Professional Documents
Culture Documents
Index:
(1): Introduction. (2): Circuit breakers (General). (3): Oil Circuit Breakers - Bulk Oil CB.
Introduction
Introduction:
The duty of the switchgears is to switch on and off and to control, once or repeatedly several times, different electrical circuits during normal as well as abnormal operating conditions. Short circuit current level & the behavior of circuits during transient condition are very essential to select proper specification of switchgears. Good practices and knowledge of circuit breakers and switchgears specification, operation, testing and maintenance are fatal for engineers concerning with electrical power system. The main subject of this lecture is about circuit breaker types and application.
Introduction:
Circuit breaker (CB) is a device to open or close an electric power circuit either during normal power system operation or during abnormal conditions. A CB serves in the course of normal system operation to energize or de-energize loads. During abnormal conditions, when excessive current develops, a CB opens to protect equipment and surroundings from possible damage due to excess current. These abnormal currents are usually the result of short circuits created by lightning, accidents, deterioration of equipment, or sustained overloads.
Introduction:
Formerly, all CBs were electromechanical devices. In these breakers a mechanism operates one or more pairs of contacts to make or break the circuit. The mechanism is powered either electromagnetically, pneumatically, or hydraulically. The contacts are located in a part termed the interrupter. When the contacts are parted, opening the metallic conductive circuit, an electric arc is created between the contacts. This arc is a high-temperature ionized gas with an electrical conductivity comparable to graphite. Thus the current continues to flow through the arc. The function of the interrupter is to extinguish the arc, completing circuit-breaking action.
CB Duties:
A CB is a complex circuit-breaking device with the following duties: 1- Make or break both normal and abnormal currents. 2- Appropriately manage the high-energy arc associated with current interruption. 3- Rapid and successive automatic breaking and making to aid stable system operation. 4- Three pole and single pole auto-relosing arrangement. Additionally, a CB is required to do so under the following typical conditions:
1- Short-circuit interruption. 2- Interruption of small inductive currents. 3- Capacitor switching. 4- Interruption of short-line fault. 5- Asynchronous switching.
CB Elements
1. Main Contact.
2.
3.
4. 5.
Control, supervisory and auxiliary devices. Insulating link between control unit and main contact.
CBs Requirements:
1.Opens & closes in shortest possible time. 2.Conducts rated current. 3.Withstands thermally & mechanically any short circuit. 4.Maintains its voltage to earth across open contacts. 5.Does not create overvoltages during circuit opening. 6.Easy to maintain. 7.Not very expensive.
Particulars of a CB:
Medium for arc extinction. Rated line voltage. Rated breaking current. Type of construction (e.g outdoor, indoor... etc). Type of operating mechanism Total breaking time. Other additional features such as switching resistors, capacitor,. .
CBs Rating:
- Rated normal current: to be carried without temperature rise. - Rated breaking current: = Highest current to be interrupted = rms of the peak value of the Asymmetrical current. - Rated MVA: = 3 *Line voltage(kV)*breaking current(kA)
Principles of Operation :
On opening moving contact moves rapidly. An electric Arc is formed. The intensity of the arc depends on the current been interrupted. As the moving contact moves further, the arc is stretched. The gas in the chamber sweeps the arc which is cooled. Circuit opening is achieved if the arc does not re-ignite.
Classification of CBs:
Generally we can classify the circuit breakers according to the constructional details as the following: Air-break circuit breaker or miniature CB. Oil circuit breaker.
Bulk Oil. Minimum oil.
Air blast circuit breaker. SF6 circuit breaker. Vacuum circuit breaker.
(OCBs)
When electric arc is drawn, the arc vaporizes the oil and creates a large bubble that surrounds the arc. The gas inside the bubble is around 80% hydrogen, which impairs ionization. The decomposition of oil into gas requires energy that comes from the heat generated by the arc. The oil surrounding the bubble conducts the heat away from the arc and thus also contributes to deionization of the arc.
Oil has to be replace after some operations because of the carbonization of oil (i.e. changing and purifying the oil).
Bulk Oil
Circuit Breakers
Bulk oil CBs are enclosed in metal-grounded weatherproof tanks that are referred to as dead tanks. The original design of bulk OCBs was very simple and inexpensive. The arc was drawn directly inside of the container tank without any additional arc extinguishing. Plain break breakers were superseded by arc controlled oil breakers. The arc controlled oil breakers have an arc control device surrounding the breaker contacts. The purpose of the arc control devices is: To improve operating capacity. To speed up the extinction of arc. To decrease pressure on the tank.
Minimum Oil
Circuit Breakers
Breaker Capacitances:
Breaker Capacitances:
Breaker Capacitors:
(ABCB)
Fast operations.
Suitability for repeated operation.
Auto reclosure.
Unit type multi break constructions.
Simple assembly.
Modest maintenance.
A compressors plant necessary to maintain high air pressure in the air receiver. The air blast CBs are especially suitable for railways and arc furnaces, where the breaker operates repeatedly. Air blast CBs is used for interconnected lines and important lines where rapid operation is desired. High pressure air at a pressure between 20 to 30 kg/ cm2 stored in the air reservoir. Air is taken from the compressed air system.
HV Air Blast CB
(Axial Flow)
Sequence Of Operation
Resistance Switching:
The post zero resistance of contact space is high in air blast circuit breakers. This is because the contact clearance space is filled with high pressure air after final current zero and high pressure air has high dielectric strength. The high restriking voltage appears across the contacts does not damp out through the gap because of the high post zero resistance. Further, voltages of the order of several times the normal voltage appear across the contacts because of current chopping.
Resistance Switching:
Further, voltages of the order of several times the normal voltage appear across the contacts because of current chopping. If these voltages are not allowed to discharge, they may cause break down of insulation of the circuit breaker or the neighboring equipment. To overcome this difficulty, resistance switching is adopted. The usual procedure is to connect a resistance in shunt with the arc. During the opening operation, air is admitted in the arc extinguishing chamber.
Resistance Switching:
It separates the main contacts and pushes the auxiliary contacts. The auxiliary contacts close, thereby the resistors are connected across the arc for a short time of arcing. The auxiliary contacts are located in the inclined V shaped insulators while the resistors are located in the vertical insulators. Immediately after the arc extinction the pressure on either side of the piston of auxiliary contacts gets so adjusted that the auxiliary contacts open and resistor circuit is interrupted. Ceramic resistances of non linear characteristics, similar to those used in the lightning arresters are used for resistance switching.
These consist of silicone carbide, bound by inorganic binders subjected to heat treatment. During high current, non liner resistor offers low resistance. Thus the main arc current is partly diverted through resistor unit. As current reduces, the resistance offered by non linear resistors increases causing a greater drop across the resistor units. Thereby the voltage available for arc between auxiliary contacts is no more sufficient and arc between auxiliary contacts is automatically extinguished.
ABCB Advantages:
An air blast CB has the following advantages: 1- The risk of fire is eliminated. 2- The arcing products are completely removed by the blast. 3- The growth of dielectric strength is so rapid that final contact gap needed for arc extinction is very small (this reduces the size of device). 4- The arcing time is very small due to the rapid build up of dielectric strength between contacts. Therefore, the arc energy is less, thus resulting in less burning of contacts. 5- Due to lesser arc energy, air blast CBs are very suitable for conditions where frequent operation is required. 6- The energy supplied for arc extinction is obtained from high pressure air and is independent of the current to be interrupted.
ABCB Disadvantages:
1- Air has relatively inferior arc extinguishing properties. 2- Air blast circuit breakers are very sensitive to the variations in the rate of restriking voltage. 3- Considerable maintenance is required for the compressor plant which supplies the air blast.
(SF6 CB)
Introduction:
Sulfur hexafluoride (SF6) gas is an alternative to air as an interrupting medium. SF6 is a colorless nontoxic gas, with good thermal conductivity and density approximately five times that of air. SF6 is chemically inert up to temperature of 150 oC and will not react with metals, plastics, and other materials commonly used in the construction of high voltage CBs. The principle of operation is similar to the air blast breakers, except that the SF6 gas is not discharged into the atmosphere. A closed compartment completely sealed and selfcontained construction is used.
Why SF6?
Sulfur Hexafluoride (SF6) is an excellent gaseous dielectric for high voltage power applications. It has been used extensively in HV CBs and other switchgears employed by the power industry. Applications for SF6 include gas insulated transmission lines and gas insulated power distributions. SF6 combined electrical, physical, chemical and thermal properties offer many advantages. Some of the properties of SF6 making it desirable to use in power applications are:
High dielectric strength. Unique arc-quenching ability. Excellent thermal stability. Good thermal conductivity.
8 ppmv
-62C
0.3 ppmw
15 ppmv
-40C
1.0 ppmw
Dew Point
Hydrolysable Fluorides (HF)
Air (wt. %)
Carbon Tetrafluoride (CF4)
500 ppmw
500 ppmw
SF6 CB Types:
There are two major types for arc extinguish principals of SF6 Circuit Breakers:
M. Khaled
SF6 CBs:
The rotating arc interrupter is as inexpensive as oil or air with reliability and performance of a vacuum interrupter. SF6 gas decomposes during arcing process but very quickly recombines at current zero regaining its dielectric properties. Fault currents up to 20kA can be cleared at 12kV with a 50mm gap (approx) at a gas pressure of a 2.0 bar. The arc current is transferred during contact separation through a solenoid of a few turns of copper strip generating a magnetic field causing the arc to rotate around the inner ring of the solenoid. The rapid movement of the arc through the SF6 gas causes cooling and enables extinction at the first current zero at high fault currents.
Operating Mechanism:
Operating Mechanism:
Step by Step (Off) Switching Operation according to (Puffer Principal) For HV SF6 CB
(VCB)
Vacuum CBs:
Vacuum CB are used for MV and HV circuits. A vacuum CB is a breaker in which a pair of contacts is tightly sealed in a vacuum envelope. The contacts are separated by using a bellows to move one of them. An arc is produced by metallic vapor boiled from the electrodes, and is extinguished when the vapor particles condense on solid surfaces. Because the contacts are in a vacuum, arcing between the contacts is suppressed, ensuring that the circuit remains open. As long as the circuit is open, it will not be energized.
Vacuum CBs:
A vacuum CB comprises a vacuum vessel made up of an insulating casing and end plates closing the opposite ends and a pair of separable electrodes in the vacuum vessel. Vacuum CBs include separable main contacts which are disposed within an insulating housing. One of the contacts is fixed relative to the housing and the other separable main contact is movable. The moveable contact assembly usually comprises a stem of circular cross-section having the contact at one end enclosed within a vacuum chamber and a driving mechanism at the other end which is external to the vacuum chamber.
Vacuum CBs:
In general, an arc electrode is required to satisfy basic characteristics such as: A large breaking capacity. High withstand voltage. Small contact resistance (high electric conductivity). High fusion resistance. Small wastage of a contact. Small chopped current.
Vacuum CB Module
Magnetic actuator
Actuator is a bi-stable Permanent Magnet. Switchover of the armature is effected by magnetic field created by the coils. The armature is held magnetically in limit position by the field of permanent magnets. Switching is released by excitation of a coil until the retaining force of the permanent magnet is exceeded.
No generation of gas during and after operation. Can interrupt any fault current.
No noise is produced while operating.
Require less power for control operation (less power for operating mechanism).