You are on page 1of 8

FC2040 Fire control panel

Series FS20 (MP4.0)

Sinteso

Compact, prefabricated, microprocessor-controlled fire control panel for the

connection of up to 504 addresses Fire control panel can be used as stand-alone version or networked Up to 64 stations (fire control panels and fire terminals) can be connected in one network Integrated emergency operation function Redundant network node, degrade operation according to EN 54 Fast Ethernet interface for heterogeneous network Integrated user-friendly operating unit Optional printer, key switch, LED indicators Slots for RS232, RS485 serial ports Emergency power supply for up to 72 h for emergency operating time Recognition and automatic read-in (auto configuration) of all FDnet devices, providing immediate simple operation Processes signals from the Sinteso detector series Time and situation-dependent change over of the detector parameters Floor repeater devices, alarm devices and mimic displays in the detector loop (FDnet) Flexible programming of complex applications and controls Stored data can be uploaded via remote access Firmware download of all processor controlled control panel components

Building Technologies
CPS Fire Safety

System overview

FT2040 FC2040
Repeater FN2002

FCnet/SAFEDLINK

Fire control panel SintesoWorks, SintesoView

FC2040

DM110x Explosionhazard area DT110x-Ex

e lectr ostati c av oi d cha rgi ng!

e lectros tat ic avoi d ch arging!

Detection line GMT detectors Siemens or SynovaTM SynoLINE300 SB3 24VDC ext. or

DO1101-Ex

Transmission of an alarm signal Transmission of a fault signa via FCI2007-A1l

FDCI222 FDL241-9 Floor repeater display FDO241 4 inputs FDCIO223 2 in-/outputs optionally FDT241

FT2011

Fire controls via FCI2008-A1


FDCL221 stub line

FDnet
FDSB291 FDT221 24VDC ext. possible FDS229 FDM22x FDCIO222 4 inputs 24VDC ext. possible Mimic display FDO221 4 outputs Floor repeater terminal

conventional horn line via FCI2009-A1


VESDA LaserFocus VLF-250/-500

4 (8) loops max. 504 addresses


FT2010

FDOOT241-9

FC10 or XC10

FDCIO222 FDCW241 FDF2x1-9 Fire detection or Extinguishing control unit collective FDOOT271

FDS221 FDM22x

Radio detectors

2 Building Technologies CPS Fire Safety

Networking topologies Up to 32 fire control panels und fire control terminals can be connected in a single cluster (FCnet/SAFEDLINK) or up to 16 stations when the cluster is connected to a danger management system.

Using a fiber-optic Backbone (FCnet/LAN) up to 14 of the above mentioned clusters (with up to 16 stations each) can be networked. The entire network may contain up to 64 stations.

For details about system networking, please refer to product data sheet 008955. 3 Building Technologies CPS Fire Safety

Characteristics The FC2040 is a compact fire control panel with an integrated operating unit that can process signals from Sinteso devices. The control panel can be used as a stand-alone unit or in a network. Using the user-friendly engineering tool SintesoWorks, the control panels can be configured to create a customized solution. All detector lines are monitored for ground faults. Adaptation of the user text directly on the terminal or with the software engineering tool. Up to 2000 events can be stored and recalled according to various criteria. Automatic daylight saving time switchover. Connection to Siemens Danger Management System. Functional elements Operating unit The following are located on the operating unit: CPU module and the electronics for the operating unit Ethernet connection Plug-ins for RS232, RS485 modules and networking modules (SAFEDLINK) Space for 'Kaba' or 'Nordic' key switch Space for event printer Peripheral board The following are located on the peripheral board: Connection terminals for FDnet loops, remote transmission (alarm, fault), horn outputs, programmable control inputs/outputs, monitored alarm and fault output, degrade supply, power supply 2 plug-ins for loop extension (FDnet) Power supply 150 W, degrade supply Provides the hardware with the necessary power and charges the batteries The batteries supply emergency power in case of power failure Housing A pivoting mounting panel can be installed on the housing backplane to allow installation of: 1 fire brigade periphery module 2 sounder modules (can also be mounted onto the U-rail TS35) Configuration The engineering tool (SintesoWorks) permits the system to be adapted to specific customers' requirements. Application ranges The FC2040 is ideally suited for medium-sized applications, e.g. in industrial plant, regional banks, office complexes, etc. or when networked as part of much larger applications. The FC2040 can be used by the flexible cross-linking possibilities however also for extensive systems. Operation Each control panel has an integrated operating unit. The control panel can also be operated from a separate FT2040 operator terminal or any other control panel. For details and further information, please refer to product data sheet 009386.
4 Building Technologies CPS Fire Safety

Overview of FC2040 fire control panels Housing (Comfort) FC2040-AE


With 48 indicator groups with each one red + yellow LED

FC2040-AA

FC2040-AG
With 96 indicator groups with each one red + yellow LED

Housing (Large) FC2040-GA


With 96 indicator groups with each one red + yellow LED

4 Loops With power supply (150 W) Battery capacity max. 26 Ah

4 Loops With power supply (150 W) Battery capacity max. 26 Ah

4 Loops With power supply (150 W) Battery capacity max. 26 Ah

4 Loops With power supply (150 W) Battery capacity max. 26 Ah

Expansion FTO2001-A1
Event printer

FH2007-A1
Housing (Std. +plan comp.) 430 x 398 x 160 mm

FH2003-A1
Housing (Comfort) 430 x 796 x 160 mm

FH2005-A1
Housing (Large) 430 x 796 x 260 mm

Can be installed in FC2040-AA FC2040-AE FC2040-AG RS232 module must be ordered separately

Empty housing for documents A4, Depth 150 mm

Empty housing for various applications

FH2002-A1
Housing (Standard) 430 x 398 x 160 mm

FH2004-A1
Housing (Large extension) 430 x 398 x 260 mm Empty housing for various applications e.g. for additional batteries, Space for larger batteries operating add-ons or 4 x FA2006-A1 (26 Ah) or event printer 4 x FA2007-A1 (45 Ah) or Space for batteries 2 x FA2008-A1 (65 Ah) 2 x FA2003-A1 (7 Ah) or 2 x FA2004-A1 (12 Ah) or 2 x FA2005-A1 (17 Ah) or 2 x FA2006-A1 (26 Ah)

e.g. for additional batteries, operating add-ons or event printer Space for batteries 2 x FA2003-A1 (7 Ah) or 2 x FA2004-A1 (12 Ah)

Space for larger batteries 2 x FA2007-A1 (45 Ah) or 2 x FA2008-A1 (65 Ah)

Operating add-ons FCM2006-A1 FCM2007-A1


48 indicator groups with each one red + yellow LED 96 indicator groups with each one red + yellow LED

External printer DL3750+


Matrix printer (Extern) RS232 interface

For retrofitting

For retrofitting RS232 module must be ordered separately

5 Building Technologies CPS Fire Safety

Configuration of FC2040 in housing (Comfort)

21 22

24

11 8 5

16 24 2 18 93 14 12 13 14 23

19 20

15

6 17 16 25 8 10 18
Designation FHA2003-A1 FCI2004-A1 V24230-Z6-A2 FCM200x-xx Z3B171 FTO2001-A1 FTO2005-C1 FTO2006-B1 FHA2007-A1 FCI2003-A1 FCA2002-A1 FCA2001-A1 FN2001-A1 FN2002-A1 FCA2005-A1 FA2003-A1 FA2004-A1 FA2006-A1 Notes Nos. 1-5 > Basic equipment for each FC2040-xx (Comfort) Space for socket, relay modules, etc. Combined system operating panel and CPU, incl. cover 2 x 12 V / 7 26 Ah Relay for fire controls For event logging For operating access rights E.g. for fire brigade peripheral For loop extension of 2 to 4, number of addresses remains the same For peripheral devices with RS485 port For stations with RS232 port For networking various stations For the extension of the system bus FCnet, max. 1 between 2 stations (mounting direct onto plane surface, onto a U-rail TS35 or in housings FDCH291/292) For split-up of 1 to 4 conventional horn lines For emergency power supply

Basic equipment 1 Rear (Comfort) 2 Peripheral board (4-loop) 3 Power supply (SV 24V-150 W) 4 Mains terminals on DIN mounting rail TS35 5 Operating unit 6 Space for batteries Expansion 7 Relay module 8 Event printer Key switch (Kaba) 9 Key switch (Nordic) 10 Mounting plate 11 Loop extension (FDnet) 12 RS485 module (isolated) 13 RS232 module (isolated) 14 Networking module (SAFEDLINK) 15 Repeater (SAFEDLINK) 16 17 Sounder module Battery (12 V, 7 Ah, VDS) Battery (12 V, 12 Ah, VDS) Battery (12 V, 26 Ah, VDS)

6 Building Technologies CPS Fire Safety

18 19 20 21 22 23 24 25

Fire brigade periphery module Battery kit (9 Volt) Lithium battery 9 V / 1 Ah 19" mounting kit FM blind 2HU License key L1 or License key (L2) Cable kit (communication) Power supply kit (150 W, B)

FCI2001-D1 FCA2010-F1 FHA2016-A1 FHA2015-A1 FCA2012-A1 FCA2013-A1 FCA2014-A1 FP2005-A1

For Germany (FBF, FSD, E, FSE, A, KL) rd For 9 Volt battery (3 voltage source only for France) For FCA2010-F1 rd For the installation in 3 party housings For the recess mounting of housings For SintesoView (Visualizer) For Management System (also includes SintesoView ) For flexible cable connections to the modules on the operating unit For additional power supply

Technical data Mains voltage Power supply Operating voltage Operating current Battery capacity Battery monitoring Mains monitoring Connectable detector series Number of lines Loops (with loop extension) or stub lines Number of addresses Integrated inputs/outputs Relay output Remote transmission alarm Remote transmission fault Monitored outputs Alarm Fault Horn Free programmable inputs/outputs Operating unit Plug-in position for RS232, RS485 serial ports Plug-in position for networking modules Plug-in position for loop extension Mounting place for cable kit (communication) Sounder module Ethernet connection RJ45 Operating temperature Storage temperature Humidity (no condensation permitted) Dimensions (W x H x D) Without cover cap With cover cap Color Housing Cover Protection category (IEC 60529) Approvals VdS LPCB AC 98 127 V / AC 196253 V 150 W DC 21 28.6 V max. 5 A 2 x 12 V, 26 Ah yes yes Sinteso (FDnet) 4 (8) 8 (16) max. 504

1 1 1 1 2 12 integrated 2 2 2 2 max. 2 1 -8 +42 C -20 +60 C 95 % rel. 430 x 796 x 160 mm 430 x 796 x 188 mm grey, ~RAL 7035 white, ~RAL 9010 IP30 G206110 126h/05

7 Building Technologies CPS Fire Safety

Details for ordering


Fire control panels Type FC2040-AA FC2040-AE FC2040-AG FC2040-GA Z3B171 FTO2001-A1 FTO2005-C1 FTO2006-B1 FHA2007-A1 FCI2003-A1 FCA2002-A1 FCA2001-A1 FN2001-A1 FN2002-A1 FCA2005-A1 FCA2014-A1 FCI2001-D1 FH2002-A1 FH2007-A1 FH2004-A1 FH2003-A1 FH2005-A1 FCM2006-A1 FCM2007-A1 FCA2010-F1 FHA2016-A1 FHA2015-A1 FN2006-A1 FN2007-A1 FP2003-A1 FP2004-A1 FP2005-A1 FN2008-A1 FN2009-A1 FHA2029-A1 FHA2030-A1 FA2003-A1 FA2004-A1 FA2005-A1 FA2006-A1 FA2007-A1 FA2008-A1 FCA2012-A1 FCA2013-A1 DL3750+ Part no A5Q00016100 A5Q00016852 A5Q00016854 S54400-C3-A3 BPZ:4843830001 A5Q00010126 A5Q00017619 A5Q00010113 A5Q00010129 A5Q00010151 A5Q00010136 A5Q00009923 A5Q00005327 A5Q00012851 S24236-B2502-A1 A5Q00014866 A5Q00023027 A5Q00013100 A5Q00018931 A5Q00022369 A5Q00018778 A5Q00009906 A5Q00019543 A5Q00021771 A5Q00021772 A5Q00012569 A5Q00004142 A5Q00020179 A5Q00024621 S54400-A61-A1 S54400-A62-A1 A5Q00016005 A5Q00020825 A5Q00018779 S54400-F94-A1 S54400-F95-A1 S54400-B79-A1 S54400-B81-A1 A5Q00019353 A5Q00019354 A5Q00019677 A5Q00019356 A5Q00022897 A5Q00019357 A5Q00018856 A5Q00018857 A5Q00023962 A5Q00023963 Designation Fire control panel (4-loop) Fire control panel (4-loop) Fire control panel (4-loop) Fire control panel (4-loop) Relay module 250 VAC / 10 A (1 relay) Event printer Replacement printer rolls (10 rolls) Key switch (Kaba) Key switch (Nordic) Mounting plate Loop extension (FDnet) RS485 module (isolated) RS232 module (isolated) Network module (SAFEDLINK) Repeater (SAFEDLINK) Sounder module Cable kit (communication) Fire brigade periphery module Housing (Standard) Housing (Std. +plan comp.) Housing (Large extension) Housing (Comfort) Housing (Large) Operating add-on (2xLED ind.) Operating add-on (4xLED ind.) Battery kit (9 Volt) (only France) Lithium battery 9 V / 1 Ah, for FCA2010-F1 19" mounting kit FM blind 2HU Module dinterconnexion (SM) Moduel dinterconnexion (MM) Power supply kit (70 W) Power supply kit (150 W) for empty housing Power supply kit (150 W) for cascading Ethernet-Switch Security module Mounting kit for Ethernet switch (Comfort) Mounting kit for Ethernet switch (Large Ext.) Battery (12 V, 7 Ah, VDS) Battery (12 V, 12 Ah, VDS) Battery (12 V, 17 Ah, VDS) Battery (12 V, 26 Ah, VDS) Battery (12 V, 45 Ah, VDS) Battery (12 V, 65 Ah, VDS) License key (L1) License key (L2) Matrix printer (Extern) Black typewriter ribbon for printer DL3750+ Weight 18.280 kg 19.200 kg 21.080 kg 21.080 kg 0.042 kg 0.250 kg 0.090 kg 0.013 kg 0.050 kg 0.800 kg 0.064 kg 0.067 kg 0.068 kg 0.077 kg 0.154 kg 0.140 kg 0.224 kg 0.482 kg 7.500 kg 12.940 kg 11.820 kg 12.600 kg 15.400 kg 2.600 kg 2.800 kg 0.100 kg 0.037 kg 3.000 kg 5.100 kg 0,770 kg 0,770 kg 0.650 kg 1.366 kg 1.100 kg 0,800 kg 0,800 kg 0,500 kg 0,500 kg 2.450 kg 3.930 kg 5.640 kg 7.572 kg 15.320 kg 22.000 kg 0.010 kg 0.010 kg 7.300 kg 0.078 kg

Expansion

Additional power supply

Networks (backbone)

Batteries

Software license External printer Spare part

Siemens Switzerland Ltd Infrastrcture & Cities Sector Building Technologies Division International Headquarters CPS Fire Safety Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724 24 24 www.siemens.com/buildingtechnologies Document no. Edition 009384_m_en_-04.2012

2012 Copyright by Siemens Switzerland Ltd Data and design subject to change without notice. Supply subject to availability. Manual FS20 Section 1

You might also like