergency One Serial No: 123456 Department: My Fire Department Test location: Their Fire Department, Any Street, Durham, NC Manufacturer's model: Pumper 44 (Typhoon) Engine Mfg: Cummins Model: ISL 400 Pump Mfg: Hale Model: QMAX150-23 Test Conditions: Barometric Pressure: Temperature: 78 30.15 Suction hose size: Hose length: 16 6 Pump inlet elevation above water: 3.33 feet

4000 3500

3000
2500 2000 1500 1000 500 0
150 test 165 test 200 test 250 test GPM 1506 1506 1056 750 PSI 145 162 198 250 Vacuum 6 4 4 3 Net PSI 151 166 202 253 eng. RPM 1318 1370 1457 1680 pump RPM 3005 3124 3321 3830 pump stage Volume Volume Volume Pressure
150 test 165 test 200 test 250 test

Relief valve increase: psi Vacuum test drop: 8 Pump prime time: 33 8 No Load goverened speed: 2330 Tank flow test: Tank size: 1250 gallons; 0 gallons flowed at 508 GPM Tank flow test: Tank size: 1250 gallons; Maximum flow rate is: 700 GPM

secs.

Test run by: