Professional Documents
Culture Documents
MID-YEAR REPORT
Liam ONeill Eleanor Taffs Supervisor: Larry Bellamy Date of submission: 4 June 2008 A report submitted in partial fulfilment of the requirements for the BE(Hons) degree in Natural Resources Engineering
EXECUTIVE SUMMARY
In developing countries like India, where electrical energy is not universally available, free running (Nicol and Pagliano 2007) buildings are common. In hot climates passive cooling techniques such as radiant and evaporative cooling, comfort and nocturnal ventilation, and thermal mass and insulation, are employed to control this response in order to improve the thermal comfort of inhabitants. Where such measures are not used effectively and there is no reliable electricity source to provide active cooling, heat stress can have negative effects on the internal living environment. Even where there is a reliable electricity source, it is still desirable to reduce energy consumption. In hot dry or warm humid countries, more than half of the urban peak load of energy consumption is used to satisfy air-conditioning demands alone (Koch-Nielsen 2002). Since the urbanisation rate in developing countries, including India, is extreme, the pressure placed on energy resources to satisfy the future requirements will be great, unless measures to reduce consumption are put in place (Koch-Nielsen 2002). This project centres on a village called Pabal, which is situated in west India in the state of Maharashtra. Most houses in Pabal are free running, yet do not have passive cooling measures integrated into their design. Therefore, during the summer months, high outside air temperatures result in similarly high indoor air temperatures which are well outside the limits of thermal comfort. Research into traditional methods of keeping homes cool during the dry season in India and in other parts of the world have been investigated in this report as well as recent developments in cost-effective housing designs. Through the use of computer modelling this report has found that increasing the thermal mass and ventilation at night and rotating the building so the largest exposure is on the North and South sides will reduce inside temperatures. Changing a roofs colour to increase the solar reflectance and adding insulation underneath the roof will reduce heat gain during the day and decrease the hours of discomfort inside. The recommendations of this report are to further investigate the following design strategies and how they interact to provide thermal comfort: - high thermal mass; - night ventilation; - orientation of the building so that the North and South sides will have the largest solar radiation exposure; - light colour with high solar reflectance on the roof; and - insulation underneath the roof. The most important factors in achieving thermal comfort inside the test building found in this report is preventing heat gain through the roof, and allowing night cooling of the interior mass.
TABLE OF CONTENTS
1. 2.
INTRODUCTION ............................................................................................................................. 1 BACKGROUND .............................................................................................................................. 2 2.1. 2.2. 2.3. 2.4. LOCATION.................................................................................................................................. 2 CLIMATE.................................................................................................................................... 3 THERMAL COMFORT .................................................................................................................. 5 CURRENT HOUSE DESIGN .......................................................................................................... 7
3.
LITERATURE REVIEW .................................................................................................................. 8 3.1. BUILDING DESIGN ...................................................................................................................... 8 Layout and Orientation .................................................................................................... 8 Windows and Shading ..................................................................................................... 9 Colour and reflectance of Envelope .............................................................................. 10 Insulation ....................................................................................................................... 11 Thermal mass ................................................................................................................ 12
PASSIVE COOLING ................................................................................................................... 12 Ventilative Cooling ......................................................................................................... 13 Radiant Cooling ............................................................................................................. 16 Evaporative Cooling ...................................................................................................... 17 Earth as Cooling Source................................................................................................ 18
MODELLING ................................................................................................................................. 19 4.1. 4.2. MODELLING METHODOLOGY ..................................................................................................... 19 MODELLING RESULTS .............................................................................................................. 20
5. 6. 7. 8.
DISCUSSION ................................................................................................................................ 23 CONCLUSIONS AND RECOMMENDATIONS ............................................................................ 24 ACKNOWLEDMENTS .................................................................................................................. 25 REFERENCES .............................................................................................................................. 26
ii
TABLE OF FIGURES
FIGURE 1: MAP OF INDIA INDICATING THE LOCATION OF PUNE WITHIN THE STATE OF MAHARASHTRA. ............. 2 FIGURE 2: SATELLITE IMAGE OF PABAL ....................................................................................................... 2 FIGURE 3: SATELLITE IMAGE OF PABAL AND DAM ......................................................................................... 3 FIGURE 4: DIRECT SOLAR RADIATION AND PRECIPITATION INDICATOR IN PUNE (MADE WITH DATA FROM (ISHRAE 2008)). .............................................................................................................................. 4 FIGURE 5: AVERAGE HOURLY DRY BULB TEMPERATURES AND HUMIDITY FOR PUNE IN MAY (MADE WITH DATA
FROM (ISHRAE 2008)). ....................................................................................................................
FIGURE 6: FLOOR PLAN OF FABLAB. (SAUNDERS 2008)............................................................................... 7 FIGURE 7: VARIATION OF ROOM TEMPERATURE FOR FOUR DIFFERENT BUILDING ORIENTATIONS IN MAY 1985 (VERMA ET AL. 1986) ......................................................................................................................... 9 FIGURE 8: LEFT: AIR TEMPERATURE IN THE SHADED AREA (THIN LINE) AND THE UNSHADED AREA (THICK LINE). RIGHT: W ALL SURFACE TEMPERATURE IN THE SHADED AREA (THIN LINE) AND THE UNSHADED AREA (THICK LINE). (PAPADAKIS ET AL. 2000) ............................................................................................ 10 FIGURE 9: ILLUSTRATION OF DIFFERENT WALL DESIGNS ............................................................................. 11 FIGURE 10: VARIATION OF ROOM TEMPERATURE WITH TIME IN DELHI (14 MAY 1985). (VERMA ET AL. 1986) 12 FIGURE 11: TYPICAL DESIGN OF A WINDCATCHER (BAHADORI, MAZIDI ET AL. 2008) .................................... 13 FIGURE 12: STACK VENTILATION SYSTEM AT THE SCHOOL OF ARCHITECTURE, BERGEN, NORWAY (FORDHAM 2000) ............................................................................................................................................. 14 FIGURE 13: VENTILATION OPTIONS IN HOT, HUMID CLIMATES (AUSTRALIAN_GOVERNMENT 2005) ................ 15 FIGURE 14: BASIC DESIGN OF THE SOLAR CHIMNEY WITH A MASSIVE ELEMENT FOR HIGH THERMAL INERTIA (MARTI-HERRERO AND HERAS-CELEMIN 2007) ............................................................................... 16 FIGURE 15: FLOOR PLAN OF BASE HOUSE DESIGN. .................................................................................... 19 FIGURE 16: HOURS OF EXTREME DISCOMFORT WHEN BASE CASE IS CHANGED ............................................ 21 FIGURE 17: INDOOR MAXIMUM OPERATIVE AIR TEMPERATURES (C) COMPARED.......................................... 22
TABLE OF TABLES
TABLE 1: AVERAGE MONTHLY TEMPERATURE DATA FOR PUNE (ISHRAE 2008). ........................................... 4 TABLE 2: RANGE AND OPTIMUM VALUES OF TROPICAL SUMMER INDEX FOR VARIOUS THERMAL SENSATIONS.... 6 TABLE 3: THERMAL COMFORT IN PUNE ....................................................................................................... 6 TABLE 4: CHARACTERISTICS OF THE ROOF IN THE BASE CASE HOUSE. ........................................................ 20 TABLE 5: CHARACTERISTICS OF THE INTERIOR AND EXTERIOR WALLS IN THE BASE CASE HOUSE................... 20 TABLE 6: CHARACTERISTICS OF THE FLOOR IN THE BASE CASE HOUSE........................................................ 20 TABLE 7: MODELLING RESULTS FOR THE BASE CASE SCENARIO AND THE EIGHT MODIFIED SCENARIOS. ......... 21
iii
1. INTRODUCTION
In developing countries like India, where electrical energy is not universally available, free running (Nicol and Pagliano 2007) buildings are common. Such buildings are not heated or cooled, meaning that the indoor air temperature changes in response to ambient air temperature changes (Givoni 1994c). In hot climates passive cooling techniques such as radiant and evaporative cooling, comfort and nocturnal ventilation, and thermal mass and insulation, are employed to control this response in order to improve the thermal comfort of inhabitants. Where such measures are not used effectively, and there is no reliable electricity source to provide active cooling, heat stress can have negative effects on health and productivity (Chandra 1995). Even where there is a reliable electricity source, it is still desirable to reduce energy consumption. This is especially true in a country such as India, which is a net importer of energy (Kakodkar 2005) and which anticipates increased energy consumption because of population and economic growth (Rodrik and Subranium 2004; Wilson and Purushothaman 2003). In hot dry or warm humid countries, more than half of the urban peak load of energy consumption is used to satisfy air-conditioning demands alone (Koch-Nielsen 2002). Since the urbanisation rate in developing countries, including India, is extreme, the pressure placed on energy resources to satisfy the future requirements will be great, unless measures to reduce consumption are put in place (Koch-Nielsen 2002). The current project centres on a village called Pabal, which is situated in west India in the state of Maharashtra. Most houses in Pabal are free running, yet do not have passive cooling measures integrated into their design. Therefore, during the summer months, high outside air temperatures result in similarly high indoor air temperatures which are well outside the limits of thermal comfort. The aim of this project, as set by Engineers Without Borders (EWB) UK and EngINdia, is to design a retrofit of a typical Pabal house so that it is cooler in high temperatures, without resorting to the use of electricity. The design should be cost-effective and take into account the local availability of construction materials. Our project will include research into traditional methods of keeping homes cool during the dry season in India as well as in other parts of the world. We will also look into recent developments in cost-effective housing designs, and into the feasibility of retrofitting the existing structures. Computer modelling will be performed to determine which design measures are more effective at reducing indoor air temperatures. If a solution is devised that meets the project criteria, it will be trialled at Vigyan Ashram, an Indian Institute of Education in Pabal. If they also believe it to be successful then they will act as a training centre for the sharing of knowledge of how to construct the cooler, more comfortable houses.
2. BACKGROUND
2.1. Location
Pabal is located in Pune, Maharashtra, India. Pune (also called Poona) is the name of both a city and district in the state of Maharashtra, which is located to the west of India as shown in Figure 1, and has a population of approximately 97 million according to the latest national census (Census 2001). Pune the city has a population of approximately 4 million (Census 2001) and is a renowned centre of learning in India.
Figure 1: Map of India indicating the location of Pune within the state of Maharashtra.
Pabal itself is located 30 km north of Pune. It is a rural, agricultural village with a population of approximately 4,300 people, or 800 households, as measured at the last census in 2001. The EngINdia team, however, reported in 2006 that this number has now grown to about 9,000 (Furminger et al. 2006). As can be seen in the satellite image below (Figure 2) the core of the village is more densely populated, with approximately 60% of the population living there. Those living outside the centre of Pabal live in hamlets and are primarily farmers who grow vegetable crops.
At the time of the engINdia expedition, Pabal was experiencing problems with its water supply. Private and public wells were being exhausted during the dry season, forcing the state government to transport water to Pabal each day in 12,000 L water tankers. In order to solve the water supply problems, a dam was constructed near Pabal, but was not in use at the time the engINdia report was published. The dam is shown in the satellite image below (Figure 3). A pipe system from the dam has now been constructed and supplies Pabal with year-round water (Saunders 2008). The water is piped into a water tower each morning, giving the village a short period in which to fill their tanks. Reports suggest that the supply lasts for most of the dry season, but is strained towards the end. During the monsoon season, there are no problems with water supply.
1 km
The electricity supply in Pabal is unreliable, with an average of eight power cuts occurring each day. These cuts are due to rationing imposed by the state government because of an electricity shortage in Maharashtra. Alternatives to electricity used in Pabal are candles, kerosene lanterns, gas lanterns, flashlights, and, for the more affluent villagers, 12 volt batteries. There are also biogas generators, installed 15 years ago, although there are problems with supplying the cattle dung from which the fuel is generated.
2.2. Climate
The climate of a given region is generally defined as the interaction of several meteorological elements (Koch-Nielsen 2002), principally: solar radiation; precipitation; humidity; air temperature; and wind.
Hourly weather data from the Indian Society of Heating, Refrigerating and Air-Conditioning Engineers (ISHRAE) were used to analyse the climate in Pune District with reference to the above parameters (ISHRAE 2008). Most of Maharashtra, including Pune, is defined under the Kppen system as having a semi arid steppe climate (ISHRAE 2008). The classification BSh denotes that the climate is predominately arid, is a steppe climate opposed to an arid desert climate, and that the coldest month has an average minimum temperature above 0C. 3
As shown in Table 1, summer in India is from April to June of each year, with the most extreme summer week occurring in mid May, week 19 of the year. The wet season begins in May also, with the heavy monsoons continuing through until November. Outdoor air temperatures fall during this period, largely because of the shading effect of cloud coverage. Little rain falls during the rest of the year, the dry season.
Table 1: Average monthly temperature data for Pune (ISHRAE 2008).
Jan Average maximum temperature (C) Average minimum temperature (C) Temperature range (C) 28.2 11.5 16.7
Apr
Oct
30.8 35.7 36.9 35.7 29.6 26.6 26.1 28.1 29.5 28.8 13.1 16 19.5 22.9 23.8 22.7 22 3.9 4.1 21.4 20.6 16.3 6.7 8.9 12.5
Solar radiation is radiation from the Sun that penetrates the Earths atmosphere and is incident on the ground. As is evident from Figure 4, the dramatic drop in the level of solar radiation measured in Pune during the months of May to October, the wet season, corresponds with an increase in precipitation. This is due to effect that storm clouds have in blocking a large amount of the direct solar radiation that would otherwise reach the ground.
8000
3
7000
2.5
6000
2
5000
4000
1.5
3000
1
Direct Average
2000
Direct Maximum
0.5
1000
Precipitation Inidcator (KPa)
0 Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Month
Figure 4: Direct solar radiation and precipitation indicator in Pune (made with data from (ISHRAE 2008)).
Humidity levels vary throughout the year as well as throughout the day. The lowest average humidity range of 18 61% is felt in April, which this corresponds with the start of summer and the end of the dry season. The greatest average humidity range of 57 95% is experienced in October, which is the start of winter and the end of the rainy season (ISHRAE 2008). Humidity is also linked to dry bulb temperature, as shown in Figure 5 below. As the temperature increases during daylight hours, humidity decreases, reflecting the evaporation that takes place at higher temperatures.
40
90
35
80
70 30
10
Figure 5: Average hourly dry bulb temperatures and humidity for Pune in May (made with data from (ISHRAE 2008)).
Wind direction varies throughout the year, but is generally of low velocity. From October through April winds are predominantly northerly while between May and September they are westerly. Maximum wind speeds of approximately 7 ms-1 are experienced in June while minimum wind speeds of approximately 3 ms-1 occur in January (ISHRAE 2008). In the summer, the period of interest for the current study, the average wind speeds are low, ranging from 1 ms-1 to 2.2 ms-1.
0: 01 -1 :0 1: 01 0 -2 :0 2: 01 0 -3 :0 3: 01 0 -4 :0 4: 01 0 -5 :0 5: 01 0 -6 :0 6: 01 0 -7 :0 7: 01 0 -8 :0 8: 01 0 -9 :0 9: 0 01 -1 0: 10 0 :0 0 111 11 :0 :0 0 112 12 :0 :0 0 113 13 :0 :0 0 114 14 :0 :0 0 115 15 :0 :0 0 116 16 :0 :0 0 117 17 :0 :0 0 118 18 :0 :0 0 119 19 :0 :0 0 120 20 :0 :0 0 121 21 :0 :0 0 122 22 :0 :0 0 123 23 :0 :0 0 124 :0 0
Time
Tn = 0.534T0 + 11.9
This reflects the gradual acclimatisation and change in behaviour that occurs as mean temperatures change each month. Effectively, as mean monthly temperatures increase, the limits of thermal comfort increase accordingly; less clothing is worn and the bodys cooling mechanisms adjust to the new cooling demands. Humphreyss formulation has been modified since it was developed. One such modification is described in Auliciems and Szokolay (1997); mean monthly temperatures and relative humidities are used to find the new effective temperature, ET*, on a psychrometric chart. This temperature indicates how humidity affects apparent temperature. ET* can then be used to find the neutral temperature, Tn, for a free running building with:
Tn = 18.9 + 0.255ET *
The zone of comfort for 90% acceptability can then be taken as Tn2.5C. acceptability is adequate, this can be increased to Tn3.5C.
If 80%
Another indicator of the thermal comfort has been devised by the Central Building Research Institute (CBRI) of India. CBRI suggests that a Tropical Summer Index (TSI) can be used to calculate thermal comfort in hot dry and hot humid climates:
TSI =
Where:
1 3 t w + t g + 2v 1/ 2 3 4
tw = the wet bulb temperature, C tg = the globe temperature, C v = air velocity, ms-1 The TSI is defined as the temperature of still air at 50% relative humidity which induces the same thermal sensation as the actual environmental conditions (Chandra 1994). The thermal comfort felt at ranges of TSI values is shown in Table 2 below:
Table 2: Range and optimum values of tropical summer index for various thermal sensations.
Although this indicator was developed especially for use in India, we are unable to use it in our project because the ISHRAE weather data does not include globe temperature, tg, which is a measure of the effect of radiation. The Auliciems and Szokolay (1997) method has therefore been followed and the following thermal comfort limits for 80% acceptability found (Table 3).
Table 3: Thermal Comfort in Pune Jan Feb Marc h Tmax (C) 28. 30. 35.7 2 8 Tmin (C) 11. 13. 16 5 1 Tmean (C) RHmean (%) ET* (C) Tn(C) 19. 8 63 20. 4 24. 1 27. 6 20. 6 21. 7 52. 5 23. 0 24. 8 28. 3 21. 3 25.8 40.0 25.5 25.4
Aug 26. 1 22
28.9
29.4
29.4
21.9
22.4
22.4
In the preliminary, sensitivity analysis the number of hours over 30C was used to compare the effectiveness of different components of the design against a base case scenario. This level will be revised to match the thermal comfort temperatures above when further analysis is undertaken.
Like typical houses in Pabal, the windows are not fitted with glass, but with metal shutters. The roof is corrugated iron and the floor is concrete. The walls are clay brick and there is an aluminium veranda connected on the exterior of the wall indicated by the blue line. The whole side of that wall (that is, the yellow and blue sections) has a gap of 0.1 m from the ceiling to provide for ventilation. (Saunders 2008) In May, the most extreme summer month, it is common for the inside air temperatures to reach and even exceed 40C (Saunders 2008). As this general maximum temperature is known, the house designed used to model sensitivity is based on this FabLab design. This will allow basic verification of results.
3. LITERATURE REVIEW
In most countries, energy use in the building sector represents about one third of the total energy consumption. In developing countries the residential building sector accounts for more than half of the electricity consumption (Synnefa et al. 2006). Considering the scale of the energy demand, a great deal of research has been done on how to increase thermal comfort in a building design by passive means. The main text referred to throughout this review is Givonis Passive and Low Energy Cooling of Buildings (Givoni 1994c). This book is a comprehensive guide to the research on passive cooling technology, especially when read in conjunction with the authors later text Climate Considerations in Building and Urban Design (Givoni 1998).
Figure 7: Variation of room temperature for four different building orientations in May 1985 (Verma et al. 1986)
Figure 7 shows indoor air temperature for 14 May 1985, which is during the Indian summer. It can be seen that large exposure on the North and South side of the building gives the lowest inside temperatures during summer.
Figure 8: Left: Air temperature in the shaded area (thin line) and the unshaded area (thick line). Right: Wall surface temperature in the shaded area (thin line) and the unshaded area (thick line). (Papadakis et al. 2000)
The air temperature in the shaded area is consistently lower than in the unshaded area and the wall surface temperature is more uniform and generally cooler in the shaded area compared to the unshaded area. External shading devices such as eaves are more efficient than internal fixed shading devices, as they lower direct radiation from reaching the internal atmosphere instead of dissipating the heat to the air gap between the shading device and the window (Gouri Datta 2001).
metal, which has poor reflective properties by itself (Givoni 1994c). The higher reflectance results in less energy supplied to the interior, so that the inside air temperature becomes lower than the temperature inside an identical building without white paint on the roof (Amer 2005). While the figures from the cited reports are merely indicative and will vary as a function of the buildings materials and features, they suggest that painting the roof of a building in a hot climate a light colour, can contribute greatly to improving indoor environmental conditions and decreasing the need for cooling (Santamouris et al. 2007).
3.1.4. Insulation
Insulation is a material that resists and therefore retards the transfer of heat. The interaction of the three modes of heat transfer, convection, radiation, and conduction, determines the overall effectiveness of insulation. Insulative material is characterised by presence of dead air cells within its mass which suppress convective heat transfer by preventing air movement. It is this trapped air that provides the insulation, not the solid material itself. Insulation also affects the rate of radiation transfer, because the temperature difference on either side of the air cells is not large. This causes the overall path of the radiation through the material to be broken into smaller, more convoluted paths. The rate of conduction is decreased due, again, to the presence of the poorly-conductive air pockets (Al-Homoud 2004). The placement of insulative material within the building component can therefore improve indoor conditions. The best performance can be achieved by placing the insulating material close to the point of entry of heat flow, that is, the outside of the building component. However, for practicality it is common to use insulation on the inside or between wall cavities, as shown in Figure 9. (Al-Homoud 2004)
A performance study of different passive cooling techniques in Delhi by Verma et al. (1986) showed that cavity walls can in fact provide better protection from heat than insulation on the outside of walls. Figure 10 shows the results of the study for different wall designs shown in Figure 9, where the room temperature for the cavity wall case is consistently lower compared to the case where insulation is on the outside of the wall.
11
Figure 10: Variation of room temperature with time in Delhi (14 May 1985). (Verma et al. 1986)
The term passive cooling applies to various simple cooling techniques that enable the indoor temperatures of buildings to be lowered through the use of natural energy sources (Givoni 1994c). It is defined as the removal of heat of the building environment by applying the natural processes of elimination of heat to the ambient atmosphere by convection, radiation and evaporation or to the adjacent earth by conduction and convection (Dilip Jain 2004). The term passive does not necessarily exclude the use of a fan or a pump. However, in the context of rural Maharashtra, which is currently experiencing electricity rationing, it is submitted that any system that relies heavily on a connection to mains electricity is not feasible. The research that has been conducted on various passive cooling techniques has been summarised below, and the feasibility of each is discussed at the end. 12
However, wind catchers require high wind speeds, and have no application in regions of low wind speed (Bahadori 1994). 13
It is estimated that comfort ventilation will only be effective up to a temperature of 30C (Givoni 1994). Because of the limited cooling effect of ventilation if outdoor air temperatures are too high, or the climate arid, active control using an air-conditioning system is usually preferred in developed countries (Mochida et al. 2005). This attitude is now beginning to change because of increased awareness of the importance of energy conservation; several recent studies have been undertaken into how ventilation can be utilised to provide thermal comfort in unfavourable climates. Mochida et al (2005) have found that an automatic window opening system that operates in accordance with the temporal variations of indoor and outdoor climates can greatly reduce indoor air temperatures and keep indoor conditions mostly within thermal comfort limits. The tests were conducted on Tohoku University in Japan during the summer of 2001. Results suggested, however, that there existed a time during a day when a comfortable indoor environment could not be achieved only with window control. In areas where air velocity is not high enough for effective ventilation, several solutions have been suggested. In Mochida et al (2005), again, the optimum placement of tree arrangements, which decrease mean velocity and increase turbulence, and openings around the building was found through Computational Fluid Dynamics (CDF) analysis and tree canopy models. The study showed that this kind of design has a major impact on the effectiveness of ventilation, and can decrease the period at which comfort levels are exceeded. Another solution is to use the density differences of indoor air to encourage throughput. This is called stack driven natural displacement (Lomas 2007) and uses the upward buoyant motion of warm indoor air through a vertical shaft to draw cooler air into the building from outside. Figure 12 below shows a natural ventilation stack system:
Figure 12: Stack ventilation system at the School of Architecture, Bergen, Norway (Fordham 2000)
In a recently published review of renewable building energy systems, the major issue with ventilation as a cooling source was identified as the difficulty in establishing a suitable datum of energy impacts for strategic planning (Omer 2008). This is attributable to an uncertainty surrounding air change rates and the difference in enthalpy between the incoming and outgoing air streams, both of which are fundamental parameters in ventilation analysis (Martin 1996). These issues are heightened when designing large scale buildings, but are not so critical in residential buildings.
14
The type of ventilation suited to the situation will depend on the building in question. Single sided ventilation is effective to a depth of 6 m into a building, and so is normally used only in smaller residential houses. Simple openings such as windows or vents along one side of an external wall are the usual method of providing this type of ventilation. Cross-ventilation, as shown in Figure 13, is encouraged by the same kind of openings on opposite walls, and is effective over 12 m. For larger spaces, such as atria, mixed flow ventilation is required. (Martin 1996)
In arid regions, such as in Pabal, the effect of cross-ventilation during the day could be more limited. Nocturnal Ventilation The ventilation of a building during the night cools its interior mass if the diurnal temperature range, that is the difference in nocturnal and daytime ambient air temperatures, is high during summer (Givoni 1994c). This temperature difference means that the interior mass is cooled effectively during the night, which has the effect of both absorbing heat during the day and lowering the internal air temperature. Experiments suggest that nocturnal ventilation will be effective where the diurnal temperature range is between 15C to 20C.
If no active cooling system is used in conjunction with passive techniques, Blondeau et al. suggested in 2002 that the ventilation scheme could be designed as follows (Blondeau et al. 2002): During the diurnal period, the air change rate is constant; it can be set to values between 0.5 and 10 air changes (with a 1 ach step between 1 and 10 ach). During the nocturnal period, the air change rate is also set to values between 0.5 and 10 ach. Nevertheless, as night ventilation seeks to cool down the building, the air change rate automatically changes from the set point rate to 0:5 ach as soon as the indoor air temperature becomes lower than the outdoor one.
A popular method of nocturnal ventilation that has developed over the last 15 years is the solar chimney. This structure, shown in Figure 14 below operates on a similar basis to stack ventilation; air is drawn out of a building by the rising air in the channel, which is heated by solar radiation.
15
Figure 14: Basic design of the solar chimney with a massive element for high thermal inertia (MartI-Herrero and Heras-Celemin 2007)
The first studies about solar chimneys began with Bansal et al. which developed a mathematical model for a steady state of a solar chimney consisting of a conventional chimney connected to a solar air collector (Bansal et al. 1993). Khedari et al. went on to show the experimental results of natural ventilation effect by a solar chimney in a school (Khedari et al. 1999). The results obtained in the school of 25 m2 and with only one room, show the viability of the system. Afonso et al. published the results of a solar chimney compared with a conventional chimney. They proposed a non-steady model of heat transfer in a single horizontal dimension, applying a model based on finite differences. In this model, the coefficients of heat transfer vary throughout the day according to temperatures. The measurements of air flow were made with tracer gas techniques, which agreed with the results of the simulation (Afonso and Oliveira 2000). Ong then proposed a mathematical model of heat transfer in a steady state for a solar chimney (Ong 2003), and contrasted the model with a real solar chimney (Ong and Chow 2003). The solar chimney was characterised by three temperatures: average temperatures of the glass, air and wall. The solar chimney was 2 m in height with the air channel width between 0.10 and 0.30 m, in real meteorological conditions. The best agreement between the simulation and experimental data occurred for solar radiation intensities of 200 to 650 W/m2 and 0.3 m width air channel. More recently, Martl -Herrero et al. modelled the effect of walls of high thermal mass in creating a greater temperature difference between the air in the channel and inside the building itself. At a maximum solar radiation on a vertical surface of 450 W/m2, it was found that an air mass flow of 0.010 kg/s could be achieved (MartI-Herrero and Heras-Celemin 2007).
The first and simplest approach to radiant cooling is to have a thermally massive, conductive roof with movable insulation on the exterior. The exterior of the roof is heavily insulated during the day to minimise heat transfer into the building, and at night is removed to allow radiation to sky from the building. Heat loss by convection to the ambient air will also occur Experiments in Israel have shown that this has the potential to lower the average indoor temperature by 3.5 K. However, at this stage movable insulation has proved expensive and unreliable(Clark 1989). Another approach is the Skytherm system developed by Hay in 1978 (Hay 1978). Here bags of water are placed directly over a metal deck on the roof. In summer these bags are cooled by exposure to the night sky, and are then covered by movable insulation during the day. In winter, the opposite is practised to provide a heat source. Studies in Florida have shown this method to be effective; the expensive and problematic movable insulation is still of concern, however (Clark 1989). Ordinary specialised radiators can be added to buildings with insulated roofs to provide radiant cooling. Givoni, in his book on passive cooling emphasises that the roof must be insulated to minimise heat loss in winter and heat gain in summer (Givoni 1998). Chandra (1994) suggests that a metal sheet coated with an emissive paint could be placed over an insulated roof to draw cool air into the thermal mass during the night. The roof would then act as a heat sink during the day. Givoni reported a drop of 3 - 5C using this method in hot arid climates (Givoni 1991). Specific to developing countries, a variation on the ordinary specialised radiator has been suggested. Considering that corrugated iron roofs are common in poorer communities, including Pabal, Givoni (1998) has put forward a metallic radiant roof method that can retrofit an existing house. The skyward side of the roof could be coated with an emissive paint to enhance radiation to sky at night. An insulative layer could then be installed underneath the roof in order to prevent heat gain during the day. This layer needs to be easily removable, so that it can be drawn aside to allow heat to escape during the day.
transfers the heat to the evaporation process, thereby reducing heat gain into the building (Kharrufa and Adil 2008). A reduction in indoor air temperature of 6 to 9 C has been recorded by this method (Tang 2005). The main issue in determining whether evaporative cooling can be employed to cool a building is the relative humidity of the region. If the ambient humidity is too high, DEC will further increase it, resulting in a possible reduction in thermal comfort. In effect, the increase in thermal comfort gained through cooling of the air will be discounted by the increased humidity. Another consideration is the availability of water. Evaporative cooling requires a considerable amount of water in order to effectively lower air temperatures (Furminger et al. 2006).
18
4. MODELLING
The base case house used in this project is shown below in Figure 15. It is a modification of the FabLab design to better represent a typical house that experiences overheating in Pabal. The internal temperatures of the base case house were modelled over a year using hourly weather data averaged over 10 years for Pune district. The purpose of this initial stage of modelling was to verify the model against collected data from the FabLab and to test the sensitivity of these modelling parameters: - thickness of the wall; - wall material; - insulation on walls; - insulation on roof; - night ventilation; - roof colour; and - building orientation.
19
The roof of the base case house is steel cladding painted green with a layer of paper underneath. A description of the properties is shown in Table 4:
Table 4: Characteristics of the roof in the base case house.
Parameter Thickness (mm) Colour Density (Kg/m3) Thermal conductivity (W/mK) Specific Heat (J/kgC) Solar absorbance Thermal Resistance (m2C/W)
Paper 0.59
Both the interior and exterior walls of the base case house are clay brick with no insulation. The windows are openings with no glass and metal shutters that are closed from 9pm to 7am. A description of the properties is shown in Table 5:
Table 5: Characteristics of the interior and exterior walls in the base case house.
Parameter Thickness (mm) Colour Density (Kg/m3) Thermal conductivity (W/mK) Specific Heat (J/kgC) Solar absorbance Thermal Resistance (m2C/W)
Clay Brick 200 light grey 1400 0.48 1000 0.4 0.29
The floor of the base case house is a concrete slab covered with a layer of cork to represent a non-conductive floor covering. A description of the properties is shown in Table 6:
Table 6: Characteristics of the floor in the base case house.
Parameter Thickness (mm) Colour Density (Kg/m3) Thermal conductivity (W/mK) Specific Heat (J/kgC) Solar absorbance
Table 7: Modelling results for the base case scenario and the eight modified scenarios.
Model scenario Base case Double wall thickness Change brick type Change wall material to concrete Add insulation to outside of wall Add insulation to underside of roof Increase night ventilation Change roof colour to light grey Rotate building 90
Hours above 30C 1807 1938 1699 1566 1942 1700 1691 1509 1615
Base case
Add insulation to outside of wall Add insulation to underside of roof Increase night ventilation
Rotate building 90 0 200 400 600 800 1000 1200 1400 1600 1800 2000
Number of Hours
When the night ventilation was changed from 0.5 ach to 2.5 ach the hours above the comfort level decreased by the same extent as when the brick type was changed but the hours below 16C increased to double that of the brick type modification. Adding insulation to the roof reduced the number of discomfort hours above 30C as well as eliminated the hours below 16C. Changing the roof colour also reduced the discomfort hours above 30C, but increased the hours below 16C. The base case house in Figure 15 is orientated so that the left wall faces north. When the house was rotated 90 so that the left wall faced west, the discomfort hours above 30C decreased and the hours below 16C remained the same.
21
The maximum indoor temperatures were recorded in the 19th week of the year in all of the scenarios, which corresponds to the highest outdoor temperatures, 41C, from the meteorological data. Maximum indoor air temperatures returned by the model in week 19 are represented in Figure 17. As can be seen from this graph,Figure 17 the base case model gave indoor air temperatures in excess of the maximum outdoor temperature, which correlates with the temperatures taken inside the FabLab during the same period.
Maximum indoor air temperature (C) Maximum outdoor air temperature (C) 42.5 41.5
te
al l
lig ht gr ey
ty pe
ca se
es
re
of w
of r
kn
co nc
ila
tio
ou ts id e
ha ng e
un de r
ur to
al l
lt
ia
gh t
ou bl
at
in su la tio n
ro of c
in su la tio n
al
In cr
ea s
lm
to
ha ng e
Ad d
Ad d
ha ng e
ot at e
er
ni
ol o
to
bu ild in g
Ba se
si
ve nt
ic
br ic
de
th
90
oo f
22
5. DISCUSSION
The modelling results along with the information gained during the literature review allowed for the sensitivity of the building parameters to be better understood. Adding insulation to the walls reduced heat gain during the day but decreased heat loss at night. This resulted in a higher maximum temperature inside and more hours above the thermal comfort level of 30C. Doubling the wall thickness had a similar effect. In contrast, adding insulation to the roof had the opposite effect. Insulation in the roof significantly reduced heat absorption during the day, to the extent that even with a reduction in heat loss at night due to the roof insulation the indoor temperatures were still lower than in the base case. From this, an inference could also be drawn that the main heat gain during the day is from solar radiation, which is mostly incident on the roof. By retarding heat transfer through the roof, more comfortable conditions can be experienced inside, whilst still allowing for heat loss through the walls at night. Changing the colour of the roof from green to light grey reduced the solar absorbance of the surface and increased the solar reflectance. This resulted in a decrease in hours above 30C. As explained by Synnefa and Santamouris et al. (2006) increasing the solar reflectance of a buildings envelope lowers the surface temperature since solar radiation is reflected rather than absorbed, which in turn decreases the amount of heat penetrating into the building. The result is fewer hours of discomfort inside the building (Synnefa et al. 2006). This case reinforces the conclusion made above, that solar radiation incident on the roof is the primary source of heat gain in the building. When the rate of night ventilation was increased, the number of hours above the thermal comfort level of 30C decreased. This is because the rate of heat loss of the interior mass at night was improved, meaning the building started the day at a lower temperature, so could absorb more heat before temperatures became uncomfortable inside. Changing the brick type to one with a higher density and thermal conductivity had a similar effect to increasing the rate of night ventilation. The higher thermal conductivity meant the building could dissipate heat better at night and it started the day at a lower temperature. This was also the case when the walls were changed to concrete, which increased the thermal mass of the wall and decreased the thermal resistance, resulting in more heat dissipation at night and lower indoor temperature during the day. When the building was rotated 90 the hours above the comfort level decreased. This is because the largest exposure of walls and windows to the sun changed from being on the East and West sides of the house to the North and South sides. This is in agreement with the study done by Verma et al (1986) which found that large exposure on the North and South side of the building gives the lowest inside temperatures during summer.(Verma et al. 1986).
23
24
7. ACKNOWLEDGEMENTS
The authors would like to thank Larry Bellamy, the project supervisor, who has been of great assistance. To EWB UK and engINdia, thank you for providing the project topic and the background information concerning conditions in Pabal, and for the help in making contacts there. Thank you also to Scott Saunders, who took temperature readings for us inside the FabLab in Pabal and provided us with a floor plan and general design information.
25
8. REFERENCES
Afonso, C., and Oliveira, A. (2000). "Solar chimneys: simulation and experiment." Energy and Buildings, 32, 71-79. Al-Homoud, D. M. S. (2004). "Performance characteristics and practical applications of common building thermal insulation materials." Amer, E. H. (2005). "Passive options for solar cooling of buildings in arid areas." Auliciems, A. (1983). "Pscho-physiological criteria for global thermal zones of building design." International Journal of Biometeorology, 26, 69-86. Auliciems, A., and Szokolay, S. (1997). "Thermal Comfort." PLEA: Passive and Low Energy Architecture International, Brisbane. Australian_Government. (2005). "Your home: design for lifestyle and the future: Technical Design Manual." Bahadori, M. N. (1994). "Viability of wind towers in achieving summer comfort in the hot arid regions of the middle east." Renewable Energy, 5(5-8), 879-892. Bahadori, M. N., Mazidi, M., and Dehghani, A. R. (2008). "Experimental investigation of new designs of wind towers." Renewable Energy, 33(10), 2273-2281. Bansal, N. K., Mathur, R., and Bhandari, M. S. (1993). "Solar chimney for enhanced stack ventilation." Building and Environment, 28, 373-377. Bellamy, L. (2008). "Evaporative cooling in Phoenix, Arizona." L. O'Neil and E. Taffs, eds., Christchurch. Blondeau, P., Sprandio, M., and Allard, F. (2002). "Multicriteria analysis of ventilation in summer period." Building and Environment, 37(2), 165-176. Census. (2001). "Census of India." Office of the Registrar General, ed. Chandra, M. (1994). "Passive and Low Energy Cooling Systems of Buildings - Review with Special Reference to Indian Conditions." Journal of the Institution of Engineers (India), 76, 12-21. Chandra, M. (1995). "Studies on potential and applicability of passive and low-energy cooling systems of building." Project No. EB/OLP 003201, Central Building Research institute, Roorkee, India. Clark, G. (1989). "Passive Cooling Systems." Passive Cooling, J. Cook, ed., MIT Press. Dilip Jain. (2004). "Modelling of solar passive techniques for roof cooling in arid regions." Fordham. (2000). "Natural ventilation." Renewable Energy, 19, 17-37. Furminger, E., John, M., Laundon, T., Shah, V., Wagh, P., and Walker, D. (2006). "engINdia Final Report: Pabal, Maharashtra,India 28 June 2005 - 7 August 2005." engINdia. Givoni, B. (1991). "Performance and applicability of passive and low energy cooling systems of buildings." Energy and Building, 17, 177-199. Givoni, B. (1994a). "Building Design Principles for Hot Humid Regions." Renewable Energy, 5, 908-916. Givoni, B. (1994c). Passive and Low Energy Cooling of Buildings, John Wiley and Sons. Givoni, B. (1998). Climate Considerations in Building and Urban Design Gouri Datta. (2001). "Effects of fixed horizontal louver shading devices on thermal performance of building by TRNSYS simulation."
26
Hay, H. "A passive heating and cooling system from concept to commercialization." Annual meeting of the American Section of the International Solar Energy Society. ISHRAE. (2008). "Indian Weather Data." Kakodkar, A. (2005). "Energy in India for the Coming Decades." I. A. E. Commission, ed. Kharrufa, S. N., and Adil, Y. (2008). "Roof pond cooling of buildings in hot arid climates." Building and Environment, 43(1), 82-89. Khedari, J., Boonsri, B., and Hirunlabh, J. (1999). "Ventilation impact of a solar chimney on indoor temperature fluctuation and air change in a school building." Energy and Buildings, 32, 89-93. Koch-Nielsen, H. (2002). Stay Cool: A Design Guide for the Built Environment in Hot Climates James & James, Michigan. Lomas, K. (2007). "Architectural design of an advanced naturally ventilated building form." Energy and Buildings, 39, 166-181. Mahadevan, V. (2007). "Storage Of Food In Developing Countries." Engineers Without Borders UK, Bristol. MartI-Herrero, J., and Heras-Celemin, M. R. (2007). "Dynamic physical model for a solar chimney." Solar Energy, 81(5), 614-622. Martin, W. (1996). "Air quality control in commercial buildings." WREC. Mochida, A., Yoshino, H., Takeda, T., Kakegawa, T., and Miyauchi, S. (2005). "Methods for controlling airflow in and around a building under cross-ventilation to improve indoor thermal comfort." Journal of Wind Engineering and Industrial Aerodynamics, 93(6), 437-449. Nicol, F., and Pagliano, L. (2007). "Allowing for thermal comfort in free-running buildings in the new European Standard EN15251." 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and Advanced Ventilation Technologies in the 21st Century, Crete Island, Greece. Omer, A. M. (2008). "Renewable building energy systems and passive human comfort solutions." Renewable and Sustainable Energy Reviews, 12(6), 1562-1587. Ong, K. S. (2003). "A mathematical model of a solar chimney." Renewable Energy, 28, 10471060. Ong, K. S., and Chow, C. C. (2003). "Performance of a solar chimney." Solar Energy, 74(1), 1-17. Papadakis, G., Tsamis, P., and Kyritsis, S. (2000). "An experimental investigation of the effects of shading with plants for solar control of buildings." Energy and Building, 33, 831-836. Rodrik, D., and Subranium, A. (2004). "Why India can grow at 7 percent or more: projections and reflections." WP/04/118, International Monetary Fund. Santamouris, M., Pavolou, K., Synnefa, A., Niachou, K., and Kolokotsa, D. (2007). "Recent progress on passive cooling techniques: Advanced technological developments to improve survivability levels in low-income households." Saunders, S. (2008). "Information concerning Pabal." L. O'Neill, ed. Synnefa, A., Santamouris, M., and Akbari, H. (2006). "Estimating the effect of using cool coatings on energy loads and thermal comfort in residential buildings in various climatic conditions." Tang, R. E. Y. (2005). "Cooling performance of roof ponds with gunny bags floating on water surface as compared with a moveable insulation." Renewable Energy, 30(13731385). 27
Thanu, N. M., Sawhney, R. L., Khare, R. N., and Buddhi, D. (1999). "An experimental study of the thermal performance of an earth-air-pipe system in single pass mode." Tsutsumi, J.-i., Katayama, T., Ishii, A., He, P., and Hayashi, T. (1996). "Investigation and numerical simulation of the wind effects on thermal comfort in a house." Journal of Wind Engineering and Industrial Aerodynamics, 60, 267-280. Verma, R., Bansal, N. K., and Garg, H. P. (1986). "The comparative performance of different approaches to passive cooling." Building and Environment, 21(2), 65-69. Wilson, D., and Purushothaman, R. (2003). "Dreaming with BRICs: the path to 2050." Global Economics Paper No 99, Goldmann Sachs. Zain-Ahmed, A., Sopian, K., Othman, M. Y. H., Sayigh, A. A. M., and Surendran, P. N. (2000). "Daylighting as a passive solar design strategy in tropical buildings: a case study of Malaysia."
28