VEGASON 65
4 20 mA/HART four-wire
Ultrasonic
Contents
Contents
1 About this document 1.1 1.2 1.3 2 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Symbolism used . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 4 4
For your safety 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 Authorised personnel . . . . . . . . . . . . . . . Appropriate use . . . . . . . . . . . . . . . . . . . Warning about misuse . . . . . . . . . . . . . . General safety instructions . . . . . . . . . . . Safety approval markings and safety tips . CE conformity . . . . . . . . . . . . . . . . . . . . Fulllment of NAMUR recommendations . Safety instructions for Ex areas . . . . . . . . Environmental instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. .. .. .. .. .. .. .. 5 5 5 5 6 6 6 6 6
Product description 3.1 3.2 3.3 3.4 Conguration . . . . . . . . . . . . . . . Principle of operation . . . . . . . . . Operation . . . . . . . . . . . . . . . . . . Packaging, transport and storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. .. .. 8 9 9 10
Mounting 4.1 4.2 4.3 General instructions . . . . . . . . . . . . . . . . . . . . . . . . . Mounting preparations . . . . . . . . . . . . . . . . . . . . . . . Mounting instructions . . . . . . . . . . . . . . . . . . . . . . . . 11 13 18
Connecting to power supply 5.1 5.2 5.3 5.4 Preparing the connection . . . . . . . . . Connection procedure. . . . . . . . . . . . Wiring plan, double chamber housing Switch on phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. .. .. 23 24 26 27
Set up with the indicating and adjustment module PLICSCOM 6.1 6.2 6.3 6.4 6.5 6.6 Short description . . . . . . . . . . . . . . . . . Insert indicating and adjustment module. Adjustment system . . . . . . . . . . . . . . . . Setup procedure. . . . . . . . . . . . . . . . . . Menu plan ultrasonic sensor . . . . . . . . . Saving the parameter adjustment data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. .. .. .. .. 29 29 31 32 38 40
Setup with PACTware and other adjustment programs 7.1 7.2 7.3 7.4 Connect the PC via VEGACONNECT . . . . . . Parameter adjustment with PACTware . . . . . . Parameter adjustment with AMS and PDM . Saving the parameter adjustment data . . . . . . . . . . . . . . . . . . . . . . .. .. .. .. 41 42 43 43
28782-EN-081127
Contents 8
Maintenance and fault rectication 8.1 8.2 8.3 8.4 8.5 Maintenance . . . . . . . . . . Remove interferences . . . . Exchanging the electronics Software update . . . . . . . . Instrument repair . . . . . . . ...... ...... module ...... ...... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. .. .. .. 44 44 45 46 46
10 Supplement 10.1 10.2 10.3 10.4 Technical data . . . . . . . Dimensions . . . . . . . . . Industrial property rights Trademark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. .. .. 50 56 59 59
Supplementary documentation Information: Supplementary documents appropriate to the ordered version come with the delivery. You can nd them listed in chapter "Product description". Instructions manuals for accessories and replacement parts Tip: To ensure reliable setup and operation of your VEGASON 65, we oer accessories and replacement parts. The associated documents are:
l l l l l l
28782-EN-081127
Indicating and adjustment module PLICSCOM Interface adapter VEGACONNECT External indication VEGADIS 61 Protective cover Electronics module VEGASON series 60 Emitting electronics VEGASON 64, 65, 66
List The dot set in front indicates a list with no implied sequence. Action This arrow indicates a single action. Sequence Numbers set in front indicate successive steps in a procedure.
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
28782-EN-081127
2.6 CE conformity
This device fullls the legal requirements of the applicable EC guidelines. By attaching the CE mark, VEGA provides a conrmation of successful testing. You can nd the CE conformity declaration in the download area of www.vega.com.
Sensor software for DTM VEGASON 65 HART, PA or FF DTM VEGASON 65 for adjustment software PACTware Indicating and adjustment module for sensor software
The parameter adjustment of the basic sensor functions is independent of the software version. The range of available functions depends on the respective software version of the individual components. The software version of VEGASON 65 can be determined as follows:
l l l
via PACTware on the type label of the electronics via the indicating and adjustment module
You can view all software histories on our website www.vega.com. Make use of this advantage and get registered for update information via e-mail.
28782-EN-081127
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
3 Product description
3 Product description
3.1 Conguration
Scope of delivery The scope of delivery encompasses:
l l l
VEGASON 65 ultrasonic sensor Unassembled cable gland Documentation - this operating instructions manual - Operating instructions manual 27835 "Indicating and adjustment module PLICSCOM" (optional) - Ex-specic "Safety instructions" (with Ex-versions) - if necessary, further certicates
Components
transducer with process tting (depending on version ange, swivelling holder or thread) housing with electronics (depending on version, separate) Housing cover, optionally available with indicating and adjustment module PLICSCOM
The components are available in dierent versions. Version A: compact in ange version Version B: compact with swivelling holder Version C: separately with swivelling holder Version D: separately with thread
1 2 3
4
Fig. 1 2 3 4 1: VEGASON 65 compact with swivelling holder Housing cover with integrated PLICSCOM (optional) Housing with electronics Swivelling holder with ange Transducer
28782-EN-081127
Type label
The type label contains the most important data for identication and use of the instrument:
l
3 Product description
l l l
Article and serial number device Article numbers documentation Technical data: For example approvals, process temperature, process tting/material, signal output, power supply, protection
With the serial number, you can access the delivery data of the instrument via www.vega.com, "VEGA Tools" and "serial number search". In addition to the type label outside, you can also nd the serial number on the inside of the instrument.
Functional principle
Power supply
3.3 Operation
VEGASON 65 can be adjusted with dierent adjustment media:
l l
l l
with indicating and adjustment module with the suitable VEGA DTM in conjunction with an adjustment software according to the FDT/DTM standard, e.g. PACTware and PC with manufacturer-specic adjustment programs AMS or PDM With a HART handheld
28782-EN-081127
The entered parameters are generally saved in VEGASON 65, optionally also in the indicating and adjustment module or in PACTware.
3 Product description
Transport inspection
Storage
Not in the open Dry and dust free Not exposed to corrosive media Protected against solar radiation Avoiding mechanical shock and vibration Storage and transport temperature see chapter "Supplement Technical data - Ambient conditions" Relative humidity 20 85 %
l l
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
10
4 Mounting
4 Mounting
4.1 General instructions
Suitability for process conditions Make sure that all parts of the instrument in contact with the measured product, especially the sensor element, process seal and process tting, are suitable for the existing process conditions such as process pressure, process temperature as well as the chemical properties of the medium. You can nd the specications in chapter "Technical data" in the or on the type label. Mounting position Select an installation position you can easily reach for mounting and connecting as well as later retrotting of an indicating and adjustment module. The housing can be rotated by 330 without the use of any tools. You can also install the indicating and adjustment module in four dierent positions (each displaced by 90). Use the recommended cables (see chapter "Connecting to power supply") and tighten the cable gland. You can give your VEGASON 65 additional protection against moisture penetration by leading the connection cable downward in front of the cable entry. Rain and condensation water can thus drain o. This applies mainly to outdoor mounting as well as installation in areas where high humidity is expected (e.g. through cleaning processes) or on cooled or heated vessels.
Moisture
28782-EN-081127
11
4 Mounting Measuring range The reference plane for the measuring range (version A) is the lower edge of the ange. The reference plane for versions B, C and D is the lower edge of the transducer. Remember that with all versions there is a minimum distance below the reference plane - the so-called dead band - in which measurement is not possible; this distance from reference plane to medium must not be underrun. The exact value of the dead band is stated in chapter "Technical data". Information: If the medium reaches the transducer, buildup can form on it and cause faulty measurements later on.
3 4 100%
0%
Fig. 3: Version A - Measuring range (operating range) and max. measuring distance 1 full (dead band) 2 empty (max. measuring distance) 3 Measuring range 4 Reference plane
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
12
4 Mounting
3 4 100%
0%
Fig. 4: Version B, C, D - Measuring range (operating range) and max. measuring distance 1 full (dead band) 2 empty (max. measuring distance) 3 Measuring range 4 Reference plane
Pressure/Vacuum
Gauge pressure in the vessel does not inuence VEGASON 65. Low pressure or vacuum does, however, damp the ultrasonic pulses. This inuences the measuring result, particularly if the level is very low. With pressures under -0.2 bar (-20 kPa) you should use a dierent measuring principle, e.g. radar or guided microwave.
Mounting - Version B
Transducer Electronics housing Loosen the screws on the xing ring (4) with a hexagon spanner (size 4), remove the transducer tube out of the swivelling holder Mount the ange
28782-EN-081127
13
4 Mounting 3 4 5 6 Insert the transducer tube in the requested length from below into the swivelling holder Fasten with screws (4); torque max. 10 Nm Remove the plug from below out of the instrument housing and plug it into the socket of the transducer tube Plug the electronics housing to the transducer tube. Do not squeeze any cables. The housing is in the correct position, if the lower notch (2) of the transducer tube is no longer visible Tighten the screws (5) on the housing moderately with an Allen wrench (size 4) Loosen terminal screw of the swivelling holder (3) with a fork spanner (SW 13) Direct the sensor with the swivelling holder to the measured product
7 8 9
10 Fasten the swivelling holder with screw (3), torque max. 20 Nm 11 Secure screw (3) with lacquer or similar to ensure permanent tightness of the swivelling holder 12 Rotate the housing in such a way that the cable entry points downwards (moisture can drain o). Fasten the housing with screws (5); torque Aluminium housing max. 5 Nm, torque plastic housing max. 2 Nm
5 1 4 2 3
Fig. 1 2 3 4 5
5: Mounting - Version B Groove to lock the housing Notch Screw of swivelling holder (hexagon SW 13) Grub screw, xing ring (hexagon spanner - size 4) Terminal screws, housing (hexagon spanner - size 4)
28782-EN-081127
14
Transducer Transducer cable electronics for wall mounting Loosen the screws on the xing ring (4) with a hexagon spanner (size 4), remove the transducer tube out of the swivelling holder Mount the ange Insert the transducer tube in the requested length from below into the swivelling holder Fasten with screws (4); torque max. 10 Nm Remove the plug from below out of the connection head and plug it into the socket of the transducer tube Plug the connection head to the transducer tube. Do not squeeze any cables. The cylinder is in the correct position, if the lower notch (2) of the transducer tube is no longer visible
5 1 4 2 3
Fig. 1 2 3 4 5
6: Mounting - Version C Groove for locking the connection head Notch Screw of swivelling holder (hexagon SW 13) Grub screw, xing ring (hexagon spanner - size 4) Terminal screws, connection head (hexagon spanner - size 4)
7 8
Tighten the screws (5) on the cylinder moderately with an Allen wrench (size 4) Loosen terminal screw of the swivelling holder (3) with a fork spanner (SW 13) Direct the sensor with the swivelling holder to the measured product
28782-EN-081127
15
4 Mounting 11 Secure screw (3) with lacquer or similar to ensure permanent tightness of the swivelling holder 12 Rotate the connection head in such a way that the cable entry points downwards (moisture can drain o). Fasten the cylinder with screws (5); torque max. 5 Nm 13 Insert the plug at the end of the transducer cable into the socket on the remote electronics
1 2 3
Fig. 1 2 3
7: Plug connector between transducer and socket of electronics housing Socket electronics housing Plug connector Connection piece, transducer tube
Mounting - Version D
Transducer Transducer cable electronics for wall mounting Loosen the hexagon nut (3) on the transducer cable Insert the transducer tube from below into the mounting opening G1A Fasten (SW 46) the hexagon nut (3) Remove the plug from below out of the connection head and plug it into the socket of the transducer tube
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
16
4 Mounting 5 Plug the connection head to the transducer tube. Do not squeeze any cables. The cylinder is in the correct position, if the lower notch (2) of the transducer tube is no longer visible
4 1 3 2
Fig. 1 2 3 4
8: Mounting - Version D Groove for locking the connection head Notch Hexagon nut SW 46 Terminal screws, connection head (hexagon spanner - size 4)
6 7
Tighten the screws (4) on the cylinder moderately with an Allen wrench (size 4) Rotate the connection head in such a way that the cable entry points downwards (moisture can drain o). Fasten the cylinder with screws (4); torque max. 5 Nm Insert the plug at the end of the transducer cable into the socket on the remote electronics
1 2 3
Fig. 1 2 3
9: Plug connector between transducer and socket of electronics housing Socket electronics housing Plug connector Connection piece, transducer tube
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
17
4 Mounting
> 500 mm
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
18
4 Mounting In vessels with conical bottom it can be advantageous to direct the sensor to the center of the vessel, as measurement is then possible down to the lowest point of the vessel bottom.
Socket
Preferably the transducer should be mounted without socket ush to the vessel top. If the reective properties of the medium are good, you can mount VEGASON 65 on a socket piece. The socket end should be smooth and burr-free, if possible also rounded. Carry out a false echo storage.
Sensor orientation
Align the sensor in liquids as vertical as possible to the product surface to achieve optimum measuring results.
To optimally align the sensor to solid products, a swivelling holder can be implemented.
28782-EN-081127
Vessel installations
The ultrasonic sensor should be installed at a location where no installations cross the ultrasonic beam.
19
4 Mounting Vessel installations such as for example, ladders, limit switches, heating spirals, struts etc. can cause false echoes that interfere with the useful echo. Make sure when planning your measuring site that the ultrasonic signals have a "clear view" to the measured product. In case of existing vessel installations, a false echo storage should be carried out during setup. If large vessel installations such as struts or supports cause false echoes, these can be attenuated through supplementary measures. Small, inclined sheet metal or plastic baes above the installations scatter the ultrasonic signals and avoid direct false echoes.
Agitators
If there are agitators in the vessel, a false echo storage should be carried out with the agitators in motion. This ensures that the interfering reections from the agitators are saved with the blades in dierent positions.
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
20
4 Mounting Material heaps Large material heaps are best measured with several instruments, which can be mounted on e.g. traverse cranes. For this type of application it is advantageous to orient the sensor perpendicular to the bulk solid surface.
Inowing medium
Do not mount the instruments in or above the lling stream. Make sure that you detect the product surface, not the inowing product.
Foam
Through the action of lling, stirring and other processes in the vessel, dense foams which considerably damp the emitted signals may form on the product surface. If foams are causing measurement errors, the sensor should be used in a standpipe or, alternatively, the more suitable guided radar sensors (TDR) should be used. Guided radar is unaected by foam generation and is particularly suitable for such applications.
28782-EN-081127
21
4 Mounting Air turbulences If there are strong air currents in the vessel, e.g. due to strong winds in outdoor installations or air turbulence, e.g. by cyclone extraction you should mount VEGASON 65 in a standpipe or use a dierent measuring principle, e.g. radar or guided radar (TDR). Strong heat uctuations, e.g. caused by the sun, can cause measurement errors. In this case, you should use a sun shield.
Heat uctuations
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
22
Connect only in the complete absence of line voltage If overvoltage surges are expected, overvoltage arresters should be installed
Tip: We recommend using VEGA overvoltage arresters B 63-48 and SB 62-36G.X. Take note of safety instructions for Ex applications Select power supply In hazardous areas you should take note of the appropriate regulations, conformity and type approval certicates of the sensors and power supply units. Voltage supply with mains voltage and current output are carried along separate two-wire connection cables if reliable separation is required. The voltage supply range can dier depending on the instrument version. The data for power supply are specied in chapter "Technical data". This instrument is designed in protection class I. To maintain this protection class, it is absolutely necessary that the ground conductor be connected to the internal ground terminal. Take note of the general installation regulations. As a rule, connect the instrument to vessel ground (potential euqalisation) or in case of plastic vessels to the next ground potential. For this purpose there is a ground terminal on the side of the instrument housing. Selecting connection cable For power supply, an approved installation cable with PE conductor is necessary. The 4 20 mA current output is connected with standard two-wire cable without screen. If electromagnetic interference is expected which is above the test values of EN 61326 for industrial areas, screened cable should be used. Use cable with round cross-section. A cable outer diameter of 5 9 mm (0.2 0.35 in) ensures the seal eect of the cable gland. If you are using cable with a dierent diameter or cross-section, exchange the seal or use a suitable cable gland.
28782-EN-081127
If screened cable is necessary, connect the cable screen on both ends to ground potential. In the sensor, the screen must be connected directly to the internal ground terminal. The ground terminal on the outside of the housing must be connected to the potential equalisation (low impedance).
23
5 Connecting to power supply If potential equalisation currents are expected, the connection on the processing side must be made via a ceramic capacitor (e. g. 1 nF, 1500 V). The low frequency potential equalisation currents are thus suppressed, but the protective eect against high frequency interference signals remains. Select connection cable for Ex applications Take note of the corresponding installation regulations for Ex applications. In particular, make sure that no potential equalisation currents ow over the cable screen. In case of grounding on both sides this can be achieved by the use of a capacitor or a separate potential equalisation.
1 2 3
Fig. 1 2 3
18: Plug connector between transducer and socket of electronics housing Socket electronics housing Plug connector Connection piece, transducer tube
Only then, the sensor may be connected to voltage supply. Proceed as follows: 1 2 3 Unscrew the housing cover Loosen compression nut of the cable entry Remove approx. 10 cm (4 in) of the cable mantle (current output), strip approx. 1 cm (0.4 in) insulation from the ends of the individual wires Insert the cable through the cable gland into the sensor Lift the opening levers of the terminals with a screwdriver
28782-EN-081127
4 5
24
5 Connecting to power supply 6 7 8 9 Insert the wire ends into the open terminals according to the wiring plan Press down the opening levers of the terminals, you will hear the terminal spring closing Check the hold of the wires in the terminals by lightly pulling on them Connect the screen to the internal ground terminal, connect the outer ground terminal with potential equalisation
10 Tighten the compression nut of the cable entry. The seal ring must completely encircle the cable 11 Connect the lead cable for power supply in the same way according to the wiring plan, in addition connect the ground conductor to the inner ground terminal. 12 Screw the housing cover on The electrical connection is nished.
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
25
Fig. 1 2 3 4 5
20: Double chamber housing Housing cover, connection compartment Blind stopper or plug M12 x 1 for VEGADIS 61 (optional) Housing cover, electronics compartment Filter element for air pressure compensation Cable gland
Electronics compartment
Display
1
IC
5 6 7 8
3
Fig. 1 2 3 21: Electronics compartment, double chamber housing Plug connector for VEGACONNECT (IC interface) Internal connection cable to the connection compartment Terminals for VEGADIS 61
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
26
1 3
L1 N
4... 20mA IS
GND
1 2
3 4
2
Fig. 1 2 3 22: Connection compartment, double chamber housing Spring-loaded terminals for signal output Ground terminal for connection of the ground conductor and screen Spring-loaded terminals for voltage supply
Wiring plan
4...20mA IS GND
L1 N
/L /N PE
4 ... 20 mA
Fig. 23: Wiring plan, double chamber housing 1 Power supply 2 Signal output
28782-EN-081127
Internal check of the electronics Indication of the instrument type, the rmware as well as the sensor TAGs (sensor designation) Output signal jumps briey (approx. 10 seconds) to the set fault current
27
5 Connecting to power supply Then the corresponding current is outputted to the cable (the value corresponds to the actual level as well as the settings already carried out, e.g. factory setting).
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
28
All sensors of the plics instrument family, in the single as well as in the double chamber housing (optionally in the electronics or connection compartment) External indicating and adjustment unit VEGADIS 61
With hardware version - 01 or higher of PLICSCOM as well as the respective sensor, an integrated backlight can be switched on via the adjustment menu. The hardware version is stated on the type label of the PLICSCOM or the sensor electronics. Information: This function is available at a later date for instruments with StEx, WHG or ship approval as well as country-specic approvals such as those according to FM or CSA. Note: You can nd detailed information on the adjustment in the operating instructions manual of the indicating and adjustment module PLICSCOM.
3 4
28782-EN-081127
The indicating and adjustment module is powered by the sensor, an additional connection is not necessary.
29
Note: If you intend to retrot the instrument with an indicating and adjustment module for continuous measured value indication, a higher cover with an inspection glass is required.
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
30
2 1
1.1
Fig. 1 2 3
25: Indicating and adjustment elements LC display Indication of the menu item number Adjustment keys
Key functions
[OK] key: - Move to the menu overview - Conrm selected menu - Edit parameter - Save value [->] key to select: - menu change - list entry - Select editing position [+] key: - Change value of the parameter [ESC] key: - interrupt input - jump to the next higher menu
l l
Adjustment system
The sensor is adjusted via the four keys of the indicating and adjustment module. The LC display indicates the individual menu items. The functions of the individual keys are shown in the above illustration. Approx. 10 minutes after the last pressing of a key, an automatic reset to measured value indication is triggered. Any values not conrmed with [OK] will not be saved.
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
31
Parameter adjustment
As VEGASON 65 is a distance measuring instrument, the distance from the sensor to the product surface is measured. To have the real product level displayed, an allocation of the measured distance to the percentage height must be made. To carry out this adjustment, the distance is entered with full and empty vessel. If these values are not known, an adjustment with the distance values, e.g. 10 % and 90 % is also possible. Starting point for these distance specications is always the lower side of the ange, with all other versions the lower side of the transducer. The actual level is then calculated on the basis of these entered values. At the same time, the operating range of the sensor is limited from maximum range to the requested range. The real product level during this adjustment is not important, because the min./max. adjustment is always carried out without changing the product level. These settings can be made ahead of time without the instrument having to be installed. In the main menu item "Basic adjustment", the individual submenu items should be selected one after the other and provided with the correct parameter values. Start your parameter adjustment with the following menu items of the basic adjustment:
Proceed as follows: 1
Move from the measured value display to the main menu by pushing [OK].
Basic adjustment Display Diagnostics Service Info
28782-EN-081127
Select the menu item "Basic adjustment" with [->] and conrm with [OK]. Now the menu item "Min. adjustment" is displayed.
32
Prepare the % value for editing with [OK] and set the cursor to the requested position with [->]. Set the requested percentage value with [+] and save with [OK]. The cursor jumps now to the distance value. Enter the suitable distance value in m for the empty vessel (e.g. distance from the sensor to the vessel bottom) corresponding to the percentage value. Save the settings with [OK] and move to "Max. adjustment" with [>].
Proceed as follows:
Max. adjustment 100.00 % = 1.000 m(d) 2.000 m(d)
Prepare the % value for editing with [OK] and set the cursor to the requested position with [->]. Set the requested percentage value with [+] and save with [OK]. The cursor jumps now to the distance value. Enter the appropriate distance value in m (corresponding to the percentage value) for the full vessel. Keep in mind that the max. level must lie below the dead band. Save the settings with [OK] and move to "Medium selection" with [->].
3 Medium selection
Each product has dierent reective properties. In addition, there are various interfering factors which have to be taken into account: agitated product surfaces and foam generation (with liquids); dust generation, material cones and echoes from the vessel wall (with solids). To adapt the sensor to these dierent conditions, you should rst select "Liquid" or "Solid".
Medium Liquid
With solids, you can also choose between "Powder/Dust", "Granular/ Pellets" or "Ballast/Pebbels".
28782-EN-081127
Through this additional selection, the sensor is adapted perfectly to the product and measurement reliability, particularly in products with bad reective properties, is considerably increased.
33
6 Set up with the indicating and adjustment module PLICSCOM Enter the requested parameter via the appropriate keys, save your settings and jump to the next menu item with the [->] key. Vessel form Apart from the medium, the vessel shape can also inuence the measurement. To adapt the sensor to these measuring conditions, this menu item oers dierent options depending on whether liquid or solid is selected. With "Liquids" these are "Storage tank", "Stilling tube", "Open vessel" or "Stirred vessel", with "Solid", "Silo" or "Bunker".
Vessel form Storage tank
Enter the requested parameter via the appropriate keys, save your settings and jump to the next menu item with the [->] key. Damping To suppress uctuations in the measured value display, e. g. caused by an agitated product surface, a damping can be set. This time can be between 0 and 999 seconds. Keep in mind that the reaction time of the entire measurement will then be longer and the sensor will react to measured value changes with a delay. In general, a period of a few seconds is sucient to smooth the measured value display.
Damping 0s
Enter the requested parameter via the appropriate keys, save your settings and jump to the next menu item with the [->] key. Linearisation curve A linearization is necessary for all vessels in which the vessel volume does not increase linearly with the level - e. g. with a cylindrical or spherical tank - and the indication or output of the volume is required. Corresponding linearization curves are preprogrammed for these vessels. They represent the correlation between the level percentage and vessel volume. By activating the appropriate curve, the volume percentage of the vessel is displayed correctly. If the volume should not be displayed in percent but e.g. in l or kg, a scaling can be also set in the menu item "Display".
Linearisation curve linear
28782-EN-081127
Enter the requested parameter via the appropriate keys, save your settings and jump to the next menu item with the [->] key.
34
6 Set up with the indicating and adjustment module PLICSCOM Sensor-TAG In this menu item you can enter an unambiguous designation for the sensor, e.g. the measurement loop name or the tank or product designation. In digital systems and in the documentation of larger plants, a singular designation should be entered for exact identication of individual measuring sites.
Sensor-TAG Sensor
With this menu item, the Basic adjustment is nished and you can now jump to the main menu with the [ESC] key. Gating out of false signals High sockets or vessel installations, such as e. g. struts or agitators as well as buildup and weld joints on the vessel walls cause interfering reections which can impair the measurement. A false echo storage detects and marks these false echoes, so that they are no longer taken into account for the level measurement. A false echo memory should be created with low level so that all potential interfering reections will be detected.
Gating out of false signals
Change now?
Proceed as follows: 1 2 3 Move from the measured value display to the main menu by pushing [OK]. Select the menu item "Service" with [->] and conrm with [OK]. Now the menu item "False signal suppression" is displayed. Conrm "False signal suppression - Change now" with [OK] and select in the below menu "Create new". Enter the actual distance from the sensor to the product surface. All false signals in this area are detected by the sensor and saved after conrming with [OK].
Note: Check the distance to the product surface, because if an incorrect (too large) value is entered, the existing level will be saved as false signal. The lling level would then no longer be detectable in this area. Extended setting/Quick level change The menu item "Extended setting" oers the possibility to optimise VEGASON 65 for applications in which the level changes very quickly. For this reason, select the function "Quick level change > 1 m/min.".
Extended setting
28782-EN-081127
35
Note: Since with the function "Quick level change > 1 m/min." the generation of an average value of the signal processing is considerably reduced, false reections by agitators or vessel installations can cause measured value uctuations. A false echo memory is thus recommended. Copy sensor data This function enables reading out parameter adjustment data as well as writing parameter adjustment data into the sensor via the indicating and adjustment module. A description of the function is available in the operating instructions manual "Indicating and adjustment module". The following data are read out or written with this function:
l l l l l l l l l l l l l
Measured value presentation Adjustment Medium Vessel form Damping Linearisation curve Sensor-TAG Displayed value Display unit Scaling Current output Unit of measurement Language HART mode PIN
Copy sensor data
Reset
Basic adjustment If the function "Reset" is carried out, the sensor resets the values of the following menu items to the reset values (see chart):1)
Function Max. adjustment Min. adjustment Medium Vessel form
1) 2)
Reset value 0 m(d) Meas. range end in m(d)2) Liquid not known
28782-EN-081127
Sensor-specic basic adjustment. Depending on the sensor type, see chapter "Technical data".
36
Function Damping Linearisation Sensor-TAG Displayed value Current output - characteristics Current output - max. current Current output - min. current Current output - failure Unit of measurement
The values of the following menu items are not reset to the reset values (see chart) with "Reset":
Function Lighting Language HART mode Reset value no reset no reset no reset
Factory setting Like basic adjustment, furthermore special parameters are reset to default values.3) Pointer The min. and max. distance and temperature values are reset to the actual value. Optional settings Additional adjustment and diagnosis options such as e.g. scaling, simulation or trend curve presentation are shown in the following menu schematic. You will nd a detailed description of these menu items in the operating instructions manual "Indicating and adjustment module".
28782-EN-081127
3)
Special parameters are parameters which are set customer-specically on the service level with the adjustment software PACTware.
37
Basic adjustment Display Diagnostics Service Info Min. adjustment 0.00 % = 4.000 m(d) 3.000 m(d) Damping 0s 1
1.1
Max. adjustment 100.00 % = 1.000 m(d) 2.000 m(d) Linearisation curve linear
1.2
Medium Liquid
1.3
1.4
1.5
1.6
Sensor-TAG Sensor
1.7
Display
2.1
2.2
2.3
Lighting Switched o
2.4
Diagnostics
Basic adjustment Display Diagnostics Service Info 3
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
38
Pointer 3.1 Distance min.: 0.234 m(d) Distance max.: 5.385 m(d) T-min.: 16.5 C T-min.: 37.5 C
3.2
3.3
Echo curve
3.4
Service
Basic adjustment Display Diagnostics Service Info 4
4.2
Current output Output mode: 4-20 mA Fail.mode: < 3.6 mA Min. current: 3.8 mA
4.3
4.4
4.5
4.6
Language Deutsch
4.7
4.8
4.9
PIN Enable?
4.10
Info
Basic adjustment Display Diagnostics Service Info Sensor type 5
5.1
5.2
5.3
5.4
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
39
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
40
Fig. 1 2 3
26: Connection of the PC via VEGACONNECT directly to the sensor USB cable to the PC VEGACONNECT Sensor
TWIST
LO
3 4
OP EN
CK
USB
28782-EN-081127
Fig. 1 2 3 4
27: Connection via IC connection cable IC bus (com.) interface on the sensor IC connection cable of VEGACONNECT VEGACONNECT USB cable to the PC
41
VEGASON 65 PC with PACTware and suitable VEGA DTM VEGACONNECT Power supply unit or processing system
1
LO CK
TWIST
3
Fig. 1 2 3 4 28: Connecting the PC via HART to the signal cable VEGASON 65 HART resistor 250 (optional depending on processing) Connection cable with 2 mm pins and terminals Processing system/PLC/Voltage supply
Necessary components:
l l l l l
VEGASON 65 PC with PACTware and suitable VEGA DTM VEGACONNECT 4 HART resistor approx. 250 Power supply unit or processing system
Note: With power supply units with integrated HART resistance (internal resistance approx. 250 ), an additional external resistance is not necessary. This applies, e. g. to the VEGA instruments VEGATRENN 149A, VEGADIS 371, VEGAMET 381). Common Ex separators are also usually equipped with a sucient current limitation resistance. In such cases, VEGACONNECT 4 can be connected parallel to the 4 20 mA cable.
OPE
USB
28782-EN-081127
42
7 Setup with PACTware and other adjustment programs Note: Keep in mind that for setup of VEGASON 65, DTM-Collection in the actual version must be used. All currently available VEGA DTMs are provided in the DTM Collection on CD and can be obtained from the responsible VEGA agency for a token fee. This CD includes also the up-to-date PACTware version. The basic version of this DTM Collection incl. PACTware is also available as a free-of-charge download from the Internet. Go via www.vega.com and "Downloads" to the item "Software".
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
43
Fault rectication
The rst measures to be taken are to check the output signals as well as to evaluate the error messages via the indicating and adjustment module. The procedure is described below. Further comprehensive diagnostics can be carried out on a PC with the software PACTware and the suitable DTM. In many cases, the causes can be determined in this way and faults can be rectied. However, should these measures not be successful, call the VEGA service hotline in urgent cases under the phone no. +49 1805 858550. The hotline is available to you 7 days a week round-the-clock. Since we oer this service world-wide, the support is only available in the English language. The service is free of charge, only the standard telephone costs will be charged.
Connect a handheld multimeter in the suitable measuring range according to the wiring plan.
Level uctuations
? 4 20 mA signal missing
l
Wrong connection
Check connection according to chapter "Connection steps" and if necessary, correct according to chapter "Wiring plan"
l
No power supply
28782-EN-081127
44
Exchange instrument or return instrument for repair In Ex applications, the regulations for the wiring of intrinsically safe circuits must be observed. Fault messages via the indicating/adjustment module
? E013
l
sensor in boot phase Sensor does not nd an echo, e.g. due to faulty installation or wrong parameter adjustment
? E017
l
Carry out a fresh adjustment and increase the distance between min. and max. adjustment
? E036
l
? E041
l
Exchange instrument or return instrument for repair Reaction after fault rectication Depending on the failure reason and measures taken, the steps described in chapter "Set up" must be carried out again, if necessary.
28782-EN-081127
In both cases, the sensor serial number is needed. The serial numbers are stated on the type label of the instrument, inside the housing or on the delivery note.
45
8 Maintenance and fault rectication Information: When loading on site, rst of all the order data must be downloaded from the Internet (see operating instructions manual "Oscillator"). Assignment The electronics modules are adapted to the respective sensor and distinguish also in the signal output or power supply.
At "www.vega.com/downloads" go to "Software". Select under "plics instruments and sensors" the suitable instrument series. Load the zip le via the right mouse key with "Save target as" e.g. on the desktop of your PC. Extract all les available in the zip le, e.g. to the desktop. Connect the sensor to power supply and provide connection from PC to the instrument via VEGACONNECT. Start PACTware and provide connection to the sensor, e.g. via the VEGA project assistant. Close the parameter window of the sensor, as far as open. Go in the PACTware menu bar to "Instrument data", "Additional functions" and "Update instrument software". PACTware checks now the actual hardware and software version of the sensor and displays the data. This procedure lasts approx. 60 s. Push the button " Update software" and select the previously extracted hex le. Then the software update can be started. Further les are installed automatically. Depending on the sensor, this procedure lasts approximately 1 h.
Prepare update
28782-EN-081127
l l l
Print and ll out one form per instrument Clean the instrument and pack it damage-proof Attach the completed form and, if need be, also a safety data sheet outside on the packaging
46
Please ask the agency serving you for the address of your return shipment. You can nd the respective agency on our website www.vega.com under: "Company - VEGA worldwide"
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
47
9 Dismounting
9 Dismounting
9.1 Dismounting steps
Danger: The individual wires of the transducer cable carry a voltage of approx. 70 V during operation (see chapter "Mounting preparations"). Therefore dismount VEGASON 65 only in complete absence of line voltage.
Warning: Before separating the transducer cable (see chapter "Mounting preparations", example see illustration below), idle condition must be provided. Non-observance can cause damage to the electronics!
1 2 3
Fig. 29: Plug connector between transducer and socket of electronics housing 1 Socket electronics housing2 Plug connector on the transducer cable3 Connection piece, transducer tube
Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order.
9.2 Disposal
The instrument consists of materials which can be recycled by specialised recycling companies. We use recyclable materials and have designed the electronics to be easily separable. WEEE directive 2002/96/EG This instrument is not subject to the WEEE directive 2002/96/EG and the respective national laws. Pass the instrument directly on to a specialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive.
28782-EN-081127
48
9 Dismounting Correct disposal avoids negative eects to persons and environment and ensures recycling of useful raw materials. Materials: see chapter "Technical data" If you have no possibility to dispose of the old instrument professionally, please contact us concerning return and disposal.
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
49
10 Supplement
10 Supplement
10.1 Technical data
General data Materials, wetted parts - Flange Swivelling holder, ange Transducer Transducer diaphragm PP or Aluminium galvanized steel UP Alu with PE foam rubber coating Aluminium die-casting powder coated Silicone Polycarbonate (UL-746-C listed) 316Ti/316L PUR (1.1082)
Materials, non-wetted parts - Housing Seal between housing and housing cover Inspection window in housing cover for indicating and adjustment module Ground terminal transducer cable with separate version C and D
Weight4) - Compact with ange (version A) Compact with swivelling holder (version B) Separate with swivelling holder (version C) Separate with threaded tting (version D)
8 13.3 kg (17.6 29.3 lbs) 8.7 10.3 kg (19.1 22.7 lbs) 9.2 11.1 kg (20.3 24.5 lbs) 6.5 7.5 kg (14.3 16.5 lbs)
Output variable Output signal HART output values - HART value (Primary Value) HART value (Secondary Value) HART value (3rd Value) 4 20 mA/HART (active) Distance to the level Temperature Distance to the level - scaled 1.6 A mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA 22 mA < 500 5) 0 999 s, adjustable
Resolution Failure signal current output (adjustable) Current limitation Load Damping (63 % of the input variable) Fullled NAMUR recommendations
28782-EN-081127
NE 43
4) 5)
Depending on size and process tting material. With inductive load ohmic share min. 25 /mH.
50
10 Supplement
Input variable Measured value - Version A version B, C and D distance between lower edge of the ange and product surface distance between lower edge of the transducer and product surface 0.8 m (2.624 ft) up to 45 m (147.6 ft) up to 25 m (82.02 ft)
Reference conditions to measuring accuracy (similar to DIN EN 60770-1) Reference conditions according to DIN EN 61298-1 - Temperature +18 +30 C (+64 +86 F) Relative humidity Air pressure 45 75 % 860 1060 mbar/86 106 kPa (12.5 15.4 psig) ideal reector, e.g. metal plate 2 x 2 m (6.56 x 6.56 ft) Biggest false echo, 20 dB smaller than the useful echo
18 kHz > 2 s (dependent on the parameter adjustment) 5 > 3 s (dependent on the parameter adjustment)
Measuring accuracy Resolution, general Deviation7) > 1 mm (0.039 in) see diagram
28782-EN-081127
6)
7)
Time to output the correct level (with max. 10 % deviation) after a sudden level change. Incl. non-linearity, hysteresis and non-repeatability.
51
10 Supplement
90 mm (3.543 in)
60 mm (2.362 in)
30 mm (1.181 in)
6 mm (0.236 in) -6 mm (-0.236 in) 3 m (9.843 ft) 15 m (49.213 ft) 30 m (98.425 ft) 45 m (147.64 ft)
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
52
10 Supplement
90 mm (3.543 in)
60 mm (2.362 in)
30 mm (1.181 in)
6 mm (0.236 in) -6 mm (-0.236 in) 3 m (9.843 ft) 15 m (49.213 ft) 30 m (98.425 ft) 45 m (147.64 ft)
Inuence of the ambient temperature to the sensor electronics8) Average temperature coecient of the zero signal (temperature error) Ambient conditions Ambient, storage and transport temperature Process conditions Process pressure - Version A with PP ange Other versions Process temperature (transducer temperature) 0 kPa -20 50 kPa/-0.2 0.5 bar (-2.9 7.3 psi) -40 +80 C (-40 +176 F) mechanical vibration with 1 g in the frequency range 5 200 Hz9)
8) 9)
0.06 %/10 K
28782-EN-081127
Vibration resistance
Relating to the nominal measuring range. Tested according to the regulations of German Lloyd, GL directive 1.
53
10 Supplement
1 x cable gland M20 x 1.5 (cable: 5 9 mm), 1 x blind stopper M20 x 1.5; plug M12 x 1 for VEGADIS 61 (optional) 1 x closing cap NPT, 1 x blind stopper NPT, plug M12 x 1 for VEGADIS 61 (optional) 1 x plug (depending on the version), 1 x blind stopper M20 x 1.5; plug M12 x 1 for VEGADIS 61 (optional)
or:
l
or:
l
Indicating and adjustment module Voltage supply and data transmission Indication Adjustment elements Protection - unassembled mounted into the sensor without cover Materials - Housing Inspection window through the sensor LC display in dot matrix 4 keys IP 20 IP 40
Power supply Operating voltage - Non-Ex and Ex-d instrument Power consumption Electrical protective measures Protection Overvoltage category Protection class IP 66/IP 67 III 20 72 V DC, 20 253 V AC, 50/60 Hz max. 4 VA; 2.1 W
28782-EN-081127
10)
54
10 Supplement
Approvals Depending on the version, instruments with approvals can have dierent technical data. For these instruments, the corresponding approval documents have to be taken into account. These are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools" and "serial number search" as well as via "Downloads" and "Approvals".
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
55
10 Supplement
10.2 Dimensions
Housing
27/
M12x
M20x1,5/ NPT
Fig. 32: Aluminium double chamber housing * Dimension with integrated indicating and adjustment module
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
56
10 Supplement VEGASON 65
130 mm (5.12")
max. 15 (0.59")
240 mm (9.45")
125 mm (4.92")
D k
DIN
mm
DN 50 DN 80 D 165 200 b 11,5 11,5 k 125 160 d 4x 18 4x 18
inch
DN 50 / 2" DN 80 / 3"
ASME
mm
2" 3"
b 11,5 11,5
k 120,7 152,4
d 4x 19,1 4x 19,1
inch
2" 3"
Fig. 1 2 3 4
33: VEGASON 65 Version A Version B Dead zone: 1 m (3.281 ft) Measuring range: with liquids up to 25 m (82.02 ft), with solids up to 15 m (49.21 ft)
28782-EN-081127
270 mm (10.63")
440 mm (17.32")
57
10 Supplement VEGASON 65
150 mm (5.91")
220 mm (8.66")
312 mm (12.28")
D k
18 mm (0.71")
DIN
mm
DN 50 DN 80 D 165 200 b 11,5 11,5 k 125 160 d 4x 18 4x 18
inch
DN 50 / 2" DN 80 / 3"
ASME
mm
2" 3" D 152,4 190,5 b 11,5 11,5 k d 120,7 4x 19,1 152,4 4x 19,1
inch
2" 3"
D 6" 7.5"
Fig. 1 2 3 4
34: VEGASON 65 Version C Version D Dead zone: 0.8 m (2.624 ft) Measuring range: with liquids up to 45 m (147.6 ft), with solids up to 25 m (82.02 ft)
143 mm (5.63")
28782-EN-081127
58
10 Supplement
10.4 Trademark
All brands used as well as trade and company names are property of their lawful proprietor/originator.
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
59
10 Supplement
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
60
10 Supplement
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
61
10 Supplement
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
62
10 Supplement
28782-EN-081127
VEGASON 65 4 20 mA/HART four-wire
63
Printing date:
VEGA Grieshaber KG Am Hohenstein 113 77761 Schiltach Germany Phone +49 7836 50-0 Fax +49 7836 50-201 E-mail: info@de.vega.com www.vega.com
ISO 9001