Insulation monitoring

Vigilohm

Catalogue

2006

The Guiding System, the new way to create your electrical installations
A comprehensive offer of products with consistent design The Guiding System is first and foremost a Merlin Gerin product offer covering all electrical distribution needs. However, what makes all the difference is that these products have been designed to operate togheter: mechanical and electrical compatibility, interoperability, modularity, communication. Thus the electrical installation is both optimised and more efficient: better continuity of supply, enhanced safety for people and equipment, guaranteed upgradeability, effective monitoring and control. Tools to simplify design and implementation With the Guiding System, you have a comprehensive range of tools - the Guiding Tools - that will help you increase your product knowledge and product utilisation. Of course this is in compliance with current standards and procedures. These tools include technical booklets and guides, design aid software, training courses, etc. and are regularly updated.

For a genuine partnership with you Because each electrical installation is unique, there is no standard solution. With the Guiding System, the variety of combinations allows for genuine customisation solutions. You can create and implement electrical installations to meet your creative requirements and design knowledge. You and Merlin Gerins Guiding System form a genuine partnership. For more details on the Guiding System, consult www.merlin-gerin.com

A consistent design of offers from Medium Voltage to Low Voltage

All Merlin Gerin offers are designed according to electrical, mechanical and communication consistency rules. The products express this consistency by their overall design and shared ergonomics.
Electrical consistency: Each product complies with or enhances system performance at coordination level: breaking capacity, Isc, temperature rise, etc. for more safety, continuity of supply (discrimination) or economic optimisation (cascading). The leading edge technologies employed in Merlin Gerins Guiding System ensure high performance levels in discrimination and cascading of protection devices, electrodynamic withstand of switches and current distributors, heat loss of devices, distribution blocks and enclosures. Likewise, inter-product ElectroMagnetic Compatibilty (EMC) is guaranteed.

Discrimination guarantees co-ordination between the operating characteristics of serial-connected circuit-breakers. Should a fault occurs downstream, only the circuit-breaker placed immediately upstream from the fault will trip.

Mechanical consistency: Each product adopts dimensional standards simplifying and optimising its use within the system. It shares the same accessories and auxiliaries and complies with global ergonomic choices (utilisation mode, operating mode, setting and configuration devices, tools, etc.) making its installation and operation within the system a simpler process.

Direct connection of the Canalis KT busbar trunking on the Masterpact 3200 A circuit breaker.

Communication consistency:
Thanks to the use of standard Web technologies, you can offer your customers intelligent Merlin Gerin switchboards allowing easy access to information: follow-up of currents, voltages, powers, consumption history, etc.

Each product complies with global choices in terms of communication protocols (Modbus, Ethernet, etc.) for simplified integration in the management, supervision and monitoring systems.

Guiding Tools for more efficient design and implementation of your installations.

SM6
Medium voltage switchboard system from 1 to 36 kV

Sepam
Protection relays

Masterpact
Protection switchgear from 100 to 6300 A

Trihal MV/LV dry cast resin transformer from 160 to 5000 kVA

Evolis MV vacuum switchgear and components from 1 to 24 kV.

The Technical guide


These technical guides help you comply with installation standards and rules i.e.: The electrical installation guide, the protection guide, the switchboard implementation guide, the technical booklets and the co-ordination tables all form genuine reference tools for the design of highperformance electrical installations. For example, the LV protection co-ordination guide - discrimination and cascading optimises choice of protection and connection devices while also increasing markedly continuity of supply in the installations.

CAD software and tools


The CAD software and tools enhance productivity and safety. They help you create your installations by simplifying product choice through easy browsing in the Guiding System offers. Last but not least, they optimise use of our products while also complying with standards and proper procedures.

Compact
Protection switchgear system from 100 to 630 A

Multi 9
Modular protection switchgear system up to 125 A

Prisma Plus
Functional system for electrical distribution switchboards up to 3200 A

Pragma Enclosures for distribution switchboards up to 160 A

Canalis Prefabricated Busbar Trunking from 25 to 4000 A

PowerLogic Power management

Training
Training allows you to acquire the Merlin Gerin expertise (installation design, work with power on, etc.) for increased efficiency and a guarantee of improved customer service. The training catalogue includes beginners courses in electrical distribution, knowledge of MV and LV switchgear, operation and maintenance of installations, design of LV installations to give but a few examples.

merlin-gerin.com
This international site allows you to access all the Merlin Gerin products in just 2 clicks via comprehensive range data-sheets, with direct links to: b complete library: technical documents, catalogs, FAQs, brochures b selection guides from the e-catalog b product discovery sites and their Flash animations. You will also find illustrated overviews, news to which you can subscribe, the list of country contacts

insulation monitoring
monitoring

Vigilohm

page

1/ presentation 2/ functions and characteristics 3/ installation and connection 4/ catalogue numbers

6 17

45

55

Vigilohm: presentation

insulation monitoring and associated functions

continuity of supply
Continuity of supply is a need that must always be satisfied by electrical installations, along with the protection of life and property. The IT system provides the best guarantee in terms of continuity of supply. Even when a first insulation fault is present, the installation can continue to supply power without endangering human life. The first fault must however be detected and repaired before a second fault occurs.

principle
Insulation monitoring is provided on IT systems to detect and indicate insulation faults as soon as they occur. The basic function is carried out by an Insulation Monitoring Device (IMD), also referred to in certain documentation as a permanent or continuous insulation monitor (PIM or CIM respectively). The monitoring device injects a DC or low-frequency AC voltage between the installation and earth. The insulation resistance is determined from the resulting current. This technique can be used on all types of installations: AC, DC, rectified, mixed AC/DC, etc.

measuring, indicating and locating insulation faults


Vigilohm System, with or without a communication bus, fulfils the following basic functions: c measurement of insulation level on all types of installations c manual or automatic locating of insulation faults.

Vigilohm System with a communication bus


The communication bus adds the following possibilities: c measurement of the insulation resistance and earth leakage capacitance of each circuit c centralisation of fault locating measurements on the IMD display units c communication with a supervisor (transmission of measurements and reception of settings).

DB100664

IO316_123

Vigilohm: presentation

Vigilohm System with or without a communication bus

Vigilohm System without a communication bus


DB100662 DB100955

Vigilohm System with a communication bus


supervision and event logging

supervisor

printer

interfaces
XAS
MERLIN GERIN
vigilohm system XAS

XAS

XLI300
MERLIN GERIN
vigilohm system XLI300

XTU300
MERLIN GERIN
vigilohm system XTU300

d faut

d faut

d faut

insulation monitoring
XML308/316 XM300c
MERLIN GERIN
vigilohm system XM300c
test

MERLIN GERIN
vigilohm system XML316
test

1 9

10 11 12 13 14 15 16

valeur 040 K TEST

d'isolement MENU

valeur 040 K TEST

d'isolement MENU

insulation fault detection and locating


XD301 XD312 XRM XD308c
MERLIN GERIN
vigilohm system XD308c
test

XL308 / 316
MERLIN GERIN
vigilohm system XL316
test

MERLIN GERIN
vigilohm system

1
test

2 5 8

3 6 9

MERLIN GERIN
vigilohm system

on

10 11 12 13 14 15 16

XD301

XD312

4 7

test

test

reset

reset
50507

10 11 12
50536

reset

on
M

P12

P50 P100

test/reset

MERLIN GERIN
vigidix

RM 10N

sensors

MERLIN GERIN
GO

S1

S2

MERLIN GERIN
PO

S1

MERLIN GERIN
vigirex - vigidix

S2

MERLIN GERIN
vigirex - vigidix

MERLIN GERIN
vigirex - vigidix

Vigilohm: presentation

Vigilohm System without a communication bus

Vigilohm System without a communication bus


This solution offers: c automatic fault detection; c accurate measurements of the insulation level for all types of installations.

Insulation monitoring devices inject a DC or low-frequency AC voltage between the installation and earth. The insulation resistance is determined by measuring the resulting leakage current. c Vigilohm EM9 devices use an indicator light to signal the presence of an insulation fault within the installation. They are modular devices (Multi 9 format) designed for small installations or sub-systems isolated from earth; c the TR22A and TR22AH (for hospitals) devices detect insulation faults and, in addition, continuously indicate the value of the insulation resistance on a digital display; c the XM200 is part of the Vigilohm System range and can be associated with automatic fault locating devices.

E18812

insulation monitoring

DB100650

TR22A
MERLIN GERIN
vigilohm TR 22A

test

off-line insulation monitoring


The failure of a motor to start can have serious consequences. This is especially true in the following applications: c safety equipment (fire pumps, smoke extractors, etc.); c production (glass works, cement plants, etc.); c manufacturing processes (rolling mills, etc.). Motors often fail to start due to insulation problems caused by the humidity that accumulates in the microscopic cracks of the insulation during periods when the motor is not running. The SM21 device monitors the insulation of critical motors while they are off-line. Insulation faults give rise to an alarm or motor starting lock-out.

E27136

SM21
E27112
1 2 3 4 5 6 7

MERLIN GERIN
vigilhom

SM21

AL. REL. OK

test

1,0
0,75 0,5

1,25

2,0

3,0
5,0 7,5

off

on

1,5

1,5

1,75 1,0
0,25 Sa 2,0 0,5 10 Sp

50761

AL. REL.

10 11 12 13

14

Vigilohm: presentation

Vigilohm System without a communication bus

fault locating
Once detected, an insulation fault must be located and eliminated in order to guarantee maximum continuity of supply. Manual fault locating The fault is located by testing different points in the installation, one after another, using a Vigilohm System XRM mobile receiver and a current probe. The receiver captures the low-frequency fault locating signal. Two cases may be encountered: c the installation is equipped with an XM200 or XM300C insulation monitoring device (Vigilohm System). In this case, the manual system is used to fine-tune the results of the automatic locating system c the installation (relatively small or an isolated sub-system) is equipped with an insulation monitoring device for DC injection. In this case, a Vigilohm XGR portable generator is used together with an XRM receiver.
DB100950

Manual fault locating


XM300C
MERLIN GERIN
vigilohm system XM100
test

valeur d'isolement 040 K MENU TEST

on

P12

P50 P100

MERLIN GERIN
v ig id ix

RM 10N

XRM

DB110935

XGR

on

P12

P50 P100

MERLIN GERIN
ix vigid

RM 10N

XRM

Automatic locating: For easy locating of insulation faults, the Vigilohm System makes it possible to combine the XM200 insulation monitoring device with: c XD301/XD312 fault detectors to monitor the different circuits of the installation; c XRM receivers for mobile fault locating.

Automatic fault locating


E27110

XM200
MERLIN GERIN
vigilohm system XM200
test

Sp

Sa
S

menu

ok

test

XD312
1 4 7 2 5 8 3 6 9
M

MERLIN GERIN
vigilohm system

XD312

test

10 11 12
50536

reset

on

P12

P50 P100

MERLIN GERIN
vigidix

RM 10N

XRM

Vigilohm: presentation

Vigilohm System with a communication bus

Vigilohm System with a communication bus


The communication bus adds the following possibilities: c communication with a supervisor (transmission of measurements and reception of settings) c measure the insulation resistance and earth leakage capacitance of each circuit c centralisation of the locator measurements on the insulation monitoring device displays.

DB100956

supervision and event logging

supervisor

printer

interfaces
XAS
MERLIN GERIN
vigilohm system XAS
dfaut

XLI200/XLI300
MERLIN GERIN
vigilohm system XLI300
dfaut

XTU300
MERLIN GERIN
vigilohm system XTU300
dfaut

insulation monitoring
XML308/316
MERLIN GERIN
vigilohm system XML316
test 1 9 2 3 4 5 6 7 8 10 11 12 13 14 15 16

XM300c
MERLIN GERIN
vigilohm system XM300c
test

valeur d'isolement 040 K MENU TEST

valeur d'isolement 040 K MENU TEST

insulation fault detection and locating


XD301
MERLIN GERIN
vigilohm system

XD312
1 2 5 8 3 6 9
M

XRM
test

XD308c
MERLIN GERIN
vigilohm system XD308c
test

XL308 / 316
MERLIN GERIN
vigilohm system XL316
test 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

MERLIN GERIN
vigilohm system

on

XD301

test

XD312

4 7

test

reset

reset
50507

10 11 12
50536

reset

on
M

P12

P50 P100

test/reset

MERLIN GERIN
vigidix

RM 10N

sensors
MERLIN GERIN
GO

S1

S2

MERLIN GERIN
PO

S1

MERLIN GERIN
vigirex - vigidix

S2

MERLIN GERIN
vigirex - vigidix

MERLIN GERIN
vigirex - vigidix

insulation monitoring and associated functions


communication features
In addition to displaying the insulation values it measures for the installation as a whole, an insulation monitoring device can also provide a centralised display for information concerning specific circuits. It receives this information from communicating insulation fault locators and detectors distributed throughout the installation. All this information may also be transmitted to a remote supervisory system. These communication features satisfy the operating requirements of modern electrical installations. All information concerning the insulation can be transmitted via a communication bus for display on a centralised insulation monitoring device or to a supervision system for centralised processing and management.
E17057

centralisation on a supervisor

centralisation on an IMD

local display

measurements

prevention of insulation faults


Prevention is the best way to ensure the continuity of supply of electrical installations. It may be applied in two ways: c the insulation monitoring device signals a drop in the insulation resistance below a non-critical prevention threshold determined by the user; c the measurements are transmitted to a supervisor, which can then process them to predict insulation faults on ageing cables. These indications can be used to schedule preventive maintenance.

E17059

preventive level

fault level

fault prevention

10

Vigilohm: presentation

Vigilohm System: general information


easier operation of IT systems
An installation implementing the IT system, i.e. isolated from earth or connected to earth through a sufficiently high impedance, gives top priority to continuity of supply. Today, the operation of such installations can be greatly facilitated by the use of devices that offer functions going far beyond the simple fault signalling imposed by standards. Other functions c measurement of the true insulation resistance c measurement of the earth leakage capacitance c indication of transient faults c prevention alarm when the insulation resistance falls below a non-critical threshold determined by the user; c remote interrogation and display, from the insulation monitoring device, of faults detected by the fault locators c setting of alarm thresholds from a supervisor
E20122

XM200
MERLIN GERIN
vigilohm system XM200
test

Sp

Sa
S

menu

ok

test

XD312
MERLIN GERIN
1 2 5 8 3 6 9
M

... with Vigilohm System


Vigilohm System is a range of Merlin Gerin products meeting the needs of IT systems in terms of performance, practical operation and continuity of supply. This range features modular design. It is made up of Insulation Monitoring Devices (IMDs) and fault detection and locating devices. Some of these devices make independent measurements of the insulation resistance on each circuit. In addition, the Vigilohm System can communicate with a supervisor or PLC.

vigilohm system

c ...
The system evolves with the needs of the installation. New devices can be added at any time to adapt to installation modifications or provide higher levels of monitoring.

XD312

test

4 7

10 11 12
50536

reset

insensitivity to electrical disturbances


The Vigilohm System offers both measurement accuracy and insensitivity to electrical disturbances. Designed to operate on modern installations, it is not affected by the harmonics generated by loads such as variable speed drives, UPSs and switchmode power supplies.
E20123

From automatic fault locating with local display ...

principle and functions


The basic device is the Insulation Monitoring Device (IMD). It injects a lowfrequency AC voltage between earth and the installation. Based on a measurement of the resulting current, the Vigilohm System accurately determines the true insulation resistance of the installation and its earth coupling capacitance. This technique can be used on all types of installations: AC, DC, rectified, mixed, etc. Fault locating is the main function associated with insulation monitoring. Toroids placed on the various circuits capture a signal proportional to the current injected by the insulation monitoring device. This signal is transmitted to fault detection and locating devices which automatically identify any faulty circuit. Distributed measurements of the insulation resistance and the earth leakage capacitance are possible on each circuit via the toroids used for fault locating. Centralisation on a supervisor. Via a communication bus using JBUS protocol, the Vigilohm System can forward all measurements, information and events to a supervisor. In this way, the supervisor maintains full knowledge on the insulation status of the overall installation and the individually monitored circuits. The supervisor (or PLC) can be connected to a printer to log all events occurring on the installation, complete with location and timestamp. Adaptation to variable installation configurations. The system automatically excludes all but one insulation monitoring device connected to the same set of busbars.

insulation resistance 1.5 K TEST MENU

XM300c
MERLIN GERIN
vigilohm system XM300c

XLI300
MERLIN GERIN
vigilohm system XLI300

supervisor
insulation valeur d'isolement resistance K 1,5 K 1.5

test

dfaut

valeur 1,5 K TEST

d'isolement MENU

XL316
MERLIN GERIN
vigilohm system XL308c
test

1 9

10 11 12 13 14 15 16

test/reset

... to distributed measurements with centralised display

11

Vigilohm: presentation

Vigilohm System: choosing the system architecture


what devices make up the system?
c XM200 and XM300C insulation monitoring devices inject a signal that is used by the detection and locating devices; c XL308 and XL316 locators, connected to 8 or 16 toroids, measure the insulation resistance of each circuit (distributed measurements) and, in the event of a fault, automatically identify the faulty circuit. They can transmit this information to a supervisor; c XML308 and XML316 monitoring-locating devices combine the monitoring and locating functions in a single unit; c the XD308C communicating insulation fault detector automatically identifies the faulty circuit and transmits this information to a supervisor; c XD301 and XD312 non-communicating insulation fault detectors automatically identify the faulty circuit; c the XRM mobile receiver can be used to fine-tune the automatic locating results by identifying the faulty circuit at the final distribution level; c XLI200, XLI300 and XTU300 interfaces make communication possible between the Vigilohm System and a supervisor; c the XAS interface is used to supply power to the communication bus.

how to choose the right system?


The right system can be chosen in four steps, described in detail below: 1. define the required level of locating and measurement performance. 2. select the corresponding locating and measurement devices. 3. select the insulation monitoring devices compatible with the locating and measurement devices. 4. check whether or not an interface is required. Note: connect the insulation monitoring device to a PHT1000 subassembly if the installation voltage U is: c 760 < U < 1700 V AC (neutral distributed); c 440 < U < 1000 V AC (neutral not distributed); c 550 < U < 1200 V DC (DC or rectified voltage).
1 level of locating and measurement

v automatic fault locating with local display The faulty circuit is identified and indicated on the front face of the fault detector. A contact is provided for remote indications, v automatic fault locating with centralised display The faulty circuit is identified and indicated on the front face of the fault detector. The information is also transmitted to a supervisor or a PLC, v distributed measurements with local display The devices measure the insulation resistance on each circuit independently. These measurements can be read on the front face of the device. Faults are located and displayed locally. A contact is provided for remote indications, v distributed measurements with centralised display The insulation measurement for each circuit and the indication of the faulty circuit are displayed on the front of the device and transmitted to a supervisor or PLC.
2 selection of the locating and measurement devices

performance According to your need, select one of the five possibilities listed in part 1 of the table. The choice depends on: c the required performance of the locating system to be associated with the fault detection function; c the need for independent insulation measurements on each circuit. The five possibilities are (in increasing order of performance): v manual fault locating The fault is located using a mobile receiver connected to a current probe placed at different points in the installation one after another. This type of system is recommended as an enhancement to the automatic system in order to determine the faulty portion of a circuit on which an insulation fault has been detected.
2

On the line selected in part 1, select the fault locating or distributed measurement device in part 2 of the table.
3 selection of the insulation monitoring device

Similarly, determine the insulation monitoring devices, in part 3 of the table, that are compatible with the selected locating and measurement devices.
4 necessity of an interface For the column selected in part 2 of the table, part 4 indicates whether or not an interface is required. If required, the interface will be selected according to the installation and the devices making up the system. See the page entitled "choosing the communication interface".

locating and measurement devices


XD301/302 detector XD308C detector XL308/316 locator

XRM receiver
1

level of performance
c c v c v v c c

manual fault locating automatic fault locating with local display automatic fault locating with centralised display distributed measurements with local display distributed measurements with centralised display
3

insulation monitoring device


c v v c v v c v c c

XM200 XM300c XML308/316

XAS, XLI200, XLI300, XTU300 interfaces


4
c device providing only the required function v device offering additional possibilities or higher performance.

12

Vigilohm: presentation

Vigilohm System: choosing the fault locating system


The Vigilohm System offers four fault locating performance levels. level 1: automatic fault detection and locating. level 2: automatic fault detection and locating with transmission to a supervisor.
E24547 E24548

level 3: automatic fault detection, locating and measurement. level 4: automatic fault detection, locating and measurement with transmission to a supervisor.
interface
MERLIN GERIN
vigilohm system XAS
dfaut

Manual fault locating with the XRM mobile receiver is generally used to fine-tune the automatic locating results.

supervisor printer

IMD
MERLIN GERIN
vigilohm system XM300c
test

XM200
MERLIN GERIN
vigilohm system XM200
test

valeur d'isolement 040 K MENU TEST

Sp

Sa
S

menu

ok

test

XRM

XD312
1
4
7

XD308c
MERLIN GERIN
vigilohm system

XD308c
MERLIN GERIN vigilohm system
XD308c

MERLIN GERIN
vigilohm system XD308c
test test

2
5
8

3
6
9

XD312

test

10 11 12
50536

reset

P12
M

P50 P100

on

on

MERLIN GERIN
RM 10N
test reset test reset

level 1: automatic fault detection and locating

XRM
XD312
MERLIN GERIN
XD312
P12
test

P50 P100

MERLIN GERIN
reset

RM 10N

level 2: automatic fault detection and locating with transmission to a supervisor.


E24550 E24549

interface
MERLIN GERIN vigilohm system
XAS
dfaut

supervisor printer

XML308/316
MERLIN GERIN
vigilohm system XML316
test

interface
MERLIN GERIN
vigilohm system XAS
dfaut

XM300c
MERLIN GERIN
vigilohm system XM300c

1
9

10 11 12 13 14 15 16

test

valeur d'isolement 040 K MENU TEST

valeur d'isolement 040 K MENU TEST

XL308/316
MERLIN GERIN
vigilohm system XL316
test

XL308/316
MERLIN GERIN
vigilohm system XL308c
test

1
9

10 11 12 13 14 15 16
1
9
2
3

10 11 12 13 14 15 16

test/reset

test/reset

XRM XD312
MERLIN GERIN
XD312
test

XD308c
MERLIN GERIN
XD308c

XRM
P12 P50 P100

XD312
MERLIN GERIN
XD312
test

reset

MERLIN GERIN
RM 10N

reset

P12

P50 P100

MERLIN GERIN
RM 10N

level 3: automatic fault detection, locating and measurement level 4: automatic fault detection, locating and measurement with transmission to a supervisor.

13

Vigilohm: presentation

Vigilohm System: choosing a communication interface


the power of a communicating system
The power of the Vigilohm System lies in the capacity it offers for communication between all its devices, thereby ensuring insulation monitoring and complementary functions such as automatic locating of faults or the anticipation of their occurrence. In addition, the Vigilohm System is capable of communicating with a supervisor or a PLC, i.e. it can both transmit data to and receive data from such units. The transfer of information takes place: c via the internal Vigilohm System bus for communication between the devices; c via the external JBUS for communication with a supervisor or PLC. In both cases, the use of an internal or external bus requires a communication interface.

four interfaces
The Vigilohm System offers four interfaces: c the XLI200 interface, for the transmission of information from the insulation monitoring device and XD308C detectors to a supervisor or PLC via JBUS. In this way, a PC can access information concerning the presence of faults and the identification of the faulty circuit. This interface cannot be used with XL308/316 or XML308/316 devices and connects only to the XM300C and XD308C (the XLI200 cannot be used with XML monitoring-locating devices or with XL locating devices). c the XLI300 interface, for the transmission of measurements and measurement parameters from the XM300C and XD308C devices to a supervisor. This interface is used on single busbar installations. The

exclusion of other insulation monitoring devices found on the same installation is managed automatically; c the XTU300 interface, for communication between the Vigilohm System and a supervisor, like the XLI300 interface. This interface is required for installations with multiple busbars and bus coupler circuit breakers. It manages the exclusion of other insulation monitoring devices found on the same installation and the link between the locators and their corresponding insulation monitoring devices; c the XAS interface, indispensable for the operation of the communication bus in the absence of one of the three other interfaces.

interface selection table


IMD associated only with XD308C communicating detectors, whatever the installation configuration ---XLI200 one XML308/316 device IMD with at least 1 locator + 1 set of busbars IMD with a least 1 locator + several sets of busbars with bus coupling XTU300 XTU300
supervisor or PLC MV/LV MV/LV XLI300 XML308 XM300c

without supervision with supervision


E20791

---XLI300
E20790A

XAS XLI300

MV/LV

MV/LV

XAS

XML308

XM300c

XL308
XL308

One set of busbars without supervisor


DB100957 E20792

One set of busbars with supervisor

supervisor or PLC MV/LV MV/LV XTU300 XML308 XM300c

supervisor or PLC MT/BT MT/BT

XM300C

XM300C

XLI200

XD308C

XL308

XD308C

Several sets of busbars with bus coupling and with or without supervisor

application of the measurement voltage internal Vigilohm System bus JBUS bus

14

Vigilohm: presentation

Vigilohm System: two examples of installations


E20788

MV/LV

MV/LV

automatic fault locating with or without supervision


The following examples cover two typical installation configurations with insulation monitoring and fault locating systems. Example 1: c automatic fault locating with local display. The use of an XM200 insulation monitoring device together with XD301 and XD312 detectors represents the typical case providing basic detection and automatic locating of insulation faults on the main feeders as well as on certain secondary feeders. Fault locating can be fine-tuned using an XRM mobile receiver and a current probe to determine the exact location of the fault on the faulty circuit. The auto-exclusion of other XM200 insulation monitoring devices is controlled by the circuit breaker position indication contacts.

XM200

XM200

XD312

XD301 XRM

XD301

E20786

supervisor or PLC MV/LV MV/LV

XTU300

XML316

XML308

XM300c

XL308

Example 2: c measurement and automatic fault locating with local and centralised display, for an installation with more than one set of busbars and a bus coupling circuit breaker. The measurement of the insulation resistance on the main feeders is provided in addition to fault detection with automatic locating (XL308/316 and XML308/316). The secondary feeders are monitored simply by an XD312/301 detector or by an XD308C detector that communicates detected faults to the supervisor (via the XTU300 interface). The architecture of the installation (several sources and sets of busbars) makes it necessary to use an XTU300 interface to handle the exclusion of other insulation monitoring devices and the link between the locators and their corresponding insulation monitoring devices.

XD312

XD308c

XRM

application of the measurement voltage internal Vigilohm System bus JBUS bus

15

16

insulation monitoring

Vigilohm 2/ functions and characteristics


page choosing an insulation monitoring device for different types of installations and associated functions Vigilhom System XM300C insulation monitoring device XL308 and XL316 insulation fault locators XML308 and XML 316 monitoringlocating devices XD308C communicating automatic insulation fault detector XLI200, XLI300, XTU300, XAS communication interfaces XM200 insulation monitoring device XD301 and XD312 automatic insulation fault detectors XRM mobile fault locating receiver and current probes Vigilohm TR22A and TR22AH insulation monitoring devices EM9 and EM9B insulation monitoring devices EM9BV insulation monitoring device EM9T insulation monitoring device TR5A insulation monitoring device SM21 insulation monitoring device mobile fault locating kit XGR + XRM + probes toroids auxiliaries 18 20 22 24 26 28 29 30 32 33

34 35 36 37 38 39 40 41 43

17

Vigilohm: functions and characteristics

choosing an insulation monitoring device for different types of installations


044147 044148

installation characteristics (1)


device
IT system for the entire installation
Continuity of supply is the requirement that most often leads designers to chose the IT system for an electrical installation. This requirement may apply to the entire installation (e.g. chemical process plant, steel plant, etc.). Such an installation requires continuous monitoring of the insulation level.
E27341

XM200

XM300C

MV/LV

P1 IMD

L1 L2 L3 N

E27336

E27427

MV/LV

PHT 1000
PHT 1000 IMD

IMD

440 to 1000 V AC* (1) 500 to 1200 V DC*


*with PHT 1000 subassembly

E27343

MV/LV

L1 L2 L3 N
IMD

i 440 V AC (1) i 500 V DC

i 440 V AC (1) i 500 V DC

L+

IT system for part of an installation


E27344

E27345

The requirement for continuity of supply may apply to only a part of an installation, for example a single shop or plant, or a circuit subject to special conditions (safety lighting). In this case, it is recommended to use the IT system for this part of the installation, whatever the system used for general distribution.

MV/LV

TN or TT

LV/LV

L1 L2 L3 N IT L1 L2 L3 N

i 440 V AC

i 440 V AC

IMD

MV/LV

TN or TT L1 L2 L3 LV/LV IT control/monitoring

machine tool or robot

IMD

IT system for DC installations


In many cases, the use of direct current corresponds to a need for continuity of supply. The use of an IT system and insulation monitoring is therefore consistent with this choice.
500 V
E27337 E27338

500 to 1200 V
E27339

TR5A
+

i 500 V DC
+ IMD

i 500 V DC 500 to 1200 V DC*


*with PHT 1000 subassembly

IMD

PHT 1000 IMD

off-line insulation monitoring


The use of motors in industrial processes creates a further need for insulation monitoring. By checking the insulation with power off, the presence of insulation faults can be determined before starting motors (fire pumps, smoke extractors, etc.). It is also possible to prevent motor starting automatically if the insulation resistance is below a certain threshold.
E27346

L1 L2 L3

IMD

(1) Phase-to-phase voltage with IMD connected to one phase. Multiply these values by e if IMD is connected to neutral. (2) Installation without frequency converter.

18

044149

041850

043274

042578

042580

042580

042582

017422

051346

042581

XML 308/316

TR22A

TR22AH

EM9

EM9B

EM9BV

EM9T

TR5A

SM21

i 1 000 V AC
(1)

with P1 subassembly

440 to 1000 V AC* (1) 500 to 1200 V DC*


*with PHT 1000 subassembly

i 440 V AC (1) i 500 V DC

i 440 V AC (1)
(2)

i 440 V AC (1)
(2)

i 440 V AC

i 440 V AC

i 440 V AC

i 440 V AC

i 440 V AC

i 440 V AC

i 220 V AC

i 500 V DC 500 to 1200 V DC*


*with PHT 1000 subassembly

i 420 V DC

i 690 V AC

19

Vigilohm: functions and characteristics

choosing an insulation monitoring device and associated functions


044147 044148

installation characteristics
device
injected signal

XM200
2.5 Hz

XM300C
2.5 Hz

IT system for the entire installation


E27328

MV/LV HV/MV MV/LV

voltage (1)

440 to 1000 V AC i 400 V AC

(2)

with rectifiers

440 to 1000 V AC i 440 V AC

(2)

for hospitals

i 440 V AC

IT system for part of an installation


E27329

MV/LV

LV/LV

high insulation level low insulation level control and monitoring of machines

i 440 V AC i 440 V AC i 220 V AC

DC installation
E27330

24 to 420 V DC i 500 V DC

500 to 1200 V DC

(2)

off-line monitoring (LV motors)


E27331

i 690 V AC
M

communication functions
insulation resistance measurement
E27332

measurement display prevention indication insulation fault indication

fault locating
E27333

manual automatic automatic + fault measurement

(4) (6)

(4) (7) (8)

communication with supervisor


E27335

external BUS

via JBUS communication bus (and interfaces)


(1) Phase-to-phase voltage with IMD connected to one phase. Multiply these values by e if IMD is connected to neutral. (2) With PHT 1000 subassembly.
(3) With P1 subassembly. (4) With XRM mobile receiver. (5) With XRM mobile receiver + XGR signal generator

20

044149

041850

043274

042578

042580

042580

042582

017422

051346

XML 308/316
2.5 Hz

042581

TR22A
DC

TR22AH
DC

EM9
DC

EM9B
DC

EM9BV
DC

EM9T
DC

TR5A
NONE

SM21
DC

(2)

(3)

(2)

(9)

(2)

(4) (7) (8)

(5)

(5)

(5)

(5)

(5)

(5)

(5)

(6) With XD301/312 detector. (7) With XD301/312 detector or communicating XD308C detector. (8) With XL308/316 locator. (9) Remote test possible.

21

Vigilohm: functions and characteristics

communicating Vigilohm System XM300C insulation monitoring device


044148

basic function: overall insulation monitoring


The XM300C provides overall insulation monitoring of electrical installations by injecting a low-frequency AC voltage between the installation and earth.

communication
Communication with the supervision system. The XLI300 and XTU300 interfaces allow monitoring devices + locators + communicating detectors to exchange information with a supervision system via JBUS protocol. The XLI300 and XTU300 interfaces connect to the Vigilohm System bus and allow timestamping of insulation monitoring events.

main functions
c measurement: v insulation resistance, v earth leakage capacitance; c indications: v satisfactory insulation resistance (green light on bargraph), v drop in insulation resistance: below prevention threshold (orange light on bargraph and relay actuated), below fault threshold (red light on bargraph and two relays actuated, including one with a failsafe feature), v transient faults (orange light); c display: v measurements, v events detected by any XL308/316 locators connected. All this data is accessible locally on the LCD screen of the insulating monitoring device and remotely via the Vigilohm System bus.

configuration management
On installations with a number of insulation monitoring devices installed to cover variable configurations, only one device at a time can be allowed to inject a voltage between earth and the installation downstream of the incoming circuit breaker. For this reason, the system must manage the exclusion of other connected insulation monitoring devices. In addition, each locator must identify the monitoring device from which it is to capture the signal. The exclusion of monitoring devices and their identification by the locators is handled in one of the following manners: c by the XTU300 interface for multiple busbar installations; c by the XLI300 interface for single busbar installations. In both cases, the circuit breaker position indication contacts are wired to the all-ornothing inputs of the XM300C or XML308/316. If only XD308C detectors are associated with the XM300C, monitoring device exclusion is handled by the XLI200 interface.

additional functions with other devices


Locating of faulty circuits This function is obtained by using the XM300C together with: c XL308 and XL316 locators connected to 8 or 16 toroids. They are linked to the XM300C by the Vigilohm System bus; c XD308C communicating detectors. They are linked to the XM300C by the Vigilohm System bus, and connected to the toroids placed on the circuits to be monitored; c XD301 and XD312 detectors connected to the toroids placed on the circuits to be monitored; c an XRM mobile receiver and a current probe to fine-tune the automatic locating results. All these devices can be combined on a given installation. Distributed measurements This function is provided by combining an XM300C monitoring device (or an XML308/316 monitoring-locating device) with XL308 or XL316 locators. These locators measure the insulation resistance and the earth leakage capacitance of each of the circuits. They have a fault alarm threshold that can be set to a different levels for each channel.
test 5 6 7 8 1 3 1 4 1 5 1 6 test/reset

standards
The XM300C insulation monitoring device complies with the following standards: c IEC 364, parts 4 and 5; c class CPI/XA of UTE C 63-080. It is implemented in accordance with standard NF C 15-100 paragraph 413.4; c IEC 61557-8.

DB100958

interfaces

MERLIN GERIN
v ig ilo h m s y s te m
XAS

MERLIN GERIN
v ig ilo h m s y s te m
X L I3 0 0

MERLIN GERIN
v ig ilo h m s y s te m
XTU300

f a

f a

f a

installation and connection


c horizontal flush mounting on the front face of a cubicle or enclosure; c easy mounting in Prisma enclosures using the corresponding mounting plates and front plates that come with the appropriate cut-outs; c the devices are interconnected by shielded cables (double 0.75 mm2 twisted pairs). The resistance between the two most distant points must not exceed 12 . The coupling capacitance between pairs must not exceed 250 nF; c if no XTU300 or XLI300 interface is included, operation of the Vigilohm System bus will require an XAS interface.

insulation monitoring XML308/316


MERLIN GERIN
v ig ilo h m s y s te m
X M L 3 16
test 1 2 3 4 5 6 7 8 1 3 1 4 1 5 1 6

XM300c
MERLIN GERIN
v ig ilo h m s y s te m
XM 300c
test

1 0

1 1

1 2

valeur d'isolement 040 K MENU TEST

valeur d'isolement 040 K MENU TEST

P 100

insulation fault detection and locating

MERLIN GERIN
v ig ilo h m s y s te m
XD308c

MERLIN GERIN
v ig ilo h m s y s te m
XL316

test

MERLIN GERIN
v ig ilo h m s y s t e m

MERLIN GERIN
1 2 3
v ig ilo h m s y s t e m

8
on
9 1 0 1 1 1 2

X D 301
te s t

X D 312

te s t

9
test

reset

10
re s e t

11

12

re s e t

P 5 0
5 0 5 0 7 5 0 5 3 6

o n

P 1 2

MERLIN GERIN
v ig id ix

R M

1 0 N

sensors
MERLIN GERIN
G O

S1

S2

MERLIN GERIN

S1

MERLIN GERIN
v ig ir e x - v ig id ix

S2

MERLIN GERIN
v ig ir e x - v ig id ix

MERLIN GERIN
v ig ir e x - v ig id ix

22

auxiliaries
Cardew surge limiter: page 43. ZX limiting impedance to create an impedance-earthed neutral: page 44. PHT1000 subassembly if the device is to be used on 1000-1700 V installations: page 44.

restrictions for use


The XM300C operates by injecting lowfrequency signals (2.5 Hz). It should not be used for circuits that include variable speed drives if this equipment continuously generates a signal with a similar frequency ( 5 Hz).

E19527

type of installation to be monitored


MERLIN GERIN
XM300C

AC or mixed AC/DC IT systems


test

DC or rectified IT systems

phase-to phase voltage with XM300C connected to neutral with XM300C connected to phase frequency size of installation line voltage

< 760 or 1700 V AC (1) < 440 or 1000 V AC (1) 45-400 Hz 0 to 30 km of cable < 500 or 1200 V DC (1)

electrical characteristics
1 7 6 2 4 5 3

1. display indicating: c the value of the overall insulation resistance R; c other information as selected via function keys. 2. red self-test light, indicating internal XM300C faults. 3. light indicating that a transient fault has occurred. 4. 5 lights indicating the insulation level. 5. instruction manual stored in a drawer on the front face 6. sealable cover ensuring tamperproof settings. 7. function keys for: c accessing earth coupling capacitance readings c setting thresholds; c accessing three last values of transient insulation faults; c remote access to faults detected by XL308 or XL316 detectors; c choice of language.

ohmmeter range for insulation resistance readings signalling number of thresholds threshold settings 1st threshold (prevent.) 2nd threshold (fault) dielectric strength auxiliary supply voltage 50/60 Hz

auxiliary supply voltage tolerances maximum device consumption measurement voltage measurement current 50 Hz/DC impedance device test failsafe feature (2) changeover output contact breaking capacity of output contacts

circuit breaker position indication contacts (3): (voltage and current supplied by XAS XLI or XTU interfaces) connection cross-sections

digital 0.1 to 999 k 2 (sealable settings) 1 to 299 k 0.2 to 99.9 k 2500 V 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC - 15 % to + 10 % 30 VA 6V 5 mA max 22 k self-test and manual test as standard quantity 3 (1 failsafe) AC 400 V p. f. = 0.7 3A 230 V p. f. = 0.7 5A DC 220 V L/R = 1 ms 0.45 A 120 V L/R = 1 ms 0.65 A 48 V L/R = 1 ms 2.5 A 24 V L/R = 1 ms 10 A voltage supplied 24 V max. current supplied 10 mA (short-circuit) rigid conductors flexible conductors 1 to 1.5 mm2 0.75 to 1.5 mm2

mechanical characteristics
weight sheet-metal case (horizontal mounting) degree of protection 3.5 kg disconnectable screw terminal block flush mounting IP 30 supervisor English/French protected by access code or sealable cover operating - 5 C to + 55 C storage - 25 C to + 70 C

other characteristics
interfacing possible with multi-language display tamperproof settings temperature range

(1) The upper limit is extended to the second value by adding a PHT1000 subassembly. (2) Failsafe feature: a failsafe relay operates in the event of an accidental interruption of auxiliary power or a fault. (3) This contact is an auxiliary switch mounted on the circuit breaker and used to indicate its operating status.

23

Vigilohm: functions and characteristics

communicating Vigilohm System XL308 and XL316 insulation fault locators


044145

basic function: local insulation fault monitoring


Used together with an XM300C or XML308/ 316 monitoring device, XL308 and XL316 locators monitor the insulation of 8 or 16 individual circuits and automatically locate any faults.

communication
Faults detected by XL308/316 locators can be displayed on the insulation monitoring device associated with the locator. The information transmitted to the insulation monitoring device can be transmitted to a supervisor via an XLI300 or XTU300 interface connect to the Vigilohm System bus.

main functions
c measurement: v insulation resistance of each monitored circuit, v earth leakage capacitance of each monitored circuit; c indications: v satisfactory insulation resistance (green light), v drop in insulation resistance below fault threshold (red light and two relays actuated, including one with a failsafe feature). The fault threshold is adjustable for each of the 8 or 16 channels corresponding to the monitored circuits, v transient faults on each of the monitored circuits; c display: v faulty circuits are indicated by the corresponding LEDs (8 or 16 depending on the model), v a flashing LED indicates a transient fault on the corresponding circuit.

standards
XL308 and XL316 locators comply with the following standards: c IEC 364, parts 4 and 5; c class DLD/M of UTE C 63-080; They are implemented in accordance with standard NF C 15-100 paragraph 413.4; c IEC 61557-8.

toroids
XL308 and XL316 locators operate with type A and OA toroids.

installation and connection


c horizontal flush mounting on the front face of a cubicle or enclosure; c easy mounting in Prisma enclosures using the corresponding mounting plates and front plates that come with the appropriate cut-outs; c the devices are interconnected by shielded cables (double 0.75 mm2 twisted pairs). The resistance between the two most distant points must not exceed 12 . The coupling capacitance between pairs must not exceed 250 nF; c connection of toroids using twisted, shielded cable (1 pair); c if no XTU300 or XLI300 interface is included, operation of the Vigilohm System bus will require an XAS interface.

DB100959

interfaces

MERLIN GERIN
v ig ilo h m s y s te m
XAS

MERLIN GERIN
v ig ilo h m s y s te m
X L I3 0 0

MERLIN GERIN
v ig ilo h m s y s te m
XTU300

f a

f a

f a

insulation monitoring

MERLIN GERIN
v ig ilo h m s y s te m
X M L 3 16

MERLIN GERIN
v ig ilo h m s y s te m
XM 300c

test

test

1 0

1 1

1 2

1 3

1 4

1 5

1 6

valeur d'isolement 040 K MENU TEST

valeur d'isolement 040 K MENU TEST

insulation fault detection and locating


XD301
MERLIN GERIN
v ig ilo h m s y s t e m

XD312
MERLIN GERIN
1 2 3
v ig ilo h m s y s t e m

XRM

XD308c XL308 / 316


MERLIN GERIN
v ig ilo h m s y s te m
XD308c

MERLIN GERIN
v ig ilo h m s y s te m
XL316
test

test

8
on
9 1 0 1 1 1 2 1 3 1 4 1 5 1 6

X D 301
te s t

X D 312

te s t

9
test

reset

10
re s e t

11

12

re s e t
test/reset

P 5 0
5 0 5 0 7 5 0 5 3 6

o n

P 1 2

P 1 0 0

MERLIN GERIN
v ig id ix

R M

1 0 N

sensors
MERLIN GERIN
G O

S1

S2

MERLIN GERIN

S1

MERLIN GERIN
v ig ir e x - v ig id ix

S2

MERLIN GERIN
v ig ir e x - v ig id ix

MERLIN GERIN
v ig ir e x - v ig id ix

24

locator electrical characteristics


ohmmeter range for insulation resistance readings signalling signalling threshold and setting range (per channel) polling time device test dielectric strength auxiliary supply voltage

XL308

XL316

fault threshold

50/60 Hz

auxiliary supply voltage tolerances maximum device consumption indicator and output relay output relays breaking capacity of output contacts

AC 400 V p.f. = 0.7 230 V p.f. = 0.7 DC 220 V L/R = 1 ms 120 V L/R = 1 ms 48 V L/R = 1 ms 24 V L/R = 1 ms rigid conductors flexible conductors

link with insulation monitoring device connection crosssections

digital 0.1 to 999 k 8 lights (1 per channel) 16 lights (1 per channel) 1 0.2 to 99.9 k 15 seconds per channel self-test and manual test 2500 V 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC - 15 % to + 10 % 30 VA local or from insulation monitoring device 2 (1 failsafe) 3A 5A 0.45 A 0.65 A 2.5 A 10 A via 4-wire communication bus 1 to 1.5 mm2 0.75 to 1.5 mm2 3.5 kg horizontal mounting disconnectable screw terminal block A and OA (XC compatible) - 5 C to + 55 C - 20 C to + 70 C

mechanical characteristics
weight sheet-metal case

other characteristics
types of toroid to be used temperature range operating storage

(1) The upper limit is extended to the second value by adding a PTH1000 subassembly. The same voltage limits apply to both the XL308 and the XL316.

MERLINGERIN
XL31 6

1 2 3 4 5 6 7 8 9 10 1 12 13 14 15 16 1

F ! /

test/rese t

5 6 4 3

1. display indicating measured insulation resistance and earth coupling capacitance value. 2. light indicating measurement units for displayed value (k, F, etc.). 3. red self-test light, indicating device faults. 4. yellow light indicating that a transient fault has occurred. 5. 2 lights indicating the insulation level: c green light: normal; c red light: insulation resistance below fault threshold on one of the circuits. 6. instruction manual stored in a drawer on the front face 7. function keys for: c accessing earth leakage capacitance readings; c setting thresholds; c accessing three last values of transient insulation faults. 8. sealable cover ensuring tamperproof settings. 9. lights indicating faulty circuits.

DB100954

25

Vigilohm: functions and characteristics

communicating Vigilohm System XML308 and XML316 monitoring-locating devices


basic function: overall and individual circuit insulation monitoring
XML308 and XML316 monitoring-locating devices combine the functions of: c the XM300C insulation monitoring device; c XL308 or XL316 insulation fault locators. They monitor the insulation of: v the overall installation by injection of a lowfrequency AC voltage between the installation and earth, v 8 or 16 individual circuits via detection toroids.
044149

communication
Communication with the supervision system. The XLI300 and XTU300 interfaces allow monitoring devices + locators + communicating detectors to exchange information with a supervision system via JBUS protocol. The XLI300 and XTU300 interfaces connect to the Vigilohm System bus and allow timestamping of insulation monitoring events.

configuration management
On installations with a number of insulation monitoring devices installed to cover variable configurations, only one device at a time can be allowed to inject a voltage between earth and the installation downstream of the incoming circuit breaker. For this reason, the system must manage the exclusion of other connected insulation monitoring devices. In addition, each locator must identify the monitoring device from which it is to capture the signal. The exclusion of monitoring devices and their identification by the locators is handled in one of the following manners: c by the XTU300 interface for multiple busbar installations with bus coupling; c by the XLI300 interface for single busbar installations. In both cases, the circuit breaker position indication contacts are wired to the all-ornothing inputs of the XM300C or XML308/316.

main functions
c measurement: v insulation resistance of the overall installation and each monitored circuit, v earth leakage capacitance of the overall installation and each monitored circuit; c indications: v satisfactory insulation resistance (green light), v drop in insulation resistance: for the overall installation, below prevention threshold (orange light and relay actuated), for the overall installation and each monitored circuit, below adjustable fault threshold (red light and two relays actuated, including one with a failsafe feature), v transient faults on the overall installation (orange light), with storage in memory of the three last values, v faulty circuit by 8 or 16 indicator lights (1 for each circuit); c display: v measurements, v events detected by any XL308/316 locators connected. All this data is accessible locally on the LCD screen of the insulating monitoring device and remotely via the Vigilohm System bus.
DB100958

standards
The XML308 and XML316 devices comply with the following standards: c IEC 364, parts 4 and 5; c class CPI/XA and DLD/M of UTE C 63-080. They are implemented in accordance with standard NF C 15-100 paragraph 413.4; c IEC 61557-8.

toroids
The XML308 and XML316 devices operate with type A and OA toroids. They are also compatible with type XS toroids.

interfaces

MERLIN GERIN
v ig ilo h m s y s te m
XAS

MERLIN GERIN
v ig ilo h m s y s te m
X L I3 0 0

MERLIN GERIN
v ig ilo h m s y s te m
XTU300

f a

f a

f a

additional functions with other devices


It is possible to monitor more than 8 or 16 circuits by adding any of the following devices: c XL308 or XL316 locators that measure the insulation resistance on each additional circuit; c XD308C communicating detectors that automatically detect the faulty circuit and communicate via an XLI300 or XTU300 interface; c XD301 and XD312 detectors that automatically detect the faulty circuit and provide local indications. The communicating detectors and locators are connected to the XML308/316 via the Vigilohm System bus.

installation and connection


c horizontal flush mounting on the front face of a cubicle or enclosure c easy mounting in Prisma enclosures using the corresponding mounting plates and front plates that come with the appropriate cutouts; c the devices are interconnected by shielded cables (double 0.75 mm2 twisted pairs). The resistance between the two most distant points must not exceed 12 . The coupling capacitance between pairs must not exceed 250 nF; c connection of toroids using twisted, shielded cable (1 pair); c if no XTU300 or XLI300 interface is included, operation of the Vigilohm System bus will require an XAS interface.

insulation monitoring XML308/316


MERLIN GERIN
v ig ilo h m s y s te m
X M L 3 16
test 1 2 3 4 5 6 7 8 1 3 1 4 1 5 1 6

XM300c
MERLIN GERIN
v ig ilo h m s y s te m
XM 300c
test

1 0

1 1

1 2

valeur 040 K TEST

d'isolement MENU

valeur 040 K TEST

d'isolement MENU

P 100

insulation fault detection and locating

MERLIN GERIN
v ig ilo h m s y s te m
XD308c

MERLIN GERIN
v ig ilo h m s y s te m
XL316
test

test

MERLIN GERIN
v ig ilo h m s y s t e m

MERLIN GERIN
1 2 3
v ig ilo h m s y s t e m

8
on
9 1 0 1 1 1 2 1 3 1 4 1 5 1 6

X D 301
te s t

X D 312

te s t

9
test

reset

10
re s e t

11

12

re s e t
test/reset

P 5 0
5 0 5 0 7 5 0 5 3 6

o n

P 1 2

MERLIN GERIN
v ig id ix

R M

1 0 N

sensors
MERLIN GERIN
G O

S1

S2

MERLIN GERIN

S1

MERLIN GERIN
v ig ir e x - v ig id ix

S2

MERLIN GERIN
v ig ir e x - v ig id ix

MERLIN GERIN
v ig ir e x - v ig id ix

26

auxiliaries
Cardew surge limiter: page 43. ZX limiting impedance to create an impedance-earthed neutral: page 44. PHT1000 subassembly if the device is to be used on 1000-1700 V installations: page 44.

restrictions for use


The XML308/316 operates by injecting lowfrequency signals (2.5 Hz). It should not be used for circuits that include variable speed drives if this equipment continuously generates a signal with a similar frequency ( 5 Hz).

E19502

type of installation to be monitored


MERLIN GERIN
XML316

AC or mixed AC/DC IT systems


test

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

DC or rectified IT systems

phase-to phase voltage with XML308/316 connected to neutral with XML308/316 connected to phase frequency size of installation line voltage

< 760 or 1700 V AC (1) < 440 or 1000 V AC (1) 45-400 Hz 0 to 30 km of cable < 500 or 1200 V DC (1)

electrical characteristics
9 8 10 1 7 2 3 6 4 5

1. display indicating measurements concerning the overall installation or each monitored circuit, and information concerning the device settings; 2. red self-test light, indicating device faults. 3. light indicating that a transient fault has occurred. 4. 5 lights indicating the insulation level. 5. instruction manual stored in a drawer on the front face 6. sealable cover ensuring tamperproof settings. 7. function keys for: c accessing earth coupling capacitance readings; c setting thresholds; c accessing three last values of transient insulation faults; c reading measurements made on individual circuits by the internal locator; c remote access to faults detected by XL308 or XL316 detectors; c choice of language. 8. two indicator lights continuously display the insulation level of the overall installation. 9. 8 or 16 indicating lights indicate faulty circuits. 10. light indicating that a transient fault has occurred.

ohmmeter range for insulation resistance readings signalling for overall instal. for each circuit threshold settings for overall instal. instal. and circuits number of toroids that can be connected (1 per channel)

digital 0.1 to 999 k number of thresholds 2 (sealable settings) number of thresholds 1 (sealable settings) 1st threshold (preven.) 1 to 299 k 2nd threshold (fault) 0.2 to 99.9 k XML308 8 XML316 16 polling time 15 s. per channel dielectric strength 2500 V auxiliary supply voltage 50/60 Hz 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC auxiliary supply voltage tolerances -15 % to +10 % maximum device consumption 30 VA measurement voltage 6V measurement current 5 mA max. 50 Hz/DC impedance 22 k device test self-test and manual test failsafe feature (2) as standard changeover output contact quantity 3 (1 failsafe) breaking capacity of AC 400 V p.f. = 0.7 3A output contacts 230 V p.f. = 0.7 5A DC 220 V L/R = 1 ms 0.45 A 120 V L/R = 1 ms 0.65 A 48 V L/R = 1 ms 2.5 A 24 V L/R = 1 ms 10 A circuit breaker position indication contacts (3): voltage supplied 24 V (voltage and current supplied by XAS, max. current supplied 10 mA (short-circuit) CLI or XTU interfaces) connection cross-sections rigid conductors 1 to 1.5 mm2 flexible conductors 0.75 to 1.5 mm2

mechanical characteristics
weight sheet-metal case (horizontal mounting) degree of protection 4.5 kg disconnectable screw terminal block flush mounting IP 30 A, OA (XS compatible) supervisor English/French protected by access code or sealable cover operating - 5 C to + 55 C storage - 20 C to + 70 C

other characteristics
types of toroid to be used interfacing possible with multi-language display tamperproof settings temperature range

(1) The upper limit is extended to the second value by adding a PHT1000 subassembly. (2) Failsafe feature: a failsafe relay operates in the event of an accidental interruption of auxiliary power or a fault. (3) This contact is an auxiliary switch mounted on the circuit breaker and used to indicate its operating status.

27

Vigilohm: functions and characteristics

communicating Vigilohm System XD308C communicating automatic insulation fault detector


044143

electrical characteristics
type of installation to be monitored operating threshold polling time fault indications operating tests functions tested clearing of memorised faults auxiliary supply voltage 50/60 Hz low voltage AC 45-400 Hz / DC 2.5 mA at 2.5 Hz (1) 20 s per channel 8 indicator lights local indicator lights and electronics local reset on front face or remote reset from supervisor 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC - 15 % to + 10 % 6 VA 2500 V via 4-wire Vigilohm System bus 0.6 kg vertical mounting IP 30 - 25 C to + 70 C - 5 C to + 55 C A (N and O compatible)

E19504

MERLIN GERIN
XD308C

test

reset

auxiliary supply voltage tolerances consumption dielectric strength connection with insulation monitoring device

mechanical characteristics
1 4 5 3 2 6

weight metal case with insulated front degree of protection flush mounting

1. lights indicating the faulty circuit. 2. power on 3. general fault indicator light. 4. test button for indicator lights. 5. device internal fault indication (self-test) 6. self-test fault indicator light.

other characteristics
temperature range types of toroid to be used storage operating

(1) The operating threshold of the XD308C detectors is not adjustable. These devices are designed to detect low-impedance faults. The detection threshold varies between 100 and 2 k depending on the characteristics of the installation.

basic function: local insulation fault detection


The XD308C provides 3 functions: c detection of insulation faults; c automatic locating of the faulty circuit, identified by the number of the illuminated indicating light; c communication of this information to an XLI200 or XLI300 or XTU300 interface for transmission to a supervisor or PLC.
DB100959

installation and connection


c live parts in a disconnectable metal case; c vertical mounting on front plate; c tunnel terminals for 1.5 mm2 wires; c the devices are interconnected by shielded cables (double 0.75 mm2 twisted pairs). The resistance between the two most distant points must not exceed 12 . The coupling capacitance between pairs must not exceed 250 nF; c if no XTU300 or XLI300 interface is included, operation of the Vigilohm System bus will require an XAS interface.

operation
MERLIN GERIN
v ig ilo h m s y s te m
XAS

MERLIN GERIN
v ig ilo h m s y s te m
X L I3 0 0

MERLIN GERIN
v ig ilo h m s y s te m
XTU300

f a

f a

f a

MERLIN GERIN
v ig ilo h m s y s te m
X M L 3 16

MERLIN GERIN
v ig ilo h m s y s te m
XM 300c

test

test

1 0

1 1

1 2

1 3

1 4

1 5

1 6

valeur d'isolement 040 K MENU TEST

valeur d'isolement 040 K MENU TEST

XD301
MERLIN GERIN
v ig ilo h m s y s t e m

XD312
MERLIN GERIN
1 2 3
v ig ilo h m s y s t e m

XRM

XD308c XL308 / 316


MERLIN GERIN
v ig ilo h m s y s te m
XD308c

MERLIN GERIN
v ig ilo h m s y s te m
XL316
test

c XD308C insulation fault detectors are fixed receivers connected to XM300C or XML308/ 316 insulation monitoring devices via the Vigilohm System communication bus; c the XD308C detector, with 8 channels connected to a maximum of 12 toroids installed on different circuits of the installation, includes the following features on its front face: v 8 fault indicator lights corresponding to the 8 channels, v 1 general fault indicator light signalling that a fault has occurred, v 1 light indicating the operating status of the device, v 2 pushbuttons (self-test and reset).

toroids
XD308C insulation fault detectors operate with type A and OA toroids. They are also compatible with the older type N and O toroids.

test

8
on
9 1 0 1 1 1 2 1 3 1 4 1 5 1 6

X D 301
te s t

X D 312

te s t

9
test

reset

10
re s e t

11

12

re s e t
test/reset

P 5 0
5 0 5 0 7 5 0 5 3 6

o n

P 1 2

P 1 0 0

MERLIN GERIN
v ig id ix

R M

1 0 N

MERLIN GERIN
G O

S1

S2

MERLIN GERIN

S1

MERLIN GERIN
v ig ir e x - v ig id ix

S2

MERLIN GERIN
v ig ir e x - v ig id ix

MERLIN GERIN
v ig ir e x - v ig id ix

28

Vigilohm: functions and characteristics

communicating Vigilohm System XLI200, XLI300, XTU300 and XAS communication interfaces
044146

use
When two or more communicating devices (XM300C, XML308/316, XL308/316 or XD308C) are used or when communication with a supervisor is required, it is necessary to connect one (and only one) interface to the communication bus. If no XTU300 or XLI300 interface is included, operation of the Vigilohm System bus will require an XAS interface.

functions
The interface allows communication between the Vigilohm System and a supervisor or PLC using a JBUS type protocol (except X25). It transmits the information provided by the Vigilohm System: c prevention and fault alarms from XM300C or XML308/316 monitoring devices (only XM300C for XLI200); c fault alarms from XML308/316 or XM308/316 locators (except XLI200); c insulation resistance and capacitance measurements; c threshold settings; c fault alarms and faulty circuit identification from XD308C detectors. The interface also allows the thresholds to be set form the supervisor.

device function
interface between the Vigilohm System bus and a supervisor or PLC power supply to Vigilohm System bus operates with monitoring device XM300C mon.-loc. device XML308/316 locator XL308/316 detector XD301/312 XD308C maximum configuration monitoring device XM300C and/or XML308/316 locator XL308/316 detector XD308C

XLI200
c c c

XLI300
c c c c c c 4 8 8

XTU300 XAS
c c c c c c 4 8 8 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC c c c c c c c 4 8 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC c c

c 4 (1) 16

electrical characteristics
auxiliary supply voltage 50/60 Hz 220/240 V AC 115/127 V AC 380/415 V AC 220/240 V AC 380/415 V AC 500/525 V AC c c c c

consumption dielectric strength

30 VA 2500 V

mechanical characteristics
weight metal case with insulated front degree of protection degree of protection of front gross net c IP30 IP40 2.228 kg 1.864 kg c 2.228 kg 1.864 kg c 2.228 kg 1.864 kg c

other characteristics
interfacing possible with supervisor JBUS connector communication with other devices temperature range storage operation Sub D 9-pin (not supplied) via 4-wire data bus - 25 C to + 70 C - 5 C to + 55 C c c c c c c c c c c

installation
vertical mounting on front plate c c c 300... 19200 9600 8 none 1 1 c c c 300... 19200 9600 8 none 1 1 c c c 300... 19200 9600 8 none 1 1 29 c c

connection
Vigilohm System bus external bus 1.5 mm2 tunnel terminals RS485 adjustable per fault sub D9 female connector

communication
speed (bauds) data length (bits) parity start bits stop bits
(1) only XM300C.

Vigilohm: functions and characteristics

Vigilohm System XM200 insulation monitoring device


044147

basic function: overall insulation monitoring


The XM200 provides overall insulation monitoring of electrical installations by injecting a low-frequency AC voltage between the installation and earth.

standards
The XM200 insulation monitoring device complies with the following standards: c IEC 364, parts 4 and 5; c class CPI/XA of UTE C 63-080. It is implemented in accordance with standard NF C 15-100 paragraph 413.4; c IEC 61557-8.

main functions
c measurement: v insulation resistance, v earth leakage capacitance; c indications: v satisfactory insulation resistance (green light), v drop in insulation resistance: below prevention threshold (orange light and failsafe relay actuated), below fault threshold (red light and relay actuated), v transient faults (orange light); c display: v measurements accessible locally on the display unit of the device, v value of the last transient fault.

operating voltage
c AC IT systems up to: v 440 V with neutral not distributed, v 760 V with neutral distributed; c DC systems up to 500 V. The XM200 cannot be adapted to installations with higher voltages by connecting it to a PHT1000 subassembly. For higher voltage, use an XM300C.

installation
c horizontal flush mounting on the front face of a cubicle or enclosure; c easy mounting in Prisma enclosures using the corresponding mounting plates and front plates that come with the appropriate cut-outs.

additional functions with other devices


Identification of faulty circuits This function is obtained by using the XM200 together with XD301/XD312 automatic insulation fault detectors. In addition, an XRM mobile receiver and a current probe can be used to determine the exact location of the fault on the faulty circuit.

auxiliaries
Cardew surge limiter: page 43. ZX impedance: page 44.

restrictions for use


The XM200 operates by injecting lowfrequency signals (2.5 Hz). It should not be used for circuits that include variable speed drives if this equipment continuously generates a signal with a similar frequency ( 10 Hz).

E24554

insuation monitoring
XM200
MERLIN GERIN
vigilohm system XM200
test

Sp

Sa
S

menu

ok

test

insulation fault detection and locating

MERLIN GERIN
vigilohm system

1
test

2
5
8

3
6
9

MERLIN GERIN
vigilohm system

XD301

XD312

4
7

test

reset
50507

10 11 12
50536

reset

on
M

P12

P50 P100

MERLIN GERIN
vigidix

RM 10N

sensors
MERLIN GERIN
GO

S1

S2

MERLIN GERIN
PO

S1

S2

MERLIN GERIN
vigirex - vigidix

MERLIN GERIN
vigirex - vigidix

MERLIN GERIN
vigirex - vigidix

30

E19051

type of installation to be monitored


MERLIN GERIN
XM200

AC or mixed AC/DC IT systems


test

i
R C Sp Sa O S k F k k k

menu

ok

test

DC or rectified IT systems

phase-to phase voltage with XM200 connected to neutral with XM200 connected to phase frequency size of installation line voltage

< 760 V AC < 440 V AC 45-400 Hz 0 to 30 km of cable < 500 V DC

electrical characteristics
1 6 2 4 5 3

1. display indicating: c the value of the overall insulation resistance R; c other information as selected via function keys. 2. red self-test light, indicating internal XM200 faults. 3. light indicating that a transient fault has occurred. 4. 3 lights indicating the insulation level. 5. sealable cover ensuring tamperproof settings. 6. function keys for: c accessing earth coupling capacitance readings; c setting thresholds; c displaying the value of the last transient insulation fault; c setting time delays.

ohmmeter range for insulation resistance readings signalling number of thresholds threshold settings 1st threshold (prevent) 2nd threshold (fault) time delay for signalling 3 settings dielectric strength auxiliary supply voltage 50/60 Hz

auxiliary supply voltage tolerances maximum device consumption measurement voltage measurement current 50 Hz/DC impedance device test failsafe feature (1) output contacts changeover breaking capacity of output contacts

connection cross-sections

digital 0.1 to 999 k 2 (sealable settings) 10 to 100 k 0.1 to 20 k 0 s,15 s, 30 s 2500 V 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC - 15 % to +10 % 30 VA variable 25 V max. 3 mA max. 33 k self-test and manual test as standard quantity 2 (1 failsafe) AC 400 V p.f. = 0.7 3A 230 V p.f. = 0.7 5A DC 220 V L/R = 1 ms 0.45 A 120 V L/R = 1 ms 0.65 A 48 V L/R = 1 ms 2.5 A 24 V L/R = 1 ms 10 A rigid conductors 1 to 1.5 mm2 flexible conductors 0.75 to 1.5 mm2 2.5 kg disconnectable screw terminal block flush mounting IP 30 behind sealable cover operating - 5 C to + 55 C storage - 25 C to + 70 C detectors XD301/312 mobile receiver XRM + probes

mechanical characteristics
weight sheet-metal case (horizontal mounting) degree of protection

other characteristics
tamperproof settings temperature range

fault locating with other devices


automatic manual
(1) Failsafe feature: a failsafe relay operates in the event of an accidental interruption of auxiliary power or a fault.

31

Vigilohm: functions and characteristics

Vigilohm System: XD301 and XD312 automatic insulation fault detectors


044144

basic function local fault detection


XD301 and XD312 insulation fault detectors have two functions: c fault detection (with respect to the fault threshold); c automatic locating of the faulty circuit.

installation and connection


c live parts in an insulated case with a sealable transparent cover. Width equal to 8 (XD301) or 12 (XD312) 9 mm width modules; c horizontal flush or surface mounting on DIN rail; c tunnel terminals for 1.5 mm2 wires.

operation
c XD301 and XD312 insulation fault detectors are fixed receivers used with (but not connected to) XM300C, XML308/316 and XM200 insulation monitoring devices. Via measurement toroids, they detect and automatically locate insulation faults c the XD312 detector, with 12 channels connected to a maximum of 12 toroids installed on different circuits of the installation, includes the following features on its front face: v 12 fault indicator lights corresponding to the 12 channels, v a selector to enable or disable latching of transient fault indications until reset; c detector XD301 is a single-channel version designed for use with one measurement toroid.

toroids
XD301 and XD312 insulation fault detectors operate with type A and OA toroids. They are also compatible with the older type N and O toroids.

insulation fault detectors electrical characteristics


1 4 2 5 3 6
test

E19500

XD301

XD312

MERLIN GERIN
XD312

10 11 12
reset

type of installation to be monitored operating threshold polling time fault indications local tests clearing of indications latching of transient fault indications output relay number of contacts breaking capacity AC 400 V p.f. = 0.7 of output contacts 230 V p.f. = 0.7 DC 220 V L/R = 1 ms 120 V L/R = 1 ms 48 V L/R = 1 ms 24 V L/R = 1 ms auxiliary 50/60 Hz supply voltage

3 2 4

1. lights indicating the faulty circuit. 2. selector to enable or disable transient fault indication latching 3. sealable cover. 4. general fault indicator light. 5. test button for indicator lights and output relay. 6. reset button (to clear fault indications).

auxiliary supply voltage tolerances consumption dielectric strength connection with insulation monitoring device

low voltage AC 45-400 Hz / DC 2.5 mA at 2.5 Hz (1) 20 s 20 s per channel 1 indicator light 12 channel indicator lights (+ 1 general) for indicator lights and output relay reset button on device on/off via selector 1 failsafe 3A 5A 0.45 A 0.65 A 2.5 A 10 A 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC - 15 % to + 10 % 6 VA 2500 V none 0.3 kg horizontal mounting IP 30 / IP 20 0.6 kg

mechanical characteristics
weight plastic case degree of protection flush/surface mounting

other characteristics
temperature range storage operating types of toroid to be used toroid for direct connection to case - 25 C to + 70 C - 5 C to + 55 C A, OA (N and O compatible) 30 and 50 mm none type A toroid

(1) The operating threshold of the XD301/312 detectors is not adjustable. These devices are designed to detect low-impedance faults. The detection threshold varies between 100 and 2 k depending on the characteristics of the installation.

32

Vigilohm: functions and characteristics

XRM mobile fault locating receiver and current probes


051350

operation
The XRM mobile receiver, used with a current probe, is mainly intended as an enhancement to automatic fault locating systems. It can be placed at various points along a faulty circuit, capturing the signal emitted by an XM300C, XML308/316 or XM200 insulation monitoring device to determine the exact location of the fault. Three current probes are available, the XM15, XP50 and XP100. The set of live conductors to be tested must have a maximum diameter of 12, 50 and 100 mm respectively.

XRM receiver

display
The XRM receiver displays a number from 0 to 19, corresponding to the insulation level: c 0: no fault; c 19: solid fault (no insulation).
DB101070 PB100471

interfaces
XP15, XP50 and XP100 current probes. Note: the photographs are for information purposes only. There are two types of probes that function in the same way but are different in shape and colour.
DB100959

MERLIN GERIN
v ig ilo h m s y s te m
XAS

MERLIN GERIN
v ig ilo h m s y s te m
X L I3 0 0

MERLIN GERIN
v ig ilo h m s y s te m
XTU300

f a

f a

f a

insulation monitoring
E24555
MERLIN GERIN
v ig ilo h m s y s te m
X M200
test

insulation monitoring

MERLIN GERIN
v ig ilo h m s y s te m
X M L 3 16

MERLIN GERIN
v ig ilo h m s y s te m
XM 300c

test

test

1 0

1 1

1 2

1 3

1 4

1 5

1 6

Sp
S

valeur 040 K TEST

d'isolement MENU

valeur 040 K TEST

d'isolement MENU

menu

ok

test

insulation fault detection and locating


XD30
MERLIN GERIN
v ig ilo h m s y s t e m

insulation fault detection and locating


XD31
MERLIN GERIN
1 2 3
v ig ilo h m s y s t e m

XRM
te s t

XD301
MERLIN GERIN
v ig ilo h m s y s t e m

XD312
MERLIN GERIN
1 2 3
v ig ilo h m s y s t e m

XRM

XD308c XL308 / 316


MERLIN GERIN
v ig ilo h m s y s te m
XD308c

MERLIN GERIN
v ig ilo h m s y s te m
XL316
test

test

8
on
9 1 0 1 1 1 2 1 3 1 4 1 5 1 6

X D 301
te s t

X D 312

X D 301
te s t

X D 312

te s t

7
M

9
test

reset

10
re s e t

11

12

re s e t
M

10
re s e t

11

12

re s e t
test/reset

5 0 5 0 7

5 0 5 3 6

P 5 0 o n P 1 2 P 1 0 0
5 0 5 0 7 5 0 5 3 6

P 5 0 o n P 1 2 P 1 0 0

M M

MERLIN GERIN
v ig id ix

MERLIN GERIN
v ig id ix

R M

1 0 N

R M

1 0 N

sensors
MERLIN GERIN
G O

sensors
MERLIN GERIN
G O

S1

S2

S1

S2
MERLIN GERIN

MERLIN GERIN

S1

S2

S1

MERLIN GERIN
v ig ir e x - v ig id ix

MERLIN GERIN
v ig ir e x - v ig id ix

S2

MERLIN GERIN
v ig ir e x - v ig id ix

MERLIN GERIN
v ig ir e x - v ig id ix

MERLIN GERIN
v ig ir e x - v ig id ix

MERLIN GERIN
v ig ir e x - v ig id ix

33

Vigilohm: functions and characteristics

Vigilohm TR22A and TR22AH insulation monitoring devices

043274

type of installation to be monitored


LV AC IT systems phase-to-phase voltage with TR22A/AH connected to neutral with TR22A/AH connected to phase frequency limited in size type reading range number thresholds threshold setting i 760 V (i 1700 V (1)) i 440 V (i 1000 V (1)) 20 to 1000 Hz IT subsystem digital 0 to 511 k 1 (sealable) 0.7 to 100 k 1 to 251 k 3s yes yes yes 1 5A 0.45 A 0.65 A 2.5 A 10 A 100 k 240 A 5 VA 115/127 V AC 220/240 V AC 380/415 V AC 440/480 V AC 500/525 V AC - 15 % to + 10 % yes class 2 0.8 kg vertical IP 40 IP 40 - 5 C to + 55 C - 40 C to + 70 C

electrical characteristics
ohmmeter fault signalling

use
IT systems: c LV AC installations up to: v neutral distributed: 760 V, v neutral not distributed: 440 V; c isolated from earth or connected to earth through a capacitive impedance. TR22H (hospitals) c high fault threshold up to 251 k. One device only for each separate installation. response time device test failsafe feature (2) output changeover contact

TR22A TR22AH

operation thresholds quantity breaking capacity

AC 400 V p.f. = 0.7 DC 230 V L/R = 1 ms 120 V L/R = 1 ms 48 V L/R = 1 ms 24 V L/R = 1 ms

operation
c injection of DC voltage; c insulation measurement: using a microprocessor device, from the leakage current created by the voltage injected between the installation and earth. Earth coupling capacitances do not affect insulation measurement; c insulation reading: digital display; c 1 alarm threshold pre-set by the user.

impedance maximum current injected maximum consumption auxiliary supply voltage

50/60 Hz

auxiliary supply voltage tolerances locating signal changeover switch (3) front insulation

installation and connection


c live part in disconnectable metal case; c vertical flush mounting on front plate (supplied); c connection: v disconnectable tunnel terminal block for 2.5 mm2 wiring. v lug for earthing of exposed conductive parts (supplied).

mechanical characteristics
weight metal case with insulated front degree of protection disconnectable mounting flush mounted surface mounted for operation for storage

other characteristics
temperature range climatic conditions (4)

fault locating with other devices


mobile XGR portable generator and XRM receiver + probes
(1) For the TR22A, the upper limit is extended to this value by adding a P1 subassembly. This is not possible for the TR22AH. (2) Failsafe: the relay is disactivated either on occurrence of a fault or if the auxiliary supply voltage accidentally fails. (3) Locating signal changeover switch: this device identifies the faulty feeder during locating by opening each feeder in turn. When the faulty feeder is opened, the alarm sounds. (4) Suitable for use in all climates: c damp heat, equipment not operating (IEC 60068-2-30) c damp heat, equipment operating (IEC 60068-2-56) c salt mist (IEC 60068-2-52).

standards
TR22A c IEC 364, chapters 4 and 5; c NF C 15-100, paragraphs 413 and 532; c UTE C 63-080 (class CPI/C); c IEC 61557-8. TR22AH c UTE C 63-080 (class CPI/MC); c IEC 364, chapters 4 and 5; c NF C 15-100, paragraphs 413 and 532; c NF C 15-211; c IEC 61557-8. 34

auxiliaries
c Cardew C surge limiter. Compulsory downstream of an MV/LV transformer; c ZX impedance; c S3 inductive neutral point; c P1 additional subassembly for installations with voltages from 440 V to 1000 V AC. Can be used with TR22A only.

Vigilohm: functions and characteristics

Vigilohm EM9 and EM9B insulation monitoring devices

042578

type of installation to be monitored


LV AC IT systems phase-to-phase voltage with EM9/EM9B connected to neutral with EM9/EM9B connected to phase frequency limited in size i 760 V i 440 V 50-60-400-1000 Hz IT subsystem

electrical characteristics
fault signalling number of thresholds 1 (sealable) threshold setting EM9: 10-20-40-60-80-100-120-150 k EM9B: 1-2.5-5-10-25-50-75-100 k response time i5s device operating test local failsafe feature (1) as an option output contact number 1 (standard or failsafe) type of contact changeover breaking capacity AC 400 V p.f. = 0.7 3A 230 V p.f. = 0,7 5A DC 220 V L/R = 1 ms 0.45 A 120 V L/R = 1 ms 0.65 A 48 V L/R = 1 ms 2.5 A 24 V L/R = 1 ms 10 A maximum consumption 5 VA impedance 100 k maximum current injected 240 A auxiliary supply voltage 50/60 Hz 115/127 V AC 220/240 V AC 380/415 V AC 440/480 V AC auxiliary supply voltage tolerances - 15 % + 10 %

use
IT systems: c LV AC installations up to: v neutral distributed: 760 V, v neutral not distributed: 440 V; c one device only for each separate installation; c isolated from earth or connected to earth through a capacitive impedance; c EM9: for installations with a high insulation level; c EM9B: for installations with a low insulation level and capacitive installations.

operation
c injection of DC voltage; c an electronic device measures insulation from the leakage current created in the installation by the voltage injected between the installation and earth and trips the alarm threshold pre-set by the user. Earth coupling capacitances do not affect insulation measurement.

mechanical characteristics
weight thermoplastic case degree of protection mounting front case for operation for storage
(2)

installation and connection


c live part in moulded, insulating, disconnectable, modular case, eight 9 mm modules wide, with transparent sealable cover; c horizontal or vertical mounting on symmetrical rail; c connection by tunnel terminals for 2.5 mm2 wiring, terminals 1 to 14.

0.4 kg horizontal or vertical IP 30 IP 20 - 5 C to + 55 C - 40 C to + 70 C

other characteristics
temperature range climatic conditions mobile

fault locating with other device


XGR portable generator and XRM receiver + probes
(1) failsafe: the relay is disactivated either on occurrence of a fault or if the auxiliary supply voltage accidentally fails. (2) Suitable for use in all climates: c damp heat, equipment not operating (IEC 60068-2-30) c damp heat, equipment operating (IEC 60068-2-56) c salt mist (IEC 60068-2-52).

standards
c UTE C 63-080; c IEC 364, chapters 4 and 5; c NF C 15-100 paragraphs 413 and 532; c NF C 15-211; c IEC 61557-8.

auxiliaries
c Cardew C surge limiter (only downstream of MV/LV transformer); c ZX impedance; c S3 inductive neutral point.

35

Vigilohm: functions and characteristics

Vigilohm EM9BV insulation monitoring devices

042580

type of installation to be monitored


LV AC IT systems phase-to-phase voltage with EM9BV connected to neutral with EM9BV connected to phase frequency limited in size type range < 760 V i 440 V 50-60-400-1000 Hz IT subsystem digital 0 to 511 k 100 k 240 A 1 (sealable) 1-2.5-5-10-25-50-75-100 k i5s local optional 1 (stand. or fail safe) changeover 3A 5A 0.45 A 0.65 A 2.5 A 10 A 5 VA 115/127 V AC 220/240 V AC 380/415 V AC 440/480 V AC - 15 % to + 10 % 0.4 kg 0.4 kg horizontal or vertical horizontal IP 30 IP 20 - 5 C to + 55 C - 40 C to + 70 C shielded cable, 1 m max. length

electrical characteristics
ohmmeter impedance maximum current injected fault number of thresholds signalling threshold setting response time device operating test fail safe device (1) output contact number type of contact breaking AC 400 V p.f. = 0.7 capacity 230 V p.f. = 0.7 DC 220 V L/R = 1 ms 120 V L/R = 1 ms 48 V L/R = 1 ms 24 V L/R = 1 ms maximum consumption auxiliary supply voltage 50/60 Hz

042581

use
IT systems: c LV AC installations up to: v neutral distributed: 760 V, v neutral not distributed: 440 V; c one device only for each separate installation; c isolated from earth or connected to earth through a capacitive impedance.

auxiliary power supply operating range

operation
c injection of DC voltage; c an electronic device measures insulation from the leakage current created in the installation by the voltage injected and trips the alarm when insulation drops below the alarm threshold pre-set by the user. Earth coupling capacitances do not affect insulation measurement; c display of insulation resistance.

mechanical characteristics
weight thermoplastic case degree of protection measuring module display module mounting measurement module display module front case for operation for storage

other characteristics
temperature range climatic conditions (2) link between display module and measurement module

installation and connection


c live part in moulded, insulating, disconnectable, modular case, eight 9 mm modules wide, with transparent sealable cover; c mounting on symmetrical rail: v measurement module: horizontal or vertical, v display module: horizontal; c connection by tunnel terminals for 2.5 mm2 wiring, terminals 1 to 14.

fault locating with other devices


mobile XRG portable generator and XRM receiver + probes
(1) failsafe: the relay is de-energized by occurrence of a fault or accidental failure of the auxiliary power supply voltage. (2) Suitable for use in all climates: c damp heat, equipment not operating (IEC 60068-2-30) c damp heat, equipment operating (IEC 60068-2-56) c salt mist (IEC 60068-2-52).

auxiliaries
c ZX impedance; c S3 inductive neutral point; c Cardew C surge limiter.

standards
c UTE C 63-080; c IEC 364, chapters 4 and 5; c NF C 15-100 paragraphs 413 and 532; c NF C 15-211; c VDE 107; c VDE 413-2; c IEC 61557-8.

36

Vigilohm: functions and characteristics

Vigilohm EM9T insulation monitoring devices

042582

type of installation to be monitored


LV AC IT systems phase-to-phase voltage with EM9T connected to neutral with EM9T connected to phase frequency limited in size i 380 V i 220 V 50-60-400-1000 Hz IT subsystem 100 k 240 A 1 (sealable) 10-20-40-60-80-100-120150 k i5s local and remote 1 changeover 3A 5A 0.45 A 0.65 A 2.5 A 10 A 5 VA 24 V AC 48 V AC 115/127 V AC 220/240 V AC - 15 % to + 10 % 0.4 kg horizontal or vertical IP 30 IP 20 - 5 C to + 55 C - 40 C to + 70 C

electrical characteristics
impedance maximum current injected fault number of threshold signalling threshold setting response time device operating test output contact

use
IT systems: c LV AC installations up to: v neutral distributed: 380 V, v neutral not distributed: 220 V; c one device only for each separate installation; c isolated from earth or connected to earth through a capacitive impedance; c specially designed for machine control and monitoring installations.

number type of contact breaking capacity

AC 400 V p.f. = 0.7 230 V p.f. = 0.7 DC 220 V p.f. = 1 ms 120 V L/R = 1 ms 48 V L/R = 1 ms 24 V L/R = 1 ms 50/60 Hz

operation
c injection of DC voltage; c an electronic device measures insulation, from the leakage current created in the installation by the voltage injected and trips the alarm when insulation drops below the alarm threshold pre-set by the user. Earth coupling capacitances do not affect insulation measurement.

maximum consumption auxiliary supply voltage

auxiliary supply voltage tolerances

mechanical characteristics
weight thermoplastic case degree of protection mounting front case for operation for storage

installation and connection


c live part in moulded, insulating, disconnectable, modular case, eight 9 mm modules wide, with transparent sealable cover; c horizontal or vertical mounting on symmetrical rail; c connection by tunnel terminals for 2.5 mm2 wiring, terminals 1 to 14.

other caractristiques
temperature range climatic conditions (1) mobile

fault locating with other devices


XRG portable generator and XRM receiver + probes
(1) Suitable for use in all climates: c damp heat, equipment not operating (IEC 60068-2-30) c damp heat, equipment operating (IEC 60068-2-56) c salt mist (IEC 60068-2-52).

standards
c UTE C 63-080; c IEC 364, chapters 4 and 5; c NF C 15-100, paragraphs 413 and 532; c NF C 15- 211; c IEC 61557-8.

auxiliaries
c ZX impedance; c S3 inductive neutral point.

37

Vigilohm: functions and characteristics

Vigilohm TR5A insulation monitoring device

017422

type of installation to be monitored


LV DC voltage between polarities limited in size 24-42-48-120-220 260-420 V IT subsystem

electrical characteristics
number of thresholds 1 (sealable) threshold setting DC 24 to 48 V installat. 5 to 25 k DC 120 V installat. 10 to 50 k DC 220 V installat. 30 to 150 k DC 260 to 420 V installat. 30 to 150 k response time on solid fault i1s device operating test yes failsafe feature (1) yes as an option changeover number 1 output contact breaking AC 230 V p.f. = 0.7 5A capacity DC 120 V L/R = 1 ms 0.65 A supply voltage tolerance (installation) - 20 % to + 20 % internal impedance between + or DC 24 to 48 V installat. 24 k polarity and earth DC 120 V installat. 46 k DC 220 V installat. 154 k DC 260 to 420 V installat. 166 k between polarity DC 24 to 48 V installat. 38 k DC 120 V installat. 55 k DC 220 V installat. 82 k DC 260 to 420 V installat. 132 k fault signalling

use
IT systems: c LV DC installations up to 420 V; c isolated from earth.

operation
c a device with a high input impedance measures the variation in potential of the two polarities of the installation compared with earth. These variations are transformed into insulation signals; c auxiliary power comes from the monitored installation; c if monitoring and signalling are required, for an insulation fault evenly divided between both polarities, use the Vigilohlm System XM200.

mechanical characteristics
weight plastic case degree of protection mounting flush mounting surface mounting for operation for storage 0.5 kg horizontal IP 30 IP 20 - 5 C to + 55 C - 40 C to + 70 C

installation and connection


c live part in moulded, insulating disconnectable, modular case eleven 9 mm modules wide, with transparent sealable cover; c horizontal flush or surface mounting on symmetrical rail; c connection by 6.35 mm tab connectors for 2.5 mm2 wiring.

other characteristics
temperature range climatic conditions (2)

fault locating with other devices


mobile XGR portable generator and XRM receiver + probes
(1) failsafe: the relay is disactivated either on occurrence of a fault or if network voltage fails. (2) Suitable for use in all climates: c damp heat, equipment not operating (IEC 60068-2-30) c damp heat, equipment operating (IEC 60068-2-56) c salt mist (IEC 60068-2-52).

standards
c UTE C 63-080; c IEC 364, chapters 4 and 5; c NF C 15-100, paragraphs 413.4-3; c IEC 61557-8.

38

Vigilohm: functions and characteristics

Vigilohm SM21 off-line insulation monitoring device

051346

type of de-energised installation to be monitored


LV AC IT (de-energised) DC (de-energised) fault signalling phase-to-phase voltage frequency voltage between polarities i 690 V (1) 50-60-400-1000 Hz i 690 V (1)

electrical characteristics
number of thresholds threshold values 15 % prealarm alarm 2 0.5-1-1.5-2-3-57,5-10 M 0.25-0.5-0.75-11.25-1.5-1.75-2 M i1s yes by selector switch as standard (3) 1.6 M 350 k 1 standard 1 failsafe 5A 0.65 A 115/127 V AC 220/240 V AC 380/415 V AC 440/480 V AC 500/525 V AC - 15 % + 10 % 0.3 kg horizontal/vertical IP 30 IP 20 - 5 C to + 55 C - 40 C to + 70 C

use
monitors de-energised equipment (e.g. motors, fire pumps,...) whatever the earthing system. De-energised installations: c AC (up to 690 V) or DC (up to 690 V); c when associated with a circuit breaker possessing an MN or MX release or with a contactor, the SM21 protects motors against insulation faults that may be produced during operating shutdowns (e.g. due to condensation), by initiating an alarm or startup lock-out.

response time device operating test alarm inoperative failsafe device (2) internal impedance changeover output contact number breaking capacity auxiliary supply voltage

yes DC AC 50-60 Hz alarm prealarm AC 230 V p.f. = 0.7 DC 120 V L/R = 1 ms 50/60 Hz

operation
c injection of DC voltage. Voltage is applied, with the motor deenergised, between the stator and earth, thereby creating a leakage current in the motor insulation resistances; c 2 pre-set thresholds: v 1 prealarm threshold, adjustable in 8 steps from 0.5 to 10 M, v 1 alarm threshold, adjustable in 8 steps from 0.25 to 2 M. An electronic device measures insulation from the leakage current created by the voltage injected and activates the alarm or prevents starting when insulation drops below the corresponding threshold. auxiliary supply voltage tolerances

mechanical characteristics
weight plastic case degree of protection mounting flush mounting surface mounting

other characteristics
temperature withstand for operation for storage climatic conditions (4)

installation and connection


c live part in moulded, insulating, disconnectable, modular case, eight 9 mm modules wide, with transparent sealable cover; c horizontal or vertical mounting on symmetrical rail; c connection: wires up to 2.5 mm2; c the SM21 is used with a contact that opens to disconnect the device from the installation when the installation is energised.

(1) depends on rated voltage withstand of the contact used to disconnect the SM21 when the network is energised. (2) failsafe: the relay is disactivated on occurrence of a fault or if the auxiliary supply voltage accidentally fails. (3) only the first alarm contact. (4) Suitable for use in all climates: c damp heat, equipment not operating (IEC 60068-2-30) c damp heat, equipment operating (IEC 60068-2-56) c salt mist (IEC 60068-2-52).

standards
IEC 61557-8.

39

Vigilohm: functions and characteristics

Vigilohm mobile fault locating kit XGR + XRM + probes


053130

type of installation to be monitored


LV AC or mixed AC/DC IT systems phase-to-phase voltage with XGR connected to neutral with XGR connected to phase frequency voltage between polarities 760 V 440 V 45 to 400 Hz 500 V

DC or rectified IT systems auxiliary supply

electrical characteristics
XGR XRM voltage 115 to 525 V AC maximum consumption 15 VA IEC alkaline 9 V cell PP3 or 6 LR61 type not supplied type digital scale 0 to 19 by potentiometer 40 k 2.5 mA 0.85 kg 0.2 kg portable portable 12 mm 50 mm 100 mm

display

XRM XRM XGR XGR XGR XRM XGR XRM XP15 XP50 XP100
DB101070

presentation
The mobile fault locating kit comes in the form of a case containing: c a locating signal generator, XGR, supplied with 220 - 240 V AC; c a locating signal receiver XRM; c three tong-type current probes: XP15, XP50 and XP100. The devices making up the kit and the XGR for other voltages are all available individually. See catalogue number tables.

calibration impedance maximum current injected weight case

mechanical characteristics
plastic plastic for cables up to for cables up to for cables up to

associated equipment
probes (1)

use
The kit is used on LV IT systems (i.e. installations with an unearthed or impedance-earthed neutral). It enables fault locating on: c AC installations 50 to 400 Hz; c DC installations. It is used mainly with insulation monitoring devices that inject DC currents (TR22A, EM9B or EM9BV, etc.).
047166

(1) Maximum diameter of all live conductors together.

c the XGR generator injects a 2.5 Hz AC voltage between the installation and the earth, thereby creating a leakage current which passes through the installation insulation impedance; c the XRM mobile receiver is associated with one of the three tong-type probes, XP15, XP50 or XP100, and detects this leakage current at 2.5 Hz. It displays a value between 1 and 19 according to the current passing through the probe, thus detecting the leakage current; c three current probes are available, the XP15, XP50 and the XP100, for cables with diameters up to 12, 50 and 100 mm respectively. Older probe models are not compatible with the XRM.

XGR locating signal generator

051350

PB100471

operation

XP15, XP50 and XP100 probes. Note: the photographs are for information purposes only. There are two types of probes that function in the same way but are different in shape and colour.

XRM locating signal receiver

40

Vigilohm: functions and characteristics

toroids

051352

characteristics
E24281 E24290

Closed toroids (type A)

toroids electrical characteristics


transformation ratio

type A
1/1000

type OA
1/1000 c

042589

c maximum permissible current: 1 kA continuous - 5 kA/1.5 s - 100 kA/0.05 s

mechanical characteristics
weight (kg) 30 50 80 120 200 300 46 110 for storage for operation 0.120 0.200 0.420 0.590 1.320 2.230 1.300 3.200 55 C to + 85 C 35 C to + 70 C IP30 (IP20 connectors) 55 C to + 85 C 35 C to + 70 C IP30 (IP20 connectors)

Split toroids (type OA)

use
The toroids are used to detect the earth leakage currents. They are used with the Vigilohm System for the detection, locating and measurement of earth fault currents on IT systems. Closed toroids (type A) are suitable for new installations and extensions. Split toroids (type OA) are suitable for renovated installations and extensions. temperature range degree of protection

other characteristics

functions
These toroids detect leakage current and transmit a proportional signal to the associated receiver.

compatibility
All type A and OA toroids are compatible with the various devices of the Vigilohm System range: XD301, XD312, XD308C, XL308, XL316, XML308 and XML316.

installation and connection


Closed toroids (type A) c enclosed in an insulated casing; c 2 possibilities for mounting: v diam. 30-50-80 mm on symmetrical rail, v all diameters on plate and cables; c connection: v diam. 30 to 200 mm by tunnel terminals for 0.22 mm2 wires (minimum), v diam. 300 mm by 6.35 mm tab connectors. Split toroids (type OA) c enclosed in an insulated casing; c mounting on plate and cable; c connection by 5 mm diam. screws for 0.22 mm2 wires.

41

E13856B

E13856A

N1

23

PE

N1

23

PE

installation precautions
Immunity to line overcurrents Line overcurrents, due to motor starting or transformer energising, may result in unnecessary fault detection by the detector. A number of simple precautions can help prevent this from happening: when used together they are even more effective: c place the toroid on a straight part of the cable; c carefully centre the cable in the toroid; c use a toroid with a diameter far larger than the diameter of the cable (2 x diameter), (figure 1). For severe operating conditions, use of a mild steel sleeve placed around the cable, in the toroid, considerably increases immunity. Recommended characteristics c mild steel foil, 1/10 mm thick, to be wound several times around the cable in the toroid (at least 1 mm thick); c internal diameter of toroid > 1.4 x external diameter of the cable bundle (figure 2); c toroid-detector link: v resistance i 3 , v cross-sectional area of wires: 0.75 mm2 to 1.5 mm2, v maximum length: 50 m.

Figure 1.

Figure 2.

sensors general characteristics


type of installation to be monitored insulation voltage Ui closed sensor split sensor operating temperature storage temperature degree of protection

type A closed toroid


LV 50/60/400 Hz 1000 V b - 35 C / + 70 C - 55 C / + 85 C IP30 (IP20 connectors) 1/1000 b b IV 12 TA30 PA50 IA80 65 85 160 25 50 95

type OA split toroid


LV 50/60/400 Hz 1000 V b - 35 C / + 70 C - 55 C / + 85 C 1/1000 b b IV 12

electrical characteristics
transformation ratio 3-phase short-circuit withstand current Icw of 100 kA/0.5 s differential short-circuit withstand current IDw of 85 kA/0.5 s (as per IEC 60947-2 in kA rms) overvoltage category rated impulse withstand voltage Uimp (kV) sensor characteristics rated operational current Ie (A) max. cross-section area of conductors per phase (mm2 of copper)

MA120 SA200 GA300 POA 250 400 630 85 240 2 x 185 2 x 240 50

GOA 250 240

mechanical characteristics
type of sensor toroid TA30 toroid PA50 toroid IA80 toroid MA120 toroid SA200 toroid GA300 toroid POA toroid GOA Diameter (mm) 30 50 80 120 200 300 Weight (kg) 0.120 0.200 0.420 0.590 1.320 2.230 Diameter (mm) 46 110 POA, GOA 28 cycles + 25 C/+ 55 C / HR 95 % 48 hours, environment category C2 KB test, severity 2 3 8.02 16.35 Weight (kg) 1.300 3.200

mounting
horizontally or vertically on symmetrical DIN rail on plain or slotted backplate or profiled sheet metal on cable TA30, PA50, IA80, MA120 TA30, PA50, IA80, MA120, SA200 IA80, MA120, SA200, GA300 28 cycles + 25 C/+ 55 C / HR 95 % 48 hours, environment category C2 KB test, severity 2 3 0.98 1.42 3.19 3.89 7.05

environment
damp heat, equipment not operating (IEC 60068-2-30) damp heat, equipment operating (IEC 60068-2-56) salt mist (IEC 60068-2-52) degree of pollution (IEC 60664-1) calorific value (MJ)
(1) Allows use in all climates.

42

Vigilohm: functions and characteristics

auxiliaries

selection of auxiliaries
A number of accessories are required for Vigilohm installations; other optional Vigilohm

accessories can be provided: c essential auxiliary; v optional auxiliary. XGR TR22A TR22AH EM9 EM9B EM9T cat. No

XM200 XM300C XML308 XML316 U < 760 VAC (4) 760 1700 VAC (4) U < 440 VAC (5) 440 1000 VAC (5) U < 500 VDC (6) 500 1200 VDC (6) c c c v v c except XM200 c v

"250 V " Cardew C (1) or "440 V" Cardew C (1) or "660 V" Cardew C (1) or "1000 V" Cardew C (1) or Cardew C base P1 subassembly ZX limiting impedance S3 inductive neutral point i 380V PHT 1000 additional subassembly

c c c c v c (3) v v

c c c c v v v

c c c c v v v

(2) (2) (2) (2)

50170 50171 50172 50183 50169 50211 50159 50113 50248

(1) See choice of the type of Cardew C (250, 440, 600 or 1000 V) below. (2) The use of a Cardew C is unnecessary with the EM9T. (3) Necessary for TR22A used on installations with U > 440 V. (4) Neutral distributed. (5) Neutral not distributed. (6) DC installation.

auxiliary characteristics
Cardew C surge limiter
041857

connection
Characteristics c non-arcing voltage at 50 Hz i 1.6 x nominal U; c certain arcing voltage at 50 Hz u 2.5 x nominal U (3 x nominal U for 220 V); c maximum current after arcing: 40 kA/0.2 sec; c insulation resistance > 1010 ohms; c cartridge not reusable; c temperature range: v operating: - 5 C to + 40 C, v storage: - 25 C to + 70 C. Standards NF C 63-150, NF C 15-100. Weight: 1 kg. Cardew selection table The selection depends on: c the operating voltage Un of the installation; c the installation insulation level; c the connection point (neutral-earth or phase-earth). Un: ph.-ph. operat. voltage of the AC instal. neutral distributed neutral not distributed U i 380 V U i 220 V 380 V < U i 660 V 220 V < U i 380 V 660 V < U i 1000 V 380 V < U i 660 V 1000 V < U i 1560 V 660 V < U i 1000 V Connecting conductor size c cable or bar with a size adapted to the transformer rating c the connecting conductor should be considered to be a protective conductor (PE) and the calculation of its crosssectional area must satisfy applicable installation standards, considering that this part of the installation is protected by protective devices located upstream of the MV/LV transformer; c according to standard IEC 364, the formula for the calculation of the of the size of the PE conductor is: S = I2t/k where S is the cross-sectional area of the

E12043

130

160 50

70

2 13

2 7 M12

100

c on LV network with isolated or impedanceearthed neutral; c connected to the secondary of the MV/ LV transformer to discharge overvoltages to earth; c capable of withstanding the short-circuit current of the transformer; c its operation causes continuous indication on the insulation monitor.
MV/LV L3 L2 L1 N cardew C
E12128

Ui arcing voltage 400 V < Ui i 750 V 700 V < Ui i 1100 V 1100 V < Ui i 1600 V 1600 V < Ui i 2400 V

Cardew C "type" "250 V" "440 V" "660 V" "1000 V"

PE conductor in mm2, I is the fault current, t is the operating time of the protective device and k is a coefficient that depends on the metal and insulation material used for the conductor. c recommendation: if insulation monitoring is provided using the Vigilohm System, install a type A toroid on the Cardew earthing circuit in order to monitor operation of the Cardew. The toroid can be connected to an XD301/ 312 detector or an XL308/316 or XML308/ 316 locating device.

43

019303

E24300

ZX limiting impedance subassembly

Connection c creates an installation with an impedanceearthed neutral; c remains connected during fault locating at 2.5 Hz: v 1500 at 50 Hz, v 1M at 2.5 Hz; c U i 500 V AC.
MV/LV L3 L2 L1 N 1
E24299

Dimensions, mounting Weight: 3.500 kg


190 170

1 2

360 380

185

4 8,2

15

ZX
2

IMD

019301

E24337

S3 inductive neutral point subassembly


E24336

Connection c creates an artificial neutral point for insulation monitoring, with the main circuitbreaker open; c U i 380 V AC.
MV/LV L3 L2 L1 N

Dimensions, mounting Weight: 1.750 kg


166 150
1 2 3 4

130 150

4 6

15

70

1 2 3 IMD S3 4

PHT1000 additional subassembly


044139

Connection c for use with the Vigilohm System XM300C and XML 308/316 on the following installations: v 440 V AC i U i 1000 V AC, neutral not distributed, v 760 V AC i U i 1700 V AC, neutral distributed, v 500 V DC i U i 1200 V DC: installation.
E19507

Dimensions, mounting Weight: 2 kg


110
E19524

4 holes 7

200 184

220

MV/LV

3 13

PHT XM

2 1 14 22
26

150

80

P1 subassembly
019302

Connection c can be used to connect a TR22A to installation > 440 V AC; v 440 V AC i U i 1000 V AC, neutral not distributed, v 760 V AC i U i 1700 V AC, neutral di distributed.
Neutral distributed
E24312 E24311

Dimensions, mounting Weight: 0.400 kg


E24330

140 128

Neutral not distributed

= =
1 RC P1 6 cardew C 4

1 RC

63
5

5,2

40 65

P1 6 cardew C

1 CPI 6

1 IMD 6

44

insulation monitoring

Vigilohm

3/ installation and connection


page dimensions connection 46 49

45

Vigilohm: installation and connection

dimensions

XM200, XM300C, XL308, XL316


Flush mounting
E24341 E24342

Cutout

129

112

153 9,5 192 12


148

XML308, XML316
Flush mounting
E24343 E24344

Cutout

129

112

229 9,5 192 12


224

XD308C
Flush mounting
E24317 E24318

Cutout

129

112

76 9,5 94 12
71,5

XD301, XD312
Flush mounting
E26419 E26419

Cutout
E26420

Surface mounting
XD312

65

XD301 2 4,2

2 4,2

XD301 2 4,2

XD312 2 4,2

45

66

66

46
6,5
37,5 49,5 73,5

46
10
7

81 66 66

81

XD301 XD312

57 73

93 107

4,5

57 72

11 6,5

93 106

7,5

XLI200, XLI300, XTU300, XAS


Flush mounting
E24319 E24318

Cutout

129

112

76 9,5 192 8
71,5

XRM + probes
XRM manual receiver
E12095 E26421

XP15, XP50 and XP100 probes

145

Inside dimensions XP15: 12 mm. XP50: 50 mm. XP100: 100 mm.

37

80

46

TR22A, TR22AH
Flush mounting IP40
E26444 E26445

Cutout

129

112

76 9,5 94 8

71,5

EM9, EM9B, EM9BV, EM9T, SM21


Mounting on symmetrical rail IP20
E21457 E26422

Cutout

Mounting on panel: use fixing lugs 20269.

45

81

46

44 60 65,5

72

73

TR5A
Flush mounting IP30 Door cutout (behind panel) and holes
4,2
E24297

Mounting on symm. rail IP20

Mounting on panel IP20


2 screws M4
E12139

Auxiliary subassembly aa > 220 V

32

45

44,5

77

64

77

68

37
53 99

99

26

99

XGR
E26423

59
189

108

47

Vigilohm: installation and connection

dimensions (cont.)

toroids (type A and OA)


type A 30 and 50
E24291 E18644

types A 80 to 200
2 4,5

type A 300
5
E24293

type OA 46 and 110


E24294

E D 8

16

F H

K B

B L

J E
4 21 29

C D L

type TA30 PA50

30 52

B 31 45

C 60 87

D 53 66

E 82 108

F 50 60

type IA80, IE80 MA120, ME120 SA200, SE200

B C 80 122 26.5 120 164 26.5 196 256 29

D 35 35 37

E F G 150 80 55 190 80 55 274 120 90

H 40 40 60

J K L 126 65 44 166 65 44 255 104 46

type H L GA300 299 29 344

type H L B C POA 46 68 148 57 38 GOA 110 68 224 76 44

Mounting examples for type A toroids On XD301detector, 30 to 50


044866 042593

On rail, 30 to 80 mm
042591

On plate or section, type A, 30 to 200 mm

On cable, 120 to 300 mm


044865 042592 042590

48

Vigilohm: installation and connection

connection

E19515

E19526

XM200
E25115

XM200

MV/LV

ut

MERLIN GERIN
vigilohm system XM200
test

10 9 8 7 6 5

prevention (failsafe feature)


4

3 2 1 N

fault

cardew C 11

XM200

MV/LV
R C Sp Sa
S

3 2 1

menu

ok

test

cardew C

XM200 11

4 3 2 1 11
4 XM200 11
+

Tunnel terminals for 1.5 mm2 wiring


Legend aa: AC auxiliary supply a -15 %, +10 %, 50-60 Hz ut: application r: installation terminal 11: earth connection by round lug (4 mm diameter) to be crimped.

aa

E19506

MV/LV

E17296

XM300C
E27116

DB101055

XM300C 12 11 10 9 8 7 6 5 4 fault (failsafe feature) fault 1 address


1

ut

3 2 1 N

ut
14 cardew C 13 XM300C

MERLIN GERIN
vigilohm system XM300c
test

ut

4 prevention
MV/LV 3 2 1

12 11 10 9 8 7 6 5 4

fault (failsafe feature) fault

valeur d'isolement 040 K MENU TEST

21 23 24 20 19 18 17 16 15 I1 I2 VB V+ S
14 XM300C 13 14 cardew C 13
+

XM300C

Tunnel terminals for 1.5 mm2 wiring


Legend aa: AC auxiliary supply a -15 %, +10 %, 50-60 Hz ut: application r: installation terminal 13: earth connection by round lug (4 mm diameter) to be crimped. *connection supplied with PHT1000.
E27168

aa

2 1

13

14 22

r
23 XM300C PHT1000

*
aa
2 1 13 14 22

24 18 17 16 15 VB V+ S
1 2 3

r
DB101056
E19509

XML308, XML316
E32439

ut

MERLIN GERIN
vigilohm XML31 6 system

ut
test

12 11 10 9 8 7 6 5 4

fault (failsafe feature) fault

XML308 XML316 1 address


1

MV/LV

t9 1 2 1

t16 2 1

t1 2 1 1-1 1-2 2-1 2-2 3-1 3-2 4-1 4-2 5-1 5-2 6-1 6-2 7-1 7-2 8-1 8-2

t8 2

3 2 1 N

4 prevention 21

1
9

10 11 12 13 14 15 16

valeur d'isolement 040 K MENU TEST

23 24

20 19 18 17 16 15

I1 I2 VB V+ S

aa

2 1

13

14 22

9-1 9-2 10-1 10-2 11-1 11-2 12-1 12-2 13-1 13-2 14-1 14-2 15-1 15-2 16-1 16-2

14 cardew C 13
3 2 1

XML316

MV/LV

14 cardew C 13 XML316

Tunnel terminals for 1.5 mm2 wiring


Legend: aa: AC auxiliary supply a -15 %, +10 %, 50-60 Hz ut: application r: installation t: toroid A or OA terminal 13: earth connection by round lug (4 mm diameter) to be crimped.
r
E17296

14 XML316 13

ut

12 11 10 9 8 7 6 5 4

fault (failsafe feature) fault

49

Vigilohm: installation and connection

connection (cont.)

E19510

XL308, XL316
E32441

E17296

ut

MERLIN GERIN
vigilohm system XL316
test

12 11 10 9 8 7 6 5 4

fault (failsafe fealure) fault

XL308 XL316 t9 1 2 1 9-1 9-2 10-1 10-2 11-1 11-2 12-1 12-2 13-1 13-2 14-1 14-2 15-1 15-2 16-1 16-2 t16 2 1 t1 2 1 1-1 1-2 2-1 2-2 3-1 3-2 4-1 4-2 5-1 5-2 6-1 6-2 7-1 7-2 8-1 8-2 t8 2 address
3

ut

12 11 10 9 8 7 6 5 4

fault (failsafe feature) fault

1 9

10 11 12 13 14 15 16

test/reset

aa

2 1

13

18 17 16 15

VB V+ S

Tunnel terminals for 1.5 mm2 wiring


Legend: aa: AC auxiliary supply a -15 %, +10 %, 50-60 Hz ut: application t: toroid A or OA terminal 13: earth connection by round lug (4 mm diameter) to be crimped

E19525

XD308C
E32443
MERLIN GERIN
vigilohm system XD308c
test

XD308c

Tunnel terminals for 1.5 mm2 wiring


Legend: aa: AC auxiliary supply a -15 %, +10 %, 50-60 Hz t: toroid A or OA

aa

1 2

t1

t8 V B V+ S

on

test

reset

3 4 5 6 7 8 9 10 11

1 address
4

E19516

XD301
E27125

Tunnel terminals for 1.5 mm2 wiring


t XD301 5 6
Legend: aa: AC auxiliary supply a -15 %, +10 %, 50-60 Hz ut: application t: toroid A or OA

MERLIN GERIN
vigilohm system

XD301

test

reset
50507

7 8 9 10 11 aa ut

E19517

XD312
E19520

n 1 n 2 n 12

1 4 7

2 5 8

3 6 9

MERLIN GERIN
vigilohm system

1 2 3 4 5 6 7 8 9 10 11 12
test

XD312

XD312

10 11 12
50536

reset

15 16

21 22 23

26

Tunnel terminals for 1.5 mm2 wiring


aa ut
Legend: aa: AC auxiliary supply a -15 %, +10 %, 50-60 Hz ut: application t: toroid A or OA

50

XLI200, XLI300, XTU300, XAS


E32434
MERLIN GERIN
vigilohm system XLI300

dfaut

XLI300 Sub D9 RS485 1 signal ground 4 received data 5 transmitted data 8 received data + 9 transmitted data + XTU300 Sub D9 RS232 2 received data 3 transmitted data 5 signal ground c never connect more than one interface to the Vigilohm System bus c to connect devices to the communication bus (shielded, double twisted pair), it is recommended to interconnect their respective terminals S, B, V + and V.

E16124

XLI200/XLI300/XTU300
JBUS address =H L H L 18 V17 B 1 not used 5 RS232 1 5 RS485 13 1 : GND 6 4 : B'(RD-) 5 : B(TD-) 9 8 : A'(RD+) 9 : A(RT+) 6 9 16 V+ 15 S

1 2

aa

XAS
E16126

18 V17 B 16 V+ 15 S

13 1 2 aa

Example of line connection


E19518

VXM300c B V+ S XL308 XL316

VB V+ S XD308c

VB V+ S XML308 XML316

VB V+ S XLI300 XTU300 XAS

VB V+ S

51

Vigilohm: installation and connection

connection (cont.)

When coupling two installations, one of the two Vigilohm insulation monitors must be disconnected momentarily.

E12008

MV LV
IMD IMD

MV LV

TR22A/TR22AH
E27111

E18471

aa

r S3 P1

2.5 mm2 wiring


Legend: aa: AC auxiliary supply, 50-60 Hz

1 2 3 TR22A TR22AH
MERLIN GERIN
vigilohm
TR 22AH

5 6 10

-15 %, +10 % 110-127 V a 220/415 V a 440/525 V a 1 2 110-127 V 220-240 V 440-480 V 1 3

380-415 V 500-525 V

8 9 7

r: installation S3: S3 subassembly (optional) ut: application P1: P1 subassembly (optional)

test

ut

Use with failsafe feature: the normally excited output relay is de-energised in the event of an auxiliary voltage failure (of internal or external origin) or an insulation fault. U < 1700 V
L3 L2 L1 5
L1 L2 L3 N 1 P1 5 10 6
6

U < 760 V
E24322 E24323

U < 440 V
L3 L2 L1 N
5
E24324

U < 760 V
E24325

U < 440 V
L3 L2 L1 N
E26347

U < 1000 V
E26346
L1 L2 L3 1 P1 5 10

auxiliary: S3 inductive neutral point subassembly


L3 L2 L1 N
6
1 2 3
TR 22A
4

L3 L2 L1 5

cardew C

TR 22A
4

cardew C

TR 22A
4

E24326

MV/LV

MV/LV

LV/LV

LV/LV

TR 22A
4

TR 22A
4

S3

TR 22A
4

TR 22A
4

E26417

TR5A
E27134

2.5 mm2 wiring 6.35 mm tab connector

+
1 2 TR5A

Legend: r: installation DC power supply, - 20 %, + 20 % ut: application

r > 220 V
TR5A

E18566

MERLIN GERIN

r
1 2

TR5A
3 9

+ 1 2 3 4 auxiliary plate TR5A 5

E26418

u. t.
Note: for a TR5A with failsafe feature, use terminals 6 and 7.

TR 3 5A
1

SM21
E27112

E26348

alarm

pre-alarm

2.5 mm2 wiring


Legend: aa: supply
L1 L2 L3 N
E26349

1 2 3
test

5 6 7 SM21

MERLIN GERIN
vigilhom

SM21

AL. REL. OK

13

1,0
0,75 0,5

1,25
1,5

2,0

3,0
5,0 7,5

off

on

SM 21

1,5

1,75 1,0
0,25 Sa 2,0 0,5 10 Sp

8 9
AL. REL.

11

13 c. a.

11

50761

10 11 12 13

14

a. a.

Note: make sure that the auxiliary contact of the motor control system can withstand the rated voltage when the contact is open.

52

E18465A

EM9, EM9B, EM9T


E27114

ut
E18461

2.5 mm2 wiring


MV/LV 3 2 1 N 13 EM 14 MV/LV 3 2 1 cardew C 13 EM 14 13 EM 14 LV/LV 3 2 1

1 2 3

EM9/EM9B

MERLIN GERIN
vigilohm EM9T

on

test

cardew C

60

80
100 120

40 20
10 150

50582

10 11 12 13

14

8 9

13 14

E18462

E27117

E18465B

EM9BV
1 2 3 4 5 6 7

aa
ut tad

13 EM 14

13 EM 14

MERLIN GERIN
vigilohm EM9BV

1 2 3
on test

4 5

EM9T

10

25
50 75

S3

S3

5 2,5
1 100

50558

10 11 12 13 14

8 9
E27113

13 14

EM9, EM9B Use with failsafe feature: the normally excited output relay is de- energised in the event of an auxiliary voltage failure (of internal or external origin) or an insulation fault. EM9T c remote test: terminals 4 and 5; c compliance with standard UTE C63-080.

aa

MERLIN GERIN
vigilohm EM9BV

E18556

ut

50570

10 11 12 13 14

1 2 3

5 6 7 EM9BV

5 6 7

Legend: aa: auxiliary supply, - 15 % + 10 % ut: application r: installation tad: remote test

8 9

13 14

8 9

aa

aa

E27423

E27426

E27424

XGR

MV/LV

a.a

3 2 1 N
IMD

a.a: auxiliary supply r.: installation

XGR

MERLIN GERIN

XGR
+
E27425

IMD XGR

53

54

insulation monitoring

Vigilhom 4/ catalogue numbers


page Vigilohm insulation monitoring Vigilohm System Vigilohm System: accessories 56 58 59

55

Catalogue numbers

Vigilohm insulation monitoring

Vigilohm TR22A/TR22AH
Installation voltage (neutral not distributed): < 440 V AC With rectifiers: balanced fault detection TR22AH: special hospital version TR22A Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 440/480 V AC 50/60 Hz 500/525 V AC 50/60 Hz TR22AH Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 440/480 V AC 50/60 Hz 500-525 V AC 50/60 Hz Installation voltage (neutral not distributed): < 440 V AC Installations with high installation levels (adjustable threshold 10-150 k) EM9 Standard model Single phase auxiliary power 115/127 V AC 50/60 Hz 50595 supply (V) 220/240 V AC 50/60 Hz 50597 380/415 V AC 50/60 Hz 50599 440/480 V AC 50/60 Hz 50601 Installation voltage (neutral not distributed): < 440 V AC Installations with low insulation levels and capacitive installations (adjustable threshold 1-100 k) EM9B Standard model Single phase auxiliary power 115/127 V AC 50/60 Hz 50555 supply (V) 220/240 V AC 50/60 Hz 50557 380/415 V AC 50/60 Hz 50559 440/480 V AC 50/60 Hz0 Hz 50561 Installation voltage (neutral not distributed): < 440 V AC Digital display of insulation resistance (adjustable threshold 1-100 k) EM9BV Standard model Single phase auxiliary power 115/127 V AC 50/60 Hz 50568 supply (V) 220/240 V AC 50/60 Hz 50570 380/415 V AC 50/60 Hz 50572 440/480 V AC 50/60 Hz 50574
E27111

vigilohm
TR 22AH

test

50395 50396 50397

50398 50399 50391

Vigilohm EM9
E27114
1 2 3 4 5 6 7

MERLIN GERIN
vigilohm EM9T

on

test

60

80
100 120

40 20
10 150

50582

1 0

1 1

1 2

1 3

1 4

Fail safe model 50596 50598 50600 50602

Vigilohm EM9B
E27117
1 2 3 4 5 6 7

MERLIN GERIN
vigilohm EM9BV

on

test

10

25
50 75

S3

S3

5 2,5
1 100

50558

1 0

1 1

1 2

1 3

1 4

Fail safe model 50556 50558 50560 50562

Vigilohm EM9BV
E27117
1 2 3 4 5 6 7

MERLIN GERIN
vigilohm EM9BV

on

test

10

25
50 75

S3

S3

5 2,5
1 100

50558

1 0

1 1

1 2

1 3

1 4

Fail safe model 50569 50571 50573 50575

E27113

MERLIN GERIN
vigilohm EM9BV

50570

1 0

1 1

1 2

1 3

1 4

Vigilohm EM9T
1 2 3 4 5 6 7

MERLIN GERIN
vigilohm EM9T

on

test

60

80
100 120

40 20
10 150

50582

1 0

1 1

1 2

1 3

1 4

Installation voltage (neutral not distributed): < 220 V AC Machine control and monitoring (adjustable threshold 10-150 k) EM9T Single phase auxiliary power 24 V AC 50/60 Hz supply (V) 48 V AC 50/60 Hz 115/127 V AC 50/60 Hz 220/240 V AC 50/60 Hz

E27114

50581 50582 50583 50584

56

Catalogue numbers

Vigilohm insulation monitoring (cont.)

Vigilohm TR5A
1 2 3 4 5

Installation voltage (neutral not distributed): < 420 V DC (adjustable threshold 5-150 k) TR5A 24 V DC 42/48 V DC 120 V DC 220 V DC 260 V DC 420 V DC (1) with supplied external subassembly. Power supplied by monitored installation (V) Standard model 50340 50341 50342 50343 50350 50351 Fail safe model 50344 50345 50346 50347

E32741

MERLIN GERIN
vigilohm TR5A
120V

test

20
6
50381

35

9 10

10

50

1 0

(1) (1)

Vigilohm SM21
1 2 3 4 5 6 7

MERLIN GERIN
vigilhom

SM21

AL. REL. OK

test

1,0
0,75 0,5

1,25

2,0

3,0
5,0 7,5

off

on

1,5

1,5

1,75 1,0
0,25 Sa 2,0 0,5 10 Sp

50761

AL. REL.

Installation voltage: < 690 V (1) SM21 Single phase auxiliary power 115/127 V AC 50/60 Hz 50760 supply (V) 220/240 V AC 50/60 Hz 50761 380/415 V AC 50/60 Hz 50762 440/480 V AC 50/60 Hz 50763 500/525 V AC 50/60 Hz 50764 (1) this voltage is depends on the rated voltage withstand performance of the open auxiliary contact used to isolate the SM21 from the installation.

E58548

Mobile 2.5 Hz fault locating


Kit case
Mobile fault locating kit case containing: XGR (220/240 V) + XRM + XP15 + XP50 + XP100 probes 50310

Mobile XGR generator


E32436

Single phase auxiliary power supply (V)


MERLIN GERIN

115/127 V AC 50/60 Hz 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz

50281 50282 50283 50284

Mobile detector and probes


E27131 / 27129

XRM and XP15 probe XRM and XP50 probe XRM and XP100 probe XRM and XP50 + XP100 probes
on P12 P50 P100

50277 50287 50288 50289

MERLIN GERIN
vigidix

RM 10N

XP15 probe
50494

Empty case for mobile fault locating kit


50285

Auxiliaries
Vigilohm TR22A TR22AH EM9 EM9B EM9BV EM9T b (1) b (1) b (1) b (1) v TR5A SM21

"250 V" Cardew C or b "440 V" Cardew C or b "660 V" Cardew C or b "1 000 V" Cardew C b Cardew C base v P1 subassembly b ZX limiting impedance v v S3 inductive neutral point v v b compulsory auxiliary v optional auxiliary (1) Use of the Cardew C is not compulsory with the EM9T.

50170 50171 50172 50183 50169 50211 50159 50113

57

Catalogue numbers

Vigilohm System

Monitors
Type of installation to be monitored: XM300C Single phase auxiliary power supply (V) AC or mixed IT DC or rectified
E27126
MERLIN GERIN
vigilohm system XM300c
test

Neutral distributed Neutral not distributed Line voltage

Voltage < 760 V AC (45/400 Hz) Voltage < 440 V AC (45/400 Hz) < 500 V DC 50540 50541 50542 50543 50727 50728 50729 50730

valeur 040 K TEST

d'isolement MENU

115/127 V AC 50/60 Hz 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz 115/127 V AC 50/60 Hz 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz

E27115

MERLIN GERIN
vigilohm system XM200
test

XM200 Single phase auxiliary power supply (V)

Sp

Sa
S

menu

ok

test

Monitors-locators
MERLIN GERIN

E32439

vigilohm XML31 6

system

test

1 9

10 11 12 13 14 15 16

valeur d'isolement 040 K MENU TEST

Type of installation to be monitored: see XM300C IMD XML308 Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz XML316 Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz Type of installation to be monitored: see XM300C IMD XL308 Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz XL316 Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz Type of installation to be monitored: see XM300C IMD XD308C Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz Type of installation to be monitored: see XM200 IMD XD301 Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz XD312 Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz

50490 50491 50492 50493 50322 50323 50324 50325

Locators
E32441
MERLIN GERIN
vigilohm system XL316
test

1 9

10 11 12 13 14 15 16

test/reset

50606 50607 50608 50609 50615 50616 50617 50618

Detectors
MERLIN GERIN
vigilohm system XD308c
test

on

test

reset

50723 50724 50725 50726

E32443

MERLIN GERIN
vigilohm system

XD301

test

reset
50507

50506 50507 50508 50509 50535 50536 50537 50538

E27126

E27125

1 4 7

2 5 8

3 6 9

MERLIN GERIN
vigilohm system

XD312

test

10 11 12
50536

reset

58

Catalogue numbers

Vigilohm System: accessories

Toroids
Closed toroid TA30 PA50 IA80 MA120 SA200 GA300 Opening toroid POA GOA 50485 50486
E27128

50437 50438 50439 50440 50441 50442

E27127

Shielded pair coil


Roll of 20 m Roll of 100 m 50137 50136

Interfaces
MERLIN GERIN
vigilohm system XD308c
test

on

test

reset

XAS For operation of Vigilohm System bus without XLI300 or XTU300 (bus power supply) Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz XLI300 External transmission of Vigilohm System information on Jbus (bus power supply) Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz XTU300 External transmission of Vigilohm System information on Jbus Controls a configuration with multi IMDs/locators/communicating detectors (bus power supply) Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz XLI200 External transmission of Vigilohm System information on Jbus (bus power supply) Single phase auxiliary power 220/240 V AC 50/60 Hz supply (V) 380/415 V AC 50/60 Hz XRM mobile detector and XP15 probe XRM mobile detector and XP50 probe XRM mobile detector and XP100 probe XRM mobile detector and XP50 + XP100 probes Empty case for mobile fault locating kit Probe XP15 Cardew base Cardew cartridge

E32433

50520 50521 50522 50523

(*)

(*)

E32434

MERLIN GERIN
vigilohm system XLI300

dfaut

50515 50516 50517 50518

(*)

E32435

MERLIN GERIN
vigilohm system XTU300

dfaut

50545 50546 50547 50548

50501 50502 50277 50287 50288 50289 50285 50494 50169 50170 50171 50172 50183

Mobile detector and probes


E27131 / 27129

on

P12

P50 P100

MERLIN GERIN
vigidix

RM 10N

Cardew surge limitor


250 V 440 V 660 V 1000 V
E36226

Additional subassembly
E36227

Used with XM300C or CML308/316 IMDs Type XM300C or CML308/316 AC or mixed IT IMDs

Neutral distributed Neutral not distributed

DC or rectified PHT1000

Line voltage

760 V AC < U < 1700 V AC (45/400 Hz) 440 V AC < U < 1000 V AC (45/400 Hz) 500 V DC < U < 1200 V DC 50248

Zx limiting impedance
Zx subassembly 50159

(*) Consult us.

59

60

Schneider Electric Industries SAS