You are on page 1of 2

CONVERSION CHART

VELOCITY PRESSURE in inches of water to VELOCITY in feet per minute


Calculating Air Velocity. Fechheimer Pitot airflow stations and traverse probes measure in the same manner and magnitude as the Pitot tube,
via separate signals of airstream total pressure and static pressure, in inches water column (IN w.c.). To obtain velocity pressure (the force
generated by the velocity of the air moving in a duct), the static pressure must be subtracted from the total pressure:
Velocity Pressure (IN w.c.) = Total Pressure (IN w.c.) Static Pressure (IN w.c.)
Air velocity, expressed in feet per minute, is a function of velocity pressure, converted by means of the following formula:
Air Velocity (FPM) = 1096.5 x

Velocity Pressure (IN w.c.)


Density of (Gas)

In commercial applications where air is the gas, its density is at 70 Fahrenheit and 29.92 inches of mercury (barometric pressure), and the
airflow is not compressed (under 10 IN w.c.), the formula reduces to:
Air Velocity (FPM) = 4005 x
VP
.001"
.002"
.003"
.004"
.005"
.006"
.007"
.008"
.009"
.010"
.011"
.012"
.013"
.014"
.015"
.016"
.017"
.018"
.019"
.020"
.021"
.022"
.023"
.024"
.025"
.026"
.027"
.028"
.029"
.030"
.031"
.032"
.033"
.034"
.035"
.036"
.037"
.038"
.039"
.040"
.041"
.042"
.043"
.044"
.045"
.046"
.047"
.048"
.049"
.050"
.051"

V
127
179
219
253
283
310
335
358
380
400
420
439
457
474
491
507
522
537
552
566
580
594
607
620
633
645
658
670
682
694
705
716
727
738
749
759
770
780
791
801
811
821
831
840
849
859
868
877
887
896
904

VP
.052"
.053"
.054"
.055"
.056"
.057"
.058"
.059"
.060"
.061"
.062"
.063"
.064"
.065"
.066"
.067"
.068"
.069"
.070"
.071"
.072"
.073"
.074"
.075"
.076"
.077"
.078"
.079"
.080"
.081"
.082"
.083"
.084"
.085"
.086"
.087"
.088"
.089"
.090"
.091"
.092"
.093"
.094"
.095"
.096"
.097"
.098"
.099"
.100"
.101"

V
913
922
931
939
948
956
964
973
981
989
996
1004
1012
1020
1029
1037
1045
1052
1060
1067
1075
1082
1089
1097
1104
1111
1119
1125
1133
1140
1147
1154
1161
1167
1175
1181
1188
1193
1201
1208
1215
1222
1228
1234
1241
1247
1254
1260
1266
1273

VP
.102"
.103"
.104"
.105"
.106"
.107"
.108"
.109"
.110"
.111"
.112"
.113"
.114"
.115"
.116"
.117"
.118"
.119"
.120"
.121"
.122"
.123"
.124"
.125"
.126"
.127"
.128"
.129"
.130"
.131"
.132"
.133"
.134"
.135"
.136"
.137"
.138"
.139"
.140"
.141"
.142"
.143"
.144"
.145"
.146"
.147"
.148"
.149"
.150"
.151"

V
1279
1285
1292
1298
1304
1310
1316
1322
1328
1334
1340
1346
1352
1358
1364
1370
1376
1382
1387
1393
1399
1404
1410
1416
1422
1427
1433
1439
1444
1449
1455
1461
1466
1471
1477
1482
1488
1493
1498
1504
1509
1515
1520
1525
1530
1536
1541
1546
1551
1556

VP
.152"
.153"
.154"
.155"
.156"
.157"
.158"
.159"
.160"
.161"
.162"
.163"
.164"
.165"
.166"
.167"
.168"
.169"
.170"
.171"
.172"
.173"
.174"
.175"
.176"
.177"
.178"
.179"
.180"
.181"
.182"
.183"
.184"
.185"
.186"
.187"
.188"
.189"
.190"
.191"
.192"
.193"
.194"
.195"
.196"
.197"
.198"
.199"
.200"
.201"

V
1561
1567
1572
1577
1582
1587
1592
1597
1602
1607
1612
1617
1622
1627
1632
1637
1642
1646
1651
1656
1661
1666
1670
1675
1680
1685
1690
1695
1699
1704
1709
1713
1718
1723
1727
1732
1737
1741
1746
1750
1755
1759
1764
1768
1773
1777
1782
1787
1791
1795

VP
.202"
.203"
.204"
.205"
.206"
.207"
.208"
.209"
.210"
.211"
.212"
.213"
.214"
.215"
.216"
.217"
.218"
.219"
.220"
.221"
.222"
.223"
.224"
.225"
.226"
.227"
.228"
.229"
.230"
.231"
.232"
.233"
.234"
.235"
.236"
.237"
.238"
.239"
.240"
.241"
.242"
.243"
.244"
.245"
.246"
.247"
.248"
.249"
.250"
.251"

V
1800
1804
1809
1813
1818
1822
1827
1831
1835
1839
1844
1848
1853
1857
1862
1866
1870
1875
1879
1883
1887
1892
1896
1900
1905
1909
1913
1917
1921
1925
1929
1933
1937
1941
1945
1950
1954
1958
1962
1966
1970
1974
1978
1982
1987
1991
1995
1999
2003
2007

VP
.252"
.253"
.254"
.255"
.256"
.257"
.258"
.259"
.260"
.261"
.262"
.263"
.264"
.265"
.266"
.267"
.268"
.269"
.270"
.271"
.272"
.273"
.274"
.275"
.276"
.277"
.278"
.279"
.280"
.281"
.282"
.283"
.284"
.285"
.286"
.287"
.288"
.289"
.290"
.291"
.292"
.293"
.294"
.295"
.296"
.297"
.298"
.299"
.300"
.301"

Velocity Pressure (IN w.c.)


V
2011
2015
2019
2023
2027
2031
2035
2039
2042
2046
2050
2054
2058
2062
2066
2070
2074
2078
2081
2085
2089
2093
2097
2101
2105
2109
2113
2116
2119
2123
2127
2131
2135
2139
2143
2147
2151
2154
2157
2161
2164
2168
2171
2175
2179
2182
2186
2189
2193
2197

VP
.302"
.303"
.304"
.305"
.306"
.307"
.308"
.309"
.310"
.311"
.312"
.313"
.314"
.315"
.316"
.317"
.318"
.319"
.320"
.321"
.322"
.323"
.324"
.325"
.326"
.327"
.328"
.329"
.330"
.331"
.332"
.333"
.334"
.335"
.336"
.337"
.338"
.339"
.340"
.341"
.342"
.343"
.344"
.345"
.346"
.347"
.348"
.349"
.350"
.351"

V
2200
2204
2208
2212
2215
2219
2223
2226
2230
2233
2236
2239
2242
2245
2248
2251
2254
2257
2260
2264
2268
2272
2276
2280
2284
2289
2293
2297
2301
2304
2308
2311
2315
2318
2322
2325
2329
2332
2335
2338
2342
2345
2349
2352
2356
2360
2363
2366
2369
2372

VP
.352"
.353"
.354"
.355"
.356"
.357"
.358"
.359"
.360"
.361"
.362"
.363"
.364"
.365"
.366"
.367"
.368"
.369"
.370"
.371"
.372"
.373"
.374"
.375"
.376"
.377"
.378"
.379"
.380"
.381"
.382"
.383"
.384"
.385"
.386"
.387"
.388"
.389"
.390"
.400"
.410"
.420"
.430"
.440"
.450"
.460"
.470"
.480"
.490"
.500"

V
2376
2379
2383
2386
2389
2393
2396
2400
2403
2406
2410
2413
2416
2420
2423
2426
2429
2433
2436
2439
2443
2445
2449
2453
2456
2459
2462
2466
2469
2472
2475
2479
2481
2485
2488
2491
2495
2499
2501
2533
2563
2595
2626
2656
2687
2716
2746
2775
2804
2832

VP
.51"
.52"
.53"
.54"
.55"
.56"
.57"
.58"
.59"
.60"
.61"
.62"
.63"
.64"
.65"
.66"
.67"
.68"
.69"
.70"
.71"
.72"
.73"
.74"
.75"
.76"
.77"
.78"
.79"
.80"
.81"
.82"
.83"
.84"
.85"
.86"
.87"
.88"
.89"
.90"
.91"
.92"
.93"
.94"
.95"
.96"
.97"
.98"
.99"
1.00"

V
2860
2888
2916
2943
2970
2997
3024
3050
3076
3102
3127
3153
3179
3204
3229
3254
3279
3303
3327
3351
3375
3398
3422
3445
3468
3491
3514
3537
3560
3582
3604
3625
3657
3669
3690
3709
3729
3758
3779
3800
3821
3842
3863
3884
3904
3924
3945
3965
3985
4005

VP
1.01"
1.02"
1.03"
1.04"
1.05"
1.06"
1.07"
1.08"
1.09"
1.10"
1.11"
1.12"
1.13"
1.14"
1.15"
1.16"
1.17"
1.18"
1.19"
1.20"
1.21"
1.22"
1.23"
1.24"
1.25"
1.26"
1.27"
1.28"
1.29"
1.30"
1.31"
1.32"
1.33"
1.34"
1.35"
1.36"
1.37"
1.38"
1.39"
1.40"
1.41"
1.42"
1.43"
1.44"
1.45"
1.46"
1.47"
1.48"
1.49"
1.50"

V
4025
4045
4064
4084
4103
4123
4142
4162
4181
4200
4219
4238
4257
4276
4295
4314
4332
4350
4368
4386
4405
4423
4442
4460
4478
4495
4513
4531
4549
4566
4583
4601
4619
4636
4653
4671
4688
4705
4722
4739
4756
4773
4790
4806
4823
4840
4856
4873
4889
4905

VP
1.51"
1.52"
1.53"
1.54"
1.55"
1.56"
1.57"
1.58"
1.59"
1.60"
1.61"
1.62"
1.63"
1.64"
1.65"
1.66"
1.67"
1.68"
1.69"
1.70"
1.71"
1.72"
1.73"
1.74"
1.75"
1.76"
1.77"
1.78"
1.79"
1.80"
1.81"
1.82"
1.83"
1.84"
1.85"
1.86"
1.87"
1.88"
1.89"
1.90"
1.91"
1.92"
1.93"
1.94"
1.95"
1.96"
1.97"
1.98"
1.99"
2.00"

V
4921
4938
4954
4970
4986
5002
5018
5034
5050
5066
5082
5098
5114
5129
5144
5160
5175
5191
5206
5222
5237
5253
5268
5283
5298
5313
5328
5343
5359
5374
5388
5403
5418
5433
5447
5462
5477
5491
5506
5521
5535
5550
5564
5579
5593
5608
5623
5637
5651
5664

Calculating Air Volume. The station air volume, expressed cubic feet per minute (CFM), is the product of the air velocity through the airflow
station and the station area in square feet (Ft2).
Station Air Volume (CFM) = Air Velocity (FPM) x Station Area (Ft 2)

Air Monitor's Product Families of Flow Measurement and Pressure Sensors

FAN-E AIRFLOW MEASURING STATION.


Multi-point, self-averaging, Pitot traverse station with integral air straightenerequalizer honeycomb cell. Capable of continuously measuring fan discharges
or ducted airflow with an accuracy of two percent or better.
AMCA CERTIFIED in accordance with Standard 610.

VOLU-PROBE/1,2,3,4 AIRFLOW TRAVERSE PROBES.


Multi-point, self-averaging, Pitot Fechheimer airflow traverse probes with
integral airflow direction correcting design. Four mounting configurations
to fit every application.
AMCA CERTIFIED in accordance with Standard 610.

VOLU-PROBE/FI FAN INLET AIRFLOW PROBES.


Multi-point, self-averaging, Pitot Fechheimer airflow probes with integral airflow
direction correcting design. For mounting directly in the inlet cones or bellmouth
of centrifugal or vane-axial fans to measure fan capacities within three percent of
actual flow.

VOLU-PROBE/VS AIRFLOW PROBE TRAVERSE STATIONS.


Multi-point, self-averaging, Pitot Fechheimer airflow probes factory mounted
in a flanged sheet metal casing, with interconnecting tubing. Capable of
measuring ducted airflow within two percent accuracy without using an air
straightener or incurring significant resistance to airflow.
AMCA CERTIFIED in accordance with Standard 610.

S.A.P./1,2,3 and S.O.A.P. STATIC PRESSURE SENSORS.


Available in three separate mounting configurations, the S.A.P. family of static
pressure sensors generate a steady, non-pulsating output of room, space or
plenum pressure.
The S.O.A.P. was designed to accurately sense outside atmospheric air pressure.

STAT-PROBE STATIC PRESSURE TRAVERSE PROBE.


Multi-point, self-averaging, Fechheimer static pressure traverse probe for
accurate sensing of duct or system static pressure in the presence of turbulent
or rotational airflows.

P.O. Box 6358 Santa Rosa, CA 95406 TEL 800-AIRFLOW Fax 707-526-9970 www.airmonitor.com
125-080 (5/00)

You might also like