Table of Contents 1 2 3 4 5 6 7 8 9 Scope............................................................. 2 Conflicts and Deviations................................ 2 References..................................................... 2 General.......................................................... 3 Types and Sizes............................................ 4 Material.......................................................... 4 Design and Construction................................ 5 Inspection and Tests...................................... 7 Preparation for Shipment............................... 7

Previous Issue: 4 January 2006

Next Planned Update: 21 June 2016 Page 1 of 8

Primary contact: Mulhim, Khalid Abdul Aziz on 966-3-8745230


CopyrightSaudi Aramco 2011. All rights reserved.

Document Responsibility: Plumbing and Utilities Standards Committee Issue Date: 21 June 2011 Next Planned Update: 21 June 2016

05-SAMSS-002 Automatic Electric Water Heaters

Scope 1.1 This Specification covers the minimum requirements for automatic electric water heating and storage tanks rated no more than 600 volts and 12 kilowatts to be installed in accordance with the National Electric Code, NFPA 70. These requirements do not cover water heaters with a storage tank capacity of less than 4 liters (1 gallon) or more than 450 liters (120 gallons). These requirements do not cover immersed electrodes, side arm, booster, instantaneous or immersion type water heaters.

1.2 1.3

Conflicts and Deviations 2.1 Any conflicts between this specification and other applicable Saudi Aramco Materials System Specifications (SAMSSs), Engineering Standards (SAESs), Standard Drawings (SASDs), or industry standards, codes and forms shall be resolved in writing by the Company or Buyer Representative through the Manager, Consulting Services Department of Saudi Aramco, Dhahran. Direct all requests to deviate from this specification in writing to the Company or Buyer Representative, who shall follow internal company procedure SAEP-302 and forward such requests to the Manager, Consulting Services Department of Saudi Aramco, Dhahran.

2.2

References The selection of material and equipment, and the design, construction, maintenance, and repair of equipment and facilities covered by this specification shall comply with the latest edition of the references listed below, unless otherwise noted. 3.1 Saudi Aramco References SAEP-302 Instructions for Obtaining a Waiver of a Mandatory Saudi Aramco Engineering Requirement

3.2

Industry Codes and Standards American Society of Heating, Refrigerating & Air Conditioning Engineers, Inc. ASHRAE 90A-80 Energy Conservation in New Building Design

American Society for Testing and Materials ASTM A20/A20M General Requirements for Steel Plates for Pressure Vessels
Page 2 of 8

Document Responsibility: Plumbing and Utilities Standards Committee Issue Date: 21 June 2011 Next Planned Update: 21 June 2016

05-SAMSS-002 Automatic Electric Water Heaters

ASTM A53 ASTM A568/A568M

Pipe, Steel, Black and Hot-Dipped, Zinc-Coated Welded and Seamless Standard Specification for Steel, Sheet, Carbon, and High-Strength, Low-Alloy, Hot-Rolled and Cold-Rolled Consumer Product Specification for Garden Hoses Standard Specification for Seamless Copper Tube

ASTM D3901 ASTM B75

American National Standards Institute/ American Society of Mechanical Engineers ANSI/ASME B1.20.1 ASME SA-20/SA-20M Pipe Threads, General Purpose General Requirements for Steel Plates for Pressure Vessels

National Fire Protection Association NFPA 70 National Electric Code

Underwriters Laboratories, Inc. UL 174 UL 1030 4 General The order to which this Specification is attached will contain the following information: a) b) c) d) Size and types of water heaters required Destination and shipping instructions Minimum heating value to be used, using 100% efficiency factor of recovery Inspection and test requirements if they differ from the Standard (procedure indicated herein) Household Electric Storage Tank Water Heaters Sheathed Heating Elements

Page 3 of 8

Document Responsibility: Plumbing and Utilities Standards Committee Issue Date: 21 June 2011 Next Planned Update: 21 June 2016

05-SAMSS-002 Automatic Electric Water Heaters

Types and Sizes The basic types and sizes of heaters are as tabulated below:
Approximate Storage Capacity Liters (Gallons) 75 115 150 190 300 450 (20) (30) (40) (50) (80) (120) Electric Water Heater Non-Simultaneous (208V (240V) (480V) Low Watt Density Heating Elements 2000 3500/3500 3500/3500 4500/4500 4500/4500 4500/4500 L/Hr (GPH) Recovery at 15.5C (60F) Rise Using 100% Efficiency Factor (Minimum Values) 51.8 (13.7) 83.2 (22.0) 83.2 (22.0) 83.2 (22.0) 83.2 (22.0) 83.2 (22.0) Water Connection NPS mm (inches) Minimum Size 20 mm 20 mm 20 mm 20 mm 20-25 mm OD () () () () (-1)

As specified

Water inlet and outlet connections are the nominal pipe size male thread to which the external piping is connected. 6 Material 6.1 Steel Plate The steel plate used in fabricating the tank shall conform to ASME SA-20/ SA-20M (ASTM A20/A20M) quality; and steel sheet material shall conform to ASTM A568/A568M. 6.2 Glass Lining The internal surface of the water heater tank shall have a vitreous (glass) or porcelain enamel lining regardless of tank wall thickness. 6.3 Insulation The thermal insulation shall be rigid polyurethane foam water heater insulation, or insulation blanket or batt fiber glass wool in accordance with UL 174. The material shall be nonconductive, nonabsorbent and resistant to combustion. The thermal conductivity shall be energy efficient. 6.4 Heating Elements The heating elements shall be high efficiency, low-watt density type elements.

Page 4 of 8

Document Responsibility: Plumbing and Utilities Standards Committee Issue Date: 21 June 2011 Next Planned Update: 21 June 2016

05-SAMSS-002 Automatic Electric Water Heaters

6.5

Pipe Pipe and pipe fittings shall conform to ASTM A53 for pipe sizes, wall thickness and material. Cold water inlet, hot water outlet and drain pipe and fitting shall be galvanized.

6.6

Gasket The sealing gasket should be non-conductive, heat resistance and resilient type.

6.7

Wiring The wiring should conform to UL standard.

Design and Construction 7.1 7.2 The tank capacity shall be as specified in paragraph 4.a. The minimum thickness of steel plates and steel sheets shall meet ASME SA-20/SA-20M (ASTM A20/A20M) standards before shaping and the glass lining is applied. The tank shall be fusion welded construction. The tank shall be treated by pickling or other process to ensure a clean surface before the internal coating is applied. The tank shall be equipped with an aluminum sacrificial anode rod or rods. The tank shall have manually adjustable automatic temperature controls for a desired temperature range from 27C to 60C (80F to 140F) for standard usage, and a specified higher temperature control range as specified. The tank shall have automatic over-temperature protectors to cut off the power if excess temperature occurs. All controls shall meet UL 174. The tank shall have a cold water inlet tube to replace the cold water at the bottom of the tank to prevent mixing with already heated water. The tank shall have high efficiency and low-watt density type elements sheathed in copper, nickel silver (UNS C75200 preferred) or alloy UNS N0800 per UL 1030. The opening for the temperature and pressure relief valve shall be located on top of the tank bell head. If it is located on the side of the tank, the opening shall be

7.3 7.4 7.5 7.6

7.7 7.8 7.9

7.10

Page 5 of 8

Document Responsibility: Plumbing and Utilities Standards Committee Issue Date: 21 June 2011 Next Planned Update: 21 June 2016

05-SAMSS-002 Automatic Electric Water Heaters

within 150 mm (6 inches) from the top of the tank. The opening shall be separate from the openings for the water connections. 7.11 The tank openings shall be reinforced with welded plate of the proper thickness to ensure that full length pipe threads are cut. Openings shall be taper pipe threads conforming to the requirements of ANSI/ASME B1.20.1. The tank water inlet, water outlet, tank drain and temperature and pressure relief valve shall not be less than 20 mm ( inch ) nominal pipe size (NPS). The control connection shall be sized as needed for the selected control equipment. The heads shall be designed to withstand the pressure rating of the tank. The connections to tank shall be fitted as follows: 7.13.1 The cold water inlet and hot water outlet shall be a galvanized nipple of minimum Schedule 40 pipe size as given in paragraph 5 of this specification. The outer end of the nipple that extends through the shell, shall be threaded with male taper pipe thread as indicated in paragraph 7.11. The nipple shall be exposed to permit the coupling of connecting pipe. A length of durable plastic or copper tubing on the cold water inlet of tank shall extend into tank to not less than six inches from the bottom as required in paragraph 7.8 of this specification. A 6 mm ( inch) diameter hole shall be drilled through the wall of this tubing, near the top of the tank as an anti-siphoning device. If copper tubing is used for the anti-siphoning device, soft annealed tubing conforming to ASTM B75 shall be used. The drain shall not be less than 20 mm ( inch) NPS, Schedule 40 male-threaded, galvanized nipple extending through the shell as indicated in paragraph 7.11. A faucet with a pressure rating suitable for the service with a composition renewable disc shall be attached to this nipple. The outlet male faucet thread shall conform to ASTM D3901 garden hose standard. The control connections needed are to comply with paragraph 7.11. All electrical connections including the thermostats and heater elements shall conform to UL 174. The tank shall be built to withstand a minimum 300 psig (2068 kPa) hydrostatic test pressure, and a minimum working pressure of 150 psig (1034 kPa).

7.12 7.13

7.13.2

7.13.3

7.13.4 7.13.5 7.13.6

Page 6 of 8

Document Responsibility: Plumbing and Utilities Standards Committee Issue Date: 21 June 2011 Next Planned Update: 21 June 2016

05-SAMSS-002 Automatic Electric Water Heaters

7.14 7.15

The outer jacket that surrounds the storage tank shall be made of steel or aluminum and shall have a minimum thickness as per UL 174. Insulation 7.15.1 The insulation shall fill the space between the inner water storage and heating tank and the outer steel jacket. The insulation shall be in accordance with paragraph 6.3. The thicknesses shall meet the energy efficient insulation standards of ASHRAE 90A-80. The insulation of all electrical devices and connections shall be tested in accordance with UL 174.

7.15.2 7.16 Controls 7.16.1 7.16.2

The controls shall comply with all requirements established in UL 174. The automatic temperature controls shall meet the requirements of paragraph 7.6 and 7.7 of this specification. The selection of the desired temperature shall be readily made without the use of special tools nor the necessity of dismantling any part of the controls. A manually operated reset thermostat control shall be provided.

7.16.3 8

Inspection and Tests 8.1 8.2 Each water heater shall be UL listed; and shall be indelibly stamped UL listed together with the UL listed number. Each water heater shall be subject to inspection by the manufacturer's Inspector during process of fabrication. Certification of compliance to this specification shall be provided with each water heater. All tests and inspections shall be made at the place or places of manufacture or fabrication. Pressure testing on the tanks shall be in accordance with UL 174. At least one water heater of each type or design shall be tested as indicated in UL 174. In addition, each unit shall be tested per the vendor's standards, to ensure consistent quality and performance per specifications established for the water heater.

8.3 8.4

Preparation for Shipment 9.1 Each water heater shall be prepared for shipment to conform with Saudi Aramco export packing specifications.

Page 7 of 8

Document Responsibility: Plumbing and Utilities Standards Committee Issue Date: 21 June 2011 Next Planned Update: 21 June 2016

05-SAMSS-002 Automatic Electric Water Heaters

9.2

All pipe connections shall be protected from the entrance of debris by use of suitable tight fitting wooden plugs, or other suitable plugs or covers of metal or plastic.

21 June 2011

Revision Summary Revised the "Next Planned Update". Reaffirmed the contents of the document, and reissued with Editorial revision to remove the committee members list.