Cavity Fixings
Type HB - Hollo-Bolt
Steel, bright zinc plated plus JS 500 Steel, hot dip galvanised Stainless Steel Grade 316 Collar Rubber Washer Sleeve Cone Bolt
Suitable for hollow sections, tubes and where access is available from one side only. For high corrosion protection the Hollo-Bolt comes with additional JS500 protection as standard or hot dip galvanised. Sizes M16 and M20 have a patented collapse mechanism for optimised clamping force. Awarded the Design Councils Millennium Product status for innovation in the year 2000.
Installation Hollo-Bolt
D Rubber Washer
1. Align pre-drilled fixture and steelwork. Insert Hollo-Bolt through fixture and steelwork.
Across Flats
A/F
3. Using a torque wrench, tighten the central bolt to the recommended torque.
41
Type HB - Hollo-Bolt
Cavity Fixings
Type HB - Hollo-Bolt
Product Code Bolt Clamping Thickness W mm 3 - 22 22 - 41 41 - 60 3 - 22 22 - 41 41 - 60 3 - 25 25 - 47 47 - 69 12 - 29 29 - 50 50 - 71 12 - 34 34 - 60 60 - 86 Outer Ply1) min t mm 8 8 8 8 8 8 Sleeve Length Outer L d 30 49 68 30 48 67 35 57 79 41.5 63 84 50 76 102 32.75 10 51 46 300 35.0 40.0 25.75 8 38 36 190 21.0 30.0 19.75 7 32 30 80 10.5 15.0 17.75 6 29 24 45 8.5 10.0 13.75 5 22 19 23 4.0 5.0 Collar Height H D A/F d mm mm TighteningTorque Nm Safe Working Loads2) (5:1 Factor of Safety) Tensile Single Shear kN kN
HB08-1 HB08-2 HB08-3 HB10-1 HB10-2 HB10-3 HB12-1 HB12-2 HB12-3 HB16-1 HB16-2 HB16-3 HB20-1 HB20-2 HB20-3
M8x50 M8x70 M8x90 M10x55 M10x70 M10x90 M12x60 M12x80 M12x100 M16x75 M16x100 M16x120 M20x90 M20x120 M20x150
Order example: HB08-1 BZP plus JS 500 1) Type HB (HB16 and HB20 only) require the thickness of the outer ply (min t) to be at least 8mm. If necessary, spacer washers should be used beneath the collar to increase the thickness to 8mm. 2) The Hollo-Bolt can be used on a wide variety of steel hollow shape sections; safe working loads shown are based on use in S275 structural hollow section. The safe working loads, in both tension and shear, are applicable to the Hollo-Bolt only. Failure of the section, particularly on those with thin walls and a wide chord face, could occur at a lower figure and its strength should be checked by a qualified structural engineer.
Bolt Diameter, Hole and Edge distances for all variants of Type HB excluding Flush Fit
For Flush Fit figures see page 43.
Clearance Type Hole d1 mm HB08 HB10 HB12 HB16 HB20 14 (+1.0 / -0.2) 18 (+1.0 / -0.2) 20 (+1.0 / -0.2) 26 (+2.0 / -0.2) 33 (+2.0 / -0.2) Hole Distances min A mm 35 40 50 55 70 min B mm 13 15 18 20 25 Edge Distances B+C mm B + C > 17.5 B + C > 22.5 B + C > 25.0 B + C > 32.5 B + C > 33.0
min t
d1
d1
42
Cavity Fixings
Characteristic values of tensile and shear resistance for Hollo-Bolt taken from ETA-10/0416 www.lindapter.com/about/CE Standard Hollo-Bolt
Designation Nominal Size Tensile Ft,Rk (kN) 23.1 39.6 45.8 84.3 124.0 26.8 46.0 53.3 98.0 154.0 Shear Fv,Rk (kN) 32.9 54.2 71.0 139.0 211.0 30.7 51.0 65.0 128.0 205.0 Material Strength of Sleeve N/mm2 430 430 430 430 390 500 500 500 500 500
HB08 HB10 HB12 HB16 HB20 HBST08 HBST10 HBST12 HBST16 HBST20
M08 M10 M12 M16 M20 M08 M10 M12 M16 M20
Countersunk Hollo-Bolt
Designation Nominal Size Tensile Ft,Rk (kN) 23.1 39.6 45.8 84.3 26.8 46.0 53.3 98.0 Shear Fv,Rk (kN) 32.9 54.2 71.0 139.0 30.7 51.0 65.0 128.0 Material Strength of Sleeve N/mm2 430 430 430 430 500 500 500 500
The characteristic values for the Hollo-Bolt listed in the above tables are for use when designing bolted connections to Eurocode 3 only, these are not standard safe working loads. Hollo-Bolt lengths 1, 2 and 3 are covered by this ETA-10/0416. The characteristic values are used to determine the design resistance of the Hollo-Bolt. The design resistance is calculated by dividing the characteristic value by a partial factor gM2. The partial factor is a nationally determined parameter (gM2 =1.25 in the UK). For standard Hollo-Bolt safe working loads with a factor of safety of 5:1 please refer to the Hollo-Bolt tables on pages 42 an 43. The characteristic values are valid for the Hollo-Bolt assembly itself, in any connection detail the design resistance of the connection may be limited to a lesser value. For example, when the thickness of the connected component is small, pull out failure may occur before failure of the Hollo-Bolt. Design checks should be carried out on the section member to determine the static design resistance. The SCI Greenbook publication P358 Joints in Steel construction, Simple Joints to Eurocode 3 contains a number of checks on the section. The characteristic values are only valid when the Hollo-Bolts are installed as per our installation instructions.
Hexagonal Head
Flush Fit
Countersunk (Head)
44
Typical Applications
Cavity Fixings
HB001
HB002
HB003
HB004
HB005
HB006
46
Typical Applications
Cavity Fixings
HB007
HB008
HB009
HB010
HB011
HB012
47