SEC-EOA Contract No.

30731117/0 0

AL-SENAEYAH BSP 69/13.8kV S/S-2


SITE TEST REPORT AC DISTRIBUTION BOARD

Date : Sheet # 1 of 9

380 V & 220 V , 3 PHASE AC DISTRIBUTION BOARDS SUMMARY OF TESTS

Sl.No. A. B. 1. 2. C. D. E. F.

Test Description MECHANICAL CHECK & VISUAL INSPECTION ELECTRICAL TESTS OPERATION OF MCBs INSULATION RESISTANCE TEST VOLTAGE AND PHASE COINCIDENCE CHECK AUTO BUS TRANSFER SCHEME CHECK UNDER VOLTAGE SENSITIVITY CHECK TESTING OF METERS

TESTED BY : NAME SIGNATURE :

NCC

WITNESSED BY NAME : :

SEC-EOA
DEPT.:

SIGNATURE

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SEC-EOA Contract No. 30731117/0 0 A.

AL-SENAEYAH BSP 69/13.8kV S/S-2


SITE TEST REPORT AC DISTRIBUTION BOARD

Date : Sheet # 2 of 9

MECHANICAL CHECK & VISUAL INSPECTION : TEST INSTRUMENT Torque Wrench Make Sl.No. Calibration Certificate Sl.No.
1. 2. 3. 4.

: : : Test Procedure
Physical damage / defects Tightness of Bolted connection with torque wrench. Proper Grounding connections Check the size & quantity of incoming & outgoing feeders as per approved drawing. Check that the appropriate cable is connected as per cable schedule. Check for proper mounting of Auto Transfer Switch Verify all front panel mounted devices are installed as per approved drawing. Check for permanent identification Panel and Breaker identification. ( Feeder identification ) of

Criteria
No defects Tightness As per approved drawing To comply with

Result

5. 6. 7. 8.

To comply with As per approved drawing To comply with As per approved drawing

TESTED BY : NAME SIGNATURE :

NCC

WITNESSED BY NAME : :

SEC-EOA
DEPT.:

SIGNATURE

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SEC-EOA Contract No. 30731117/0 0 B.

AL-SENAEYAH BSP 69/13.8kV S/S-2


SITE TEST REPORT AC DISTRIBUTION BOARD

Date : Sheet # 3 of 9

ELECTRICAL TESTS : Sl.No. 1. Test Procedure Peform ON / OFF Operation of all MCB's and check the circuit continuity. Insulation reistance of wiring ( 500V DC ) A - Phase to Earth B - Phase to Earth C - Phase to Earth A - Phase to A Phase B - Phase to C Phase C - Phase to A Phase buses and > 1 M Ohms > 1 M Ohms > 1 M Ohms > 1 M Ohms > 1 M Ohms > 1 M Ohms Criteria Proper Operation Result

2.

TESTED BY : NAME SIGNATURE :

NCC

WITNESSED BY NAME : :

SEC-EOA
DEPT.:

SIGNATURE

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SEC-EOA Contract No. 30731117/0 0

AL-SENAEYAH BSP 69/13.8kV S/S-2


SITE TEST REPORT AC DISTRIBUTION BOARD

Date : Sheet # 4 of 9

C. VOLTAGE AND PHASE COINCIDENCE CHECK : Procedure 1. Apply 380 V, 3 Phase to the 34.5kV side of Station Transformers 1 & 2 from a common source as in test connection. 2. Measure the voltage across the phases in the Bus tie as given in table. 3. Both the Transformer shall be kept at Normal Tap Measured at Auto Transfer Switch Terminal Measured Between Criteria Volts Measured Volts Remarks

A Phase of Incomer # 1 & A Phase of Incomer # 2 B Phase of Incomer # 1 & B Phase of Incomer # 2

C Phase of Incomer # 1 & C Phase of Incomer # 2

TESTED BY : NAME SIGNATURE :

NCC

WITNESSED BY NAME : :

SEC-EOA
DEPT.:

SIGNATURE

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SEC-EOA Contract No. 30731117/0 0 D.

AL-SENAEYAH BSP 69/13.8kV S/S-2


SITE TEST REPORT AC DISTRIBUTION BOARD

Date : Sheet # 5 of 9

AUTO TRANSFER SCHEME CHECK : Functional Check : Procedure 1) 2) Sl. No. 1. 2. Energise the sources of both Main supplies, Main I & II keeping the Main Incomer 1 & 2 and ATS switch in OFF position. The magnitude of both the voltages shall be 380 V, 3 phase. Test Switch Position OFF MANUAL Both the closed. Criteria Main ACB's shall not be Result

Closing Interlock for Incomer A. Incomer ACB shall be closed when i) The other Incomer & Bus tie are in OPEN position. ii) The other Incomer in closed & Bus tie in OPEN position. iii) O/C & E/F relay not operated. B. Incomer ACB shall not be closed when i) The other Incomer & Bus tie ACB's are in closed position.

TESTED BY : NAME SIGNATURE :

NCC

WITNESSED BY NAME : :

SEC-EOA
DEPT.:

SIGNATURE

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SEC-EOA Contract No. 30731117/0 0 Sl. No.

AL-SENAEYAH BSP 69/13.8kV S/S-2


SITE TEST REPORT AC DISTRIBUTION BOARD

Date : Sheet # 6 of 9

Test Switch Position AUTO

Criteria Closing Interlock for Incomer A. Incomer ACB shall be closed when i) No under voltage respective Incomer. in the

Result

ii) O/C & E/F Relays not operated. iii) Either or both the Bus tie & the other Incomer in Open position. iii) Incomer will close after the set time delay. Tripping Interlock for Incomer 3. A. B. 4. MANUAL A) Bus tie Breaker shall be closed when i) O/C & E/F relays not operated. ii) Either Open. one of the Incomer is not be Under voltage in Incoming source. the respective

O/C or Earth fault operated.

Closing Interlock for Bus tie

B) Bus tie Breaker closed when

shall

i) Both the Incomers are in Closed position

TESTED BY : NAME SIGNATURE :

NCC

WITNESSED BY NAME : :

SEC-EOA
DEPT.:

SIGNATURE

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SEC-EOA Contract No. 30731117/0 0 Sl. No.

AL-SENAEYAH BSP 69/13.8kV S/S-2


SITE TEST REPORT AC DISTRIBUTION BOARD

Date : Sheet # 7 of 9

Test Switch Position

Criteria Closing Interlock for Bus tie

Result

AUTO

i) Under voltage in any one of the Incomer source ii) O/C & E/F relay not operated iii) Incomer of under voltage source is Open.

5.

TRIPPING INTERLOCK

i) O/C & E/F relay operated. ii) Resumption of supply voltage for the Incomer source.

6.

AUTO TRANSFER

A.

De-energise Incomer # 1 source & check for i) Tripping of Incomer # 1 through under voltage relay after set time delay ii) Bus tie breaker close after Incomer # 1 has tripped

B.

Energise Incomer # 1 source & check for i) Bus tie breaker instantaneously trips

ii) Closing of Incomer # 1 after the set time delay

TESTED BY : NAME SIGNATURE :

NCC

WITNESSED BY NAME : :

SEC-EOA
DEPT.:

SIGNATURE

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SEC-EOA Contract No. 30731117/0 0

AL-SENAEYAH BSP 69/13.8kV S/S-2


SITE TEST REPORT AC DISTRIBUTION BOARD

Date : Sheet # 8 of 9

Sl. No.

Test Switch Position AUTO TRANSFER

Criteria C. De-energise Incomer # 2 source & check for i) Tripping of Incomer # 2 through under voltage relay after the set time delay ii) Bus tie Breaker closing after the set time delay. D) Energise check for Incomer # 2 source & breaker trips

Result

i) Bus tie instantaneously.

ii) Closing of Incomer # 2 after the set time delay. 7. Check all other functional checks as per approved drawing.

TESTED BY : NAME SIGNATURE :

NCC

WITNESSED BY NAME : :

SEC-EOA
DEPT.:

SIGNATURE

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SEC-EOA Contract No. 30731117/0 0

AL-SENAEYAH BSP 69/13.8kV S/S-2


SITE TEST REPORT AC DISTRIBUTION BOARD

Date : Sheet # 9 of 9

TESTED BY : NAME SIGNATURE :

NCC

WITNESSED BY NAME : :

SEC-EOA
DEPT.:

SIGNATURE

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SEC-EOA Contract No. 30731117/0 0 E.

AL-SENAEYAH BSP 69/13.8kV S/S-2


SITE TEST REPORT AC DISTRIBUTION BOARD

Date : Sheet # 10 of 9

UNDER VOLTAGE SENSIVITY CHECK : Test Instrument 1) Single phase Variac : Make Sl. No. Type : : :

2) Multimeter ( Voltmeter range ) Make Sl.No. Type Sl. No. 1. : : : Description 75% Under Voltage Pick-up Volts Incomer # 1 80% 85% 95% 75% Incomer # 2 80% 85% 95%

2.

Under Voltage Drop-off Volts

Final Settings Under Voltage Set at :

TESTED BY : NAME SIGNATURE :

NCC

WITNESSED BY NAME : :

SEC-EOA
DEPT.:

SIGNATURE

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SEC-EOA Contract No. 30731117/0 0 F.

AL-SENAEYAH BSP 69/13.8kV S/S-2


SITE TEST REPORT AC DISTRIBUTION BOARD

Date : Sheet # 11 of 9

TESTING OF METERS : Sl.No. 1. 2. 3. Test Instruments Current & Voltage Injection Test Kit Voltmeter Ammeter INCOMER # 1 Class of Accuracy Injected Current / Voltage Meter reading Result Serial Number

Field Measurements : Meter Ammeter Range

Voltmeter INCOMER # 2 Meter Ammeter Range Class of Accuracy Injected Current / Voltage Meter reading Result

Voltmeter

TESTED BY : NAME SIGNATURE :

NCC

WITNESSED BY NAME : :

SEC-EOA
DEPT.:

SIGNATURE

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA