HCMC PC

SPECIFICATION

STANDARD VOLTAGE INSTRUMENT TRANSFORMER I. SCOPE : This specification covers the supply of standard voltage instrument transformer. II. STANDARD OF MANUFACTURE AND TEST : The equipment shall conform to the latest edition of the appropriate IEC specification or ASTM standard. III. DESCRIPTION:

1. Function of equipment : - The standard voltage instrument transformer used to be as reference transformer for voltage transformer measurement. - Test method : conform to the specification of IEC standard 2. Technical specification : - Insulation : Dry insulation or SF6 insulation. - Primary voltage : 8.4 - 12 -14.4 - 24KV - Secondary Voltage : 120V - Voltage error : 0.005% - Phase angel : 0.5 min - Load : Max.15VA/ cos = 1 - Test voltage : 60KV IV. REQUIREMENT OF TECHNICAL EQUIPMENT : - Technical description, data sheet, catalogues and other material submitted with the quotation must enable the purchaser to thoroughly evaluate the proposals as to it compliance with the inquiry specification. - Minimum requirements : Detail summary of deviations to the inquiry specification Complete inquiry data sheet expressed at section V Catalog containing outline dimension, technical data List of main equipment and completed accessories which can perform all function described in section III have the following requirements : . Individual cost of main equipment and each accessory . Total cost of main equipment and completed accessory . Manufactures code of main equipment and each accessory
/var/www/apps/conversion/tmp/scratch_5/138239121.doc 1/4

HCMC PC

SPECIFICATION

STANDARD VOLTAGE INSTRUMENT TRANSFORMER Connection diagram Certificate of quality management V. REQUIREMENT OF DOCUMENT INCASE OF BID WINNING :

1. Documents required to be provide for commission : In order to ensure the quality of supplied goods, in case of bid winning, the Tenderer shall supply the following documents for the Purchaser : - Manufacturers Certificate of Quality. - Certificate of Origin issued by Chamber of Commerce of the manufacturing country. - Certificate of calibration of equipment approved by an independent lawful organization. 2. Documents required to be provide in accompany with supplied products : The Supplier shall enclose the following documents for supplied products : - 01 catalog. - 01 instruction manual of installation, operation and maintenance. VI. REQUIREMENT OF INSTALLATION AND INSTRUCTION FOR USE :

The Supplier shall ensure to supply the following service : - Installation the equipment completely. - Instruction to Purchasers staff how to use this equipment on site. - Trial run this equipment.

VII. DATA SHEET:


/var/www/apps/conversion/tmp/scratch_5/138239121.doc 2/4

HCMC PC

SPECIFICATION

STANDARD VOLTAGE INSTRUMENT TRANSFORMER

N 1. 2. 3. 4.

DESCRIPTION

REQUIREMENT QUOTE S D

Manufacturer Country of origin Manufacturer s code Standard of manufacture and test 5. Standard of quality management 6. Organization which approved certificate of quality management 7. In case of bid winning, the Tenderer shall supply the following documents for the Purchaser : - Manufacturers Certificate of Quality. - Certificate of Origin issued by Chamber of Commerce of the manufacturing country. - Certificate of calibration of equipment approved by an independent lawful organization. 8. List of main equipment and completed accessories met all requirements of section IV is supplied in tender proposal. 9. Quoted main equipment and completed accessories described in above list can perform all function described in section III without addition of other necessary materials. 10. The Supplier shall ensure to supply the following service : - Installation the equipment completely. - Instruction to Purchasers staff
/var/www/apps/conversion/tmp/scratch_5/138239121.doc

Yes Yes Yes

Yes

Yes

Yes Yes
3/4

HCMC PC

SPECIFICATION

STANDARD VOLTAGE INSTRUMENT TRANSFORMER how to use this equipment on site. - Trial run this equipment. 11. Function of equipment

Yes It use to be standard transformer for voltage transformer measurement Conform to IEC standard Dry or SF6 8.4-12-14.424KV 120V 0.005% 0.5 min Max. 15VA/ cos = 1 60 KV The tenderer has to quote the dimensions and weight of standard voltage transformer that can be fabricated.

12. Methods for determination 13. Material of insulation 14. Primary voltage 15. 16. 17. 18. Secondary voltage Voltage Error Phase angel Load

19. Power frequency withstand voltage (dry for 01 minute) 20. - Dimensions : + Width + Height + Depth - Weight

/var/www/apps/conversion/tmp/scratch_5/138239121.doc