You are on page 1of 16

SECTION

DRIVE
ISOLATION
TRANSFORMERS
&
AC LINE REACTORS
Specifically designed to accommodate
the special voltage and KVA sizes unique
to AC and DC drive applications. Shielded
for extra protection from supply line
transients.
General Description & Features . . . . . . . . . . .54-55
Thermal Switches . . . . . . . . . . . . . . . . . . . . . . . .57
Selection Charts . . . . . . . . . . . . . . . . . . . . . . .56-57
Windings, Terminations & Construction . . . . . . .57

AC Line Reactors are designed to


protect DC motor drives, AC variable
frequency drives and the motors
they power.
AC LINE REACTORS

General Description & Features . . . . . . . . . . .58-59


Selection Charts . . . . . . . . . . . . . . . . . . . . . . . . . .60
ENCAPSULATED AC LINE REACTORS

General Description & Features . . . . . . . . . . . . .61


Selection Charts . . . . . . . . . . . . . . . . . . . . . . . . . .62
Design figures, connection
diagrams and accessories begin on page 146.
NOTE:

SECTION

DRIVE ISOLATION TRANSFORMERS

Drive Isolation Transformers

The Acme Drive Isolation Transformers are


specifically designed to accommodate the
special voltages and KVA sizes unique to AC
and DC motor drive applications.

FEATURES

UL Type 3R Enclosures with Weather Shield


on Ventilated Units (above 20 KVA). Type 2
Enclosure without weather shield. UL Listed and
CSA certified. 7.520.0 KVA are encapsulated,
UL 3R.
3-Phase 60 Hertz.
180C and 220C insulation systems.
Encapsulated and ventilated designs. All
ventilated units, are of strip wound construction.
Acmes reinforced core assemblies enhance
quiet operation.
Nominally 6% impedance.
Designed for use with AC, adjustable frequency
or DC drives.
Full capacity taps are featured on all units. On
7.5 through 20 KVA units, taps are 1-5% ANFC
and 1-5% BNFC. On 27 through 660 KVA units,
taps are 2-2 1/2 % ANFC and 2-2 1/2 % BNFC.
Full range of KVA ratings cover all standard
drive systems.
Ample wiring compartment for easy cable entry.
Optional wall mounting brackets for certain sizes.

Stress
relief
Acme uses strip conductors (above 7.5 KVA) instead

of wire for a DIT series that easily accommodates


the severe electrical and mechanical stresses
found in todays AC & DC motor drives. The inherent
excellent line isolation of these transformers is
further enhanced with the extra protection of
Acmes Electrostatic Shield free in all DITs.

Lower
losses
The harmonic currents generated by AC & DC

drives increase eddy current losses (heat) in


transformer windings. The thicker the winding
conductor, the greater the losses. Acme uses one
turn per layer of thin strip conductor which provides
lower eddy current losses than comparable wire
wound units. Lower losses = cooler operation
and longer transformer life.

54

DTGB-040-4S
DTGA-7-2S

DTHA-0330-4S

DTGA-014-2S

Reduced short
circuit
forces
Strip windings minimize axial short

circuit forces that can cause mechanical


displacement of the windings under
fault conditions. For extra protection all
designs 7.5 KVA and above use primary
and secondary coils of equal axial
length. This feature tends to negate
axial short circuit forces, further
improving transformer life expectancy.

Selection
instructions
If you know the motor horse-power,

simply follow the drive system manufacturer's recommendation. Or, select


the corresponding KVA from the chart
at right.
For example, a 40 Hp motor requires a
51 KVA DIT.

H.P.

KVA

5.0

7.5

7.5

11.0

10.0

14.0

15.0

20.0

20.0

27.0

25.0

34.0

30.0

40.0

40.0

51.0

50.0

63.0

60.0

75.0

75.0

93.0

100.0

118.0

125.0

145.0

150.0

175.0

200.0

220.0

250.0

275.0

300.0

330.0

400.0

440.0

500.0

550.0

600.0

660.0

ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION LUMBERTON, NC 800-334-5214 www.acmepowerdist.com

SECTION

DRIVE ISOLATION TRANSFORMERS

Acme Advantages

Copper terminations provide


Wound Cores and Strip
trouble-free operation
Winding
mean
lower
losses
All Acme DITs above 7.5 KVA are wound with strip windings All Acme DITs up to and including 220 KVA have copper termito ensure the lowest possible eddy current losses. All our
DITs use a three leg wound core. This superior design has
very low losses and quiet operation. Both of these features
combine to significantly reduce losses and operating costs
compared to other types of constructions.

nations. The transition from aluminum strip coil conductors


to copper terminations is accomplished by a bonding process
known as Koldwelding. This process has been used by
Acme for over 25 years to provide a trouble-free, permanent
bonding of the two metals.

Wound core construction showing all copper terminations

ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION LUMBERTON, NC 800-334-5214 www.acmepowerdist.com

55

DRIVE ISOLATION TRANSFORMERS


SELECTION CHARTS

SECTION

GROUP A

KVA
7.5
11.0
14.0
20.0
27.0
34.0
40.0
51.0
63.0
75.0
93.0
118.0
145.0
175.0
220.0
275.0
330.0
440.0
550.0
660.0
770.0
880.0

Primary 460V Delta


Secondary 230Y/133
CATALOG NO.

DTGA-7-2S or TS # (37)
DTGA-011-2S or TS # (37)
DTGA-014-2S or TS # (37)
DTGA-020-2S or TS # (37)
DTGA-027-4S (38)
DTGA-034-4S
DTGA-040-4S
DTGA-051-4S
DTGA-063-4S
DTGA-075-4S
DTGA-093-4S
DTGA-0118-4S
DTGA-0145-4S
DTGA-0175-4S
DTGA-0220-4S
DTGA-00275-4S
DTGA-0330-4S
DTGA-440-4S (39)
DTGA-550-4S
DTGA-660-4S

GROUP C
KVA
7.5
11.0
14.0
20.0
27.0
34.0
40.0
51.0
63.0
75.0
93.0
118.0
145.0
175.0
220.0
275.0
330.0
440.0
550.0
660.0
!

Primary 575V Delta


Secondary 230Y/133
CATALOG NO.

DTHA-7-2S or TS # (40)
DTHA-011-2S or TS # (40)
DTHA-014-2S or TS # (40)
DTHA-020-2S or TS # (40)
DTHA-027-4S (41)
DTHA-034-4S
DTHA-040-4S
DTHA-051-4S
DTHA-063-4S
DTHA-075-4S
DTHA-093-4S
DTHA-0118-4S
DTHA-0145-4S
DTHA-0175-4S
DTHA-0220-4S
DTHA-00275-4S
DTHA-0330-4S
DTHA-440-4S (42)
DTHA-550-4S
DTHA-660-4S

GROUP B

Primary 460V Delta


Secondary 460Y/266
CATALOG NO.

APPROX. DIMENSIONS "


Inches (Cm.)
HEIGHT
WIDTH
DEPTH

APPROX.
TYPE MTG. WEATHER
SHIP WEIGHT W - Wall SHIELD
DIM.
Lbs. (Kg.)
F - Floor
P/N
DRAWING

APPROX. DIMENSIONS "


Inches (Cm.)
HEIGHT
WIDTH
DEPTH

APPROX.
TYPE MTG. WEATHER
SHIP WEIGHT W - Wall SHIELD
DIM.
Lbs. (Kg.)
F - Floor
P/N
DRAWING

DTGB-7-2S or TS # (34)
15.21 (38.6)
DTGB-011-2S or TS # (34) 18.86 (47.9)
DTGB-014-2S or TS # (34) 18.86 (47.9)
DTGB-020-2S or TS # (34) 20.77 (52.8)
DTGB-027-4S (35)
25.50 (64.8)
DTGB-034-4S
25.50 (64.8)
DTGB-040-4S
25.50 (64.8)
DTGB-051-4S
29.90 (75.9)
DTGB-063-4S
29.90 (75.9)
DTGB-075-4S
29.90 (75.9)
DTGB-093-4S
35.90 (91.2)
DTGB-0118-4S
35.90 (91.2)
DTGB-0145-4S
41.52 (105.5)
DTGB-0175-4S
41.52 (105.5)
DTGB-0220-4S
41.52 (105.5)
DTGB-00275-4S
45.60 (115.8)
DTGB-0330-4S
45.60 (115.8)
DTGB-440-4S (36)
62.00 (157.5)
DTGB-550-4S
64.00 (162.6)
DTGB-660-4S
64.00 (162.6)
DTGB-770-4S (35)
62.84 (159.61)
DTGB-0880-4S
62.84 (159.61)

19.25 (48.9)
20.30 (51.6)
20.30 (51.6)
20.94 (53.2)
24.39 (61.9)
24.39 (61.9)
24.39 (61.9)
28.15 (71.5)
28.15 (71.5)
28.15 (71.5)
31.90 (81.0)
31.90 (81.0)
32.90 (83.6)
32.90 (83.6)
32.90 (83.6)
39.50 (100.3)
39.50 (100.3)
54.00 (137.2)
60.00 (152.4)
64.00 (162.6)
54.00 (137.2)
54.00 (137.2)

7.37 (18.7)
9.03 (22.9)
9.03 (22.9)
10.18 (25.9)
19.37 (49.2)
19.37 (49.2)
19.37 (49.2)
22.37 (56.8)
22.37 (56.8)
22.37 (56.8)
26.88 (68.3)
26.88 (68.3)
29.88 (75.9)
29.88 (75.9)
29.88 (75.9)
35.50 (90.2)
35.50 (90.2)
42.00 (106.7)
42.00 (106.7)
42.00 (106.7)
41.50 (105.4)
41.50 (105.4)

180 (81.6)
265 (120.0)
270 (123.0)
435 (197.0)
320 (145.0)
340 (154.0)
395 (179.0)
400 (181.0)
550 (250.0)
570 (259.0)
685 (311.0)
765 (347.0)
990 (449.0)
1100 (499.0)
1120 (508.0)
2090 (948.0)
2090 (948.0)
2625 (1191.0)
3000 (1361.0)
3700 (1678.0)
3600 (1633.0)
3816 (1730.9)

W
F
F
F
F!
F!
F!
F!
F!
F!
F
F
F
F
F
F
F
F
F
F
F
F

F
I
I
I
E
E
E
E
E
E
E
E
E
E
E
E
G
G
G
G
G
G

GROUP D
Primary 575V Delta
Secondary 460Y/266
CATALOG NO.

DTHB-7-2S or TS # (43)
DTHB-011-2S or TS # (43)
DTHB-014-2S or TS # (43)
DTHB-020-2S or TS # (43)
DTHB-027-4S (44)
DTHB-034-4S
DTHB-040-4S
DTHB-051-4S
DTHB-063-4S
DTHB-075-4S
DTHB-093-4S
DTHB-0118-4S
DTHB-0145-4S
DTHB-0175-4S
DTHB-0220-4S
DTHB-00275-4S
DTHB-0330-4S
DTHB-440-4S (45)
DTHB-550-4S
DTHB-660-4S

15.21 (38.6)
18.86 (47.9)
18.86 (47.9)
20.77 (52.8)
25.50 (64.8)
25.50 (64.8)
25.50 (64.8)
29.90 (75.9)
29.90 (75.9)
29.90 (75.9)
35.90 (91.2)
35.90 (91.2)
41.52 (105.5)
41.52 (105.5)
41.52 (105.5)
45.60 (115.8)
45.60 (115.8)
62.00 (157.5)
64.00 (162.6)
64.00 (162.6)

Optional wall mounting kits part # PL 79911 refer to Page 157.


Optional wall mounting kits part # PL 79912 refer to Page 157.

19.25 (48.9)
20.30 (51.6)
20.30 (51.6)
20.94 (53.2)
24.39 (61.9)
24.39 (61.9)
24.39 (61.9)
28.15 (71.5)
28.15 (71.5)
28.15 (71.5)
31.90 (81.0)
31.90 (81.0)
32.90 (83.6)
32.90 (83.6)
32.90 (83.6)
39.50 (100.3)
39.50 (100.3)
54.00 (137.2)
60.00 (152.4)
64.00 (162.6)

7.37 (18.7)
9.03 (22.9)
9.03 (22.9)
10.18 (25.9)
19.37 (49.2)
19.37 (49.2)
19.37 (49.2)
22.37 (56.8)
22.37 (56.8)
22.37 (56.8)
26.88 (68.3)
26.88 (68.3)
29.88 (75.9)
29.88 (75.9)
29.88 (75.9)
35.50 (90.2)
35.50 (90.2)
42.00 (106.7)
42.00 (106.7)
42.00 (106.7)

180 (81.6)
265 (120.0)
270 (123.0)
435 (197.0)
320 (145.0)
340 (154.0)
395 (179.0)
400 (181.0)
550 (250.0)
570 (259.0)
685 (311.0)
765 (347.0)
990 (449.0)
1100 (499.0)
1120 (508.0)
2090 (948.0)
2090 (948.0)
2625 (1191.0)
3000 (1361.0)
3700 (1678.0)

W
F
F
F
F!
F!
F!
F!
F!
F!
F
F
F
F
F
F
F
F
F
F

NA
NA
NA
NA
WS-A-1
WS-A-1
WS-A-1
WS-A-2
WS-A-2
WS-A-2
WS-A-3
WS-A-3
WS-A-4
WS-A-4
WS-A-4
WS-A-5
WS-A-5
WS-B-3
WS-B-4
WS-B-5

F
I
I
I
E
E
E
E
E
E
E
E
E
E
E
E
G
G
G
G

Dimensions may change and are not to be used for detailed construction purposes.
Please contact the factory for certified dimensional drawings.
# For factory added thermal protection, 7.5 thru 20.0 KVA change suffix -2S to -TS.
"

The number in ( )s following the catalog number is the electrical wiring diagram number beginning on page 146.
56

NA
NA
NA
NA
WS-A-1
WS-A-1
WS-A-1
WS-A-2
WS-A-2
WS-A-2
WS-A-3
WS-A-3
WS-A-4
WS-A-4
WS-A-4
WS-A-5
WS-A-5
WS-B-3
WS-B-4
WS-B-5
WS-A-6
WS-A-6

ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION LUMBERTON, NC 800-334-5214 www.acmepowerdist.com

SECTION

DRIVE ISOLATION TRANSFORMERS

GROUP E
KVA
7.5
11.0
14.0
20.0
27.0
34.0
40.0
51.0
63.0
75.0
93.0
118.0
145.0
175.0
220.0
!

PRIMARY 230 Delta


SECONDARY 230Y/133
CATALOG NO.
DTFA-7-2S (62)
DTFA-011-2S (62)
DTFA-014-2S
DTFA-020-2S
DTFA-027-4S (59)
DTFA-034-4S
DTFA-040-4S
DTFA-051-4S
DTFA-063-4S
DTFA-075-4S
DTFA-093-4S
DTFA-0118-4S
DTFA-0145-4S
DTFA-0175-4S
DTFA-0220-4S

APPROX. DIMENSIONS
Inches (Cm.)
Height
Width
Depth
15.21 (38.6)
19.25 (48.9)
7.37 (18.7)
18.86 (48.0)
20.30 (51.6)
9.03 (22.9)
18.86 (48.0)
20.30 (51.6)
9.03 (22.9)
20.77 (52.8)
20.94 (53.2)
10.18 (25.9)
25.48 (64.8)
24.39 (62.0)
19.40 (49.3)
25.48 (64.8)
24.39 (62.0)
19.40 (49.3)
25.48 (64.8)
24.39 (62.0)
19.40 (49.3)
29.40 (74.7)
28.15 (71.5)
22.40 (56.9)
29.40 (74.7)
28.15 (71.5)
22.40 (56.9)
29.40 (74.7)
28.15 (71.5)
22.40 (56.9)
35.40 (89.9)
31.90 (81.0)
26.90 (68.3)
35.40 (89.9)
31.90 (81.0)
26.90 (68.3)
41.52 (105.5)
32.90 (83.6)
29.90 (75.9)
41.52 (105.5)
32.90 (83.6)
29.90 (75.9)
41.52 (105.5)
32.90 (83.6)
29.90 (75.9)

APPROX.
SHIP WEIGHT
Lbs. (Kg.)
180 (81.6)
265 (120.0)
265 (120.0)
435 (197.0)
302 (137.0)
330 (150.0)
370 (168.0)
375 (170.0)
495 (225.0)
525 (238.0)
685 (311.0)
710 (322.0)
980 (445.0)
1110 (504.0)
1120 (508.0)

TYPE MTG.
W Wall
F Floor
W
F
F
F
F!
F!
F!
F!
F!
F!
F
F
F
F
F

Knockouts
Inches (Cm.)
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA

WEATHER
SHIELD
DIM.
P/N
DRAWING
NA
F
NA
I
NA
I
NA
I
WS-A-1
E
WS-A-1
E
WS-A-1
E
WS-A-2
E
WS-A-2
E
WS-A-2
E
WS-A-3
E
WS-A-3
E
WS-A-4
E
WS-A-4
E
WS-A-4
E

Optional wall mounting kits part # PL 79911 refer to Page 157.


Optional wall mounting kits part # PL 79912 refer to Page 157.

The number in ( )s following the catalog number is the electrical wiring diagram number beginning on page 146.

DRIVE ISOLATION DESIGN FIGURES (Refer to pg 146)

Windings, Terminations and Construction


KVA
7.5
11-20
27-220
275-660

PRIMARY
WINDING
CU wire
AL foil
AL foil
AL foil

SECONDARY
WINDING
CU wire
AL foil
AL foil
AL foil

INSULATION
SYSTEM
180C
180C
220C
220C

TERMINATION
CU wire
CU wire
CU bus
AL bus

CONSTRUCTION

ENCLOSURE
Epoxy encapsulated
Epoxy encapsulated
Ventilated
Ventilated

Thermal
Switch Kit - PL-79900
Acme Thermal Switch Kits are designed for use with single and three phase

Figure 1

drive isolation and distribution transformers. Thermal switch kits are available
for a one or three sensor system.
Thermal sensors can be field or factory installed in the transformer winding ducts
to detect abnormal temperatures. The thermal sensors are a normally closed
contact that opens at 200C 10C and has a current capacity of 5 amps @
120V or 2.5 amps @ 240V. This contact can activate any number of different
types of alarms or mechanisms that could warn of a potential failure.
KVA
27.0-118.0
145-750

MOUNTING POSITION
Bottom of the case
Top flange of the core bracket

COIL 1

Transformers rated primary 230 volts delta, secondary 460Y/266 volts.


2. Low temperature rise units using class 220C insulation with
either 115C or 80C rise operating temperature.
3. Totally enclosed non-ventilated units.

COIL 2

COIL 3

CORE
BOTTOM OF CASE

ILLUSTRATION
Figure 1
Figure 2

For Information On The Following,


Please Contact The Factory

CORE
Wound/distributed gap
Wound/distributed gap
Wound/distributed gap
Butt stacked/Step lap

Figure 2
TERMINAL BLOCK
EPOXY LAYER

.625 (1.6 cm) H DIA.


EPOXY-RING

THERMAL SWITCH
.5H
(1.3 cm)

1.

H
COIL 1

COIL 2

COIL 3

CORE

ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION LUMBERTON, NC 800-334-5214 www.acmepowerdist.com

57

ACME TRANSFORMER DESIGN FIGURES

GENERAL

Design Figures
Sections I, II, III & IV

These drawings are for reference only.


Contact factory for certified drawings.

Design A

W
H

Design B

Design C

Design D

D
H

H
H

Design E

Design F

Design G

D
D

Design H
146

Design I

ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION LUMBERTON, NC 800-334-5214 www.acmepowerdist.com

ACME TRANSFORMER WIRING DIAGRAMS

GENERAL

Wiring Diagrams
Sections I, II, III & IV
1

PRIMARY: 240 X 480


SECONDARY: 120/240
TAPS: None

2
H4

H1
H3

H2

X2

X3

X4

Primary
Volts

Connect
Primary
Lines To

H1-H4
H1-H3
&
240
H2-H4
Secondary Volts
240
120/240

X2 to X3
X2 to X3
X1 to X3
X2 to X4

X1-X4
X1-X2-X4
X1-X4

PRIMARY: 240 X 480


SECONDARY: 120/240
2, 2 1/2 % ANFC, 2, 2 1/2 % BNFC
H1
H2 H3 H4

X2

Connect
Primary
Lines To

216

H1-H10

228

H1-H10

X1-X4
X1-X2-X4
X1-X4

PRIMARY: 240 X 480


SECONDARY: 120/240
TAPS: 2, 2 1/2 % ANFC, 2, 2 1/2 % BNFC
H2

X2

X3

Primary
Volts

Connect
Primary
Lines To

216

H1-H4

228

H1-H4

240

H1-H4

252

H1-H4

432
444

H1-H4
H1-H4

456
468
480

H1-H4
H1-H4
H1-H4

H2, 2 & H3, 7


H2, 3 & H3, 7
H2, 3 & H3, 6

492
H1-H4
504
H1-H4
Secondary Volts
240

H2, 4 & H3, 6


H2, 4 & H3, 5

H1-H10

252

H1-H10

432
444

H1-H10
H1-H10

456
468
480

H1-H10
H1-H10
H1-H10

H3 to H8
H4 to H8
H4 to H7

492
H1-H10
504
H1-H10
Secondary Volts
240

H5 to H7
H5 to H6
X2 to X3

X1-X4

120/240

X2 to X3
X1 to X3
X2 to X4

X1-X3-X4

120/240

X1-X4

120

Primary
Volts

Connect
Primary
Lines To

252

H1-H8

240

H1-H7

228

H1-H6

504

H1-H8

Connect
Secondary
Lines To

InterConnect
H1 to H5
H4 to H8
H1 to H5
H3 to H7
H1 to H5
H2 to H6
H4 to H5

492
H1-H8
480
H1-H7
468
H1-H7
456
H1-H6
Secondary Volts

H3 to H5
H3 to H5
H2 to H5
H2 to H5

240
120/240

X2 to X3
X2 to X3
X1 to X3
X2 to X4

X1

Connect
InterSecondary
Connect
Lines To
H1, H3, 8 &
H2, H4, 1
H1, H3, 7 &
H2, H4, 2
H1, H3, 6 &
H2, H4, 3
H1, H3, 5 &
H2, H4, 4
H2, 1 & H3, 8
H2, 2 & H3, 8

240

X3

X1-X4
X1-X2-X4
X1-X4

X3

X4

H7

X1

120

H4
1

InterConnect
H1 to H9
H10 to H2
H1 to H8
H10 to H3
H1 to H7
H10 to H4
H1 to H6
H10 to H5
H2 to H9
H3 to H9

120

Connect
Secondary
Lines To

X2 to X3
X2 to X3
X1 to X3
X2 to X4

H6

X4

H2 to H3

H3

H3

X2

InterConnect

H8

H4 H5
H2

H1

Connect
Secondary
Lines To

H1

X1

120

X1

Primary
Volts

X3

Connect
Primary
Lines To

H7 H8 H9

X4

X2

H1-H4
H1-H3
&
240
H2-H4
Secondary Volts
240
120/240

H10

H5 H6

H2

480

H2 to H3

120

Primary
Volts

PRIMARY: 240 X 480


SECONDARY: 120/240
TAPS: 2, 2 1/2 % ANFC, 2, 2 1/2 % BNFC

H4
H3

X4

Connect
Secondary
Lines To

InterConnect

H1

X1

480

PRIMARY: 240 X 480


SECONDARY: 120/240
TAPS: None

PRIMARY: 208
SECONDARY: 120/240
TAPS: 2, 5% BNFC
H1

H4
H2

X2

Primary
Volts
208
198
187

Connect
Primary
Lines To
H1 & H4
H1 & H3
H1 & H2

120
X1-X4

X2 to X3
X1 to X3
X2 to X4

X1-X2-X4

X3

X4

Secondary Volts
240
120/240

X2 to X3

H3

X1

InterConnect

X2 to X3
X2 to X3
X1 to X3
X2 to X4

Connect
Secondary
Lines To

X1-X4
X1-X2-X4
X1-X4

X1-X4

ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION LUMBERTON, NC 800-334-5214 www.acmepowerdist.com

147

ACME TRANSFORMER WIRING DIAGRAMS

GENERAL
PRIMARY: 277
SECONDARY: 120/240
TAPS: 2, 5% BNFC
H1
H2

X2

H4

H1

X1

X4

240
120/240

X3

X2

X2

570
H1-H3
540
H1-H2
Secondary Volts
240
120/240
120

13

X4

Connect
Primary
Primary
Volts
Lines To
240
H1-H4
H1-H3
&
120
H2-H4
Secondary Volts
240
120/240
120

X1-X4

X2

X2 to X3
X2 to X3
X1 to X3
X2 to X4

X1-X4
X1-X2-X4
X1-X4

H2

X3
X1

X2 to X3
X2 to X3
X1 to X3
X2 to X4

Connect
Secondary
Lines To

X1-X4
X1-X2-X4
X1-X4

120

555
570
585
600
615

H1-H2
H1-H2
H1-H2
H1-H2
H1-H2

1-5
2-6
2-5
3-5
2-4

635

H1-H2

3-4

Secondary Volts
240
120/240

X2 to X3
X2 to X3
X1 to X3
X2 to X4

X1-X4

X2 to X3
X1 to X3
X2 to X4

X1-X2-X4
X1-X4

PRIMARY: 240
SECONDARY: 120/240
TAPS: None
1

Primary
Volts
240

X1

InterConnect
1-6

X2 to X3

X3

Primary
Volts
540

Connect
Secondary
Lines To

InterConnect

120/240

Connect
Primary
Lines To
H1-H2

120

InterConnect
H2 to H3

X4

Connect
Secondary
Lines To

Connect
Primary
Lines To
H1-H2

H2
1

H4

X2

X1-X2-X4

H1

PRIMARY: 120 x 240


SECONDARY: 120/240
TAPS: None
H3

X2 to X3
X1 to X3
X2 to X4

X1

Secondary Volts
240

PRIMARY: 600
SECONDARY: 120/240
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC

H3

InterConnect

H1

X1-X4

Primary
Volts
600

12

X1

Connect
Primary
Lines To
H1-H4

X2 to X3

X1-X4

X3

X4

Primary
Volts
600

120

H4
H2

Connect
Secondary
Lines To

InterConnect

X3

X4

X1

Connect
Primary
Primary
Volts
Lines To
600
H1-H2
Secondary Volts
240

11

H1

X2

X3

120/240
X1-X4
X1-X2-X4

PRIMARY: 600
SECONDARY: 120/240
TAPS: 2, 5% BNFC

14

Connect
Secondary
Lines To

InterConnect

X2 to X3
X2 to X3
X1 to X3
X2 to X4

120

H2

H1

H2

H3

X4

Connect
Primary
Primary
Volts
Lines To
277
H1 & H4
263
H1 & H3
250
H1 & H2
Secondary Volts

PRIMARY: 600
SECONDARY: 120/240
TAPS: None

PRIMARY: 600
SECONDARY: 120/240
TAPS: None

Connect
Secondary
Lines To

Connect
Primary
Lines To
1-3

Secondary Volts
240
120
120/240

14

1-3
1-2 or 2-3
1-2-3

EXPORT MODEL
PRIMARY: 190-220 x 380-440
SECONDARY: 120/240
H1

X1-X4
X1-X2-X4

H10

H5 H6
H2 H3 H4

X1-X4

Connect
Secondary
Lines To

InterConnect

X2

H7 H8 H9

X3

X4

Primary
Volts

Connect
Primary
Lines To

190

H1 & H7

200

H1 & H8

208

H1 & H9

220

H1 & H10

380
400
416
440

H1 & H7
H1 & H8
H1 & H9
H1 & H10

Secondary Volts
240
120/240
120

X1

InterConnect
H1 to H6
H2 to H7
H1 to H6
H3 to H8
H1 to H6
H4 to H9
H1 to H6
H5 to H10
H2 & H6
H3 & H6
H4 & H6
H5 & H6
X2 to X3
X2 to X3
X1 to X3
X2 to X4

ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION LUMBERTON, NC 800-334-5214 www.acmepowerdist.com

Connect
Secondary
Lines To

X1-X4
X1-X2-X4
X1-X4

ACME TRANSFORMER WIRING DIAGRAMS

GENERAL

15

EXPORT MODEL
PRIMARY: 190-220 x 380-440
SECONDARY:120/240

16

INPUT LINE

H2

H3

H4

H1
1

X2

190

H1 & H4

200

H1 & H4

208

H1 & H4

220

H1 & H4

380
400
416

H1 & H4
H1 & H4
H1 & H4

440
H1 & H4
Secondary Volts
240
120/240
120

12
13

InterConnect
H1, H3, 8 &
H2, H4, 1
H1, H3, 7 &
H2, H4, 2
H1, H3, 6 &
H2, H4, 3
H1, H3, 5 &
H2, H4, 4
H2, H3, 1, 8
H2, H3, 2, 7
H2, H3, 3, 6

Input ConnectionsInsulate
Volts

Connect
1, 3, 6, 8 to A
2, 5, 7, 10 to B
1, 6 to A
4, 9 to B
2, 3 to C
7, 8 to D
1, 6 to A
5, 10 to B
2, 3 to C
7, 8 to D
1 to A
10 to B
2, 3 to C
5, 6 to D
7, 8 to E

120

208

240

H2, H3, 4, 5
480
X2 to X3
X2 to X3
X1 to X3
X2 to X4

X4

9
10

Connect
Secondary
Lines To

X1-X4
X1-X2-X4

Volts

PRIMARY: 240 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 2, 5% BNFC
H1
3 2 1

120/240

H2
3 2 1

H3

208

3 2 1

240
X0

Primary
Volts
240
228

Connect
Primary
Lines To
H1, H2, H3
H1, H2, H3

216
H1, H2, H3
Secondary Volts
208
120
1 phase

X2

X1

InterConnect
1
2

X3

Connect
Secondary
Lines To

4, 9

192
H1 & H2
187
H1 & H2
Secondary Volts

Output
Lines
To

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

Primary
Volts
252

X1

Connect
Primary
Lines To
H1, H2, H3

246
H1, H2, H3
240
H1, H2, H3
234
H1, H2, H3
228
H1, H2, H3
Secondary Volts
208
120
1 phase

Connect
Secondary
Lines To

2 to 6
1 to 6

240

X2 to X3

X1-X4

X2 to X3
X1 to X3
X2 to X4

X1-X2-X4

120

X1-X4

PRIMARY: 380 Volts Delta


SECONDARY: 220Y/127 Volts
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC

H2

F, H

F, H

H2
5 4 3 2 1

H3
5 4 3 2 1

76 5 4 3 21

X0

76 5 4 3 21

X1

X2

InterConnect
1

X3

Connect
Secondary
Lines To

X2

Primary
Volts
399

Connect
Primary
Lines To
H1, H2, H3

InterConnect
1

390
380
371
361
352

H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3

2
3
4
5
6

342
H1, H2, H3
Secondary Volts

220
X0

X1

120/240

F, G, H

H1
5 4 3 2 1

InterConnect
3 to 4
2 to 4
3 to 5
2 to 5
1 to 5

H1

PRIMARY: 240 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 2, 2 1/2 % ANFC, 2, 2 1/2 % BNFC

H2

F, G

NOTE: To pre ent e ternall shorting, all leads marked


INSULATE m st be indi id all capped ith ire
n ts or eq i alent. Ins late leads indi id all !

X3

Connect
Primary
Lines To
H1 & H2
H1 & H2
H1 & H2
H1 & H2
H1 & H2

5, 10

&
Isolate

4, 9

Connect
11 to F
12 to G
14 to H
11 to F
12 to G
14 to H
11 to F
12 to G
13 to H
11 to F
12 to G
14 to H

X2

Primary
Volts
218
213
208
203
198

4, 9

Output Connections

X1-X4

4 5 6

1 2 3

14

120

H1

F
G
H

7
8
X1

Connect
Primary
Lines To

11

4
5
6

X3

X4

Primary
Volts

1
2
3

A
B
C
D
E

PRIMARY: 208 Volts


SECONDARY: 120/240 Volts
TAPS:

POWER LINE CONDITIONER

127
1 phase

H3
76 5 4 3 21

X3

Connect
Secondary
Lines To

X1, X2,X3
X1 to X0
X2 to X0
X3 to X0

2
3
4
5
X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION LUMBERTON, NC 800-334-5214 www.acmepowerdist.com

14

ACME TRANSFORMER WIRING DIAGRAMS

GENERAL

21

PRIMARY: 480 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 2, 5% BNFC
H1

H2

3 2 1

PRIMARY: 480 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC

22

H1

H3

3 2 1

7 6 5 4 3 2 1

3 2 1

H2
7 6 5 4 3 2 1

23

PRIMARY: 120/208/240/277 Volts


SECONDARY: 120/240 Volts
H2 H3 H4 H5

H1

H3
7 6 5 4 3 2 1

X4
X0

X2

X1

Connect
Primary
Lines To

Primary
Volts

InterConnect

480
H1, H2, H3
456
H1, H2, H3
432
H1, H2, H3
Secondary Volts

Connect
Secondary
Lines To

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

120
1 phase

Connect
Primary
Lines To
H1, H2, H3
H1, H2, H3

InterConnect
1
2

456
H1, H2, H3
444
H1, H2, H3
432
H1, H2, H3
Secondary Volts

5
6
7

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

H2
5 3 1

H1

2 4 6

3 2 1

Primary
Volts
480
456

Connect
Primary
Lines To
H1, H2, H3
H1, H2, H3

3 2 1

X2

X3

X2

Primary
Volts
504
492
480

Connect
Primary
Lines To
H1, H2, H3
H1, H2, H3
H1, H2, H3

InterConnect
1 to 2
2 to 3
1 to 4

468
456
444

H1, H2, H3
H1, H2, H3
H1, H2, H3

3 to 4
1 to 6
3 to 6

432
H1, H2, H3
Secondary Volts
240

5 to 6

120

15

X4

PRIMARY: 600 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 2, 5% BNFC

3 2 1

Connect
Secondary
Lines To

X0

X1

X1, X2, X3
X1, X4 or
X2, X4

H2
3 2 1

X2

Primary
Volts

Connect
Primary
Lines To

InterConnect

600
570
540

H1, H2, H3
H1, H2, H3
H1, H2, H3

1
2
3

Secondary Volts
208
120
1 phase

H2
7 6 5 4 3 2 1

X4

Connect
Primary
Primary
Volts
Lines To
504
H1, H2, H3
492
H1, H2, H3
480
H1, H2, H3
468
H1, H2, H3
456
H1, H2, H3
444
H1, H2, H3
432
H1, H2, H3
Secondary Volts
240

X1-X4
X1-X2-X4
X1-X4

H3
7 6 5 4 3 2 1

X2

X3

InterConnect
1
2
3
4
5
6
7

Connect
Secondary
Lines To

X1, X2, X3
X1, X4 or
X2, X4

PRIMARY: 600 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC
H1
7 6 5 4 3 2 1

H2
7 6 5 4 3 2 1

H3
7 6 5 4 3 2 1

H3
X0

X3

Connect
Secondary
Lines To

120
X1, X2, X3
X1, X4 or
X2, X4

H1
X1

Connect
Secondary
Lines To

InterConnect
1
2

120

2 4 6

H3

InterConnect

H1

X1

3 2 1

X4

432
H1, H2, H3
Secondary Volts
240

H3
5 3 1

H2

X1

PRIMARY: 480 Volts Delta


SECONDARY: 240 Volts Delta/120 Volts
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC

PRIMARY: 480 Volts Delta


SECONDARY: 240 Volts Delta/120 Volts
TAPS: 2, 5% BNFC

25

X1

H1

120/240
240

26

X2

X1 to X3
X2 to X4
X2 to X3
X2 to X3

120

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

Connect
Secondary
Lines To

PRIMARY: 480 Volts Delta


SECONDARY: 240 Volts Delta/120 Volts
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC

2 4 6

1
2
3
4

X3

127
1 phase

5 3 1

H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3

7 6 5 4 3 2 1

321

X2

342
H1, H2, H3
Secondary Volts
220

504
492
480
468

Connect
Secondary
Lines To

Connect
Primary
Primary
Volts
Lines To
277
H1, H5
240
H1, H4
208
H1, H3
120
H1, H2
Secondary Volts

H3

321

X1

Primary
Volts
380
361

InterConnect

120
1 phase

H2

321

X0

Connect
Primary
Lines To

X3

208

PRIMARY: 380 Volts Delta


SECONDARY: 220Y/127 Volts
TAPS: 2, 5% BNFC
H1

X2

X1

Primary
Volts

1
2
3

208

24

X0

X3

X3

3 2 1

X3

Connect
Secondary
Lines To

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

X1

Connect
Primary
Primary
Volts
Lines To
630
H1, H2, H3
615
H1, H2, H3
600
H1, H2, H3
585
H1, H2, H3
570
H1, H2, H3
555
H1, H2, H3
540
H1, H2, H3
Secondary Volts
208

X2

InterConnect
1
2
3
4
5
6
7

120
1 phase

ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION LUMBERTON, NC 800-334-5214 www.acmepowerdist.com

X3

Connect
Secondary
Lines To

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

ACME TRANSFORMER WIRING DIAGRAMS

GENERAL

PRIMARY: 600 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC

H1
5 3 1

H2

2 4 6

5 3 1

2 4 6

31

PRIMARY: 480 Volts Delta


SECONDARY: 480Y/277 Volts
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC

H3
5 3 1

H1

H2

32

PRIMARY: 480 Volts Delta


SECONDARY: 480Y/277 Volts
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC
H1

H3
5 3 1

2 4 6

7 6 5 4 3 2 1

7 6 5 4 3 2 1

2 4 6

X2

X1

Primary
Volts

Connect
Primary
Lines To

InterConnect

630
615
600
585
570

H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3

1 to 2
2 to 3
1 to 4
3 to 4
1 to 6

555
H1, H2, H3
540
H1, H2, H3
Secondary Volts
208

3 to 6
5 to 6

Connect
Secondary
Lines To

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

120
1 phase
PRIMARY: 380 Volts Delta
SECONDARY: 208/120 Volts
TAPS: 2-2 1/2 % ANFC and BNFC

33

H2

H1
5 4 3 21

Primary
Volts
399

390
H1, H2, H3
380
H1, H2, H3
371
H1, H2, H3
361
H1, H2, H3
Secondary Volts

InterConnect
1
2
3
4
5

Primary
Volts
483
472
460
449
437
Secondary Volts
460
266
1 phase

Connect
Secondary
Lines To

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

277
1 phase

X0

InterConnect

504
492
480
468
456
444

H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3

1 to 2
2 to 3
1 to 4
3 to 4
1 to 6
3 to 6

432
H1, H2, H3
Secondary Volts
480

5 to 6

3 2 1

X1

X2

X3

2 4 6

5 3 1

X3

105
102.5

1 to 2
2 to 3

100
97.5
95

1 to 4
3 to 4
4 to 5
X1, X2, X3
X1 & X0
X2 & X0
X3 & X0

100
95

2
3
X1, X2, X3
X1 & X0
X2 & X0
X3 & X0

PRIMARY: 460 Volts Delta


SECONDARY: 230Y/133 Volts
TAPS: 1-5% ANFC and BNFC

2 4 6

Connect Leads
to Tap No.

%
105

Connect Leads
to Tap No.
1

H1

X0

PRIMARY: 460 Volts Delta


SECONDARY: 460Y/266 Volts
TAPS: 2-2 1/2 % ANFC and BNFC

5 4 3 2 1

230
133
1 phase

H2

3 2 1

X1

X2

X3

%
105

Connect Leads
to Tap No.
1

100
95

2
3
X1, X2, X3
X1 & X0
X2 & X0
X3 & X0

H3
5 4 3 2 1

X2

X3

%
105

Connect Leads
to Tap No.
1

102.5
100
97.5
95

2
3
4
5
X1, X2, X3
X1 & X0
X2 & X0
X3 & X0

266
1 phase

PRIMARY: 460 Volts Delta


SECONDARY: 230Y/133 Volts
TAPS: 2-2 1/2 % ANFC and BNFC
H1

H3

3 2 1

460
437
Secondary Volts

472
460
449
437
Secondary Volts
460

H2
5 4 3 2 1

X1

Primary
Volts
483

3 2 1

Primary
Volts
483

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

277
1 phase

H3

3 2 1

266
1 phase

Connect
Secondary
Lines To

H1

H2

3 2 1

Primary
Volts
483

2 4 6

X3

Primary
Volts

35

PRIMARY: 460 Volts Delta


SECONDARY: 460Y/266 Volts
TAPS: 1-5% ANFC and BNFC

H3

X2

6
7

H2

X1

444
H1, H2, H3
432
H1, H2, H3
Secondary Volts
480

460
437
Secondary Volts
460

H1

X0

1
2
3
4
5

5 3 1

X2

X1

X0

PRIMARY: 460 Volts Delta


SECONDARY: 460Y/266 Volts
TAPS: 2-2 1/2 % ANFC and BNFC

5 3 1

H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3

2 4 6

Connect
Primary
Lines To

X3

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

2 4 6

504
492
480
468
456

H1

Connect
Secondary
Lines To

120
1 phase

5 3 1

InterConnect

5 4 3 21

208

36

X3

Connect
Primary
Lines To

34

X2

Connect
Primary
Lines To
H1, H2, H3

X2

X1

Primary
Volts

H3

5 4 3 21

X1

X0

X0

X3

5 3 1

H3

7 6 5 4 3 2 1

X0

X0

H2

5 4 3 2 1

X0

H2

H3

5 4 3 2 1

X1

5 4 3 2 1

X2

X3

Primary
Volts

Connect Leads
to Tap No.

483
472
460
449
437

105
102.5
100
97.5
95

1
2
3
4
5

Secondary Volts
230
133
1 phase

ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION LUMBERTON, NC 800-334-5214 www.acmepowerdist.com

X1, X2, X3
X1 & X0
X2 & X0
X3 & X0
151

ACME TRANSFORMER WIRING DIAGRAMS

GENERAL

PRIMARY: 460 Volts Delta


SECONDARY: 230Y/133 Volts
TAPS: 2-2 1/2 % ANFC and BNFC

H1

PRIMARY: 575 Volts Delta


SECONDARY: 230Y/133 Volts
TAPS: 1-5% ANFC and BNFC

H2

2 4 6

X0

5 3 1

2 4 6

5 3 1

X3

Primary
Volts

Connect Leads
to Tap No.

483
472
460
449
437

105
102.5
100
97.5
95

1 to 2
2 to 3
1 to 4
3 to 4
4 to 5

Secondary Volts
230

H1
5 3 1

2 4 6

X0

2 4 6

5 3 1

Connect Leads
to Tap No.

604
589
575
561

105
102.5
100
97.5

1 to 2
2 to 3
1 to 4
3 to 4

95

4 to 5

2 4 6

5 3 1

2 4 6

152

X2

X3

5 4 3 2 1

%
105
102.5

Connect Leads
to Tap No.
1 to 2
2 to 3

575
561

100
97.5

1 to 4
3 to 4

546
Secondary Volts
460

95

4 to 5
X1, X2, X3
X1 & X0
X2 & X0
X3 & X0

Primary
Volts
218

277
1 phase

H2

H1

Connect
Primary
Lines To
X1, X2, X3

213
X1, X2, X3
208
X1, X2, X3
203
X1, X2, X3
198
X1, X2, X3
Secondary Volts
480

5 4 3 2 1

InterConnect
1

Connect Leads
to Tap No.
1

102.5
100
97.5
95

2
3
4
5
X1, X2, X3
X1 & X0
X2 & X0
X3 & X0

5 4 3 2 1

Primary
Volts
604
589
575
561
546
Secondary Volts
460

X1, X2, X3
X1 & X0
X2 & X0
X3 & X0

X2

X3

PRIMARY: 575 Volts Delta


SECONDARY: 460Y/266 Volts
TAPS: 2-2 1/2 % ANFC and BNFC

X0

Connect Leads
to Tap No.
1
2
3

X1

X3

Primary
Volts
604
589

266
1 phase

X1

%
105
100
95

X2

H1

3 2 1

H2

X1

X2

%
105
102.5
100
97.5

Connect Leads
to Tap No.
1
2
3
4

95

X3

X1, X2, X3
X1 & X0
X2 & X0
X3 & X0

H1
5 4 3 2 1

5 4 3 2 1

X0

H3

Primary
Volts
437

X1

Connect
Primary
Lines To
H1, H2, H3

426
H1, H2, H3
416
H1, H2, H3
406
H1, H2, H3
395
H1, H2, H3
Secondary Volts

2
3
4
5
H1, H2, H3
H1 to H0
H2 to H0
H3 to H0

5 4 3 2 1

PRIMARY: 416 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 2, 2 1/2 % ANFC, 2, 2 1/2 % BNFC

X3

Connect
Secondary
Lines To

H3

5 4 3 2 1

266
1 phase

5 4 3 2 1

%
105

H3

3 2 1

H3

5 4 3 2 1

133
1 phase

PRIMARY: 208 Volts Delta


SECONDARY: 480Y/277 Volts
TAPS: 2, 2 1/2 % ANFC, 2, 2 1/2 % BNFC

2 4 6

X2

X1

589
575
561
546
Secondary Volts
230

44

H2

266
1 phase

H0
X0

1
2
3

H2

X1

Primary
Volts
604

3 2 1

H3
5 3 1

105
100
95

X0

X1, X2, X3
X1 & X0
X2 & X0
X3 & X0

Primary
Volts
604
575
546

46

H2

Connect Leads
to Tap No.

Secondary Volts
460

PRIMARY: 575 Volts Delta


SECONDARY: 460Y/266 Volts
TAPS: 2-2 1/2 % ANFC and BNFC

5 3 1

X0

X1, X2, X3
X1 & X0
X2 & X0
X3 & X0

H1

X3

H1

2 4 6

45

X2

5 4 3 2 1

PRIMARY: 575 Volts Delta


SECONDARY: 460Y/266 Volts
TAPS: 1-5% ANFC and BNFC

X3

133
1 phase

X1

133
1 phase

Primary
Volts

546
Secondary Volts
230

3 2 1

H3

X2

X1

3 2 1

Primary
Volts

43

H2
5 3 1

H1

H3

3 2 1

604
575
546
Secondary Volts
230

PRIMARY: 575 Volts Delta


SECONDARY: 230Y/133 Volts
TAPS: 2-2 1/2 % ANFC and BNFC

42

X0

X1, X2, X3
X1 & X0
X2 & X0
X3 & X0

133
1 phase

H2

2 4 6

X2

X1

PRIMARY: 575 Volts Delta


SECONDARY: 230Y/133 Volts
TAPS: 2-2 1/2 % ANFC and BNFC

H3
H1

5 3 1

41

H2
5 4 3 2 1

X2

InterConnect
1

H3
5 4 3 2 1

X3

Connect
Secondary
Lines To

2
3
4
5

208
120
1 phase

ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION LUMBERTON, NC 800-334-5214 www.acmepowerdist.com

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

ACME TRANSFORMER WIRING DIAGRAMS

GENERAL

PRIMARY: 208 Volts Delta


SECONDARY: 480Y/ 277 Volts
TAPS: 2, 5% BNFC

X2

X1

PRIMARY: 600 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 2, 2 1/2 % ANFC, 2, 2 1/2 % BNFC

H1

X3

H2

5 4 3 2 1

X0

H0

H1

H3

H2

Connect
Primary
Primary
Volts
Lines To
208
X1, X2, X3
198
X1, X2, X3
187
X1, X2, X3
Secondary Volts

Connect
Secondary
Lines To

InterConnect
1
2
3

480

H1, H2, H3
H1 to H0
H2 to H0
H3 to H0

277
1 phase

51

PRIMARY: 600 Volts Delta


SECONDARY: 480Y/277 Volts
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC
H1
7 6 5 4 3 2 1

X0

H2
7 6 5 4 3 2 1

X2

X1

InterConnect

630
615
600

H1, H2, H3
H1, H2, H3
H1, H2, H3

1
2
3

585
H1, H2, H3
570
H1, H2, H3
555
H1, H2, H3
540
H1, H2, H3
Secondary Volts

4
5
6
7

480

347
1 phase

H2
7 6 5 4 3 2 1

H3
7 6 5 4 3 2 1

7 6 5 4 3 2 1

H3
7 6 5 4 3 2 1

Primary
Volts

InterConnect

630
615
600
585
570
555

H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3

1
2
3
4
5
6

540
H1, H2, H3
Secondary Volts
380

53

InterConnect

630
615
600

H1, H2, H3
H1, H2, H3
H1, H2, H3

1
2
3

585
H1, H2, H3
570
H1, H2, H3
555
H1, H2, H3
540
H1, H2, H3
Secondary Volts

4
5
6
7

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

PRIMARY: 600 Volts Delta


SECONDARY: 380Y/220 Volts
TAPS: 2, 5% BNFC

X2

X3

Connect
Secondary
Lines To

2
3
X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

Connect
Secondary
Lines To
X0

Primary
Volts
600
570
540

600

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

347
1 phase
PRIMARY: 600 Volts Delta
SECONDARY: 480Y/277 Volts
TAPS: 2, 5% BNFC
H1

X0

Primary
Volts
600
570
540

H3

3 2 1

3 2 1

3 2 1

X1

X2

X3

Connect
Primary
Lines To
H1, H2, H3
H1, H2, H3
H1, H2, H3

InterConnect
1
2
3

Connect
Secondary
Lines To

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

220
1 phase

PRIMARY: 600 Volts


SECONDARY: 480 Volts
TAPS: 2, 5% BNFC

H3

3 2 1

3 2 1

X1

X2

X3

Secondary Volts
480
277
1 phase

H2

InterConnect
1
2
3

H2

Secondary Volts
380

56

3 2 1

Connect
Primary
Lines To
H1, H2, H3
H1, H2, H3
H1, H2, H3

Connect
Secondary
Lines To

X3

Connect
Primary
Lines To

H3

X1

X2

X1

Primary
Volts

55
3 2 1

InterConnect
1

7 6 5 4 3 2 1

X3

220
1 phase

PRIMARY: 600 Volts Delta


SECONDARY: 600Y/347 Volts
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC
H2

X2

X1

Connect
Primary
Lines To

H1

3 2 1

570
H1, H2, H3
540
H1, H2, H3
Secondary Volts
600

120
1 phase

X0

3 2 1

Connect
Primary
Lines To
H1, H2, H3

Connect
Secondary
Lines To

1
2
3
4
5

H1

Connect
Secondary
Lines To

H2

InterConnect

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

H3

PRIMARY: 600 Volts Delta


SECONDARY: 600Y/347 Volts
TAPS: 2, 5% BNFC

Primary
Volts
600

Connect
Primary
Lines To

X0

X3

208

52

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

277
1 phase

X0

7 6 5 4 3 2 1

5 4 3 2 1

X2

X1

630
H1, H2, H3
615
H1, H2, H3
600
H1, H2, H3
585
H1, H2, H3
570
H1, H2, H3
Secondary Volts

X3

Connect
Primary
Lines To

H1

Primary
Volts

7 6 5 4 3 2 1

Primary
Volts

54

5 4 3 2 1

H1

H3

3 21

32 1

32 1

PRIMARY: 600 Volts Delta


SECONDARY: 380Y/220 Volts
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC

Connect
Secondary
Lines To

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

H1 H4 H7 X1

H2 H5 H8 X2

H3 H6 H9 X3

X0
H0

Connect
Connect
Primary
Alt
Primary
Inter- Secondary
Volts Rating Lines To Connect Lines To
600
480 H1, H2, H3
570
456 H4, H5, H6
540
432 H7, H8, H9
Secondary Volts
480
380
277
220
1 phase 1 phase

ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION LUMBERTON, NC 800-334-5214 www.acmepowerdist.com

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0
153

ACME TRANSFORMER WIRING DIAGRAMS

GENERAL
PRIMARY: 600 Volts
SECONDARY: 480 Volts
TAPS: 2, 5% BNFC

PRIMARY: 208 Volts


SECONDARY: 120/240 Volts
TAPS: 2, 5% BNFC

H1
H1

H2

H3

1 2 3 X1

1 2 3 X2

1 2 3 X3

X4

Connect
Connect
Primary Alt
Primary
Inter- Secondary
Volts Rating Lines To Connect Lines To
600
480 H1, H2, H3
1
570
456 H1, H2, H3
2
540
432 H1, H2, H3
3
Secondary Volts
380

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

277
220
1 phase 1 phase

H1

X0

187
H1 & H2
Secondary Volts
240
120/240

61

H3
3 2 1

X3

%
100

Connect Leads
to Tap No.
1

95
90

2
3

198
187
Secondary Volts
208

X1, X2, X3
X1 & X0
X2 & X0
X3 & X0

120
1 phase

PRIMARY: 120/208/240/277 Volts


SECONDARY: 120/240 Volts
H1

H4
H2 H3

X4

X2

Primary
Volts
218
213
208
203
198
Secondary Volts
208

Primary
Volts

Connect
Primary
Lines To

120

H1 & H8

208
240
277

H1 & H8
H1 & H8
H1 & H8

Secondary Volts
240
120/240
120
154

InterConnect
H1 to H6
H3 to H8
H2 to H7
H3 to H6
H4 to H5
X2 to X3
X2 to X3
X1 to X3
X2 to X4

X1-X4
X1-X2-X4
X1-X4

H2
5 4 3 2 1

242
236
230
224
219
Secondary Volts
230

64

62

5 4 3 2 1

Connect Leads
to Tap No.

105
102.5
100
97.5
95

1
2
3
4
5
X1, X2, X3
X1 & X0
X2 & X0
X3 & X0

PRIMARY: 230 Volts Delta


SECONDARY: 230Y/133 Volts
TAPS: 1-5% ANFC and 1-5% BNFC

X1

Connect
Secondary
Lines To

X1 & X4
X1, X3, X4
X1 & X4

X3

%
105
102.5
100

Connect Leads
to Tap No.
1
2
3

97.5
95

4
5

H3

H4

H5

X3

Primary
Volts

Connect
Primary
Lines To

190

H1& H7

208

H1 & H8

220

H1 & H9

240

H1& H10

380
416

H1 & H7
H1 & H8

440
H1 & H9
480
H1 & H10
Secondary Volts
240
120/240
120

X0

H6

H7

H8

X2

Connect
Secondary
Lines To

H4 to H6
H5 to H6
X2 to X3
X2 to X3
X1 to X3
X2 to X4

X1

X2

X3

Connect Leads
to Tap No.

105
100
95

1
2
3
X1, X2, X3
X1 & X0
X2 & X0
X3 & X0

133
1 phase

X1

InterConnect
H1 to H6
H2 to H7
H1 to H6
H3 to H8
H1 to H6
H4 to H9
H1 to H6
H5 to H10
H2 to H6
H3 to H6

3 2 1

230

H10

X1 - X4
X1- X2 - X4
X1 - X4

H1

H3

3 2 1

241
230
218
Secondary Volts

65
H9

H2

3 2 1

Primary
Volts

X1, X2, X3
X1 & X0
X2 & X0
X3 & X0

PRIMARY: 190/208/220/240 x
380/440/480 Volts
SECONDARY: 120/240 Volts
H2

X3

133
1 phase

H3

X2

120
1 phase

X4

H5
H8
H6 H7

X3

X2 to X3
X2 to X3
X1 to X3
X2 to X4

X1

5 4 3 2 1

X2

X1

Primary
Volts

PRIMARY: 208 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 2-2 1/2 % ANFC and 2-2 1/2 % BNFC

X0

H1

63

X0

Connect
Secondary
Lines To

1 to 6

120

H3

5 4 3 2 1

H1

X2

Primary
Volts
208

H2

X1

InterConnect
3 to 4
2 to 5

5 4 3 2 1

3 2 1

X1

X3

H1

H2

3 2 1

X2

Connect
Primary
Lines To
H1 & H2
H1 & H2

Primary
Volts
208
198

PRIMARY: 208 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 2-5% BNFC

H1
5 4 3 2 1

X0
H0

480

H2

4 5 6

1 2 3

PRIMARY: 230 Volts Delta


SECONDARY: 230Y/133 Volts
TAPS: 2-2 1/2 % ANFC and 2-2 1/2 % BNFC

PRIMARY: 190/200/208/220 x
380/400/416/440 Volts
SECONDARY: 110/220 Volts
H2

X4

H3

H4

H5

H6

X3

X2

Primary
Volts

Connect
Primary
Lines To

190

H1 & H7

200

H1 & H8

208

H1 & H9

220

H1 & H10

380
400
415

H1 & H7
H1 & H8
H1 & H9

440
H1 & H10
Secondary Volts
220
110/220
110

H7

H8

H9

H10

X1

InterConnect
H1 to H6
H2 to H7
H1 to H6
H3 to H8
H1 to H6
H4 to H9
H1 to H6
H5 to H10
H2 to H6
H3 to H6
H4 to H6

Connect
Secondary
Lines To

H5 to H6
X2 to X3
X2 to X3
X1 to X3
X2 to X4

ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION LUMBERTON, NC 800-334-5214 www.acmepowerdist.com

X1-X4
X1-X2-X4
X1-X4

ACME TRANSFORMER WIRING DIAGRAMS

GENERAL

PRIMARY: 416 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 2, 5% BNFC

66

H1

H2

H3

H1
7 6 5 4 3 2 1

X0

X1

Primary
Volts

Connect
Secondary
Lines To

InterConnect

437
H1, H2, H3
416
H1, H2, H3
395
H1, H2, H3
Secondary Volts
208

1
2
3
X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

120
1 phase

PRIMARY: 600 Volts Delta


SECONDARY: 240 Delta/120 Volts
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC

H1
7 6 5 4 3 2 1

H2
7 6 5 4 3 2 1

X4

X1

H3
7 6 5 4 3 2 1

X2

%
105

Connect Leads
to Tap No.
1

615
600
585
570

102.5
100
97.5
95

2
3
4
5

92.5
90

6
7

H1

H2
7 6 5 4 3 2 1

H3

Connect
Primary
Lines To

InterConnect

504
492
480
468
456

H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3

444
H1, H2, H3
432
H1, H2, H3
Secondary Volts
208

%
105
102.5

Connect Leads
to Tap No.
1
2

380
371
361

100
97.5
95

3
4
5

92.5
90

6
7

120
1 phase

H2

H3

7 6 5 4 3 2 1

7 6 5 4 3 2 1

Connect
Primary
Lines To

InterConnect

1
2
3
4
5

504
492
480
468
456

H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3

1
2
3
4
5

6
7

444

H1, H2, H3

432
H1, H2, H3
Secondary Volts

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

H2

321

240

X1
54 3 21

216
Secondary Volts
480

%
100
95

Connect Leads
to Tap No.
1
2

90

3
X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

PRIMARY: 440 Volts Delta


SECONDARY: 220Y/127 Volts
TAPS: 2, 5% ANFC & BNFC
H2

H1

X2
54 321

X3
54 321

X3

277
1 phase

Connect
Secondary
Lines To

PRIMARY: 240 Volts Delta


SECONDARY: 480Y/277 Volts
TAPS: 2, 2 1/2 % ANFC & BNFC

321

X2

X3

X1, X2, X4
X1, X4, or
X2, X4

120

H3

321

X1

X2

Primary
Volts

PRIMARY: 240 Volts Delta


SECONDARY: 480Y/277 Volts
TAPS: 2, 5% BNFC
H1

X4

X1

H0

H1

Primary
Volts
252
246

Connect
Primary
Lines To
X1, X2, X3
X1, X2, X3

240
X1, X2, X3
234
X1, X2, X3
228
X1, X2, X3
Secondary Volts
480
277
1 phase

H3

5 4 3 21

5 4 3 21

X2

X3

H3

H2

InterConnect
1
2

Connect
Secondary
Lines To

3
4
5
H1, H2, H3
H1 to H0
H2 to H0
H3 to H0

X3

Primary
Volts
399
390

352
342
Secondary Volts
208

Connect
Secondary
Lines To

120
1 phase

7 6 5 4 3 2 1

X2

X1

7 6 5 4 3 2 1

X3

Primary
Volts

5 4 3 21
X0

H1

7 6 5 4 3 2 1

X2

Primary
Volts
240
228

PRIMARY: 380 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC

7 6 5 4 3 2 1

7 6 5 4 3 2 1

X1

X0

X1, X2, X3
X1, X4, or
X2, X4

120

X0

X3

Primary
Volts
630

555
540
Secondary Volts
240

H3

X3

X2

Connect
Primary
Lines To

H2

PRIMARY: 480 Volts Delta


SECONDARY: 240 Volts Delta/120 Volts
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC

3 21

32 1

32 1

PRIMARY: 480 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 2-2 1/2 % ANFC, 4, 2 1/2 % BNFC

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

X1

X0

Primary
Volts
484

%
110

Connect Leads
to Tap No.
1

462
440
418

105
100
95

2
3
4

396
Secondary Volts
220

90

127
1 phase

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION LUMBERTON, NC 800-334-5214 www.acmepowerdist.com

155

ACME TRANSFORMER WIRING DIAGRAMS

GENERAL

PRIMARY: 190/200/210/220/
230/240 Volts Delta
SECONDARY: 400Y/231 Volts
X1
6 5 4 3 2 1

H0

X2
6 5 4 3 2 1

6 5 4 3 21

6 5 4 3 2 1

H3

Primary
Volts
240

Connect
Primary
Lines To
X1, X2, X3

InterConnect
1

230
220
210

X1, X2, X3
X1, X2, X3
X1, X2, X3

2
3
4

200
X1, X2, X3
190
X1, X2, X3
Secondary Volts

5
6

400

Connect
Secondary
Lines To

H1, H2, H3
H1 to H0
H2 to H0
H3 to H0

231
1 phase

X0

X1

Primary
Volts
240
230
220
210
200

Connect
Primary
Lines To
H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3
H1, H2, H3

H2

X2

X3

Connect
Secondary
Lines To

321

H1

Connect
Primary
Lines To
H1, H2, H3

7654 321

Primary
Volts
420
410

Connect
Primary
Lines To
H1, H2, H3
H1, H2, H3

400
H1, H2, H3
390
H1, H2, H3
380
H1, H2, H3
370
H1, H2, H3
360
H1, H2, H3
Secondary Volts
240
120

X4

X2

InterConnect
1
2

X3

Connect
Secondary
Lines To

3
4
5
6
7

Connect
Primary
Primary
Volts
Lines To
277
H1 & H2
480
H1 & H3
Secondary Volts
208

InterConnect
1

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

H2

Connect
Secondary
Lines To

2
3
X1, X2, X3
X1 to X4 or
X2 to X4

120

PRIMARY: 277/480 Volts


SECONDARY: 208/277 Volts
TAPS: NONE
H1

H6
H3

H2

H5

H4

X5

H3

X2

X3

InterConnect

Connect
Secondary
Lines To

Primary
Volts
277

X2
X3

X1 to X3

X4

X1

H2

H1
3 21

3 21

Primary
Volts

Connect
Primary
Lines To

504
H1, H2, H3
480
H1, H2, H3
456
H1, H2, H3
Secondary Volts
208
120
1 phase

X2

InterConnect

Connect
Secondary
Lines To

H3 to H4
X2 to X4
X3 to X4

H2

H1
54 3 21

X1- X5
X1- X6

H3
54 321

54 321

H3
3 21

X0
X1

X1

InterConnect
H2 to H4

PRIMARY: 480 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 2, 2 1/2 % ANFC, 2, 2 1/2 % BNFC

PRIMARY: 480 Volts Delta


SECONDARY: 208Y/120 Volts
TAPS: 1-5% ANFC & 1-5% BNFC
X1, X2, X3
X1 to X4 or
X2 to X4

Connect
Primary
Lines To
H1 - H5

480
H1 - H6
Secondary Volts
208
277

X1 to X2

277

X0

156

X3

7654 321

X1
X1

X2

240

X6

7654 321

321

PRIMARY: 277/480 Volts


SECONDARY: 208/277 Volts
TAPS: NONE

H3

X4

X1

Primary
Volts
400

H3

321

380
H1, H2, H3
360
H1, H2, H3
Secondary Volts

231
1 phase

PRIMARY: 400 Volts Delta


SECONDARY: 240 Delta/120 Volts
TAPS: 2, 2 1/2 % ANFC, 4, 2 1/2 % BNFC
H1

6 5 4 3 21

InterConnect
1
2
3
4
5

H2

H1

H3

6 5 4 3 21

190
H1, H2, H3
Secondary Volts
400

PRIMARY: 400 Volts Delta


SECONDARY: 240 Volts Delta/120 Volts
TAPS: 2, 5% BNFC

H2

H1

X3

H2

H1

PRIMARY: 190/200/210/220/
230/240 Volts Delta
SECONDARY: 400Y/231 Volts

X3

Connect
Secondary
Lines To

1
2
3
X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

X3

X2

Primary
Volts
504

Connect
Primary
Lines To
H1, H2, H3

InterConnect
1

492
480
468

H1, H2, H3
H1, H2, H3
H1, H2, H3

2
3
4

456
H1, H2, H3
Secondary Volts
208

120
1 phase

ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION LUMBERTON, NC 800-334-5214 www.acmepowerdist.com

Connect
Secondary
Lines To

X1, X2, X3
X1 to X0
X2 to X0
X3 to X0

You might also like