Power supply consumption calculation for Medium Voltage switchgear type Unigear ZS1

ABB s.r.o., Czech Republic Project/contract name: Switchgear name: Required supply: 1000029697 - Sonatrach 12kV Switchgear, 17-panels type UniGear ZS1 110 V DC Prepared by: Revision: Date: Doc. No.: LOAD PROFILES AND POWER CONSUMPTION [W] Continuous Inrush (150ms) Peak (5s) Sum for Sum for Sum for Sum for Sum for Sum for Sum for Sum for Sum for Sum for ARRIVE TRANSFO. PUISSANCE DPART ARMOIRES (RSERVE) DPART CABLE PUIT DPART TRANSFO. AUX. DPART ARMOIRES VARIATEURS REMONTE ET MESURE COUPLAGE MEASURE 0 0 Total swg. consumption [W]: 97,1 41,8 404,3 83,6 83,6 33,2 58,0 35,4 0,0 0,0 836,9 Continuous SUMMARY FOR THE REQUIRED SUPPLY 110V DC 1. 2. 3. For proper function of the switchgear is necessary cover Continuous current demand: For proper function of the switchgear is necessary cover Inrush (150ms) current demand: For proper function of the switchgear is necessary cover Peak (5s) current demand: Note: Frequency of the inrush and peak profiles depends on site conditions (as per frequency of the switching operations). Real AC consumption may vary from 0 VA to the calculated value (assumed worst case with all the heaters and lights operating), depending on site conditions. Calculated value is without spare - for increase value please multiplie with spare coefficient (typicaly for spare 20% multiple by *1,2). Inrush and Peak consumption for CB coils (-MS, -MC, -RL1, -MO1) are calculated only for Incoming + Tie Breaker feeders in section (typicaly no more feeders will operate at the same time). PARTICULAR CALCULATIONS: Net values: 7,61 A 68,41 A 3,64 A 2650,0 375,0 2625,0 750,0 750,0 0,0 375,0 0,0 0,0 0,0 7525,0 Inrush (150ms) 400,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 400,0 Peak (5s) Multiplied with safety coefficient: 1,2 1,2 1,2 9,13 A 82,09 A 4,36 A SEDY 0 17.6.2013

A B C D E F G H I J

Typical panels ARRIVE TRANSFO. PUISSANCE DPART ARMOIRES (RSERVE) DPART CABLE PUIT DPART TRANSFO. AUX. DPART ARMOIRES VARIATEURS REMONTE ET MESURE COUPLAGE MEASURE

Qty 2 1 7 2 2 1 1 1 0 0

Note

Total No. of panels:

17

ARRIVE TRANSFO. PUISSANCE Type of consumption Equipment of the panel (load profile) Inrush (150ms) Continuous Inrush (150ms) Continuous Continuous Continuous Continuous Continuous Continuous Inrush (150ms) Peak (5s) Inrush (150ms) Inrush (150ms) Continuous Unit cons. [W] 250 5 250 5 5 2,2 3,5 12 2,2 500 200 200 250 5

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 1 1 1 1 3 1 3 1 1 1 1 2 Simult. oper. coefficient 0,50 0,50 1,00 1,00 1,00 1,00 0,50 1,00 1,00 1,00 1,00 1,00 1,00 1,00 Panel cons. [W] 125,0 2,5 250,0 5,0 5,0 2,2 5,3 12,0 6,6 500,0 200,0 200,0 250,0 10,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per panel: [W] Continuous Inrush (150ms) Peak (5s) 48,6 1200,0 200,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Total panels in swg. 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Swg. cons. [W] 250,0 5,0 500,0 10,0 10,0 4,4 10,5 24,0 13,2 1000,0 400,0 400,0 500,0 20,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [W] Continuous Inrush (150ms) Peak (5s) 97,1 2650,0 400,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

CB blocking coil -RL1 CB blocking coil -RL1 Truck blocking coil -RL2 Truck blocking coil -RL2 ES blocking coil RL3 Signal lamp Auxiliary relay KC6 Protection Relay REF 615 Status indicator CB motor charger -MS CB motor charger -MS CB closing coil -MC CB tripping coil -MO1 Programmable Transducer

DPART ARMOIRES (RSERVE) Type of consumption Equipment of the panel (load profile) Inrush (150ms) Continuous Inrush (150ms) Continuous Continuous Continuous Continuous Continuous Continuous Continuous Unit cons. [W] 250 5 250 5 5 2,2 3,5 12 2,2 5

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 1 1 1 1 2 1 3 1 Simult. oper. coefficient 0,50 0,50 1,00 1,00 1,00 1,00 0,50 1,00 1,00 1,00 Panel cons. [W] 125,0 2,5 250,0 5,0 5,0 2,2 3,5 12,0 6,6 5,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per panel: [W] Continuous Inrush (150ms) Peak (5s) 41,8 375,0 0,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 1 1 1 1 1 1 1 1 1 1 Total panels in swg. 1 1 1 1 1 1 1 1 1 1 Swg. cons. [W] 125,0 2,5 250,0 5,0 5,0 2,2 3,5 12,0 6,6 5,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [W] Continuous Inrush (150ms) Peak (5s) 41,8 375,0 0,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

CB blocking coil -RL1 CB blocking coil -RL1 Truck blocking coil -RL2 Truck blocking coil -RL2 ES blocking coil RL3 Signal lamp Auxiliary relay KC6 Protection Relay REF 615 Status indicator Programmable Transducer

DPART CABLE PUIT Type of consumption Equipment of the panel (load profile) Inrush (150ms) Continuous Inrush (150ms) Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Unit cons. [W] 250 5 250 5 5 2,2 3,5 12 2,2 5 12

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 1 1 1 2 3 1 3 1 1 Simult. oper. coefficient 0,50 0,50 1,00 1,00 1,00 1,00 0,50 1,00 1,00 1,00 1,00 Panel cons. [W] 125,0 2,5 250,0 5,0 5,0 4,4 5,3 12,0 6,6 5,0 12,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per panel: [W] Continuous Inrush (150ms) Peak (5s) 57,8 375,0 0,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 7 7 7 7 7 7 7 7 7 7 7 Total panels in swg. 7 7 7 7 7 7 7 7 7 7 7 Swg. cons. [W] 875,0 17,5 1750,0 35,0 35,0 30,8 36,8 84,0 46,2 35,0 84,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [W] Continuous Inrush (150ms) Peak (5s) 404,3 2625,0 0,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

CB blocking coil -RL1 CB blocking coil -RL1 Truck blocking coil -RL2 Truck blocking coil -RL2 ES blocking coil RL3 Signal lamp Auxiliary relay KC6 Protection Relay REF 615 Status indicator Programmable Transducer Protection Relay RED 615

DPART TRANSFO. AUX. Type of consumption Equipment of the panel (load profile) Inrush (150ms) Continuous Inrush (150ms) Continuous Continuous Continuous Continuous Continuous Continuous Continuous Unit cons. [W] 250 5 250 5 5 2,2 3,5 12 2,2 5

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 1 1 1 1 2 1 3 1 Simult. oper. coefficient 0,50 0,50 1,00 1,00 1,00 1,00 0,50 1,00 1,00 1,00 Panel cons. [W] 125,0 2,5 250,0 5,0 5,0 2,2 3,5 12,0 6,6 5,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per panel: [W] Continuous Inrush (150ms) Peak (5s) 41,8 375,0 0,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 2 2 2 2 2 2 2 2 2 2 Total panels in swg. 2 2 2 2 2 2 2 2 2 2 Swg. cons. [W] 250,0 5,0 500,0 10,0 10,0 4,4 7,0 24,0 13,2 10,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [W] Continuous Inrush (150ms) Peak (5s) 83,6 750,0 0,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

CB blocking coil -RL1 CB blocking coil -RL1 Truck blocking coil -RL2 Truck blocking coil -RL2 ES blocking coil RL3 Signal lamp Auxiliary relay KC6 Protection Relay REF 615 Status indicator Programmable Transducer

DPART ARMOIRES VARIATEURS Type of consumption Equipment of the panel (load profile) Inrush (150ms) Continuous Inrush (150ms) Continuous Continuous Continuous Continuous Continuous Continuous Continuous Unit cons. [W] 250 5 250 5 5 2,2 3,5 12 2,2 5

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 1 1 1 1 2 1 3 1 Simult. oper. coefficient 0,50 0,50 1,00 1,00 1,00 1,00 0,50 1,00 1,00 1,00 Panel cons. [W] 125,0 2,5 250,0 5,0 5,0 2,2 3,5 12,0 6,6 5,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per panel: [W] Continuous Inrush (150ms) Peak (5s) 41,8 375,0 0,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 2 2 2 2 2 2 2 2 2 2 Total panels in swg. 2 2 2 2 2 2 2 2 2 2 Swg. cons. [W] 250,0 5,0 500,0 10,0 10,0 4,4 7,0 24,0 13,2 10,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [W] Continuous Inrush (150ms) Peak (5s) 83,6 750,0 0,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

CB blocking coil -RL1 CB blocking coil -RL1 Truck blocking coil -RL2 Truck blocking coil -RL2 ES blocking coil RL3 Signal lamp Auxiliary relay KC6 Protection Relay REF 615 Status indicator Programmable Transducer

REMONTE ET MESURE Type of consumption Equipment of the panel (load profile) Continuous Continuous Continuous Continuous Continuous Continuous Unit cons. [W] 2,2 3,5 12 2,2 5 10

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 1 1 1 1 Simult. oper. coefficient 1,00 0,50 1,00 1,00 1,00 1,00 Panel cons. [W] 2,2 1,8 12,0 2,2 5,0 10,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per panel: [W] Continuous Inrush (150ms) Peak (5s) 33,2 0,0 0,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 1 1 1 1 1 1 Total panels in swg. 1 1 1 1 1 1 Swg. cons. [W] 2,2 1,8 12,0 2,2 5,0 10,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [W] Continuous Inrush (150ms) Peak (5s) 33,2 0,0 0,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Signal lamp Auxiliary relay KC6 Protection Relay REU 615 Status indicator Programmable Transducer Ethernet switch

COUPLAGE Type of consumption Equipment of the panel (load profile) Inrush (150ms) Continuous Inrush (150ms) Continuous Continuous Continuous Continuous Continuous Continuous Unit cons. [W] 250 5 250 5 5 2,2 3,5 12 2,2

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 1 1 1 2 6 2 3 Simult. oper. coefficient 0,50 0,50 1,00 1,00 1,00 1,00 0,50 1,00 1,00 Panel cons. [W] 125,0 2,5 250,0 5,0 5,0 4,4 10,5 24,0 6,6 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per panel: [W] Continuous Inrush (150ms) Peak (5s) 58,0 375,0 0,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 1 1 1 1 1 1 1 1 1 Total panels in swg. 1 1 1 1 1 1 1 1 1 Swg. cons. [W] 125,0 2,5 250,0 5,0 5,0 4,4 10,5 24,0 6,6 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [W] Continuous Inrush (150ms) Peak (5s) 58,0 375,0 0,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

CB blocking coil -RL1 CB blocking coil -RL1 Truck blocking coil -RL2 Truck blocking coil -RL2 ES blocking coil RL3 Signal lamp Auxiliary relay KC6 Protection Relay REF 615 Status indicator

MEASURE Type of consumption Equipment of the panel (load profile) Continuous Continuous Continuous Continuous Continuous Continuous Unit cons. [W] 2,2 3,5 12 2,2 5 10

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Sum per panel: [W] Continuous Inrush (150ms) Peak (5s) Simult. oper. coefficient 1,00 0,50 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 Panel cons. [W] 2,2 1,8 12,0 4,4 5,0 10,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 35,4 0,0 0,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 1 1 1 1 1 1 Total panels in swg. 1 1 1 1 1 1 Swg. cons. [W] 2,2 1,8 12,0 4,4 5,0 10,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [W] Continuous Inrush (150ms) Peak (5s) 35,4 0,0 0,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Signal lamp Auxiliary relay KC6 Protection Relay REU 615 Status indicator Programmable Transducer Ethernet switch

Power supply consumption calculation for Medium Voltage switchgear type Unigear ZS1
ABB s.r.o., Czech Republic Project/contract name: Switchgear name: Required supply: 1000029697 - Sonatrach 12kV Switchgear, 17-panels type UniGear ZS1 230 V AC (50Hz) Prepared by: Revision: Date: Doc. No.: LOAD PROFILES AND POWER CONSUMPTION [VA] Typical panels A B C D E F G H I J Total No. of panels: ARRIVE TRANSFO. PUISSANCE DPART ARMOIRES (RSERVE) DPART CABLE PUIT DPART TRANSFO. AUX. DPART ARMOIRES VARIATEURS REMONTE ET MESURE COUPLAGE MEASURE Qty 2 1 7 2 2 1 1 1 0 0 17 Sum for Sum for Sum for Sum for Sum for Sum for Sum for Sum for Sum for Sum for ARRIVE TRANSFO. PUISSANCE DPART ARMOIRES (RSERVE) DPART CABLE PUIT DPART TRANSFO. AUX. DPART ARMOIRES VARIATEURS REMONTE ET MESURE COUPLAGE MEASURE 0 0 Total swg. consumption [VA]: Continuous 382,0 191,0 1337,0 382,0 382,0 191,0 191,0 191,0 0,0 0,0 3247,0 Continuous Inrush (150ms) 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Inrush (150ms) Peak (5s) 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Peak (5s) Note SEDY 0 17.6.2013

SUMMARY FOR THE REQUIRED SUPPLY 230V AC (50Hz) 1. 2. 3. For proper function of the switchgear is necessary cover Continuous current demand: For proper function of the switchgear is necessary cover Inrush (150ms) current demand: For proper function of the switchgear is necessary cover Peak (5s) current demand:

Net values: 14,12 A 0,00 A 0,00 A or or or

Multiplied with safety coefficient: 1,2 1,2 1,2 16,94 A 0,00 A 0,00 A

Note: Real AC consumption may vary from 0 VA to the calculated value (assumed worst case with all the heaters and lights operating), depending on site conditions. PARTICULAR CALCULATIONS:

ARRIVE TRANSFO. PUISSANCE Type of consumption Equipment of the panel (load profile) Continuous Continuous Unit cons. [VA] 180 11

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 Simult. oper. coefficient 1,00 1,00 Panel cons. [VA] 180,0 11,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per panel: [VA] Continuous Inrush (150ms) Peak (5s) 191,0 0,0 0,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 2 2 Total panels in swg. 2 2 Swg. cons. [VA] 360,0 22,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [VA] Continuous Inrush (150ms) Peak (5s) 382,0 0,0 0,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Heating Lighting

DPART ARMOIRES (RSERVE) Type of consumption Equipment of the panel (load profile) Continuous Continuous Unit cons. [VA] 180 11

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 Simult. oper. coefficient 1,00 1,00 Panel cons. [VA] 180,0 11,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per panel: [VA] Continuous Inrush (150ms) Peak (5s) 191,0 0,0 0,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 1 1 Total panels in swg. 1 1 Swg. cons. [VA] 180,0 11,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [VA] Continuous Inrush (150ms) Peak (5s) 191,0 0,0 0,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Heating Lighting

DPART CABLE PUIT Type of consumption Equipment of the panel (load profile) Continuous Continuous Unit cons. [VA] 180 11

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 Simult. oper. coefficient 1,00 1,00 Panel cons. [VA] 180,0 11,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per panel: [VA] Continuous Inrush (150ms) Peak (5s) 191,0 0,0 0,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 7 7 Total panels in swg. 7 7 Swg. cons. [VA] 1260,0 77,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [VA] Continuous Inrush (150ms) Peak (5s) 1337,0 0,0 0,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Heating Lighting

DPART TRANSFO. AUX. Type of consumption Equipment of the panel (load profile) Continuous Continuous Unit cons. [VA] 180 11

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 Simult. oper. coefficient 1,00 1,00 Panel cons. [VA] 180,0 11,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per panel: [VA] Continuous Inrush (150ms) Peak (5s) 191,0 0,0 0,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 2 2 Total panels in swg. 2 2 Swg. cons. [VA] 360,0 22,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [VA] Continuous Inrush (150ms) Peak (5s) 382,0 0,0 0,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Heating Lighting

DPART ARMOIRES VARIATEURS Type of consumption Equipment of the panel (load profile) Continuous Continuous Unit cons. [VA] 180 11

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 Simult. oper. coefficient 1,00 1,00 Panel cons. [VA] 180,0 11,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per panel: [VA] Continuous Inrush (150ms) Peak (5s) 191,0 0,0 0,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 2 2 Total panels in swg. 2 2 Swg. cons. [VA] 360,0 22,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [VA] Continuous Inrush (150ms) Peak (5s) 382,0 0,0 0,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Heating Lighting

REMONTE ET MESURE Type of consumption Equipment of the panel (load profile) Continuous Continuous Unit cons. [VA] 180 11

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 Simult. oper. coefficient 1,00 1,00 Panel cons. [VA] 180,0 11,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per panel: [VA] Continuous Inrush (150ms) Peak (5s) 191,0 0,0 0,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 1 1 Total panels in swg. 1 1 Swg. cons. [VA] 180,0 11,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [VA] Continuous Inrush (150ms) Peak (5s) 191,0 0,0 0,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Heating Lighting

COUPLAGE Type of consumption Equipment of the panel (load profile) Continuous Continuous Unit cons. [VA] 180 11

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 Simult. oper. coefficient 1,00 1,00 Panel cons. [VA] 180,0 11,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per panel: [VA] Continuous Inrush (150ms) Peak (5s) 191,0 0,0 0,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 1 1 Total panels in swg. 1 1 Swg. cons. [VA] 180,0 11,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [VA] Continuous Inrush (150ms) Peak (5s) 191,0 0,0 0,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Heating Lighting

MEASURE Type of consumption Equipment of the panel (load profile) Continuous Continuous Unit cons. [VA] 180 11

Stand alone typical panel consumption Unit Oty. [Nos] 1 1 Simult. oper. coefficient 1,00 1,00 Panel cons. [VA] 180,0 11,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per panel: [VA] Continuous Inrush (150ms) Peak (5s) 191,0 0,0 0,0

Consumption of typical panels in the switchgear Simult. oper. panels in swg. 1 1 Total panels in swg. 1 1 Swg. cons. [VA] 180,0 11,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 Sum per swg.: [VA] Continuous Inrush (150ms) Peak (5s) 191,0 0,0 0,0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Heating Lighting