You are on page 1of 8

HCM534D - Technical Data Sheet

HCM534D
SPECIFICATIONS & OPTIONS
TERMINALS & TERMINAL BOX Standard generators are 3-phase reconnectable with 12 ends brought out to the terminals, which are mounted on a cover at the non-drive end of the generator. A sheet steel terminal box contains the AVR and provides ample space for the customers' wiring and gland arrangements. It has removable panels for easy access.

STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards and certifications can be considered on request.

VOLTAGE REGULATORS MX341 AVR - STANDARD This sophisticated Automatic Voltage Regulator (AVR) is incorporated into the Stamford Permanent Magnet Generator (PMG) control system, and is standard on marine generators of this type. The PMG provides power via the AVR to the main exciter, giving a source of constant excitation power independent of generator output. The main exciter output is then fed to the main rotor, through a full wave bridge, protected by a surge suppressor. The AVR has in-built protection against sustained overexcitation, caused by internal or external faults. This de-excites the machine after a minimum of 5 seconds. An engine relief load acceptance feature can enable full load to be applied to the generator in a single step. If three-phase sensing is required with the PMG system the MX321 AVR must be used. We recommend three-phase sensing for applications with greatly unbalanced or highly non-linear loads. MX321 AVR The most sophisticated of all our AVRs combines all the features of the MX341 with, additionally, threephase rms sensing, for improved regulation and performance. Over voltage protection is built-in and short circuit current level adjustments is an optional facility.

SHAFT & KEYS All generator rotors are dynamically balanced to better than BS6861:Part 1 Grade 2.5 for minimum vibration in operation. Two bearing generators are balanced with a half key.

INSULATION/IMPREGNATION The insulation system is class 'H'. All wound components are impregnated with materials and processes designed specifically to provide the high build required for static windings and the high mechanical strength required for rotating components.

QUALITY ASSURANCE Generators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001. The stated voltage regulation may not be maintained in the presence of certain radio transmitted signals. Any change in performance will fall within the limits of Criteria 'B' of EN 61000-6-2:2001. At no time will the steady-state voltage regulation exceed 2%.

WINDINGS & ELECTRICAL PERFORMANCE All generator stators are wound to 2/3 pitch. This eliminates triplen (3rd, 9th, 15th ) harmonics on the voltage waveform and is found to be the optimum design for trouble-free supply of non-linear loads. The 2/3 pitch design avoids excessive neutral currents sometimes seen with higher winding pitches, when in parallel with the mains. A fully connected damper winding reduces oscillations during paralleling. This winding, with the 2/3 pitch and carefully selected pole and tooth designs, ensures very low waveform distortion.

NB Continuous development of our products entitles us to change specification details without notice, therefore they must not be regarded as binding. Front cover drawing typical of product range.

HCM534D
WINDING 311
CONTROL SYSTEM A.V.R. VOLTAGE REGULATION SUSTAINED SHORT CIRCUIT INSULATION SYSTEM PROTECTION RATED POWER FACTOR STATOR WINDING WINDING PITCH WINDING LEADS STATOR WDG. RESISTANCE ROTOR WDG. RESISTANCE EXCITER STATOR RESISTANCE EXCITER ROTOR RESISTANCE R.F.I. SUPPRESSION WAVEFORM DISTORTION MAXIMUM OVERSPEED BEARING DRIVE END BEARING NON-DRIVE END 1 BEARING WEIGHT COMP. GENERATOR WEIGHT WOUND STATOR WEIGHT WOUND ROTOR WR INERTIA SHIPPING WEIGHTS in a crate PACKING CRATE SIZE 1393 kg 657 kg 563 kg 8.0068 kgm 1355kg 166 x 87 x 124(cm) 50 Hz TELEPHONE INTERFERENCE COOLING AIR VOLTAGE SERIES STAR VOLTAGE PARALLEL STAR VOLTAGE SERIES DELTA 380/220 190/110 220/110 THF<2% 1.035 m/sec 2202 cfm 400/231 200/115 230/115 435 415/240 208/120 240/120 435 440/254 220/127 254/127 435 416/240 208/120 240/120 500
2

SEPARATELY EXCITED BY P.M.G. MX321 0.5 % MX341 1.0 % With 4% ENGINE GOVERNING

REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7) CLASS H IP23 0.8 DOUBLE LAYER LAP TWO THIRDS 12 0.0049 Ohms PER PHASE AT 22C SERIES STAR CONNECTED 1.77 Ohms at 22C 17 Ohms at 22C 0.092 Ohms PER PHASE AT 22C BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0% 2250 Rev/Min BALL. 6220 (ISO) BALL. 6314 (ISO) 2 BEARING 1395 kg 657 kg 535 kg 7.7289 kgm2 1395kg 166 x 87 x 124(cm) 60 Hz TIF<50 1.312 m/sec 2780 cfm 440/254 220/127 254/127 520 460/266 230/133 266/133 545 480/277 240/138 277/138 570

kVA BASE RATING FOR 435 REACTANCE VALUES Xd DIR. AXIS SYNCHRONOUS 2.63 X'd DIR. AXIS TRANSIENT 0.14 X''d DIR. AXIS SUBTRANSIENT 0.10 Xq QUAD. AXIS REACTANCE 2.16 X''q QUAD. AXIS SUBTRANSIENT 0.23 0.04 XL LEAKAGE REACTANCE 0.17 X2 NEGATIVE SEQUENCE 0.09 X0 ZERO SEQUENCE REACTANCES ARE SATURATED T'd TRANSIENT TIME CONST. T''d SUB-TRANSTIME CONST. T'do O.C. FIELD TIME CONST. Ta ARMATURE TIME CONST. SHORT CIRCUIT RATIO

2.37 2.20 1.96 3.06 2.85 2.73 2.62 0.12 0.11 0.10 0.15 0.14 0.13 0.12 0.09 0.08 0.07 0.10 0.10 0.10 0.09 1.95 1.81 1.61 2.50 2.32 2.22 2.13 0.22 0.20 0.17 0.27 0.25 0.24 0.23 0.03 0.03 0.03 0.05 0.05 0.04 0.04 0.15 0.14 0.12 0.19 0.18 0.17 0.17 0.08 0.07 0.06 0.09 0.08 0.08 0.07 VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED 0.08s 0.012s 2.2s 0.018s 1/Xd

50 Hz

HCM534D
Winding 311 THREE PHASE EFFICIENCY CURVES

60 Hz

HCM534D
Winding 311 THREE PHASE EFFICIENCY CURVES

HCM534D
Winding 311 Locked Rotor Motor Starting Curve

50
Hz
30
346V 380V 400V 415V 440V

25

PER CENT TRANSIENT VOLTAGE DIP .

20

15

10

0 0 200 400 600 800 1000 1200 1400 1600 1800


LOCKED ROTOR kVA

60
30

Hz

380V

416V

440V 460V

480V

25

PER CENT TRANSIENT VOLTAGE DIP .

20

15

10

0 0 200 400 600 800 1000 1200 1400 1600 1800 2000
LOCKED ROTOR kVA

HCM534D
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed Based on star (wye) connection.

50 Hz

100000

SYMMETRICAL ASYMMETRICAL

CURRENT (Amps)

10000

1000

100 0.001

0.01

0.1 TIME (secs)

10

Sustained Short Circuit = 2,400 Amps

60 Hz

100000

SYMMETRICAL ASYMMETRICAL

CURRENT (Amps)

10000

1000

100 0.001

0.01

0.1 TIME (secs)

10

Sustained Short Circuit = 2,500 Amps


Note 1 The following multiplication factors should be used to adjust the values from curve between time 0.001 seconds and the minimum current point in respect of nominal operating voltage : 50Hz
Voltage 380v 400v 415v 440v Factor X 1.00 X 1.06 X 1.09 X 1.12

Note 2 The following multiplication factor should be used to convert the values calculated in accordance with NOTE 1 to those applicable to the various types of short circuit :
3-phase 2-phase L-L 1-phase L-N

60Hz
Voltage 416v 440v 460v 480v Factor X 1.00 X 1.06 X 1.12 X 1.20

The sustained current value is constant irrespective of voltage level

Instantaneous x 1.00 x 0.87 x 1.30 Minimum x 1.00 x 1.80 x 3.20 Sustained x 1.00 x 1.50 x 2.50 Max. sustained duration 10 sec. 5 sec. 2 sec. All other times are unchanged Note 3 Curves are drawn for Star (Wye) connected machines. For other connection the following multipliers should be applied to current values as shown : Parallel Star = Curve current value X 2 Series Delta = Curve current value X 1.732 Note 3

HCM534D
Winding 311 / 0.8 Power Factor RATINGS
Class - Temp Rise Cont. E - 65/50C 380 190 220 340 272 400 200 230 345 276 95.3 290 415 208 240 360 288 95.3 302 440 220 254 360 288 95.3 302 380 190 220 355 284 95.2 298 Cont. B - 70/50C 400 200 230 365 292 95.2 307 415 208 240 375 300 95.2 315 440 220 254 375 300 95.3 315 380 190 220 405 324 95.0 341 Cont. F - 90/50C 400 200 230 415 332 95.1 349 415 208 240 430 344 95.1 362 440 220 254 430 344 95.2 361 Cont. H - 110/50C 380 190 220 435 348 94.9 367 400 200 230 435 348 95.0 366 415 208 240 435 348 95.1 366 440 220 254 435 348 95.2 366 Series Star (V) Parallel Star (V) Series Delta (V) kVA kW

50
Hz

Efficiency (%) 95.2 kW Input 286

60
Hz

Series Star (V) Parallel Star (V) Delta (V) kVA kW

416 208 240 385 308

440 220 254 400 320 95.1 336

460 230 266 420 336 95.2 353

480 240 277 445 356 95.2 374

416 208 240 405 324 95.0 341

440 220 254 425 340 95.1 358

460 230 266 445 356 95.1 374

480 240 277 465 372 95.2 391

416 208 240 463 370 94.9 390

440 220 254 488 390 95.0 411

460 230 266 506 405 95.1 426

480 240 277 531 425 95.1 447

416 208 240 500 400 94.8 422

440 220 254 520 416 94.9 438

460 230 266 545 436 94.9 459

480 240 277 570 456 95.0 480

Efficiency (%) 95.1 kW Input 324

DIMENSIONS

Barnack Road Stamford Lincolnshire PE9 2NB Tel: 00 44 (0)1780 484000 Fax: 00 44 (0)1780 484100

2006

TD_HCM534D.GB_10.06_03_GB