You are on page 1of 15

UNCONTROLLED COPY

OVERHEAD DESIGN MANUAL


Section 8 Cable Data

Approved by: R. English

ENERGEX 2009

BMS 01613

UNCONTROLLED COPY

UNCONTROLLED COPY
CABLE SELECTION
CABLE INSULATED CONDUCTORS GUIDELINES For use: in the vicinity of vegetation (present or future) where there is a likelihood of objects falling or blowing onto the mains, eg tree branches, chains where wildlife may otherwise cause outages where mains are likely to be contacted by crane jibs, boat masts or other objects where there is minimal clearance from structures. All-aluminium conductors are recommended for stringing tensions up to and including T110. These have excellent conductivity and since their weight is low, the tensions upon structures are moderate. AAC can suffer from annealing when subjected to excessive heat, eg due to overloading or cane fires.

AAC

ACSR

Aluminium conductors with galvanized steel reinforcing are recommended for stringing tensions of T110 and above. ACSR is stronger than AAC, but has inferior conductivity. ACSR conductors are typically used in rural applications where spans are very long and electrical loads are light. ACSR is more prone to corrosion in polluted environments than AAC, particularly where salt spray is present. NOTE: Due to rising fault levels consult Protection Department for application of Raisin within 12km of a substation.

HDC AND SC/GZ

Hard drawn copper and steel (galvanized) conductors are obsolete and would normally only be specified for sleeving of short sections onto existing mains.

B
CKD

DATE

30/6/03

APPD DATE RECD COPYRIGHT 2003 ENERGEX CKD This drawing must not be reproduced AUTHR in part or whole without written permission from ENERGEX

D Lloyd 28/05/02 M Irvine G Dowling S Hennessy

CABLE DATA
CABLE SELECTION GUIDELINES

APPD D LLOYD G BARTLETT ATHR M IRVINE RAISIN APPLICATION LIMITATION DEFINED

SHEET 1 OF 1
FILE ODM\6935\7026a4

WORD

7026-A4

UNCONTROLLED COPY
ELECTRICAL RATINGS OF CONDUCTORS
STANDARD NOMINAL RATINGS (in Amps) FOR ENERGEX CIRCUITS - Category A Circuits = Single Circuits, Sub-circuits & Super -circuits with Skip Poles - Category B Circuits = Super-circuits without Skip Poles S/D = Summers Day W/N = Winters Night ATR = Allowable Temperature Rise (above ambient) Ref Table Conductor ATR (C) Max Conductor Temperature (C) ACSR/GZ - IMPERIAL 3/4/.093 6/1/.118 6/1/.144 6/1/.161 6/.186 +7/.062 30/7/.102 30/7/.118 30/7/.132 30/7/.146 54/7/.132 ACSR/GZ - METRIC 3/4/2.50 6/1/3.00 6/1/3.75 6/4.75 +7/1.60 30/7/2.50 30/7/3.00 54/7/3.25 RAISIN APPLE BANANA CHERRY GRAPE LEMON ORANGE 81 126 160 200 251 296 386 102 160 205 263 337 409 620 152 243 324 432 575 728 1126 152 243 324 432 575 728 1126 130 207 271 355 465 578 863 155 247 324 425 557 695 1078 180 289 384 512 683 865 1338 180 289 384 512 683 865 1338 KBURRA FERRET MINK RACOON DOG WOLF PANTHER BEAR GOAT CAMEL Cat A Ccts S/D 5.2 20 55 76 127 158 175 202 259 296 325 350 394 S/D (Emrg) 5.4 20 55 95 162 202 226 265 350 408 461 523 646 W/N 5.3 40 55 141 246 318 362 434 602 727 840 953 1173 55 Deg C Design CatB Ccts All Year 5.3 40 55(WN)-90(SD) 141 246 318 362 434 602 727 840 953 1173 CatA Ccts S/D 5.2 40 75 122 210 267 301 357 485 578 660 740 895 S/D (Emrg) 5.4 40 75 145 250 318 360 427 582 694 794 903 1125 W/N 5.3 60 75 168 292 377 429 515 715 864 998 1132 1393 75 Deg C Design CatB Ccts All Year 5.3 60 75(WN)-110(SD) 168 292 377 429 515 715 864 998 1132 1393

Original Issue
DATE

APPD DATE RECD COPYRIGHT 2003 ENERGEX CKD This drawing must not be reproduced AUTHR in part or whole without written permission from ENERGEX

D Lloyd 28/05/02 M Irvine G Dowling S Hennessy

CABLE DATA
ELECTRICAL RATINGS

B
CKD

30/06/03

APPD D LLOYD G BARTLETT DWN M IRVINE


Added CCT, AAAC & Amended Cable Ratings

SHEET 1 OF 3
FILE ODM\6935\7027a4

WORD

7027-A4

STANDARD NOMINAL RATINGS (in Amps) FOR ENERGEX CIRCUITS - Category A Circuits = Single Circuits, Sub-circuits & Super -circuits with Skip Poles - Category B Circuits = Super-circuits without Skip Poles S/D = Summers Day W/N = Winters Night ATR = Allowable Temperature Rise (above ambient) Ref Table Conductor ATR (C) Max Conductor Temperature (C) HARD DRAWN COPPER - IMPERIAL 7/.064 7/.080 7/.104 7/.136 19/.064 19/.072 19/.083 19/.101 19/.104 HARD DRAWN COPPER - METRIC 7/2.75 AAC - IMPERIAL 7/.118 7/.134 7/.144 7/.161 7/.173 7/.186 7/.211 37/.102 37/.118 CCT (AAC) - METRIC 7/4.75CCT 120 CCT Values for an 80C Conductor Temp 379 WASP GRUB FLY 141 161 174 195 210 226 256 283 323 178 206 223 253 274 297 341 381 445 272 320 351 405 444 487 573 657 793 272 320 351 405 444 487 573 657 793 231 270 294 337 367 401 466 529 630 COPPER 162 204 308 308 264 7/16 7/14 7/12 7/.136Cu 19/16 18/15 19/14 19/.101Cu 19/12 90 116 155 207 157 179 208 256 263 111 144 195 265 198 227 267 332 343 158 210 293 412 299 347 416 535 556 158 210 293 412 299 347 416 535 556 140 183 251 348 256 295 351 445 461 Cat A Ccts S/D 5.2 20 55 S/D (Emrg) 5.4 20 55 W/N 5.3 40 55 55 Deg C Design CatB Ccts All Year 5.3 40 55(WN)-90(SD)

UNCONTROLLED COPY
75 Deg C Design CatA Ccts S/D 5.2 40 75 S/D (Emrg) 5.4 40 75 166 218 299 415 305 352 419 531 551 314 276 322 351 402 439 479 559 635 757 449 W/N 5.3 60 75 188 250 348 490 355 412 495 636 661 366 322 379 416 480 527 578 680 780 942 533 CatB Ccts All Year 5.3 60 75(WN)-110(SD) 188 250 348 490 355 412 495 636 661 366 322 379 416 480 527 578 680 780 942

Original Issue
DATE

APPD DATE RECD COPYRIGHT 2003 ENERGEX CKD This drawing must not be reproduced AUTHR in part or whole without written permission from ENERGEX

D Lloyd 28/05/02 M Irvine G Dowling S Hennessy

CABLE DATA
ELECTRICAL RATINGS

B
CKD

30/06/03

APPD D LLOYD G BARTLETT DWN M IRVINE


Added CCT, AAAC & Amended Cable Ratings

SHEET 2 OF 3
FILE ODM\6935\7027a4

WORD

7027-A4

STANDARD NOMINAL RATINGS (in Amps) FOR ENERGEX CIRCUITS - Category A Circuits = Single Circuits, Sub-circuits & Super -circuits with Skip Poles - Category B Circuits = Super-circuits without Skip Poles S/D = Summers Day W/N = Winters Night ATR = Allowable Temperature Rise (above ambient) Ref Table Conductor ATR (C) Max Conductor Temperature (C) AAC METRIC 7/3.00 7/3.75 7/4.75 19/3.25 19/3.75 19/4.75 37/3.00 AAAC 6201 METRIC 7/3.75 37/3.00 AAAC 1120 - METRIC 7/3.75 7/4.75 19/3.75 19/4.75 37/3.00 STEEL 3/12 7/12 3/.104 STEEL 7/.104 STEEL 31 50 39 62 56 94 56 94 49 80 HELIUM IODINE NEON OXYGEN NITROGEN 176 224 288 354 318 226 294 391 505 438 356 483 678 921 782 356 483 678 921 782 299 397 545 723 621 GARNET RUBY 167 302 215 416 338 742 338 742 284 591 LIBRA MARS MOON NEPTUNE PLUTO TAURUS SATURN 141 179 228 256 293 360 323 178 230 299 340 397 513 446 272 362 490 573 689 936 794 272 362 490 573 689 936 794 231 303 403 466 553 734 631 Cat A Ccts S/D 5.2 20 55 S/D (Emrg) 5.4 20 55 W/N 5.3 40 55 55 Deg C Design CatB Ccts All Year 5.3 40 55(WN)-90(SD)

UNCONTROLLED COPY
75 Deg C Design CatA Ccts S/D 5.2 40 75 S/D (Emrg) 5.4 40 75 276 362 483 558 664 883 758 339 710 357 475 654 870 746 59 95 W/N 5.3 60 75 323 430 582 680 818 1112 943 403 884 423 573 806 1094 929 66 111 CatB Ccts All Year 5.3 60 75(WN)-110(SD) 323 430 582 680 818 1112 943 403 884 423 573 806 1094 929 66 111

Notes: Category A circuits are standard lines designed for 75C operation (or 55C for certain older lines designed prior to 1980). Category B circuits are HV (mostly 33kV) lines designated for high temperature operation for increased current rating, having similar current ratings for both Summer Day and Winter Night conditions. These lines may operate up to 110C (or 90C for older lines) under summer day conditions. The planning group may provide advice as to which feeders are classified as Category B. Alternatively, information may be obtained from the Equipment Rating (ERAT) Database custodian.

Original Issue
DATE

APPD DATE RECD COPYRIGHT 2003 ENERGEX CKD This drawing must not be reproduced AUTHR in part or whole without written permission from ENERGEX

D Lloyd 28/05/02 M Irvine G Dowling S Hennessy

CABLE DATA
ELECTRICAL RATINGS

B
CKD

30/06/03

APPD D LLOYD G BARTLETT DWN M IRVINE


Added CCT, AAAC & Amended Cable Ratings

SHEET 3 OF 3
FILE ODM\6935\7027a4

WORD

7027-A4

UNCONTROLLED COPY
MECHANICAL PROPERTIES STANDARD DISTRIBUTION CABLES Code Name Bare AAC LIBRA MARS MOON PLUTO Bare ACSR APPLE BANANA RAISIN Insulated/Covered LVABC95 HVABC35 Stranding/Area Imperial Metric 2 (Inches/Gauge) (mm/mm ) 7/3.00 7/3.75 7/4.75 19/3.75 Nom. Overall Dia. (mm) 9.0 11.3 14.3 18.8 CrossSectional 2 Area (mm ) 49.48 77.31 124 209.8 Min. Breaking Load (kN) 7.91 11.9 18.8 32.3 Mass (kg/m) 0.135 0.212 0.340 0.578 Modulus of Elasticity (GPa) 59 59 59 56 Coefficient of Linear Expansion -6 (/C x 10 ) 23 23 23 23

6/1/3.00 6/1/3.75 3/4/2.50

9.0 11.3 14.3

49.48 77.31 34.36

14.9 22.8 24.4

0.171 0.268 0.193

79 79 139

19.3 19.3 13.9

HVABC120

Pilot 20 Pair

Pilot 30 Pair ADSS CCT 120mm Other OPGW 65mm2 OPGW 117mm2
2

4 x 95 AAC 3 x 35 AAC + 1 x 60 GZ (catenary) 3 x 120 AAC + 1 x 60 GZ (catenary) Muticore + 22 GZ (catenary) Muticore + 22 GZ (catenary) 7/4.75 AAAC 1350

42.0 55.0

380 59.7

63.4 74.4

1.35 1.9

56 186

23 11.5

69.8

59.7

70.5

3.19

166

11.5

32.0

21.99

27.38

0.687

193

11.5

37.0 13.5 22

21.99

27.38 50

0.846 0.15 570

193 11.5 65

11.5 13.1 23

124

18.8

2/3.7 ACS 4/3.7 AA 7/4.48 ACS 11/3.1 AA

11.1 14.5

0.286 0.473

96 92

17.2 17.7

B
CKD

DATE

07/04/10

APPD DATE RECD COPYRIGHT 2010 ENERGEX CKD This drawing must not be reproduced AUTHR in part or whole without written permission from ENERGEX

D Lloyd 28/05/02 M Irvine G Dowling S Hennessy

CABLE DATA
MECHANICAL PROPERTIES

APPD C. Lee D. Park ATHR G. Treagle HVABC and CCT properties updated sht 1

SHEET 1 OF 4
FILE ODM\6935\7029a4

WORD

7029-A4

UNCONTROLLED COPY
MECHANICAL PROPERTIES STANDARD DISTRIBUTION CABLES Code Name Stranding/Area Imperial Metric 2 (Inches/Gauge) (mm/mm ) Nom. Overall Dia. (mm) CrossSectional 2 Area (mm ) Min. Breaking Load (kN) Mass (kg/m) Modulus of Elasticity (GPa) Coefficient of Linear Expansion -6 (/C x 10 )

Service Cables 2B25 3B25 4B25 4B35 2B6

2 x 25 AAC 3 x 25 AAC 4 x 25 AAC 4 x 35 AAC 2 x 6 HDC

13.8 16 22.2 24.9 10.6

50 75 100 140 12

7.64 11.46 15.28 21.39 4.8

0.18 0.27 0.36 0.5 0.153

59 59 59 59 124

23 23 23 23 17

Bare AAC THRIP GNAT JUPITER LOCUST GRUB FLY WASP MERCURY

7/.074 7/.087 7/2.25 7/.093 7/.118 7/.134 7/.144 7/.173 7/4.50 7/.186 7/.211 37/.102 37/.118

5.64 6.62 6.75 7.08 9.0 10.21 10.97 13.18 14.17 16.08 18.13 20.98 21.0

SATURN

37/3.00

19.42 26.84 27.8 30.67 49.39 63.69 73.54 106.16 111 122.7 158.0 195.0 261.0 261.5

3.42 4.73 4.76 5.41 8.23 10.61 11.82 17.7 16.8 19.17 24.68 30.54 40.35 41.8

0.054 0.074 0.076 0.085 0.135 0.174 0.201 0.290 0.305 0.327 0.421 0.537 0.719 0.721

59 59 59 59 59 59 59 59 59 59 59 56 56 56

23 23 23 23 23 23 23 23 23 23 23 23 23 23

Bare AAAC (Alloy 1120) IODINE OXYGEN

7/4.75 19/4.75

14.25 23.75

124 336.7

34.72 94.28

0.339 0.925

59 56

23 23

B
CKD

DATE

07/04/10

APPD DATE RECD COPYRIGHT 2010 ENERGEX CKD This drawing must not be reproduced AUTHR in part or whole without written permission from ENERGEX

D Lloyd 28/05/02 M Irvine G Dowling S Hennessy

CABLE DATA
MECHANICAL PROPERTIES

APPD C. Lee D. Park ATHR G. Treagle HVABC and CCT properties updated sht 1

SHEET 2 OF 4
FILE ODM\6935\7029a4

WORD

7029-A4

UNCONTROLLED COPY
MECHANICAL PROPERTIES STANDARD DISTRIBUTION CABLES Code Name Stranding/Area Imperial Metric 2 (Inches/Gauge) (mm/mm ) Nom. Overall Dia. (mm) CrossSectional 2 Area (mm ) Min. Breaking Load (kN) Mass (kg/m) Modulus of Elasticity (GPa) Coefficient of Linear Expansion -6 (/C x 10 )

Bare ACSR FERRET MINK RACOON DOG CHERRY WOLF LEMON PANTHER BEAR GOAT CAMEL KOOKABURRA

6/1/.118 6/1/.144 6/1/.161 6/.186+7/.062 6/4.75+7/1.60 30/7/.102 30/7/3.00 30/7/.118 30/7/.132 30/7/.146 54/7/.132 3/4/.093

9.0 10.97 12.26 14.15 14.3 18.3 21.0 21.0 23.46 25.96 30.17 7.09

49.4 73.54 91.9 118.5 120.4 194.9 261.5 261.5 326.6 399.6 538.6 30.7

14.74 21.67 26.96 32.5 33.2 32.5 90.1 92.25 111.34 135.47 145.14 22.29

0.171 0.255 0.319 0.396 0.404 0.396 0.973 0.975 1.22 1.494 1.809 0.174

86 86 86 83 76 92 80 80 92 92 83 139

19.3 19.3 19.3 19.9 19.9 18.4 18.4 18.4 18.4 18.4 19.9 13.9

Bare Copper 7/.064 (7/16) 7/.080 (7/14) 7/.104 (7/12) 19/.044 19/.052 19/.064 (19/16) 19/.072 19/.083 (19/14) 19/.101 (19/12) 19/.116 37/.064 (37/16) 37/.072 37/.083 (37/14) 37/.093 37/.103 (37/12) 4.87 6.09 7.92 5.58 6.6 8.12 9.14 10.54 12.8 14.73 11.37 12.8 14.75 16.53 18.31 14.5 22.7 38.4 18.36 26.0 39.4 49.9 66.3 98.2 129.6 76.8 97.2 129.1 162.2 198.9 6.1 9.45 15.78 7.82 10.82 16.2 20.5 26.97 39.64 51.72 31.24 39.53 51.5 64.7 79.37 0.131 0.206 0.348 0.168 0.236 0.357 0.452 0.603 0.890 1.175 0.698 0.883 1.170 1.470 1.803 124 124 124 124 124 124 124 124 124 124 124 124 124 124 124 17 17 17 17 17 17 17 17 17 17 17 17 17 17 17

B
CKD

DATE

07/04/10

APPD DATE RECD COPYRIGHT 2010 ENERGEX CKD This drawing must not be reproduced AUTHR in part or whole without written permission from ENERGEX

D Lloyd 28/05/02 M Irvine G Dowling S Hennessy

CABLE DATA
MECHANICAL PROPERTIES

APPD C. Lee D. Park ATHR G. Treagle HVABC and CCT properties updated sht 1

SHEET 3 OF 4
FILE ODM\6935\7029a4

WORD

7029-A4

UNCONTROLLED COPY
MECHANICAL PROPERTIES STANDARD DISTRIBUTION CABLES Code Name Stranding/Area Imperial Metric 2 (Inches/Gauge) (mm/mm ) Nom. Overall Dia. (mm) CrossSectional 2 Area (mm ) Min. Breaking Load (kN) Mass (kg/m) Modulus of Elasticity (GPa) Coefficient of Linear Expansion -6 (/C x 10 )

Cadmium-Copper 7/.113 19/.089 8.6 11.3 45.3 76.2 26.5 45.14 0.410 0.695 124 124 17 17

Bare Steel 3/.104 (3/12) 7/.104 (7/12) 7/2.75 19/2.00 19/.080 (19/14) 19/2.75 5.1 7.92 8.25 10.0 10.16 13.75 16.77 38.70 41.58 56.59 61.61 112.9 21.85 50.83 51.77 74.0 76.79 140.56 0.130 0.304 0.326 0.483 0.499 0.888 193 193 193 193 193 193 11.52 11.52 11.52 11.52 11.52 11.52

B
CKD

DATE

07/04/10

APPD DATE RECD COPYRIGHT 2010 ENERGEX CKD This drawing must not be reproduced AUTHR in part or whole without written permission from ENERGEX

D Lloyd 28/05/02 M Irvine G Dowling S Hennessy

CABLE DATA
MECHANICAL PROPERTIES

APPD C. Lee D. Park ATHR G. Treagle HVABC and CCT properties updated sht 1

SHEET 4 OF 4
FILE ODM\6935\7029a4

WORD

7029-A4

UNCONTROLLED COPY
BROADBAND COMMUNICATION CABLE (BBCC) IDENTIFICATION

TELSTRA Where multiple circuits are present, Telstra take the bottom position. Earthing of catenary is via a driven stake near the base of a wood pole. Cantilever brackets may be present. Power supply units are clearly marked and are small shoe box sized units. Fibre optic cables are underground, ie no overhead fibre

OPTUS Where multiple circuits are present, Optus take the top position.

Earthing of the catenary is via the ENERGEX neutral.

Power supply units are clearly marked and are larger than Telstra Units. Overhead fibre optic cables are present in ENERGEXs area of supply. These are indicated by: Figure of eight configurations, Cables that continue straight through the expansion loops.

Lashing wire is generally terminated within the expansion loop.

Lashing wire is generally terminated outside the expansion loop area. Service drops may be attached either at the pole or in-line (flying fox). Usually it is only Optus that employs in-line service arrangements.

Service drops are taken from service T hooks at the pole. These hooks may be present even though no service is attached.

Note: Refer Shared Assets Installations Manual 7192-A4, for further detail.

A
APPD CKD ATHR

DATE

APPD DATE RECD COPYRIGHT 2002 ENERGEX CKD This drawing must not be reproduced AUTHR in part or whole without written permission from ENERGEX

D Lloyd 28/05/02 M Irvine G Dowling S Hennessy

CABLE DATA
BROADBAND COMMS CABLE ID. .

ORIGINAL ISSUE

SHEET 1 OF 1
FILE ODM\6935\7030a4

WORD

7030-A4

UNCONTROLLED COPY
ENGINEERING BACKGROUND
MECHANICAL PROPERTIES Nominal or projected diameter is of relevance when determining cable behaviour under wind conditions. Insulation, if present, is included. Cross-sectional area is important in determining the cable strength, weight and potential elastic stretch. Where a cable has a supporting catenary, only the cross-sectional area of the catenary is included. Current-carrying conductors and insulation, if present, are excluded. Mass determines the amount of sag within a span strung at a given tension, or conversely the amount of tension applied to the supports by a line with a given sag. Minimum breaking load is the ultimate tensile strength of the cable. In general, conductor tension should not exceed 50% of breaking load, even under wind conditions or cold conditions. Modulus of elasticity is a measure of stress or load applied to a material to cause a given strain (deformation or stretch). Coefficient of Linear Expansion is the degree to which a cable expands in length as temperature increases. This determines the relationship between sag/tension and temperature. CABLE DESIGNATIONS Cables may be known by: A code name, eg MOON, which represents 7/4.75 AAC Stranding and material, eg 7/4.75 AAC. Here the 7 is the number of strands and the 4.75 is the strand diameter in millimetres. For older imperial conductor sizes, the diameter may be expressed in terms of inches (eg 7/.104) or as a standard wire gauge (eg 7/12). The smaller the wire gauge number, the larger the diameter. ACSR conductors have a more complex designation because of the combination of materials, eg RAISIN is designated 3/4/2.50, having 3 strands of aluminium and 4 strands of galvanized steel, all with a 2.5mm diameter. 2 Nominal cross-sectional area, eg LVABC95 (95mm LVABC) 2 or CCT120 (120mm covered conductor with added insulation thickness). This is used primarily with insulated conductors and cables. Note that actual cross-sectional area may differ slightly from nominal cross-sectional area. 37/3.00 AAC (SATURN) 7/3.00 AAC (LIBRA)

3.00 mm

30/7/3.00 ACSR (LEMON) LVABC

B
CKD

DATE

30/6/03

APPD DATE RECD COPYRIGHT 2003 ENERGEX CKD This drawing must not be reproduced AUTHR in part or whole without written permission from ENERGEX

D Lloyd 28/05/02 M Irvine G Dowling S Hennessy

CABLE DATA
ENGINEERING BACKGROUND .

APPD D LLOYD G BARTLETT ATHR M IRVINE DIAGRAMS ADDED

SHEET 1 OF 1
FILE ODM/6935\7031a4

WORD

7031-A4

UNCONTROLLED COPY
GLOSSARY OF ABBREVIATIONS
AAAC AAC ABC ABS ACR ACSR AHD AMG Al AS BIG BPM CAA CAD CB CBD CBL CCF CCT CCT Chng C/I, C&I CMEN Conc CT Cu ECM EDT ESAA All Aluminium Alloy Conductor All Aluminium Conductor Aerial Bundled Cable Air Break Switch Automatic Circuit Reclosure Aluminium Conductor Steel Reinforced Australian Height Datum Australian Map Grid Aluminium Australian Standard Buried In Ground Base Plate Mounted Civil Aviation Authority Computer Aided Drafting Circuit Breaker Central Business District Calculated Breaking Load Concrete Collar Foundation Circuit Covered Conductor Thick Chainage Commercial and/or Industrial Common Multiple Earth Neutral Concrete Current Transformer Copper Electronic Cable Marker Every Day Tension Electricity Supply Association of Australia Ex Exc Fdr GI GT GZ HAT HDPE HV HVABC KBS LTS LV LVABC LVM MCBL MDCF MEN MES MWT NAEF NB Existing Excavate, also Excavation Notice Feeder Galvanised Iron Ground Transformer Galvanised Steel Highest Astronomical Tide High Density Polyethylene High Voltage (Greater than 1000V) High Voltage Aerial Bundled Cable King Bolt Spacing Load Transfer Switch Low Voltage (240 V/415 V) Low Voltage Aerial Bundled Cable Low Voltage Main Minimum Conductor Breaking Load Maximum Depth Concrete Foundation Multiple Earthed Neutral Mean Equivalent Span (ruling span) Maximum Working Tension Natural Earth Foundation Nominal Bore NTS OH P/BRANCH PCPF PE Ph PLA PMR PMT, PM Prop PSM PSTN PT PTS PVC PW QESI RBGF RC RL RMU RP XLPE NMSHVABC Non Metallic Screened HV Aerial Bundled cable Neutral Screened NS Not To Scale Overhead Parallel Branch Precast Concrete Pad Foundation Photoelectric Phase Paper Lead Alloy Pole Mounted Recloser Padmounted Transformer Proposed (also Property Pole) Permanent Survey Mark Public Switched Telephone Network Pole-mounted Transformer Pole Top Switch Polyvinyl Chloride Parallel Webbed Queensland Electricity Supply Industry Road Base Gravel Foundation Reinforced Concrete Reduced Level Ring Main Unit Registered Plan Cross Linked Polyethylene

DATE

APPD DATE RECD COPYRIGHT 2006 ENERGEX CKD This drawing must not be reproduced AUTHR in part or whole without written permission from ENERGEX

D Lloyd 28/05/02 M Irvine G Dowling S Hennessy

APPD K Nuttall CKD J Tunney ATHR J Tunney ACR, CCF, MCBL ADDED.

GLOSSARY OF TERMS

SHEET 1 OF 6
FILE ODM\6935\7054

WORD

7054-A4

UNCONTROLLED COPY
GLOSSARY OF TERMS
AERIAL BUNDLED CABLE A type of overhead cable available in both LV and HV comprising XLPE insulated compacted aluminium phase conductors laid together to form a bundle. HVABC incorporates a catenary wire for extra support and earthing and either a metallic or nonmetallic screen. LVABC is self supporting. In some cases, a HDPE oversheath is incorporated for improved abrasion resistance. A staywire erected between two poles or between a pole and a bollard. A level surface based on the mean sea level at thirty tide gauges around Australias mainland coast. A means of identifying a site within Australia by coordinate (Northing and Easting). 3, ganged, pole mounted switching device utilising air as an insulation medium. Capable of making, carrying and breaking currents to specified levels under normal conditions. Capabilities are extended through use of arcing horns or Arcmasters which respectively provide limited to full load break ability. Air breaks cannot interrupt fault currents. Refer Isolator Switch. A popular proprietary software Computer-Aided Drafting package suitable for use with Personal Computers. Registered Trademark of AutoDesk, Inc. Addition to a LV switchboard. In general it: includes a GPO with fuse and link may have additional fused supplies is connected between the LV switch (ie. isolator or switch fuse), and the most convenient LV fuse or switch fuse. See Span. The horizontal deviation from centre of powerline conductors subjected to wind forces. A pole specifically for supporting an aerial staywire. Short flexible leads providing electrical continuity across points on the system which are structurally broken. CADASTRAL MAP (Parish Map) CADASTRAL SURVEY PLAN CALCULATED BREAKING LOAD CANTILEVER STAY CAPITAL CONTRIBUTION A map or plan showing details of land tenure (e.g., property boundaries or natural features). A map or plan showing details of land tenure use for lodgement to the titles office. The minimum load (in kN) at which a conductor fails, >breaks= or exceeds its maximum tensile strength. See Sidewalk Stay. A payment which an electricity authority requires a customer to make before starting work on a capital (new, or adding to the value of the authoritys assets) project on behalf of the customer. The payment may fully or partly cover the cost of the works. An instrument for measuring slope. The distance from a datum along the centreline of a roadway. This term and offset are used to make reference to points on roadworks plans. Mechanical switching device capable of making, carrying and breaking currents under normal conditions. Capable of making, carrying for a specified time and breaking currents under specified abnormal conditions (eg. short circuits). Primary control is via external protection relays and manual overrides. Circuit breakers are normally ground mounted. A circuit breaker (fitted with automatic reclose and external protection relays) is operationally similar to a recloser. Circuit breakers may occur in ring main units. Refer Recloser. A combination of links that, close the through circuit and then isolate the apparatus in one sequenced action, or vice versa (eg. Live bypass for single-phase regulators). The LV MEN system extended to include the HV system earthing with voltages up to subtransmission level. See Multiple Earth Neutral.

AERIAL STAY AUSTRALIAN HEIGHT DATUM AUSTRALIAN MAP GRID AIR BREAK SWITCH

CLINOMETER CHAINAGE

CIRCUIT BREAKER

AutoCAD

AUXILIARY BOARD

COMBINATION LINKS

BAY BLOWOUT BOLLARD BRIDGING

COMMON MEN SYSTEM (CMEN)

A
APPD CKD ATHR

DATE

APPD DATE RECD COPYRIGHT 2006 ENERGEX CKD This drawing must not be reproduced AUTHR in part or whole without written permission from ENERGEX

D Lloyd 28/05/02 M Irvine G Dowling S Hennessy

GLOSSARY OF TERMS

ORIGINAL ISSUE

SHEET 2 OF 6
FILE ODM\6935\7054

WORD

7054-A4

UNCONTROLLED COPY
COMMON USE POLE A pole owned by either the electricity authority or some other authority (e.g., Telstra) used by both parties to support their mains. A pole assessed as unsuitable to remain in service, typically due to diminished strength from white-ant attack, below-ground rot or some other cause. A wire or other form of conducting material suitable for carrying current. See Duct. Pole attachments and their configuration, including crossarms and insulators. See Works Plan. A commercial name for a type of ribbed UPVC conduit. A service pillar fed by underground supply from the opposite side of the road. See Padmounted Transformer. The depth of excavation needed to reduce the existing ground levels to proposed ground levels at a particular point in a roadworks or other construction project. Junction box (typically set in the ground), which permits cables to be connected in various configurations, via use of links. 1, air insulated (normally), switch used to isolate lines and apparatus from the network. A disconnect link shall be easily operable as a switch. It shall not require unbolting (or otherwise complex disconnection), of electrical connections. Refer Link. That part of the electricity supply network at voltages below transmission/ subtransmission level (typically 22 kV, 11 kV and LV). See also Distribution Mains or Distribution System. A substation that transforms or converts electrical energy from a higher voltage network to a secondary distribution network (see also Padmounted Transformer). Drop Out fuse (DO) is a fuse where the fuse carrier drops DROP OUT FUSE DUCT into an open position, after the fuse has operated. Use of the term EDO shall be discontinued. A pipe or closed passage formed underground or in a structure and intended to receive one or more cables which may be drawn through them. The process of connecting components of electricity supply networks to ground to prevent dangerous voltages occurring on components which may be contacted by persons, or which may be damaged by the voltages. Usually applied to rods, metallic electrodes or a group of interconnected rods and the wire making connection to the distribution system component that is earthed. A strip of land registered on the title deed in the office of the Registrar of Titles allowing access or other rights to a public body or party other than the owner of the parcel of land on which the easement exists. See Sustained Load. A charge electricity authorities apply to customers to cover the cost of service cable and installation longer than the maximum length provided free of charge. A form electricity authorities use to obtain approval to excavate a local or public authority footpath to erect poles or install underground cables. A circuit (normally HV) emanating from a substation for distributing electric power. A notebook used to record site survey data (e.g., distances, bearings, angles, slope readings and topographical features). The depth of earth to be deposited and compacted to raise existing ground levels to proposed ground levels at a particular point in a roadworks or other construction project. A distance relative to the edge of a footpath (usually the property boundary side) used to describe the position of an underground service or pole. A space in the footpath between two alignments designated by the local or public authority in which a pole or underground service may be located. A commercial name for a type of segmented steel and concrete cover used on cast-in-situ pits in roadways and
D Lloyd 28/05/02 M Irvine G Dowling S Hennessy

CONDEMNED POLE

EARTHING (Earths)

CONDUCTOR CONDUIT CONSTRUCTION CONSTRUCTION DRAWING CORFLO CROSS-ROAD PILLAR CUBICLE TRANSFORMER CUT

EASEMENT

EVERY DAY TENSION EXCESS CABLE CHARGE EXCAVATION NOTICE

DISCONNECT BOX

FEEDER FIELD BOOK

DISCONNECT LINK

FILL

DISTRIBUTION NETWORK

FOOTPATH ALIGNMENT FOOTPATH ALLOCATION GATIC

DISTRIBUTION SUBSTATION DROP OUT (DO) or


DATE

A
APPD CKD ATHR

APPD DATE RECD COPYRIGHT 2006 ENERGEX CKD This drawing must not be reproduced AUTHR in part or whole without written permission from ENERGEX

GLOSSARY OF TERMS

ORIGINAL ISSUE

SHEET 3 OF 6
FILE ODM\6935\7054

WORD

7054-A4

You might also like