1. Equipment Detail
Equipment Circuit Position Manufacturer Serial No Vector Group Type of Cooling Rated Power : 132/33 kV Power Transformer : 132/33 kV Transformer Bay : : : : :
Page 1 of 3
1.5 Vector Group Test Test Items Measured Voltage Verifying condition Result 1V-2V 1W-2W Ok 1V-2W 1W-2V Power Transformer Vector Group Testing (YNyn0) : R-r Shorted Tap position = 9 , three phase voltage applied on the primary side.
R R Y B N r y b n
X
Y
X
B
X
N
X
r
X
y
X
b
X
X X
X X X
X X X X
X X X X X
X X X X X X
Remarks
17
LV Side Polarity
Remark
Tested by:
Witnessed by: