Professional Documents
Culture Documents
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________
Data sheed
Geometry:
Length of north and south facade:
Length of west and east facade:
Height (without roof):
Number of floors:
Deviation from south direction (east positiv):
6,0 m
16,0 m
7,6 m
3
-18,0
Ground area:
Useful area:
Volume total:
Air volume:
Facade north resp. south:
Facade east resp. west:
Surface-to-volume value:
96,0 m
230,4 m
729,6 m
583,7 m
45,6 m
121,6 m
0,6 1/m
Insulation:
U values of the walls:
north:
south:
east:
west:
Upper floor:
Towards:
U value:
Lower floor:
Towards:
U value:
Door (north facade):
Area:
U value:
Wrmebrcken:
0,27 W/(m K)
0,27 W/(m K)
0,01 W/(m K)
0,01 W/(m K)
outside or non-insulated roof
0,27 W/(m K)
outside air
0,26 W/(m K)
10,0 m
1,50 W/(m K)
increase U-values of surounding planes by 0.10
W/(m K) (normal construction)
Building:
Interior temperature:
Limit of overheating:
Ventilation:
Natural ventilation (infiltration):
Mechanical ventilation:
Heat recovery (only mech. ventilation):
Internal gains:
Kind of indoor walls:
20,0 C
26,0 C
0,00 1/h
0,30 1/h
0%
25,0 kWh/(m a)
medium construction
medium construction
east
Climate:
Climate station:
Milano (Italia)
Windows:
North:
Windows area:
Fraction of windows area at the facade:
Kind of windows:
U value glazing:
U value frame:
g value glazing:
Fraction of frame:
Shading:
South:
Window area:
Fraction of windows area at the facade:
Kind of windows:
U value glazing:
U value frame:
g value glazing:
Fraction of frame:
Shading:
East:
Window area:
Fraction of windows area at the facade:
Kind of windows:
U value glazing:
U value frame:
g value glazing:
Fraction of frame:
Shading:
West:
Window area:
Fraction of windows area at the facade:
Kind of windows:
U value glazing:
U value frame:
g value glazing:
Fraction of frame:
Shading:
6,8 m
15,0 %
heat protection double glazing (U = 1.4 W/(m K))
1,40 W/(m K)
1,50 W/(m K)
0,58
20,0 %
20,0 %
16,0 m
35,0 %
heat protection double glazing (U = 1.4 W/(m K))
1,40 W/(m K)
1,50 W/(m K)
0,58
20,0 %
19,0 %
0,0 m
0,0 %
heat protection double glazing (U = 1.4 W/(m K))
1,40 W/(m K)
1,50 W/(m K)
0,58
20,0 %
20,0 %
19,5 m
16,0 %
heat protection double glazing (U = 1.4 W/(m K))
1,40 W/(m K)
1,50 W/(m K)
0,58
20,0 %
20,0 %
Energy:
Heating system:
Heat transfer / system temperature:
Source of energy:
CASAnova
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________
Output: Overview
Heat energy and cooling demand:
Heat energy demand
Cooling demand
in kWh/m
in kWh/m
______________________________________________________________________________
January
9,1
0,0
February
6,6
0,0
March
3,7
0,0
April
1,1
0,0
May
0,0
0,8
June
0,0
1.8
July
0,0
3.6
August
0,0
3.1
September
0,0
1.3
October
0,6
0,1
November
5,8
0,0
December
9,0
0,0
______________________________________________________________________________
Yearly sum
35,9
10,7
4788
54,7
1127
12,9
2349
26,8
CASAnova
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________
11,9
Building data:
Mean U value:
Specific transmission losses:
Specific ventilation losses:
Sum specific losses:
Thermal inertia:
Maximum heating load:
Maximum specific heating load:
Maximum cooling load:
Maximum specific cooling load:
Limit temperature for heating:
Effective heating days:
0,44 W/(m K)
177,9 W/K
62,7 W/K
240,7 W/K
96,9 hours
7,4 kW
32,3 W
6,3 kW
27.5 W
17,2C
240 Tage
CASAnova
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________
55,8
20,1
15,6
24,3
35,9
12847
4620
3600
5592
8276
CASAnova
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________
15,3
3516
12926,9
CASAnova
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________
35,9 kWh/(m a)
0,1 kWh/(m a)
0,6 kWh/(m a)
1,1 kWh/(m a)
0,23
8,7 kWh/(m a)
1,1 kWh/(m a)
0,3 kWh/(m a)
1,7 kWh/(m a)
3,1 kWh/(m a)
3,0
35,4 kWh/(m a)
11,8
35,4
CASAnova
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________
Cooling demand
End energy demand for cooling
Primary energy demand
in kWh/m
in kWh/m
in kWh/m
______________________________________________________________________________
January
0,0
0,0
0,0
February
0,0
0,0
0,0
March
0,0
0,0
0,0
April
0,2
0,1
0,2
May
1,3
0,5
1,6
June
2,5
1,0
3,0
July
4,8
1,9
5,7
August
4,2
1,7
5,0
September
2,0
0,8
2,4
October
0,3
0,1
0,4
November
0,0
0,0
0,0
December
0,0
0,0
0,0
______________________________________________________________________________
Yearly sum
15,3
6,1
18,3