Oil Distribution Transformers

Minera Up to 2500 kVA, insulation 24 kV, losses


4 bi-directional flat rollers 2 lifting and untanking lugs 2 pulling eyes on the frame 2 earthing terminals on the cover (M12 studs) 1 filling plug 1 draining device according to EN 50216-4 or DIN 42551 1 aluminium rating plate

C0

Ck

PM102308

Options
Protection relays (DMCR or DGPT2) on the filling plug 1 free, thermometer pocket Control device in the thermometer pocket (pointer thermometer with 0 or 2 contacts max, 2-contact thermostat, etc.) 3 HV porcelain bushings (250 A) 4 LV porcelain bushings (from 250 kVA) LV, cable box IP21 or IP54 (only with plug-in bushings on the HV side) Locking device for plug-in bushings (with or without lock) 3 mobile connectors for plug-in bushings straight or elbow (cable characteristics must be specified) Liquid retention bund

Minera - Oil immersed Transformer Standard


These transformers comply with standards: EN 50464-1 EN 60076-1 to 10 Schneider Electric guarantees that its transformers are assembled using new, PCB-free components.

Description
Mineral oil-immersed, 50 Hz, three-phase distribution transformers with the following characteristics: Hermetically sealed with integral filling Cover bolted to the tank ONAN-type natural cooling Indoor / outdoor use (depending on selected fittings and options) Anti-corrosion surface treatment : corrositivity category class C3, Medium durability (according to ISO 12944-2) Final colour RAL 7033 Protection index IP00 (coverless version)

The above options concern usual cases and are not restrictive. For other information,please consult us.
No-load losses performance
SM100100 SM100117

Load losses performance


According to EN 50464-1

According to EN 50464-1

Optimum efficiency 0

Optimum efficiency

A0 B0 C0 D0 E0
Standard efficiency

Ak Bk

C0

Ck Dk
Standard efficiency

Ck

Dielectric liquid
First refining mineral oil Tested in accordance with IEC 60296 Compatible with all the transformers components

Standard fitting
One 3 or 5 positions off-circuit tap changer on the cover, with padlocking facility 3 HV plug-in bushings (250 A / 24 kV) on the cover 4 LV flat-bars (from 250 kVA) 4 LV porcelain bushings (from 50 to 160 kVA)

Oil Distribution Transformers


Electrical characteristics
Power (kVA) Primary voltage Secondary voltage HV insulation level HV tapping range Vector group No-load losses (w) Load losses (w) Impedance voltage (%) Acoustic Level dB(A): - power LWA - pressure LPA (1m) 49 41 52 43 55 45 57 47 100 160 250

Minera

C0

Ck

315

400

500

630

630

800

1000

1250

1600

2000

2500

15 and/or 20kV 400 to 433V between phases, 231 to 250V phase to neutral (at no load) 17.5kV for 15kV - 24kV for 20kV 2.5 % and/or 5 % Yzn 5 / Yzn 11 (50kVA version only) - Dyn 5 / Dyn 11 210 1750 4 300 2350 4 425 3250 4 520 3900 4 610 4600 4 720 5500 4 860 6500 4 800 6750 6 930 8400 6 1100 10500 6 1350 13500 6 1700 17000 6 2100 21000 6
2500
26500

58 48

59 49

60 50

60 50

61 50

63 52

64 53

66 55

68 56

71 59

Dimensions and weights


lifting lug
SM100027 SM100026

HV side
F F tap changer earthing terminal

Note: Bushings are marked according to the IEC 60616 standard. D: Height over LV cable box (optional accessory, compatible with HV plug-in bushings only).
filling plug

D C

earthing terminal

1W 1V 1U 2W 2V 2U 2N

free thermometer pocket rating plate

H A

40 K J B

125 38

corrugated panels in the corners according to cooling needs

Dimensions and weights are for guidance only, and are provided for a single-voltage transformer with the following electrical characteristics: 20 kV (HV) / 400 V (LV) 5-position tap changer, 2 x 2.5 %.

LV side

Rated power (kVA) Dimensions


(mm)

100 1000 600 880 1160 265 80 520 105 125 580

160 1000 750 1030 1310 265 75 520 105 160 750

250 1050 800 1040 1380 265 150 520 105 200 950

315 1250 850 1140 1480 265 150 670 105 230 1100

400 1300 850 1140 1480 265 150 670 105 260 1300

500 1400 900 1240 1580 265 150 670 105 300 1500

630 1450 950 1240 1580 265 150 670 105 350 1800

630 1550 950 1240 1580 265 150 670 105 390 1780

800 1550 1000 1300 1640 265 150 670 105 420 2100

1000 1750 1100 1350 1690 265 150 670 85 480 2400

1250 1800 1150 1350 1755 265 170 820 85 580 2750

1600 1850 1200 1400 1805 265 170 820 85 670 3250

2000 2000 1350 1450 1950 265 170 820 85 800 4000

2500 2250 1300 1680 2180 265 170 820 85 1050 5200

-A -B -C -D -F -H -J -K

Weight
(kg)

-Oil -Total

Terminations
Rated current (A) LV flat-bars LV porcelain bushings On request 250 250 1250 630 1250 630 1250 630 1250 1000 1250 1000 1250 1000 1250 2000 1600 2000 2500 2000 2500 3150 3150 3150 5000 4500

LV Terminations
63 100 31,5 97,5 31,5 12 106,5 31,5 221 31,5 14,5 11 31,5 12 50 35 250 250 50 50 18 52 45 120 12 135 50 18 45 50 310 120 50 25 20

HV Terminations - EN 50180
200
SM100030

SM100028

63 31,5 31,5

31,5 12 155

31,5 31,5 31,5 11

255 locking device 87

290 locking device

52

LV bus-bars terminations - EN 50387 (standard from 250 kVA)

1250 A

1600 A

52

11

14,5

14,5

2500 A

3150 A
20 120 70 40

5000 A
150 40

HV plug-in bushings 250 A/24 kV (standard).

15 10 M 20 60 14 263 165 178 26 M 30 26 60 17 100

50

100

25 20 40

15 120

60

30 20 40

150

70 18

M 12

SM100029

340

M 42

372

M 48

250A

630A

1000A

2000A

3150A

4500A

SM100031

M 12

M 55

385

LV porcelain bushings - EN 50386 (in standard from 50 to 160 kVA in option for other powers)

250 A HV porcelain bushing 250 A (option)

Schneider Electric Industries SAS


35, rue Joseph Monier CS 30323 F - 92506 Rueil Malmaison Cedex (France) Tl. : +33 (0)1 41 29 70 00 RCS Nanterre 954 503 439 Capital social 896 313 776 www.schneider-electric.com NRJED312371EN As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Design: Schneider Electric Industries SAS Photos: Schneider Electric Industries SAS 05-2012