You are on page 1of 20

42EM

Ducted Fan Coil Unit

Selection manual

Contents
1 - FUNCTIONS................................................................................................................................................................................ 3
2 - FEATURES.................................................................................................................................................................................. 3
2.1 - Configuration flexibility............................................................................................................................................................ 3
2.2 - Low noise levels........................................................................................................................................................................ 3
2.3 - Compact design ........................................................................................................................................................................ 3
2.4 - Physical and electrical data...................................................................................................................................................... 4
2.5 - Dimensional drawings ............................................................................................................................................................. 5
3 - MAIN MODULES AND COMPONENTS............................................................................................................................ 8
3.1 - Fan motor assembly.................................................................................................................................................................. 8
3.2 - Water coil.................................................................................................................................................................................... 8
3.3 - One-piece condensate drain pan............................................................................................................................................. 8
3.4 - Filter and filter access............................................................................................................................................................... 8
3.5 - Fresh air controller.................................................................................................................................................................... 8
3.6 - Electric heater............................................................................................................................................................................ 9
4 - TECHNICAL SPECIFICATIONS........................................................................................................................................... 9
4.1 - Valves (option)........................................................................................................................................................................... 9
4.2 - Technical specification, flexible water pipes (option)............................................................................................................ 9
5 - Control (OPTION)............................................................................................................................................................ 10
6 - Atmosphera performance data......................................................................................................................... 11
6.1 - Cooling capacity - water coil.................................................................................................................................................. 11
6.2 - Heating capacity - water coil.................................................................................................................................................. 12
6.3 - Sound power levels................................................................................................................................................................. 15
6.4 - Electrical data.......................................................................................................................................................................... 16
6.5 - Water coil pressure drop . ...................................................................................................................................................... 18
6.6 - Air flow data............................................................................................................................................................................ 18
7 - codification ..................................................................................................................................................................... 20
8 - SPECIFICATION GUIDE...................................................................................................................................................... 20

The photograph on the front cover is for illustrative purposes only and is not part of any offer for sale or contract. The
manufacturer reserves the right to change the design at any moment without prior warning.


1 - FUNCTIONS

The 42EM Atmosphera from Carrier is available in eight


sizes with 2-pipe, 2-pipe plus electric heater or 4-pipe
coils, with an air flow range from 66 to 259 l/s, a nominal
cooling capacity range from 1.3 to 7.3 kW and a nominal
heating capacity range from 1.5 to 8.6 kW.
Decentralised, compact ducted unit, designed for false
ceiling installation.
Reliable and economical for light commercial and
office applications.
Low height of 225 or 250 mm.
Two versions for increased installation flexibility:
modular or compact.
Compatible with the Carrier 35BD/SR diffuser range.
Air outlet configuration modularity with different
plenums.
Extremely low sound levels for ducted applications.
Six-speed fan motor offers a wide choice of medium
speeds.
High-pressure centrifugal fan.
High-efficiency EU3 filters.
Safe factory-installed electric heater with one or two
capacity stages.
Low water pressure drop with factory-installed valves.
Factory-installed options (valves and controllers) for
fast and easy installation in false ceilings.

Filter

NOTE: Carrier recommends not to exceed an air velocity


of 4 m/s (125 l/s) per spigot.

One-piece compact in-line units (for sizes 1, 2, 3) are


models with in-line ducted supply and return air (only
125 mm diameter fresh air ducts can be connected on
the sides).
Size 1

Sizes 2 et 3

This version does not allow the use of 200 mm diameter


spigots on the sides. Filter removal is from below.

2 - FEATURES
2.1 - Configuration flexibility
Depending on the size, several motor drive selections are
available:
Sizes 0.5 and 1: one motor drive
Sizes 2 and 3: three motor drive selections possible
There are two unit models available:
modular models for all sizes, offering maximised
flexibility with side connection spigots.
This model consists of a non-ducted base unit. In this
configuration filter removal is from the rear:

In order to further enhance occupant comfort this product


range offers especially low noise levels. The casing of the
42EM Atmosphera is made of galvanised sheet steel with
full high-efficiency internal lining for optimised thermal
and sound insulation of the unit.
In order to comply with the various local regulations (fire
class) the 42EM Atmosphera is available with class M1
type insulation. It is also equipped with anti-vibration
mounts as standard.

Filter

In models with ducted return air it is possible to add a


factory-assembled return air plenum.
Connection possibilities

Accessory
return air plenum

Base unit

Base unit

Sizes 2 and 3
Accessory
return air plenum

Size 1

Size 0.5
Accessory
return air plenum

2.2 - Low noise levels

Base unit

2.3 - Compact design


The condensate removal pan height is optimised at 215 mm.
In order to reduce the dimensions of the 42EM Atmosphera
to the minimum, the units are equipped with high-efficiency
heat exchangers with very high cooling capacity/treated air
flow ratios.

2.4 - Physical and electrical data



42EM 0.5
42EM 1.0
42EM 2.1
42EM 2.2
Fan speed
L
M
H
L
M
H
L
M
H
L
M
H
Air flow
l/s
66
97
104
75
122
136
73
143
156
96
183
207
Available static pressure
Pa
23
50
58
19
50
62
13
50
60
14
50
64
Cooling mode
Total cooling capacity
kW
1.26
1.75
1.85
1.92
2.90
3.18
1.99
3.63
3.92
2.54
4.47
4.94
Sensible capacity
kW
1.01
1.43
1.52
1.42
2.20
2.43
1.44
2.69
2.92
1.85
3.36
3.74
Water flow rate
l/s
0.06
0.08
0.09
0.09
0.14
0.15
0.10
0.17
0.19
0.12
0.21
0.24

l/h
217
301
318
331
499
547
342
624
674
437
769
850
Water pressure drop
kPa
6
10
11
19
37
43
9
26
29
14
37
48
Water content
l
0.7
0.7
0.7
1
1
1
1.7
1.7
1.7
1.7
1.7
1.7
Heating mode - 2 pipes
Heating capacity
kW
1.92
2.71
2.89
2.33
3.59
3.96
2.37
4.41
4.77
3.03
5.50
6.10
Heating mode - 4 pipes
Heating capacity
kW
1.52
2.00
2.10
1.67
2.38
2.57
1.74
2.89
3.08
2.14
3.45
3.75
Water flow rate
l/s
0.04
0.05
0.05
0.04
0.06
0.06
0.04
0.07
0.07
0.05
0.08
0.09

l/h
134
175
185
144
205
221
150
249
265
184
297
323
Water pressure drop
kPa
3
4
5
5
9
10
3
13
15
7
20
23
Water content
l
0.15
0.15
0.15
0.2
0.2
0.2
0.3
0.3
0.3
0.3
0.3
0.3
Electric heater
230 V - 1 ph - 50 Hz 15%
Maximum capacity
W
1000
1000
1000
2000
Current drawn
A
4.35
4.35
4.35
8.7
Sound levels
Sound power level (return and radiated)
dB(A) 43
51
53
41
51
53
39
46
49
41
55
58
Sound power level (supply)
dB(A) 42
49
50
38
49
51
38
44
47
40
54
56
Sound pressure level
dB(A) 29
36
38
25
35
38
23
30
34
25
39
42
NR value*
24
31
33
19
30
33
17
25
28
19
33
37
Motor electrical data

230 V - 1 ph - 50 Hz 15%
Power input
W
45
77
102
40
80
110
58
97
104
70
120
140
Current drawn
A
0.20
0.34
0.45
0.17
0.35
0.48
0.27
0.45
0.49
0.30
0.50
0.63
Air filter G3
mm
230 x 408
208 x 578
208 x 978
208 x 978
Technical data
Connection diameters, cold- and hot water coils
inch
1/2 gas (union nut female)
Connection spigot diameter
mm
200
200
200
200
Height
mm
250
250
250
250
Depth
mm
700
810
810
810
Length
mm
1015
870
1270
1270
Unit weight
kg
22
35
53
53

42EM 2.3
42EM 3.1
42EM 3.2
42EM 3.3
Fan speed
L
M
H
L
M
H
L
M
H
L
M
H
Air flow
l/s
153
256
259
73
143
156
96
183
207
153
256
259
Available static pressure
Pa
18
50
51
13
50
60
14
50
64
18
50
51
Cooling mode
Total cooling capacity
kW
3.86
5.87
5.96
2.33
4.34
4.69
2.99
5.38
5.97
4.62
7.15
7.26
Sensible capacity
kW
2.87
4.52
4.59
1.59
3.01
3.26
2.05
3.77
4.20
3.21
5.09
5.17
Water flow rate
l/s
0.18
0.28
0.28
0.11
0.21
0.22
0.14
0.26
0.29
0.22
0.34
0.35

l/h
664
1010
1025
401
746
807
514
925
1027
795
1230
1249
Water pressure drop
kPa
29
60
62
9
25
30
13
35
45
29
70
71
Water content
l
1.7
1.7
1.7
1
1
1
1.7
1.7
1.7
1.7
1.7
1.7
Heating mode - 2 pipes
Heating capacity
kW
4.69
7.32
7.46
2.59
4.94
5.36
3.34
6.21
6.90
5.27
8.45
8.59
Heating mode - 4 pipes
Heating capacity
kW
3.05
4.36
4.41
1.66
2.92
3.14
2.08
3.56
3.92
3.10
4.63
4.70
Water flow rate
l/s
0.07
0.10
0.11
0.04
0.07
0.08
0.05
0.09
0.09
0.07
0.11
0.11

l/h
262
375
379
143
251
270
179
306
337
267
398
404
Water pressure drop
kPa
14
29
30
6
16
19
9
23
27
18
32
34
Water content
l
0.3
0.3
0.3
0.2
0.2
0.2
0.3
0.3
0.3
0.3
0.3
0.3
Electric heater
230 V - 1 ph - 50 Hz 15%
Maximum capacity
W
2000
1000
2000
2000
Current drawn
A
8.7
4.35
8.7
8.7
Sound levels
Sound power level (return and radiated)
dB(A) 45
58
60
39
46
49
41
55
58
45
58
60
Sound power level (supply)
dB(A) 45
58
59
38
44
47
40
54
56
45
58
59
Sound pressure level
dB(A) 31
43
45
23
30
34
25
39
42
31
43
45
NR value*
25
39
41
17
25
28
19
33
37
25
39
41
Motor electrical data

230 V - 1 ph - 50 Hz 15%
Power input
W
100
174
197
58
97
104
70
120
140
100
174
197
Current drawn
A
0.44
0.77
0.90
0.27
0.45
0.49
0.30
0.50
0.63
0.44
0.77
0.90
Air filter G3
mm
208 x 978
208 x 978
208 x 978
208 x 978
Technical data
Connection diameters, cold- and hot water coils
inch
1/2 gas (union nut female)
Connection spigot diameter
mm
200
200
200
200
Height
mm
250
250
250
250
Depth
mm
810
990
990
990
Length
mm
1270
1270
1270
1270
Unit weight
kg
53
69
69
69
Legend:
Fan speed: L = Low, M = Medium, H = High
Based on Eurovent rating standards:
Cooling: Entering/leaving air temperature = 27C db/19C wb entering/leaving water temperature = 7C/12C
Heating (2 pipes): Entering air temperature = 20C, entering water temperature = 50C, same water flow rate as in cooling
Heating (4 pipes): Entering air temperature = 20C, entering/leaving water temperature = 70C/60C
* Based on a hypothetical acoustic attenuation for the room and the air distribution system of -18 dB(A)

2.5 - Dimensional drawings (dimensions in mm)


Size 0.5 - Modular model (with optional1012
return air plenum)
242

770

60

726

22

250

215

60

120

115
308

34

10
12

41

Return air
plenum
199

45

16

18

Size 1 - Modular model (with optional return air plenum)

120

19

60

770
726

248

Return air
plenum

225

215

1050
22
250

280

248

145

59

10

50

67

199

30
16

7
18

62

Size 1 - Compact in-line model, ducted return air


60

60

Size 2 - Modular model (with optional return air plenum)


60

60

Return air
plenum

Size 2 - Compact in-line model, ducted return air


60

60

Size 3 - Modular model (with optional return air plenum)

Return air plenum


60

60

Left-hand connections

Right-hand connections

Size 3 - Compact in-line model, ducted return air

60

60

Left-hand connections

60

60

Right-hand connections

3 - MAIN MODULES AND COMPONENTS

3.3 - One-piece condensate drain pan

3.1 - Fan motor assembly

Pan with a 16 mm external drain connection diameter and


insulation class M1 in accordance with standard NFP 92-507.

Description/codification

3.4 - Filter and filter access


The Carrier 42EM Atmosphera is fitted with a nonregenerable EU3 filter according to standard EN 779,
medium fire rating M1, metal wire frame.

Unit size (chassis): 0, 1, 2, 3


Fan motor assembly size: 0, 1, 2, 3, 5

Asynchronous motors, 230 V - 1 ph - 50 Hz, 4 poles


with internal overload protection.
Permanent capacitor.
Class B winding insulation, varnish class F.

The 42EM Atmosphera sizes 0 and 1 have a multi-speed


fan motor assembly with forward-curved, double-inlet,
single-wheel fans. Sizes 2 and 3 can be equipped with three
double-wheel fan-motor assembly sizes (1, 2 or 3), depending
on the required air flows/pressures.
Six speeds are available as standard. From these three speeds
must be selected to allow connection of the fan motor in
accordance with the applicable electromechanical or
electronic regulations.
Minimum speed: terminal 6
Maximum speed: terminal 1
As standard, 42EM units are prewired to the factory
settings, for speeds 1, 3 and 5.
For other fan motor speed wiring combinations refer
to the unit codification.
Fan motor assembly
= Terminal 6
= Terminal 1
= Red wire
= Grey wire
= Black wire
= Live

3.2 - Water coil





Aluminium fins mechanically bonded by expansion


onto copper tubes
1/2 threaded water inlet and outlet connections
(female)
Air purge valves and drain are standard.
Service pressure 1600 kPa.

The coil is integral with the drain pan and coil access door
to ease of removal during service and maintenance.
NOTE: The connection side for the coil can be changed
on site, by turning the coil. Remember to reverse the water
entering/leaving sides for size 3 (42EM models 3.1, 3.2
and 3.3).


3.5.1 - Constant volume fresh air controller


The 42EM Atmosphera can be fitted with a constant fresh
air flow controller allowing the introduction of fresh air and
the air change rate to be controlled. The fresh air supply is
normally located ahead of the water coil.
The following range of fresh air controllers is available:
Option a: 8.3 l/s (30 m3/h) (-10%; +20%)
Option b: 16.6 l/s (60 m3/h) (-10%; +20%)
Options a and b: the diameter of the spigot housing the
fresh air flow controller is 125 mm.
The 16.6 1/s (60 m3/h) or fresh air controller may be modified
on site by relocating or removing two plastic restrictors in
order to increase the maximum constant fresh air flow
capacity to 44.4 1/s (160 m3/h).
IMPORTANT: If the Atmosphera is fitted with a return
air temperature sensor, the constant fresh air flow rate
must not exceed 50% of the unit supply air flow rate at
minimum speed.
NOTE: To operate correctly, the 8.3 l/s or 30 m3/h
constant fresh-air flow controller requires a differential
pressure in the range of 50 Pa to 200 Pa. The 16.6 l/s or
60 m3/h con-stant fresh-air flow controller requires a
differential pres-sure in the range of 70 to 200 Pa.

Red
Grey
Black

Minimum speed
Maximum speed
Low speed
Medium speed
High speed
L

3.5 - Fresh air controller

3.5.2 - Variable volume fresh air controller


The 42EM Atmosphera can be equipped with an optional
variable fresh air flow controller from 0 to 55 l/s (0 to 200
m3/h).
This is connected to the numeric Carrier controller and
can regulate the fresh air intake in two ways:
either using a fixed rate set by the installer that can be
reconfigured as required
or based on the CO2 level; in this case it is connected
to a CO2 sensor via the Carrier numeric controller
(the CO2 sensor is located opposite the fresh air inlet).
NOTE: With the variable fresh air flow controller the
upstream pressure in the fresh air duct must be 180 Pa.

Electric heater-resistance wire type


Supply voltage: 230 V - 1 ph - 50 Hz
Heater size and capacity per unit:

- Size 0.5, 1.0: 500 or 1000 W (+5%; -10%)

- Sizes 2.1, 3.1: 500 or 1000 W (+5%; -10%)

- Sizes 2.2, 2.3, 3.2, 3.3: 1000 or 2000 W(+5%; -10%)
The heater is protected with a dual safety device:

a) Self-holding automatically reset integrated safety
thermostat

b) Destructive thermofuse link
NOTE: Minimum air flow must be maintained to avoid
damaging the electric heaters:
Unit sizes 0.5, 1.0: minimum air flow 28 l/s (100 m3/h)
Unit sizes 2.1, 3.1: minimum air flow 42 l/s (150 m3/h)
Unit sizes 2.2, 2.3, 3.2, 3.3: minimum air flow 55 l/s
(200 m3/h)
4 - TECHNICAL SPECIFICATIONS

4.1.4 - Water valve pressure drop


4
3
2
1

Water flow rate, l/s (l/h)

3.6 - Electric heater (option)

Pressure drop, kPa


Legend:

Kvs = 0.63

Kvs = 1

Kvs = 1.6

Kvs = 2.5

4.2 - Technical specification, flexible water pipes


(option)

4.1 - Valves (option)


It should be noted that the valve body is the same for whatever controller option is chosen.
4.1.1 - Electrothermal actuator (on/off)
The actuator is a 230 V a.c. on/off type. Linear movement is
provided by the expansion and contraction of a wax element
heated by an electrical resistor.
4.1.2 - Two-way valve body
Features of the 1/2 two-way valve
1/2 male BSP connection for union nuts
Straight valve body with arrow indicating direction of
flow embossed on valve body
Nominal size DN 15 for 1/2 valve
Fluid: water and glycol solution (max. 40% glycol)
Operating range: 2-90C
Nominal pressure: PN 16 bar
4.1.3 - Three-way valve body (with integral bypass)
Features of the 1/2 three-way valve
1/2 male BSP connection for union nuts
Straight valve body with arrow indicating direction of
flow embossed on valve body
Nominal size DN 15 for 1/2 valve
Fluid: water and glycol solution (max. 40% glycol)
Operating range: 2-90C
Nominal pressure: PN 16 bar

4.2.1 - Materials
Pipes: MEPD-based elastomer (modified ethylenepropylene-diene)
Braid: 304L stainless steel
Insulation: cellular foam rubber with M1 fire rating
(9 mm thick, flexible water pipes).
4.2.2 - Characteristics
Minimum bend radius: 106 mm
Ten-year guarantee
The flexible water pipes are designed for treated or
untreated water (maximum 40% ethylene glycol or
propylene glycol).
Maximum hot water temperature 90C
Maximum operating pressure: 16 bar
1/2 flat gas connections
Length: 1 m.

5 - Control (OPTION)
The Atmosphera can be supplied with a wide range of
Carrier controls. These offer functions to suit the various
application requirements, summarised in the table below.
Control
algorithms

On-Off
Proportional-integral
Valve
Air flow control only (no valve)
management
On-off actuators
Proportional valves
Fan control
Three speeds
Automatic fan speed selection
Main functions Setpoint control
Occupied/unoccupied mode
Frost protection mode
Window contact input
Measurement of water inlet
temperature for automatic
seasonal changeover (2 pipes)
Automatic seasonal changeover
(4 pipes and 2 pipes + electric
heater)
Manual changeover
Continuous ventilation within
dead-band
Periodical ventilation within
dead-band
Unit grouping
Louvre control
On-site configuration
Supply air temperature
monitoring limiting
Communication (CCN)
Electrical heater loadshed
Dirty filter alarm
Alarm reporting
IAQ control
Demand control ventilation
(DCV)
Free cooling mode
User interface Digital display
Automatic or manual fan speed
control
Operating mode selection
Eco/unoccupied button

Thermostats HDB
X
X

NTC
X

X
X

X
X

X
X
X
X
X
X
Type A

X
X
X
X
X
X
X

X
O
X
X
X
X
X
X
X

Type B

X
X

X
X

X
X

X
X
X

X
X
X
X
X
X
X
X
O
O

X
X

O
X
X

X
X

X
X

X
X

Legend:
HDB Hydronic Dual Boaord
NTC New Terminal Controller
X
Standard function
O
Available as an option

NOTE: For the features and specifications of the Carrier


controllers refer to the technical documentation for each
controller.
Upon special request other controller types can be factoryinstalled on the units (supplied by Carrier or the customer).

10

6 - Atmosphera performance data


6.1 - Cooling capacity - water coil
Entering/
leaving water
temp. (C)
6-12

7-12

8-13

10-15

TC
SHC
TSA
AF
TC
SHC
TSA
AF
TC
SHC
TSA
AF
TC
SHC
TSA
AF

Size 0.5
Relative humidity 50%
Air flow l/s (m3/h)
28 (100)
56 (200)
Dry bulb temperature at coil inlet (C)
27
25
23
27
25
0.62
0.50
0.40
1.15
0.88
0.45
0.40
0.36
0.85
0.74
13.7
13.1
12.5
14.3
14.0
89
72
58
165
127
0.63
0.49
0.39
1.18
0.90
0.45
0.39
0.35
0.86
0.75
13.6
13.3
12.7
14.1
13.8
108
84
67
202
155
0.56
0.44
0.35
1.04
0.79
0.42
0.37
0.33
0.81
0.70
14.5
14.0
13.4
15.0
14.6
96
75
60
179
136
0.43
0.34
0.28
0.79
0.61
0.37
0.33
0.28
0.70
0.60
16.0
15.3
14.8
16.5
16.1
75
59
48
137
106

Size 1.0
Relative humidity 50%
Entering/
Air flow l/s (m3/h)
leaving water
56 (200)
83 (300)
temp. (C)
Dry bulb temperature at coil inlet (C)
27
25
23
27
25
23
6-12
TC
1.58 1.24 0.95 2.26 1.78 1.36
SHC
1.08 0.95 0.82 1.57 1.38 1.19
TSA
10.8 10.9 10.8 11.2 11.2 11.1
AF
226
178
136
324
255
195
7-12
TC
1.56 1.23 0.94 2.23 1.76 1.34
SHC
1.07 0.94 0.82 1.56 1.37 1.19
TSA
10.9 11.0 10.9 11.3 11.3 11.2
AF
268
211
161
384
302
231
8-13
TC
1.40 1.08 0.81 2.00 1.54 1.17
SHC
1.01 0.88 0.76 1.46 1.27 1.10
TSA
11.9 12.0 11.8 12.3 12.3 12.1
AF
241
185
140
344
265
201
10-15 TC
1.08 0.81 0.64 1.55 1.17 0.92
SHC
0.87 0.75 0.63 1.27 1.10 0.92
TSA
14.0 13.8 13.6 14.2 14.0 13.9
AF
186
140
110
266
201
158
Size 2.1
Relative humidity 50%
Entering/
Air flow l/s (m3/h)
leaving water
83 (300)
125 ( 450)
temp. (C)
Dry bulb temperature at coil inlet (C)
27
25
23
27
25
23
6-12
TC
2.42 1.90 1.46 3.49 2.74 2.10
SHC
1.64 1.44 1.25 2.40 2.11 1.83
TSA
10.5 10.6 10.6 10.9 11.0 10.9
AF
346
272
209
500
393
301
7-12
TC
2.38 1.87 1.43 3.44 2.71 2.07
SHC
1.62 1.42 1.24 2.38 2.09 1.81
TSA
10.6 10.7 10.7 11.0 11.1 11.0
AF
410
322
246
591
465
355
8-13
TC
2.14 1.64 1.25 3.09 2.37 1.81
SHC
1.52 1.32 1.15 2.23 1.94 1.68
TSA
11.7 11.7 11.6 12.1 12.1 11.9
AF
368
282
214
531
407
310
10-15 TC
1.65 1.24 0.97 2.38 1.80 1.42
SHC
1.32 1.15 0.97 1.94 1.68 1.42
TSA
13.7 13.5 13.4 14.0 13.8 13.6
AF
283
214
167
409
310
244

Legend:
TC - Total cooling capacity (kW)
SHC - Sensible cooling capacity (kW)
TSA - Supply air temperature (C)
AF - Water flow rate (l/h)

83 (300)
23
0.68
0.64
13.5
97
0.69
0.65
13.4
119
0.61
0.60
14.1
105
0.49
0.49
15.8
84

27
1.62
1.22
14.7
232
1.66
1.24
14.5
285
1.46
1.16
15.4
252
1.12
1.01
16.8
193

25
1.24
1.07
14.3
178
1.27
1.08
14.2
218
1.12
1.01
14.9
192
0.87
0.86
16.4
151

111 (400)
27
2.90
2.04
11.6
415
2.86
2.02
11.7
491
2.56
1.90
12.7
440
1.98
1.66
14.5
342

25
2.29
1.80
11.5
328
2.25
1.78
11.6
387
1.98
1.66
12.5
341
1.51
1.43
14.3
260

111 (400)
23
0.96
0.92
13.9
137
0.98
0.93
13.7
168
0.87
0.86
14.5
150
0.69
0.69
16.1
119

27
2.06
1.58
15.1
295
2.09
1.60
15.0
359
1.86
1.50
15.7
319
1.43
1.32
17.1
247

139 (500)
23
1.76
1.56
11.4
252
1.73
1.55
11.5
297
1.51
1.43
12.3
260
1.19
1.19
14.1
206

27
3.48
2.49
12.0
498
3.44
2.47
12.1
591
3.07
2.32
13.1
529
2.38
2.03
14.8
410

25
2.75
2.20
11.9
394
2.71
2.18
12.0
466
2.39
2.03
12.8
410
1.84
1.76
14.5
317

139 (500)

25
1.58
1.39
14.7
227
1.62
1.40
14.5
279
1.43
1.31
15.2
245
1.13
1.12
16.7
194

23
1.23
1.19
14.2
176
1.26
1.21
14.0
216
1.12
1.11
14.8
193
0.89
0.89
16.4
153

27
1.48
1.44
14.4
213
1.51
1.47
14.3
260
1.35
1.35
15.0
233
1.08
1.08
16.6
185

167 (600)
23
2.13
1.91
11.6
305
2.10
1.90
11.7
360
1.84
1.76
12.6
317
1.46
1.46
14.3
251

27
4.02
2.91
12.4
575
3.98
2.89
12.5
684
3.56
2.72
13.4
611
2.76
2.38
15.1
474

25
3.18
2.57
12.2
455
3.13
2.55
12.3
538
2.76
2.39
13.1
474
2.14
2.06
14.7
369

23
2.44
1.91
15.5
349
2.46
1.92
15.4
424
2.19
1.81
16.1
377
1.72
1.60
17.4
296

27
2.57
2.04
15.6
369
2.61
2.05
15.6
448
2.32
1.93
16.2
399
1.82
1.70
17.5
313

23
2.48
2.25
11.9
355
2.43
2.23
12.0
418
2.15
2.07
12.8
370
1.71
1.71
14.5
295

27
4.26
3.10
12.6
610
4.22
3.08
12.6
725
3.77
2.90
13.5
648
2.92
2.54
15.2
503

25
3.37
2.74
12.3
482
3.32
2.72
12.4
571
2.93
2.55
13.2
503
2.28
2.20
14.8
393

25
2.02
1.80
15.0
289
2.05
1.82
15.0
352
1.82
1.70
15.6
313
1.45
1.45
17.0
250

23
1.58
1.54
14.5
226
1.61
1.57
14.4
277
1.44
1.44
15.1
248
1.15
1.15
16.7
197

194 (700)
23
2.64
2.40
12.0
378
2.58
2.38
12.1
444
2.29
2.20
12.9
393
1.83
1.83
14.6
315

27
4.51
3.31
12.7
646
4.47
3.29
12.8
769
3.99
3.09
13.7
687
3.10
2.71
15.3
534

25
3.57
2.92
12.5
511
3.52
2.91
12.5
605
3.10
2.72
13.4
534
2.43
2.35
14.9
417

23
2.80
2.56
12.1
400
2.74
2.54
12.2
471
2.43
2.35
13.0
418
1.95
1.95
14.7
335

Size 2.3

167 (600)
25
3.54
2.75
11.3
507
3.48
2.73
11.4
598
3.05
2.54
12.3
525
2.34
2.21
14.0
402

25
1.90
1.68
14.9
272
1.93
1.70
14.8
332
1.71
1.59
15.5
294
1.36
1.36
16.9
235

180 (650)

Size 2.2

27
4.48
3.13
11.3
642
4.42
3.10
11.5
760
3.96
2.90
12.5
681
3.05
2.53
14.3
526

150 540)

208 (750)
23
2.72
2.39
11.2
390
2.68
2.38
11.3
460
2.34
2.21
12.1
403
1.84
1.84
13.9
318

27
5.38
3.80
11.7
770
5.31
3.77
11.8
913
4.75
3.54
12.8
817
3.67
3.09
14.6
631

25
4.25
3.35
11.6
608
4.18
3.32
11.7
718
3.67
3.10
12.6
631
2.83
2.70
14.3
487

264 (950)
23
3.29
2.93
11.4
471
3.23
2.90
11.5
555
2.84
2.70
12.3
488
2.25
2.25
14.1
387

27
6.51
4.67
12.2
932
6.44
4.64
12.3
1106
5.75
4.36
13.2
989
4.44
3.82
14.9
765

25
5.13
4.13
12.0
735
5.05
4.10
12.1
869
4.45
3.83
13.0
765
3.46
3.33
14.6
596

319 (1150)
23
4.01
3.61
11.7
574
3.93
3.58
11.8
675
3.47
3.33
12.6
597
2.77
2.77
14.4
477

27
7.53
5.49
12.6
1078
7.46
5.45
12.7
1281
6.65
5.12
13.6
1144
5.15
4.49
15.2
886

25
5.93
4.85
12.4
849
5.85
4.82
12.5
1005
5.15
4.50
13.3
886
4.04
3.91
14.8
695

347 (1250)
23
4.65
4.25
12.0
666
4.56
4.21
12.1
784
4.05
3.91
12.9
696
3.25
3.25
14.6
559

27
8.02
5.89
12.8
1148
7.95
5.86
12.9
1366
7.09
5.50
13.7
1219
5.50
4.83
15.4
946

25
6.31
5.20
12.5
904
6.23
5.17
12.6
1072
5.50
4.84
13.4
946
4.32
4.20
15.0
743

23
4.97
4.56
12.2
711
4.87
4.52
12.2
838
4.33
4.20
13.0
745
3.48
3.48
14.7
599

NOTE: Operating limits: air discharge temperature 12C


when the unit is installed in an ambient temperature of
27C dry bulb and 65% relative humidity.

NOTE: To convert l/h to l/s, divide by 3600.

11

6.1 - Cooling capacity - water coil (cont.)


Size 3.1
Relative humidity 50%
Entering/
Air flow l/s (m3/h)
leaving water
83 (300)
125 ( 450)
temp. (C)
Dry bulb temperature at coil inlet (C)
27
25
23
27
25
23
6-12
TC
2.88 2.36 1.88 4.20 3.43 2.72
SHC
1.85 1.64 1.44 2.72 2.41 2.12
TSA
8.3
8.5
8.6
8.7
8.9
9.0
AF
413
338
269
601
492
390
7-12
TC
2.78 2.27 1.79 4.06 3.30 2.60
SHC
1.80 1.60 1.40 2.65 2.35 2.06
TSA
8.8
9.0
9.0
9.2
9.3
9.3
AF
477
389
308
697
567
446
8-13
TC
2.54 2.04 1.57 3.70 2.96 2.30
SHC
1.69 1.49 1.30 2.49 2.20 1.92
TSA
9.9
10.0 10.1 10.2 10.3 10.3
AF
437
350
270
637
509
395
10-15 TC
2.06 1.57 1.19 2.99 2.29 1.73
SHC
1.49 1.29 1.12 2.18 1.91 1.65
TSA
12.0 12.1 11.9 12.3 12.3 12.1
AF
354
270
204
514
395
298

Size 3.2

Size 3.3

167 (600)
27
5.46
3.56
9.1
781
5.26
3.47
9.6
905
4.80
3.26
10.6
825
3.87
2.87
12.6
666

25
4.46
3.17
9.2
639
4.29
3.09
9.6
736
3.84
2.89
10.6
661
2.95
2.50
12.5
508

208 (750)
23
3.53
2.77
9.2
505
3.37
2.70
9.6
579
2.95
2.51
10.6
508
2.26
2.16
12.3
388

27
6.60
4.34
9.5
945
6.38
4.24
9.9
1096
5.80
3.99
10.9
998
4.67
3.51
12.9
804

Legend:
TC - Total cooling capacity (kW)
SHC - Sensible cooling capacity (kW)
TSA - Supply air temperature (C)
AF - Water flow rate (l/h)

264 (950)

25
5.40
3.87
9.5
773
5.18
3.77
9.9
890
4.64
3.53
10.9
799
3.59
3.07
12.8
617

23
4.27
3.40
9.5
612
4.09
3.31
9.9
702
3.59
3.08
10.8
617
2.75
2.65
12.5
473

27
8.04
5.35
10.0
1151
7.79
5.24
10.4
1339
7.08
4.93
11.4
1217
5.68
4.34
13.3
978

25
6.57
4.77
9.9
941
6.32
4.66
10.3
1086
5.65
4.36
11.3
972
4.38
3.80
13.0
754

319 (1150)
23
5.22
4.20
9.8
748
4.98
4.09
10.2
856
4.39
3.82
11.1
755
3.39
3.28
12.7
583

27
9.38
6.31
10.4
1342
9.10
6.18
10.8
1564
8.26
5.82
11.7
1420
6.61
5.12
13.6
1138

25
7.66
5.63
10.3
1096
7.37
5.50
10.7
1267
6.59
5.15
11.6
1132
5.11
4.50
13.3
880

347 (1250)
23
6.08
4.96
10.2
871
5.81
4.83
10.5
998
5.13
4.51
11.3
882
3.99
3.88
13.0
686

27
10.02
6.77
10.6
1434
9.71
6.64
11.0
1670
8.82
6.25
11.9
1517
7.06
5.51
13.7
1215

25
8.17
6.04
10.5
1170
7.88
5.91
10.8
1353
7.03
5.54
11.7
1209
5.47
4.84
13.4
941

23
6.49
5.33
10.3
930
6.21
5.20
10.6
1067
5.48
4.85
11.4
943
4.28
4.17
13.1
736

NOTE: Operating limits: air discharge temperature 12C


when the unit is installed in an ambient temperature of
27C dry bulb and 65% relative humidity.

NOTE: To convert l/h to l/s, divide by 3600.

6.2 - Heating capacity - water coil


6.2.1 - Two-row changeover coil
Size 0.5
Air flow l/s (m3/h)
Entering/
leaving water 28 (100)
56 (200)
temp. (C)
Dry bulb temperature at coil inlet (C)
21
20
19
21
20
70-60 P
1.42
1.46
1.49
2.81
2.89
TSA
63.1
63.0
62.9
62.0
61.9
AF
125
128
131
247
254
60-50 P
1.09
1.13
1.16
2.15
2.23
TSA
53.3
53.3
53.2
52.4
52.3
AF
95
99
102
188
195
55-40 P
0.81
0.85
0.89
1.59
1.66
TSA
45.1
45.1
45.1
44.2
44.1
AF
47
50
52
93
97
50-40 P
0.76
0.79
0.83
1.49
1.56
TSA
43.4
43.4
43.4
42.7
42.6
AF
66
69
72
129
136

83 (300)
19
2.96
61.8
260
2.30
52.2
201
1.74
44.1
101
1.63
42.6
142

21
4.08
61.0
359
3.12
51.5
273
2.29
43.4
133
2.14
42.0
187

20
4.19
60.9
368
3.22
51.4
282
2.39
43.3
139
2.24
41.9
196

111 (400)
19
4.30
60.8
378
3.33
51.3
291
2.50
43.3
146
2.35
41.8
205

21
5.32
60.0
468
4.05
50.7
354
2.96
42.7
172
2.77
41.3
241

139 (500)

20
5.46
59.8
480
4.18
50.5
366
3.09
42.6
180
2.90
41.2
253

19
5.60
59.7
492
4.32
50.4
378
3.23
42.5
188
3.04
41.1
265

21
6.50
59.0
571
4.94
49.9
433
3.58
42.0
208
3.36
40.7
293

20
6.67
58.9
586
5.11
49.8
447
3.75
41.8
218
3.53
40.6
308

150 (540)
19
6.84
58.7
601
5.27
49.6
461
3.91
41.7
228
3.69
40.4
322

21
6.92
58.7
608
5.25
49.6
460
3.81
41.7
222
3.58
40.5
312

20
7.11
58.5
625
5.43
49.5
475
3.98
41.6
232
3.75
40.4
327

19
7.29
58.4
641
5.62
49.4
492
4.16
41.5
242
3.93
40.2
343

Size 1.0

Air flow l/s (m3/h)


Entering/
leaving water 56 (200)
83 (300)
temp. (C)
Dry bulb temperature at coil inlet (C)

111 (400)

70-60

5.48

60-50

55-40

50-40

HC

TSA
AF

HC

TSA
AF

HC

TSA
AF

HC

TSA
AF

12

139 (500)

167 (600)

180 (650)

194 (700)

21

20

19

21

20

19

21

20

19

21

20

19

21

20

19

21

20

19

21

20

19

63.2

63.1

63.1

62.2

62.1

62.1

61.2

61.1

61.1

60.3

60.2

60.1

59.5

59.4

59.3

59.1

59.0

58.9

58.8

58.6

58.5

2.89
254

2.20
53.0
192

1.54
43.5
90

1.48
42.6
129

2.97
261

2.27
53.0
199

1.62
43.5
94

1.56
42.7
136

3.05
268

2.35
53.0
206

1.70
43.6
99

1.64
42.7
143

4.20
369

3.18
52.1
278

2.22
42.8
129

2.14
41.9
186

4.31
379

3.29
52.1
288

2.33
42.8
136

2.24
41.9
196

4.43
389

3.40
52.0
297

2.45
42.8
143

2.35
41.9
205

481

4.12
51.3
361

2.87
42.1
167

2.76
41.2
240

5.63
494

4.27
51.2
374

3.01
42.0
175

2.90
41.2
253

5.77
508

4.41
51.2
386

3.16
42.0
184

3.04
41.1
265

6.71
589

5.03
50.5
440

3.47
41.3
202

3.34
40.6
292

6.89
605

5.21
50.4
456

3.64
41.3
212

3.52
40.6
307

7.07
622

5.39
50.4
472

3.82
41.2
222

3.69
40.5
322

7.88
693

5.90
49.8
516

4.03
40.7
235

3.90
40.1
340

8.10
712

6.11
49.7
535

4.24
40.6
247

4.11
40.0
358

8.32
731

6.32
49.6
553

4.44
40.6
259

4.31
39.9
376

8.41
740

6.29
49.5
551

4.28
40.4
250

4.16
39.8
362

8.64
760

6.52
49.4
570

4.51
40.3
262

4.37
39.7
381

8.87
780

6.74
49.3
590

4.73
40.3
275

4.59
39.7
400

8.98
789

6.71
49.2
587

4.55
40.1
265

4.42
39.6
386

9.23
811

6.95
49.1
608

4.79
40.1
279

4.65
39.5
406

9.47
833

7.19
49.0
629

5.02
40.0
293

4.89
39.4
426

6.2 - Heating capacity - water coil (cont.)


Size 2.1
Entering/
leaving water
temp. (C)
70-60

60-50

55-40

50-40

HC

TSA
AF

HC

TSA
AF

HC

TSA
AF

HC

TSA
AF

Air flow l/s (m3/h)


83 (300)

Size 2.2
125 (450)

Dry bulb temperature at coil inlet (C)

60-50

55-40

50-40

TSA
AF

HC

TSA
AF

HC

TSA
AF
P

TSA
AF

208 (750)

264 (950)

319 (1150)

347 (1250)

20

19

21

20

19

21

20

19

21

20

19

21

20

19

21

20

19

21

20

19

63.8

63.8

63.8

62.8

62.7

62.7

61.8

61.8

61.7

61.0

60.9

60.8

59.9

59.8

59.7

58.9

58.8

58.7

58.3

58.3

58.2

7.68

7.95

8.22

9.45

9.78

10.12 11.09 11.49 11.89 11.90 12.33 12.75

827

856

886

4.37
384

3.33
53.6
291

2.34
43.9
136

2.25
43.1
196

4.49
394

3.44
53.6
301

2.46
44.0
143

2.36
43.1
206

4.60
405

3.55
53.6
311

2.58
44.1
150

2.48
43.1
216

6.40
563

4.85
52.6
424

3.39
43.1
197

3.26
42.3
284

6.57
578

5.01
52.6
438

3.57
43.2
208

3.43
42.3
299

6.74
593

5.18
52.6
453

3.74
43.3
218

3.59
42.3
313

21

20

19

67.8

67.7

4.77

4.89

420

430

67.8
3.74
57.7
327

3.02
50.6
176

2.69
47.4
234

3.86
57.7

125 (450)

338

3.14
50.6
183
2.8

47.4
244

21

20

19

67.1

67.1

67

5.01

7.1

440

624

3.97
57.7
348

3.26
50.7
190

2.92
47.4
255

8.37
736

6.31
51.8
552

4.39
42.4
256

4.22
41.6
368

8.59
755

6.53
51.7
571

4.61
42.4
269

4.44
41.6
387

8.82
775

6.75
51.7
591

4.83
42.4
282

4.65
41.5
406

10.22 10.49 10.77 12.62 12.96 13.31 14.86 15.27 15.67 15.96 16.40 16.84
898

51.0
672

5.29
41.7
308

5.11
41.0
445

922

51.0
696

5.56
41.7
324

5.37
40.9
468

946

1109 1140 1170 1307 1342 1378 1404 1442 1481

50.9

50.1

719

5.83

6.44

41.6

40.8

339

375

5.64

6.25

40.9

40.2

491

545

50.0
6.77
40.8
394

6.57
40.2
573

49.9

49.3

49.2

49.1

48.8

48.8

48.7

7.11

7.50

7.89

8.28

8.01

8.43

8.85

459

482

467

491

515

40.7
414

6.90
40.1
602

Size 3.2

Dry bulb temperature at coil inlet (C)

HC

167 (600)

21

Size 3.1
Entering/
3
leaving water Air flow l/s (m /h)
temp. (C)
83 (300)

70-60

Size 2.3

5.55
57.1
486

4.44
49.8
258

3.97
46.8
346

7.27
639

5.72
57

501

4.62
49.9
269

4.14
46.8
361

21

20

66.4

66.4

9.31

655

818

5.9
57

516
4.8

49.9
279

4.32
46.8
376

7.26
56.4
635

5.77
49.2
336

5.17
46.3
451

208 (750)

49.2
349
5.4

46.3
470

637

264 (950)

40.1
7.69
39.5
670

40.0
8.07
39.4
704

319 (1150)

19

21

20

19

21

66.3

65.8

65.7

65.7

65

64.9

64.8

64.2

8.91

9.19

9.47

11.06 11.41 11.76 13.1

780

804

829

968

859

39.6

20

838

655

7.30

21

9.77

56.4

437

19

9.54

7.49

40.1

1006 1040 1042 1079 1116


39.7

39.7

7.82

8.23

39.3

39.2

682

718

39.6
8.65
39.1
754

Size 3.3

167 (600)

7.45

971

7.71
56.4
675

6.23
49.2
363

5.62
46.2
490

11.45 11.74 12.02 14.25 14.61 14.97 16.9

347 (1250)

20

19

64.1

64

17.3

17.8

21

20

19

63.8

63.7

63.6

18.23 18.69 19.15

1007 1032 1057 1253 1284 1316 1488 1525 1563 1603 1644 1684
55.9

55.8

7.03

7.32

48.5

48.5

409

426

6.33

6.6

45.8

45.7

551

576

55.8
7.6

48.5

54.5

8.66

9.02

9.37

10.2

10.6

11

10.94 11.4

11.85

546

594

618

643

637

690

504

6.88

7.82

45.7

45.1

600

682

47.7
525

8.17
45.1
712

54.3

14.11 14.56 15.01

55

998

54.4

13.9

55.1

47.7

443

13.5

55.1

54.1

54.1

54

1029 1147 1183 1220 1234 1274 1313


47.7
8.51
45.1
742

47

9.2

44.6
805

47

9.6

44.5
841

47

10.1
44.5
877

46.7

46.7

9.93

10.37 10.82

664

44.3

44.3

866

905

46.6

44.2
943

6.2.2 - Four-row coil, 1-row heating


Entering/
leaving water
temp. (C)
70-60
60-50
55-40
50-40

P
TSA
AF
P
TSA
AF
P
TSA
AF
P
TSA
AF

Size 0.5
Air flow l/s (m3/h)
28 (100)
56 (200)
Dry bulb temperature at coil inlet (C)
21
20
19
21
20
0.75
0.77
0.80
1.31
1.35
43.3
42.9
42.4
40.1
39.5
66
68
70
115
118
0.54
0.56
0.58
0.94
0.98
36.9
36.5
36.0
34.7
34.2
47
49
51
82
85
0.34
0.36
0.38
0.50
0.53
31.2
30.6
30.0
28.3
27.6
20
21
22
29
31
0.33
0.34
0.36
0.54
0.58
30.7
30.2
29.6
28.9
28.4
29
30
31
47
50

Legend:
HC - Heating capacity (kW)
TSA - Supply air temperature (C)
AF - Water flow rate (l/h)
NOTE: To convert l/h to l/s, divide by 3600.

83 (300)
19
1.38
39.0
122
1.01
33.7
89
0.55
27.0
32
0.62
27.9
54

21
1.74
38.1
153
1.25
33.3
110
0.63
27.1
36
0.72
28.1
63

20
1.79
37.5
158
1.30
32.7
114
0.68
26.6
39
0.78
27.6
68

111 (400)
19
1.84
36.9
162
1.35
32.1
118
0.73
26.1
42
0.83
27.0
72

21
2.13
36.6
187
1.52
32.2
133
0.77
26.6
45
0.89
27.5
78

20
2.19
36.0
192
1.58
31.6
139
0.83
26.1
48
0.95
27.0
83

139 (500)
19
2.25
35.4
198
1.64
30.9
144
0.89
25.5
52
1.01
26.4
89

21
2.47
35.5
217
1.76
31.3
154
0.89
26.2
52
1.04
27.1
91

20
2.54
34.8
223
1.83
30.7
160
0.97
25.6
56
1.11
26.5
97

150 (540)
19
2.61
34.2
230
1.90
30.0
166
1.04
25.1
61
1.18
25.9
103

21
2.59
35.1
228
1.85
31.1
162
0.94
26.1
55
1.09
26.9
95

20
2.66
34.4
234
1.92
30.4
168
1.02
25.5
59
1.17
26.3
102

19
2.74
33.8
241
1.99
29.8
174
1.09
24.9
64
1.24
25.7
108

WARNING: The supply air temperature must not exceed


60C otherwise damage may occur to the supply air spigot
connections.
NOTE: Carrier advises that the supply air temperature be
kept below 35C in order to avoid the risk of stratification.
If the Atmosphera unit size 2 or 3 has only two spigots,
the above performance data is reduced by 3%.

13

6.2.2 - Four-row coil, 1-row heating (cont.)


Size 1.0

Air flow l/s (m3/h)


Entering/
leaving water 56 (200)
83 (300)
temp. (C)
Dry bulb temperature at coil inlet (C)

111 (400)

70-60

2.25

60-50

55-40

50-40

HC

TSA
AF

HC

TSA
AF

HC

TSA
AF

HC

TSA
AF

60-50

55-40

50-40

TSA
AF

HC

TSA
AF

HC

TSA
AF

HC

TSA
AF

21

20

19

21

20

19

21

20

19

21

20

19

21

20

19

21

20

19

40.2

39.7

39.1

38.7

38.1

37.5

37.5

36.9

36.2

36.6

35.9

35.2

35.8

35.1

34.4

35.5

34.8

34.1

35.1

34.4

33.7

116

1.01
35.8
89

0.76
32.1
44

0.70
31.3
61

119

1.05
35.2
91

0.79
31.5
46

0.74
30.7
64

1.39
122

1.08
34.6
94

0.83
31.0
48

0.77
30.1
67

1.81
159

1.39
34.6
121

1.04
31.2
61

0.96
30.4
84

1.85
163

1.43
34.0
125

1.09
30.6
63

1.01
29.8
88

1.90
167

1.48
33.4
129

1.13
30.0
66

1.05
29.2
92

198

1.73
33.7
151

1.30
30.5
76

1.20
29.8
105

2.31
203

1.78
33.0
156

1.35
29.9
79

1.26
29.2
109

55-40

50-40

AF

HC

TSA
AF

HC

TSA
AF

161

1.41
29.3
82

1.31
28.6
114

2.04
32.9
178

1.53
30.0
89

1.41
29.3
123

239

2.10
32.3
184

1.60
29.3
93

1.48
28.7
129

2.79
245

2.17
31.6
190

1.66
28.7
97

1.55
28.0
135

3.03
266

2.32
32.3
203

1.74
29.5
102

1.61
28.9
141

3.10
273

2.40
31.7
210

1.82
28.9
106

1.69
28.2
147

3.18
280

2.47
31.0
216

1.89
28.2
110

1.76
27.5
153

3.19
281

2.45
32.1
214

1.84
29.3
107

1.70
28.7
148

3.27
288

2.53
31.4
221

1.92
28.7
112

1.78
28.0
155

3.35
295

2.61
30.7
228

2.00
28.0
116

1.86
27.3
162

3.36
296

2.58
31.8
226

1.94
29.1
113

1.79
28.5
156

3.45
303

2.66
31.1
233

2.02
28.5
118

1.87
27.8
163

3.53
311

2.74
30.5
240

2.10
27.8
122

1.95
27.2
170

Size 2.3
208 (750)

264 (950)

319 (1150)

347 (1250)

19

21

20

19

21

20

19

21

20

19

21

20

19

21

20

19

21

20

19

39.4

38.8

38.2

37.7

37.0

36.4

36.4

35.7

35.0

35.4

34.7

34.0

34.4

33.7

32.9

33.6

32.8

32.1

33.2

32.5

31.7

165

1.43
35.1
125

1.06
31.4
62

0.99
30.7
86

1.92
169

1.48
34.5
130

1.11
30.9
65

1.04
30.1
90

1.97
173

1.53
33.9
134

1.16
30.3
67

1.08
29.6
95

2.55
224

1.95
33.7
171

1.45
30.4
84

1.35
29.8
117

2.62
230

2.01
33.1
176

1.51
29.8
88

1.41
29.2
123

2.68
236

2.08
32.5
182

1.58
29.2
92

1.47
28.5
128

3.15
277

2.41
32.8
211

1.79
29.7
104

1.66
29.1
145

3.23
284

2.49
32.1
218

1.87
29.1
109

1.74
28.5
152

3.32
292

2.57
31.4
225

1.95
28.4
113

1.82
27.8
159

3.69
324

2.81
32.0
246

2.09
29.2
121

1.94
28.6
169

3.78
332

2.91
31.3
254

2.18
28.5
127

2.03
27.9
177

3.87
340

3.00
30.6
262

2.27
27.8
132

2.12
27.2
185

4.34
381

3.31
31.2
290

2.45
28.6
143

2.28
28.0
199

4.45
391

3.42
30.5
299

2.56
27.9
149

2.39
27.3
208

4.56
401

3.53
29.8
309

2.67
27.2
155

2.50
26.6
218

Size 3.2

3.23

TSA

32.4

234

2.72

20

1.87

70-60

HC

1.84

167 (600)

167 (600)

60-50

208

2.66

Size 2.2

Entering/
leaving water 83 (300)
125 (450)
temp. (C)
Dry bulb temperature at coil inlet (C)

AF

2.37

21

Air flow l/s (m3/h)

TSA

194 (700)

19

1.35

Size 3.1

HC

180 (650)

20

1.32

Size 2.1

HC

167 (600)

21

Air flow l/s (m3/h)


Entering/
leaving water 83 (300)
125 (450)
temp. (C)
Dry bulb temperature at coil inlet (C)
70-60

139 (500)

4.92
432

3.75
30.6
328

2.77
28.1
162

2.58
27.6
225

5.04
443

3.88
29.9
339

2.90
27.4
169

2.70
26.9
236

5.17
454

4.00
29.1
350

3.02
26.7
176

2.83
26.2
246

5.19
457

3.96
30.3
347

2.93
27.9
171

2.73
27.4
238

5.33
468

4.09
29.6
358

3.06
27.2
178

2.86
26.7
249

5.46
480

4.22
28.8
370

3.19
26.4
186

2.98
26.0
260

Size 3.3
208 (750)

264 (950)

319 (1150)

347 (1250)

21

20

19

21

20

19

21

20

19

21

20

19

21

20

19

21

20

19

21

20

19

38.7

38.1

37.5

37.6

37

36.3

36.8

36.1

35.5

36.1

35.4

34.7

35.3

34.6

33.9

34.6

33.9

33.2

34.3

33.6

32.9

1.81
159

1.39
34.7
122

1.08
31.6
63

0.98
30.6
86

1.85
163

1.44
34.1
126

1.12
31
65

1.03
30
90

1.9

167

1.49
33.5
130

1.17
30.4
68

1.07
29.4
93

2.56
225

1.98
33.8
173

1.53
30.9
89

1.39
30

121

Legend:
HC - Heating capacity (kW)
TSA - Supply air temperature (C)
AF - Water flow rate (l/h)
NOTE: To convert l/h to l/s, divide by 3600.

2.63
231

2.04
33.2
179

1.59
30.3
93

1.45
29.4
127

2.69
237

2.11
32.6
184

1.65
29.7
96

1.52
28.8
132

284
2.5

33.2
218

1.93
30.4
112

1.76
29.6
153

3.31
291

2.58
32.5
225

2.01
29.8
117

1.84
28.9
160

3.4

299

2.66
31.9
233

2.09
29.1
121

1.91
28.3
167

3.85
339

2.97
32.6
260

2.29
30

134

2.09
29.2
182

3.95
347

3.07
32

269

2.39
29.3
139

2.19
28.5
191

4.05
356

3.17
31.3
277

2.48
28.7
145

2.28
27.9
199

4.63
407

3.57
32

313

2.75
29.5
160

2.51
28.8
219

4.75
417

3.69
31.3
323

2.87
28.8
167

2.63
28.1
229

4.86
427
3.8

30.6
333

2.98
28.1
174

2.74
27.4
239

5.33
469

4.12
31.5
360

3.17
29.1
185

2.89
28.4
252

5.47
481

4.25
30.8
372
3.3

28.4
192

3.02
27.7
264

5.6

493

4.38
30.1
383

3.43
27.7
200

3.15
27

275

5.68
499

4.38
31.3
383

3.37
28.9
196

3.08
28.2
268

5.82
512

4.52
30.6
396

3.51
28.2
205

3.22
27.5
280

5.96
524

4.66
29.9
408

3.65
27.5
213

3.36
26.8
293

WARNING: The supply air temperature must not exceed


60C otherwise damage may occur to the supply air spigot
connections.
NOTE: Carrier advises that the supply air temperature be
kept below 35C in order to avoid the risk of stratification.
If the Atmosphera unit size 2 or 3 has only two spigots,
the above performance data is reduced by 3%.

14

6.3 - Sound power levels


6.3.1 - Standard insulation
42EM 0.5 with one discharge spigot
Octave band frequency (Hz)
V
Typ
125
250
500
1K
V1
SUP
55
50
49
42
RET
61
60
56
51
RAD
62
49
45
41
V2
SUP
54
49
48
41
RET
59
58
54
49
RAD
55
46
44
40
V3
SUP
53
48
47
40
RET
58
57
53
49
RAD
51
44
42
38
V4
SUP
51
46
44
37
RET
56
55
51
46
RAD
50
43
41
37
V5
SUP
49
44
43
35
RET
53
52
48
43
RAD
47
40
38
34
V6
SUP
47
42
41
34
RET
52
50
47
42
RAD
46
38
35
31
42EM 1.0 with two discharge spigots
Octave band frequency (Hz)
V
Typ
125
250
500
1K
V1
SUP
57.3
55.1
46.2
43.1
RET
60
57.8
52
46.8
RAD
57.6
50.3
45.2
37.6
V2
SUP
55.8
52.4
43.7
40.4
RET
57.8
54.1
49
43.3
RAD
54.1
46.8
41.7
34.2
V3
SUP
51.5
48.8
40.1
36.5
RET
55
51.5
46.4
40.8
RAD
53.2
44.1
37
31
V4
SUP
48.4
45.2
36.9
33
RET
51.9
47.7
43.2
37.1
RAD
49.9
40.7
33.8
27.4
V5
SUP
46.4
43.5
35.1
30.7
RET
49.9
45.6
41.6
34.7
RAD
47.6
39.2
32.3
25.6
V6
SUP
45.1
42.1
34.1
28.9
RET
48.7
44.6
40.6
32.9
RAD
45.2
37.3
30.5
22.9
42EM 2.1 und 3.1 with two discharge spigots
Octave band frequency (Hz)
V
Typ
125
250
500
1K
V1
SUP
56
51.0
44.0
38.0
RET
58.5
53
48.5
42
RAD
51
43
37
29
V2
SUP
53.4
47.4
41.1
33.3
RET
55
50
46
39
RAD
48
40
34
25.5
V3
SUP
49.5
44.2
37.9
30.0
RET
51.9
46.6
42.5
34.8
RAD
45
36.0
30.6
21.7
V4
SUP
47.5
43
36.3
27
RET
49.3
44.5
40
31
RAD
42.8
34.6
28.1
18
V5
SUP
45.5
41
34.3
24.9
RET
47.3
42.5
38
28.8
RAD
39.8
31.6
25.1
15
V6
SUP
RET
Speed not available for 230 V
RAD
Legend:
V
- Fan speed
SUP - Supply (dB re = 10-12 W)
RET - Return (dB re = 10-12 W)
RAD - Radiated (dB re = 10-12 W)

2K
40
40
34
39
39
32
39
38
31
36
35
30
34
33
27
33
30
24

2K
37.1
43.5
32.2
34.4
39.9
28.4
30.4
36.8
25.6
26.4
32.5
21.7
23.4
29
19.1
21
26.5
16.4

2K
30.0
36.5
25
25
32
20
19.7
27.7
16.2
17
27
14.2
14.8
24.9
11.2

4K
33
32
23
32
31
21
31
29
19
27
26
*
23
*
*
22
*
*

4K
31.3
38.7
24.7
27.1
34
19.9
22.2
29.8
16.8
18
23.9
14.2
16.8
20.2
14.6
17
18.9
14.3

4K
23.0
30
15
19
27
13
15.0
23.1
11.3
16
22.5
12
14.7
21.1
11

dB(A)
50
57
49
49
55
46
48
54
44
45
52
43
43
49
39
42
48
37

42EM 2.2 and 3.2 with three discharge spigots


Octave band frequency (Hz)
V
Typ
125
250
500
1K
V1
SUP
64.4
59.6
52.2
46.8
RET
66.4
61.9
56.2
50.8
RAD
57.2
51.3
44.6
38.3
V2
SUP
63.7
57.8
50.6
44.9
RET
64.8
60
54.7
49
RAD
55.9
49.6
43.2
36.5
V3
SUP
62
56.1
49.4
43.2
RET
63
58.3
53.2
47.2
RAD
53.8
46.1
40.3
33.1
V4
SUP
56.9
50.9
44.6
37.8
RET
58.8
53.5
49.1
42.4
RAD
51.2
43
37.4
29.5
V5
SUP
51.5
46.2
39.9
32
RET
53.3
48
43.9
36.2
RAD
46.7
37.7
32.3
23.4
V6
SUP
47.5
43
36.3
26.9
RET
48.8
44
39.5
30.3
RAD
42.3
34.1
27.6
17.4

2K
38.3
45.8
34.2
36.4
43.8
32.3
34.3
41.5
28.7
28.2
36
24.4
21.7
29.1
17.9
16.8
26.4
13.7

4K
33.9
40.3
25.1
31.5
37.8
22.4
28.5
35
18.3
21.7
29.6
15.1
17
24.5
13
16.7
22.6
13.3

dB(A)
55.2
58.5
47.5
53.7
56.8
45.9
52.1
55
43
47
50.5
40
42
45
35
38.4
40.7
31

dB(A)
50.3
54.3
47.3
47.8
51
43.8
44
48.3
41.1
40.6
44.7
37.8
38.7
42.7
36
37.4
41.5
34

42EM 2.3 and 3.3 with four discharge spigots


Octave band frequency (Hz)
V
Typ
125
250
500
1K
V1
SUP
67.2
64
55.9
51.4
RET
68
64.8
58.4
53.6
RAD
58.9
54.6
46.5
41.3
V2
SUP
66
61.8
54.1
49.5
RET
66.6
63
56.6
51.8
RAD
57.1
52.6
44.6
39.4
V3
SUP
64.5
60.3
52.8
48
RET
65.4
61.3
55.4
50.5
RAD
55.9
50.9
43.4
38
V4
SUP
62.6
57.6
50.6
45.4
RET
64.1
58.9
53.6
48.4
RAD
54.2
48.4
41.3
35.5
V5
SUP
58.3
52.8
46.2
40.3
RET
59.4
53.9
49.3
43.4
RAD
49.9
43.6
37.3
30.7
V6
SUP
53.7
49.1
42.6
35.6
RET
56
49.9
45.8
38.8
RAD
45.3
39.1
32.8
25.1

2K
42.6
49.2
36.3
40.8
47.3
34.4
39.3
45.9
33
36.6
43.6
30.4
31.3
37.9
25.9
25.3
32
19.1

4K
39.2
44.4
29.1
37.1
42.3
26.9
35.2
40.5
24.9
31.8
37.6
21.4
25
31
16
18.6
25.9
12.5

dB(A)
59.2
61.1
50.1
57.3
59.3
48.1
55.9
57.9
46.7
53.5
55.9
44.4
48.8
51.1
40
44.8
47.1
35.3

dB(A)
46.7
50.1
39.8
43.4
47.1
36.7
40
43.6
33.3
38.4
41.2
31.3
36.4
39.2
28.6

NOTE: The measurements are based on ISO standards


and are without supply and return octopus plenums.
The room sound level calculations must take account of
the sound absorption of the duct, the plenum, the room
and ceiling.
For a selected speed the sound level can vary within a
tolerance of 2.5 dB(A), depending on the available
static pressure.
6.3.2 - Return air plenum attenuation
The sound power level measurements were carried out on
a non-ducted unit without return air plenum. If the unit
includes a return air plenum, correct the sound power levels
(RET) using the correction factors in the table below:
Unit size 42EM
0.5
1, 2, and 3

Octave band frequency (Hz)


125
250
500
1K
-4
-7
-6
-5
-0.4
-1.1
-2.6
-7.4

2K
-9
-10.7

4K
-3
-6.8

dB(A)
-6
-2.5

15

6.4 - Electrical data


Size 0.5
Vn
V1

V2

V3

V4

V5

V6

I (A)
0.49
0.49
0.48
0.47
0.47
0.46
0.45
0.45
0.44
0.43
0.43
0.36
0.36
0.35
0.34
0.34
0.33
0.32
0.31
0.31
0.31
0.31
0.31
0.30
0.29
0.29
0.28
0.28
0.28
0.27
0.26
0.26
0.26
0.26
0.24
0.24
0.24
0.23
0.23
0.22
0.22
0.22
0.22
0.21
0.21
0.20
0.20
0.20
0.19
0.19
0.19
0.19
0.19
0.18
0.18
0.17
0.17

P (W)
112
112
110
107
105
103
101
101
100
99
99
83
83
78
77
76
74
72
70
69
69
71
71
67
66
65
64
64
62
61
58
57
59
59
57
55
55
53
52
50
49
50
50
49
48
47
47
45
45
46
46
45
45
44
42
41
39

Qv (m3/h)
612
592
528
469
429
395
316
280
236
141
93
537
523
430
371
334
286
213
139
107
74
473
462
411
353
325
292
266
231
184
111
74
397
390
328
265
234
193
151
102
70
336
330
293
252
210
192
127
91
301
289
256
228
187
143
85
50

Legend:
Vn
Fan motor speed
I
Current drawn by the fan motor
P
Power input to the fan motor
Qv
Air flow rate
PR
Available static pressure

NOTE: Voltage supply: 230 V 15%

16

Qv (l/s)
170
164
147
130
119
110
88
78
66
39
26
149
145
119
103
93
79
59
38
30
20
131
128
114
98
90
81
74
64
51
31
21
110
108
91
74
65
54
42
28
19
93
92
81
70
58
53
35
25
84
80
71
63
52
40
23
14

PR (Pa)
0
6
27
41
54
64
81
91
101
113
119
0
5
34
53
63
75
95
106
110
115
0
5
21
43
52
62
71
82
92
103
110
0
4
27
51
63
77
85
96
103
0
2
17
33
51
59
78
88
0
6
19
30
47
60
79
90

Size 1.0
Vn
V1

I (A)
0.52
0.52
0.51
0.50
0.50
0.48
0.48
0.47
0.46
0.37
0.37
0.36
0.35
0.34
0.34
0.34
0.33
0.33
0.31
0.31
0.30
0.29
0.29
0.28
0.28
0.26
0.25
0.25
0.24
0.24
0.23
0.21
0.21
0.21
0.20
0.20
0.19
0.18
0.18
0.18
0.18
0.17
0.17

P (W)
119
118
117
115
114
111
110
108
107
87
85
82
81
78
78
77
76
75
73
72
69
68
67
65
64
60
59
58
57
55
54
51
51
49
48
47
45
44
43
43
42
41
41

Qv (m3/h)
705
675
650
596
560
410
321
227
141
594
525
460
400
335
294
222
180
149
522
473
393
332
278
217
179
437
385
315
246
187
147
370
312
255
179
150
330
274
196
150
120
87
63

Qv (l/s)
196
188
181
166
156
114
89
63
39
165
146
128
111
93
82
62
50
41
145
131
109
92
77
60
50
121
107
88
68
52
41
103
87
71
50
42
92
76
54
42
33
24
18

PR (Pa)
0
10
20
39
50
92
114
135
149
0
28
50
69
89
102
122
130
135
0
22
51
72
91
110
118
0
23
53
80
100
110
1
25
48
80
90
0
20
52
70
80
90
99

Sizes 2.1 and 3.1


Vn
I (A)
V1
0.60
0.57
0.52
0.49
0.46
0.45
0.43
0.40
V2
0.52
0.50
0.46
0.43
0.41
0.39
0.37
0.35
V3
0.42
0.41
0.37
0.36
0.34
0.33
0.31
V4
0.35
0.34
0.31
0.30
0.28
0.28
V5
0.27
0.26
0.25
0.25
0.24
0.24

P (W)
128
122
111
104
99
95
91
85
111
108
99
94
89
85
79
74
92
89
82
78
74
72
68
77
74
69
66
62
62
59
57
56
54
53
53

Qv (m3/h)
834
765
654
581
499
437
373
290
720
652
547
483
413
353
286
211
583
503
398
341
283
248
173
477
390
275
228
143
87
347
241
192
160
97
20

Qv (l/s)
232
213
182
161
139
121
104
81
200
181
152
134
115
98
79
59
162
140
111
95
79
69
48
133
108
76
63
40
24
96
67
53
44
27
6

PR (Pa)
0
20
50
65
80
91
100
110
0
21
50
65
79
90
100
110
0
21
50
65
80
90
100
0
20
50
65
80
90
0
20
30
40
50
62

V2

V3

V4

V5

V6

Sizes 2.2 and 3.2


Vn
I (A)
V1
0.82
0.75
0.70
0.67
0.63
0.60
0.57
0.56
V2
0.70
0.66
0.61
0.58
0.54
0.52
0.50
0.49
V3
0.62
0.59
0.53
0.50
0.47
0.45
0.43
0.40
V4
0.51
0.49
0.44
0.42
0.40
0.38
0.35
0.33
V5
0.39
0.38
0.35
0.33
0.32
0.30
0.29
V6
0.30
0.29
0.27
0.26
0.25

P (W)
182
168
155
150
139
132
126
121
158
149
138
131
121
115
112
107
140
132
120
113
105
101
95
91
114
110
100
96
90
87
81
76
89
86
79
75
73
68
65
68
66
62
59
58

Qv (m3/h)
1203
1114
1020
920
807
707
549
524
1070
976
837
754
661
590
514
440
926
849
723
649
559
493
423
340
760
693
568
513
437
376
304
239
574
499
386
331
293
240
189
417
333
241
193
128

Legend:
Vn
Fan motor speed
I
Current drawn by the fan motor
P
Power input to the fan motor
Qv
Air flow rate
PR
Available static pressure

Qv (l/s)
334
309
283
256
224
196
153
146
297
271
232
209
184
164
143
122
257
236
201
180
155
137
117
94
211
193
158
143
121
104
84
66
159
139
107
92
81
67
53
116
92
67
54
36

PR (Pa)
0
15
35
53
70
85
106
110
0
20
50
65
80
90
101
110
0
20
51
66
81
91
100
110
0
20
51
64
80
90
101
111
0
20
51
65
74
85
95
0
20
44
55
69

Sizes 2.3 and 3.3


Vn
I (A)
V1
1.01
0.94
0.91
0.89
0.86
0.83
0.81
0.80
V2
0.89
0.85
0.80
0.77
0.74
0.71
0.68
0.67
V3
0.80
0.76
0.70
0.67
0.63
0.60
0.58
0.56
V4
0.71
0.66
0.60
0.58
0.53
0.51
0.50
0.47
V5
0.58
0.55
0.50
0.47
0.44
0.42
0.40
0.38
V6
0.45
0.43
0.40
0.38
0.36
0.34
0.32
0.30

P (W)
225
209
201
193
189
182
176
172
203
194
179
174
165
158
152
148
184
173
159
153
143
135
133
127
162
151
139
133
122
117
113
107
132
125
116
108
101
98
94
88
102
98
91
87
83
79
73
70

Qv (m3/h)
1494
1266
1141
1074
920
812
701
610
1414
1290
1104
1007
880
774
666
578
1314
1199
1033
932
797
695
625
522
1138
1043
901
817
700
621
536
426
878
811
714
639
550
492
422
335
631
566
482
426
362
317
253
186

Qv (l/s)
415
352
317
298
256
225
195
169
393
358
307
280
244
215
185
161
365
333
287
259
221
193
174
145
316
290
250
227
194
172
149
118
244
225
198
178
153
137
117
93
175
157
134
118
101
88
70
52

PR (Pa)
1
31
50
60
80
90
100
111
0
20
51
65
81
90
101
110
0
22
51
65
81
91
100
111
0
21
50
65
80
90
100
110
0
20
50
65
81
91
100
110
1
21
51
65
80
90
100
110

NOTE: Voltage supply: 230 V 15%

17

6.5 - Water coil pressure drop


Size 0.5

Size 1
1000

100

Pressure drop (kPa)

Pressure drop (kPa)

1 000

10

0,1

0,03
(100)

0,13
(500)

0,083
(300)

0,1

0,003

0,03

(10)

(100)

Water flow rate, l/s (l/h)

0,28

(1 000)

Water flow rate, l/s (l/h)

Size 3

1 000

1 000

Pressure drop (kPa)

Pressure drop (kPa)

10

0,28
(1 000)

Size 2

100

100

10

100

0,028
(100)

0,556

0,278
(1 000)

0,139
(500)

(2 000)

Water flow rate, l/s (l/h)

10

0,833
(3 000)

0,056

0,028

0,139

(200)

(100)

0,556

0,278
(1 000)

(500)

(2 000)

Water flow rate, l/s (l/h)

Heating
Cooling

0,833

(3 000)

6.6 - Air flow data


Static pressure available (Pa) as a function of the air flow, l/s (m3/h)
Size 1.0 (unit without spigot)
160

140
120
100
80
60

V5

V6

40

V4

V3

V1

V2

20
0

50
(180)

0
(0)

100
(360)

150
(540)

200
(720)

Air flow, l/s (m3/h)

Available static pressure (Pa)

Available static pressure (Pa)

Size 0.5 (unit without spigot)

140
120
100
80
60
40

28

(0)

83

56

(100)

V4

V5

V6

20

(200)

(300)

V3

V2

V1

139

111

(400)

194

167

(500)

(600)

(700)

Air flow, l/s (m3/h)

Pressure drop (Pa) for supply and return air plenum boxes as a function of the number of spigots ( 200 mm)
Size 0.5

Air flow (l/s)

Air flow (m3/h)


1 spigot

SUP

2 spigots

SUP

Legend:
SUP Supply
RET Return

18

RET
RET

28

56

83

111

139

167

14

19

0
0
0
0

100
0
0
0

200
1
1
0

300
2
2
0

400
3
3
1

500
5
5
2

600
6
6
3

Size 1

Air flow (l/s)

28

56

83

111 125 139 153 167 181 194

1 spigot

SUP

15

19

24

2 spigots

SUP

10

Air flow (m3/h)

3 spigots

RET
RET

SUP
RET

100 200 300 400 450 500 550 600 650 700
2
0
0
0

7
2
0
1

15
4
1
2

27
6
1
3

35
8
2
4

43
10
2
5

12
3
6

16
3
7

18
4
8

20
4

10

Static pressure available (Pa) as a function of the air flow, l/s (m3/h)
Sizes 2.2 and 3.2 (unit without spigot)

120

120

100

100

Available static pressure (Pa)

Available static pressure (Pa)

Sizes 2.1 and 3.1 (unit without spigot)

80
60
40
20
0

0
(0)

28
(100)

V4

V5

V6
56
(200)

83
(300)

V2

V3

111
(400)

139
(500)

167
(600)

Air flow, l/s (m3/h)

V1
222
(800)

194
(700)

80
60
40
20
0

250
(900)

56

(0)

(200)

V4

V5

V6
111
(400)

V3
222

167
(600)

(800)

Air flow, l/s (m3/h)

V2

V1

278

(1000)

333
(1200)

Sizes 2.3 and 3.3 (unit without spigot)


IMPORTANT: The curves were derived by smoothing,
based on the information shown in the electrical data
table.

Available static pressure (Pa)

120
100
80

NOTE: The data is for units without supply and return


plenums. See chapter Air pressure drop for octopus
plenum boxes as a function of the number of spigots for
the plenum pressure drops.

60
40
20
0

(0)

56

(200)

111

(400)

V4

V5

V6
167

(600)

222

(800)

278

(1000)

Air flow, l/s (m3/h)

V3
333

(1200)

V2

V1
388

(1400)

444

(1600)

Pressure drop (Pa) for supply and return air plenum boxes as a function of the number of spigots ( 200 mm)
Sizes 2.1 - 2.2 - 2.3 - 3.1 - 3.2 - 3.3
Air flow (l/s)
0
28
Air flow (m3/h)
0
100
1 spigot
SUP
0
0.9
RET
0
0.7
2 spigots
SUP
0
0.2
RET
0
0.2
3 spigots
SUP
0
0.1
RET
0
0.2
4 spigots
SUP
0
0.0
RET
0
0.1
5 spigots
SUP
0
0.0
RET
0
0.0

56
200
3.5
2.7
0.7
0.7
0.5
0.7
0.1
0.2
0.1
0.2

83
300
7.9
6.1
1.6
1.7
1.1
1.5
0.3
0.5
0.3
0.4

111
400
14
10.9
2.9
3.0
2.0
2.6
0.6
0.9
0.5
0.7

139
500
21.8
17.1
4.5
4.6
3.1
4.1
0.9
1.3
0.7
1.1

167
600
31.4
24.6
6.5
6.7
4.4
5.9
1.3
1.9
1.0
1.6

194
700

222
800

250
900

278
1000

306
1100

333
1200

361
1300

389
1400

417
1500

8.9
9.1
6.0
8.0
1.7
2.6
1.4
2.1

11.6
11.9
7.9
10.5
2.3
3.4
1.8
2.8

14.7
15.0
10.0
13.3
2.9
4.3
2.3
3.5

18.1
18.6
12.3
16.4
3.6
5.3
2.9
4.3

21.9
22.5
14.9
19.8
4.3
6.5
3.5
5.3

17.7
23.6
5.1
7.7
4.1
6.3

20.8
27.7
6.0
9.0
4.9
7.3

24.1
32.1
7.0
10.4
5.6
8.5

27.7
36.9
8.0
12.0
6.5
9.8

Legend:
SUP Supply
RET Return

19

7 - codification
See POD (Product Order Form)
Fan motor speed wiring
Codification (last digit)
or option 600

Fan set

Red wire

Grey wire
Black wire
Rep. L wire
Terminal marking (standard
wiring), option 600 not selected

NOTE:
Terminal 1 = highest speed
Terminal 6 = lowest speed
8 - SPECIFICATION GUIDE

Six wired
speeds

Supply 42EM Atmosphera fan coil units in accordance


with the certified drawings.
The performance of each 42EM unit shall conform to
the published technical and performance data.
The casings of 42EM units shall be made from galvanised sheet steel, thermally and acoustically insulated,
and shall be provided with adequate access for service
and maintenance. 42EM units shall be provided with
suspension lugs with rubber anti-vibration mounts.
The supply and return air connection spigots (199 mm
diameter) shall be integral with each 42EM unit.
42EM units shall be equipped with either a cooling/
heating changeover coil, a monobloc heating and cooling coil or a cooling coil and an electric heater. The
water coils shall be provided with manual air purge
valves.
The cooling and heating coils shall be made from
copper tubes of 3/8 external diameter and aluminium
fins. The maximum water side working pressure shall
not exceed 10 bar (1000 kPa).
The aluminium drain pan beneath the coil and valves
shall be monobloc to avoid the possibility of leaks.
The two-way or three-way on/off water flow control
valves shall be provided with flexible water pipes with
1/2 BSP union nuts to simplify connections on site
and maintenance and servicing work.
42EM units supplied shall be provided with disposable
85% gravimetric (EU3 or G3) and M1 fire class filters.
Filter access shall be:

- From below the unit for ducted models,

- From the rear of the unit for non-ducted models.

Fans shall be a double-inlet centrifugal forward-curved


type, with 1 or 2 fans per unit depending upon unit size.
The direct-drive fan motor shall be connected to the
3-speed terminals of the controller. It shall be protected
against overloads.
42EM units shall be suitable for connection to electronic controllers (wall-mounted thermostats) which
enable the user to change the fan speed manually so
as to adjust the units heating and cooling capacity.
Electrical connections carried out on 42EM units shall
be the quick-connection type in order to simplify
maintenance. A plastic cover shall protect the terminals.
Numerical control
The numerical controls shall use the CCN (Carrier
Comfort Network) communication protocol.
These controls shall have the following functions:

- Control of the Atmosphera fan speed.

- Control of the water flow through the on/off type
two or three-way valves with reference to internal
and external loads, in order to maintain a constant
ambient temperature in the conditioned space.

- Provide on/off control of the resistance wire type
electric heater.

- Be controlled by a Zone User Interface.
The power supply to the controller shall be 230 V a.c.
15% single-phase, 50 Hz, to avoid the need for a
transformer. The electric heater shall be controlled
directly from the numerical controller to avoid the
need for a power Triac.

Carrier is participating in the Eurovent


Certification Programme. Products are
as listed in the Eurovent Directory of
Certified Products.

Order No.: 14225-20, 01.2009. Supersedes order No.: 14225-20, 12.2007


Manufacturer reserves the right to change any product specification without notice.

Manufacturer: Carrier SCS, Montluel, France


Printed in Holland.