You are on page 1of 2

RA12-200

(12V200Ah)

RA12-200 is a general purpose battery with 10 years floating


design life, meet with IEC, JIS .BS and Eurobat standard. With
heavy duty grid, thickness plates, special additives, RA series
battery have long and reliable standby service life. Our RA Series
batteries keep high consistent for better performance in series
usage.

Specification
Cells Per Unit

Voltage Per Unit

12

Capacity

200Ah@10hr-rate to 1.80V per cell @25 oC

Weight

Approx. 60.0 Kg

Max. Discharge Current

2000A (5 sec)

Internal Resistance

Approx. 4 m

Operating Temperature Range

Discharge: -20 C ~60 C


Charge: 0 oC~50 oC
Storage: -20 oC~60 oC

Normal Operating Temperature Range

25 oC5 oC

Float charging Voltage

13.6 to 13.8 VDC/unit Average at 25 oC

Recommended Maximum Charging


Current Limit

60 A

Equalization and Cycle Service

14.6 to 14.8 VDC/unit Average at 25 oC

Self Discharge

RITAR Valve Regulated Lead Acid (VRLA) batteries can be stored


o
for more than 6 months at 25 C. Self-discharge ratio less than 3%
per month at 25 oC. Please charge batteries before using.

Terminal

Terminal F10

Container Material

A.B.S. (UL94-HB), Flammability resistance of UL94-V1


can be available upon request.

Dimensions
Unit: mm

Dimension: 522(L)240(W)223(H)

Terminal F10

Constant Current Discharge Characteristics: A (25 oC)


F.V/Time

5MIN

10MIN

15MIN

30MIN

1HR

2HR

3HR

4HR

5HR

8HR

10HR

20HR

9.60V

545.12

408.33

344 .69

22 5.33

130.00

77.788

53.766

4 4.064

36.067

24.844

21.006

11 .553

10.0V

529.36

388.53

337 .62

22 1.61

129.40

77.204

53.560

4 3.860

35.855

24.642

20.804

11 .343

10.2V

513.67

374.81

332 .31

21 9.65

128.20

76.619

53.148

4 3.656

35.643

24.440

20.602

11 .133

10.5V

461.25

345.86

316 .41

21 4.16

127.00

76.034

52.942

4 3.248

35.219

24.238

20.400

10 .923

10.8V

416.33

315.39

291 .66

20 4.76

124.00

74.669

51.500

4 2.228

34.582

23.834

20.198

10 .713

11.1V

355.48

281.87

261 .61

19 1.83

117.80

71.355

49.234

4 0.188

33.097

22.824

19.592

10 .083

Constant Power Discharge Characteristics: W(25 oC)


F.V/Time

5MIN

10MIN

15MIN

30MIN

1HR

2HR

3HR

4HR

5HR

8HR

10HR

20HR

9.6 V

5638.2

4348.7

379 1.6

25 68.8

1502.2

916.87

639.82

5 25.24

430.28

296.63

251 .02

13 8.52

10.0V

5527.2

4215.5

373 0.7

25 37.4

1498.6

912.01

640.04

5 24.57

429.18

295.21

249 .44

13 6.12

10.2V

5464.0

4104.2

368 8.7

25 19.4

1487.0

906.51

637.24

5 23.44

427.71

293.28

247 .22

13 3.60

10.5V

4974.3

3821.8

351 8.4

24 60.7

1473.7

899.92

634.77

5 18.54

422.62

290.85

244 .80

13 1.08

10.8V

4530.6

3522.9

325 2.0

23 58.8

1446.5

888.45

617.49

5 06.74

414.98

286.00

242 .38

12 8.56

11.1V

3979.4

3185.1

292 7.4

22 15.6

1384.6

855.45

590.81

4 82.26

397.16

273.89

235 .10

12 0.99

All mentioned values are average values.

RA12-200

12V200Ah
Storage characteristic

15

100

12

80

Supplementary charge required


(Carry out supplementary charge
before use if 100% capacity is
requires)

Capacity (%)

L ife E xp e cta ncy (years)

10

60

Supplementary charge required


before use.
This supplementary charge will help
to recover the capacity and should
be made as early as possible.

20

40

30

40

Supplementary charge may often


fail to recover the capacity.
The battery should never be left
standing till this state is reached

20
3

0
2

0
0

10

20

30

40

10 12 14 16 18 20 22 24

Supplementary charge and storage


guidelines

Storage Time (months)

50

Battery Temperature

Discharge characteristic Curve

Charge characteristic Curve for standby use


15

7.5

5.0

0.24

120

4.7

13

6.5

4.3

12

11

6.0

5.5

80
Discharge
100%0.05CA20h
50%0.05CA10h
Charge
Chcrge Voltage2.275V/C
Charge Current0.1CA
Temperature 25

4.0

3.7

60

40

13

6.5

4.3

12

6.0

4.0

11

5.5

3.7

0.20

100

Chcrge Voltage

0.16

0.12

0.08

Terminal Voltage (V)

7.0

Charge Current (CA)

14

Charge Volume (%)

Charge VoltageV

Chcrge Volume

0.05C
0.16C 0.093C

10

5.0

0.35C

3.3

0.62C
1C

3C

10

5.0

3.3

20

0.04

4.5

3.0

Charge Current

4.5

3.0
0

0.6

1.2

12

30

Charge Timeh

10

20

24

Hr

min

10 12 14 16 18 20 24 28

Discharge Time

Capacity Factors With Different Temperature


Battery Type

-20

-10

10

20

25

30

40

45

GEL
6V&12V
Battery
2V

50%

70%

83%

85%

90%

98%

100%

102%

104%

105%

60%

75%

85%

88%

92%

99%

100%

103%

105%

106%

AGM
6V&12V
Battery
2V

46%

66%

76%

83%

90%

98%

100%

103%

107%

109%

55%

70%

80%

85%

92%

99%

100%

104%

108%

110%

Discharge Current VS. Discharge Voltage


Final Discharge
Voltage V/cell

1.75V

Discharge
Current (A)

A0.2C

Maintenance & Cautions


1.60V

1.70V

Float Service:
Every month, recommend inspection every battery voltage.

0.2CA1.0C

A1.0C

Every three months, recommend equalization charge for one time.


Equalization charge method:

Charge the batteries at least once every six months,


if they are stored at 25 oC.

Discharge: 100% rate capacity discharge.

Charging Method:

Charge: Max. current 0.3CA, constant voltage 2.4-2.45V/Cell charge 24h.


Effect of temperature on float charge voltage: -3mV//Cell.

Constant Voltage

-0.2Cx2h+2.4-2.45V/cellx24h,Max. Current 0.3CA

Constant Current

-0.2Cx2h+0.1CAx12h

Fast

-0.2Cx2h+0.3CAx4.0h

Length of service life will be directly affected by the number of discharge


.
cycles, depth of discharge, ambient temperature and charging voltage.

SHENZHEN RITAR POWER CO.,LTD.

Address: Rm405,Tower C, Huahan Building,Langshan Rd16, Nanshan District, ShenZhen, 518057, China

URL:www.rit arpower.com

Tel:+86-755-33981668 Fax:86-755-8347-5180

2010 - Version 1

You might also like