You are on page 1of 2

TSI VEDA 48/230

Technical features

Version 02

TSI-VEDA REG 48/230


Modular Inverter without single point of failure

The TSI is designed according to the golden rules of True Redundant Systems. One of the most important features is the disconnection capability. A TSI converter has no less than 3 disconnecting levels in series (i.e. electronics, relay and fuse) on its DC power port as well as an optical isolation on the double communication bus. Extremely compact with total depth of 264 mm, the VEDA range is specifically designed for ETSI and even outdoor enclosures with a very wide T operating range of -25C to +65C.

GENERAL
EMC (immunity) EMC (emission) Safety Cooling Isolation MTBF Efficiency (Typical)
On Line

AC OUTPUT SPECIFICATIONS
EN 61000-4 EN 55022 (Class 1) EN 60950 Forced Doubled 230000 hrs Nominal voltage (AC) (*) Voltage range (AC) (Adjustable) Voltage accuracy Frequency Frequency accuracy Total harmonic distortion (resistive load) Load impact recovery time Turn on delay Nominal current
Protected against reverse current

230 V 200 240 V 2% 50 60 Hz 0.03 % <2 % 0.4 ms 30 s 2,17 A 3

88%

Dielectric strength DC/AC True Redundant Systems RoHS Connection I/O

4300Vdc Compliant Compliant Terminal block

3 disconnection levels on ACout and DCin power ports (electronics , fuses, relays)

Crest factor at nominal power


With short circuit management and protection

Protected against inversion of polarity Self adaptive to wide operating conditions and comprehensive table of troubleshooting codes

AC OUTPUT POWER
600 VA @50C 500 VA @65C 480 W @50C Output power (resistive load) 400 W @65C Short time overload capacity 150% 15 second Permanent overload capacity 110% Admissible Full power rating from load power factor 0 inductive to 0 capacitive Internal temperature management and switch off Nominal Output power

ENVIRONMENT
Altitude above sea Ambient temperature Storage temperature Relative humidity < 4,900 Ft -25 to 65 C -40 to 80 C 95% , non condensing

SIGNALING & SUPERVISION


Display Alarms output Supervision Synoptic LED Dry contacts on shelf Use optional devices

DC INPUT SPECIFICATIONS
Nominal voltage (DC) Voltage range (DC) Nominal current (at 48Vdc) Maximum input current (for 15 second) Voltage ripple Input voltage boundaries user selectable 48 V 40 - 60 V 12 A 21 A 2mV

WEIGHT & DIMENSIONS


19 Width 264 mm Depth 1U Height 5 kg (Shelf + 2 modules) Weight Coated steel Material (casing) (*) Operation within lower voltage networks leads to derating of power performances.

Specifications can change without notice. New data will be updated on our Web site: www.cet.be. The present equipment is protected by several international patents, trademarks and copyrights.

CE+T S.A. Zoning Industriel de Wandre B-4020 WANDRE

Tel + 32 4 345 67 00 Fax + 32 4 345 67 01

ISO 9001 I certified I

You might also like