You are on page 1of 2

ABB Power T&D Company Inc. Low Voltage Instrument Transformer Pinetops, North Carolina, U.S.A.

27864

Product Bulletin

42-926
Page 1

June 1991 Supersedes Descriptive Bulletin 42-926, pages 1-2, dated January 1990 Mailed to: E, D, C/42-900A

NSV 25.0 kV, Outdoor, 150 kV BIL Primary Amperes: 10 through 800 25 Through 60 Hertz

Type KOR-15 Current Transformer

Application Type KOR-15 current transformers are designed for metering and relaying applications on outdoor 25 kV circuits. Construction Features Weather Case The core and coil assembly is cast under vacuum in a polyurethane resin formulated for outdoor service and combining superior arc track, ozone and ultraviolet resistive properties with physical strength and flexibility.

Terminals Primary terminals are electro-tin plated copper. Secondary terminals are clamp type suitable for #14 to #1 wire. Terminal screws are slotted hex head type.

Base The base is constructed of "marine environment resistant" aluminum. After a zinc chromate plating, the base is given a finish coat of light gray, alkyd enamel paint. Electrical Clearances Strike 13.625 inches Creep 24.500 inches Selector Guide Rating KOR-15 Primary Style Amperes Number Single Ratio 10 15 20 25 30 40 50 75 100 150 200 300 400 500 600 800 1200 7524A17G02 7524A17G03 7524A17G04 7524A17G05 7524A17G06 7524A17G07 7524A17G08 7524A17G09 7524A17G10 7524A17G11 7524A17G12 7524A17G13 7524A17G14 7524A17G17 7524A17G15 7524A17G16 7524A17G18

Continuous Current Rating Factor (30C Ambient) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.0 1.25 3.0 2.0 1.50

ANS' Metering Accuracy (60 Hz) B0.1 Thru B0.9 B0.1 Thru B0.9 B0.1 Thru B0.9 B0.1 Thru B0.9 B0.1 Thru B0.9 B0.1 Thru B0.9 B0.1 Thru B0.9 B0.1 Thru B0.9 B0.1 Thru B0.9 B0.1 Thru B0.9 B0.1 Thru B0.9 B0.1 Thru B0.9 B0.1 Thru B0.9 B0.1 Thru B1.8 B0.1 Thru B0.9 B0.1 Thru B0.9 B0.1 Thru B1.8

ANSI Relaying Accuracy (60 Hz) T-90 T-90 T-90 T-90 T-90 T-90 T-90 T-90 T-90 T-90 T-90 T-90 T-90 T-200 T-90 T-90 T-200

Mechanical Rating (RMS Sym.) x Normal 250 250 250 250 250 250 250 250 250 250 250 250 250 100 250 250 100

Thermal Rating (1 Sec.) x Normal 100 100 100 100 100 100 100 100 100 100 100 100 100 80 100 100 80

Double Ratio 10/20 20/40 25/50 50/100 75/150 100/200 150/300 200/400 300/600 400/800* 600/1200 7524A14G02 7524A14G03 7524A14G04 7524A14G05 7524A14G06 7524A14G07 7524A14G08 7524A14G09 7524A14G10 7524A14G11 7524A14G12 All Ratings Except* 3.0 Tap 1.5 Full All Ratings 0.3 through B0.9 Tap B1.8 Full All Ratings T90 Tap T200 Full All Ratings 250 Tap 125 Full All Ratings 100 Tap 100
Full

2.0 Tap/1.0 Full

Product Bulletin 42-926 Page 2

Dimensions (in Inches) and Weights

Performance Curves Typical Ratio and Phase Angle Curves Single Ratio Transformers Type KOR-15 Current Transformer, 150 kV BIL, NSV 25 kV Ratio 10 Thru 800 to 5 Amperes (except 500/5) Ratio 10 Thru 800 to 5 Amperes (except 500/5)

Double Ratio Transformers B-0.1: 0.1 Ohm, 90% Pf, 60 Hertz, 2.5 VA High Ratio (Full Winding)

B-0.2: 0.2 Ohm, 90% Pf, 60 Hertz, 5.0 VA B-0.5: 0.5 Ohm, 90% Pf, 60 Hertz, 12.5 VA

B-0.9: 0.9 Ohm, 90% Pf, 60 Hertz, 22.5 VA

Low Ratio (Tapped Winding)

ABB Power T&D Company Inc. Low Voltage Instrument Transformer Pinetops, North Carolina U.S.A. 27864

June 1991