You are on page 1of 18

Air Conditioning Systems

Summer air
conditioning Winter air conditioning







.

)(Summer Air Conditioning Systems



TR = 25 o C 2 R = 50 % 5
Room heat load QS
Q L
Room sensible heat factor,
RSHF
.

Refrigeration and Air Conditioning

Website: http://guider55.4t.com


)(Summer air conditioning system without by pass
) (-
) (- .

Fig. 8-1 Summer air conditioning system

Fig. 8-2 Summer air conditioning processes


Fresh air Return air Air
handling unit

Refrigeration and Air Conditioning

Website: http://guider55.4t.com

S
.90 % 5 ~ 10 oC
R o
m
S
a = 100 % mS S = 90 %
S Apparatus dew Point, Adp
.
Room heat load SR,
& a (hR hS )
Qt = m

(8-1)

Cooling coil capacity and efficiency mS and a,


& a (hm hS )
Qcoil = m
coil =

(8-2)

hm hS
hm ha

(8-3)

Condensate water through dehumidification process mS,


&w = m
& a ( m S )
m

(8-4)

Example 8-1
An air conditioning room is maintained at 25 oC db and RH 50 %. The ambient
conditions are 38 oC db and 27 oC wb. The room has sensible heat gain of 40 kW
and latent heat gain of 10 kW. The re-circulated air contains 30 % by weight fresh
air. The re-circulated air is supplied to the room at 14 oC. Calculate, the sensible
heat factor, the total amount of conditioned air, the cooling coil dew point, the
cooling coil capacity in TR, the cooling coil efficiency, and the rate of water
removed from the air.
Data: t R = 25 o C , RH R = 50 %, t o = 38 o C db, t o = 27
QS = 40 kW, QL = 10 kW , t S = 14

& o = 0.3 m
&a
C wb , m

Required: RSHF , m& a , Adp, RC, coil , m& w


Website: http://guider55.4t.com

Refrigeration and Air Conditioning

Solution
As shown in Fig. 8-2 of Psychrometric chart and the air properties are,
hR = 50.34 kJ / kg , ho = 84.55 kJ / kg
& o = 0.3 m
&a, m
& R = 0.7 m
&a
m
Qt = QS + Q L = 40 + 10 = 50 kW
RSHF =

QS
40
=
= 0.8
QS + Q L 40 + 10

Heat balance of mixing point m,


& o ho + m
& R hR = m
& a hm
m
& a 84.55 + 0.7 m
& a 50.34 = m
& a hm
0.3 m
hm = 60.6 kJ / kg , m = 12.5 g / kg da

Processes mSR, cooling and dehumidification from m to S at 90 % RH, from


S to R, room total heat released parallel to RSHF.
hS = 35.5 kJ / kg , S = 8.7 g / kg da , ha = 27 kJ / kg , t a = Adp = 9

Re-circulated air,
& a (hR hS ),
Qt = m

& a (50.34 35.5),


50 = m

& a = 3.369 kg / s
m

Cooling coil capacity,


RC =

& a (hm hS ) 3.369 (60.6 35.5)


m
=
= 24.162 TR
3.5
3.5

Cooling coil efficiency,


coil =

hm hS 60.6 35.5
=
= 0.747 = 74.7 %
60.6 27
hm h a

Condensate water,
&w = m
& a ( m S ),
m

& w = 3.369 (12.5 8.7) 10 3 60 = 0.768 kg / min


m

Example 8-2
In a summer air conditioning system shown the fresh air is mixed with return air
by equal mass before entering the cooling coil. After pre-cooled the air
adiabatically humidified in air washer to 90 % RH. The outside air conditions
are 35 C db and 17 C wb. The inside air conditions are 27 C db and 21 C wb.
Internal sensible heat gain is 35 kW and latent heat gain is 15 kW. Estimate; the
Website: http://guider55.4t.com

Refrigeration and Air Conditioning

temperature to which the air is pre-cooled, the temperature to which the sprayed
water must be held, the amount of supplied air, the capacity of the pre-cooler, and
the make up water.
Data: t R = 27

C db, t R = 21 o C wb, , t o = 35
QS = 35 kW, Q L = 15 kW, RH S = 90 %
o

C db, t o = 17

C wb

Required: t1 , t S , m& a , RC , m& w


Solution

From Psychrometric chart and the air properties are,


hR = 60.68 kJ / kg , ho = 47.3 kJ / kg
&o = m
& R = 0.5 m
&a
m
Qt = QS + Q L = 35 + 15 = 50 kW
RSHF =

QS
35
=
= 0.7
QS + Q L 35 + 15

Heat balance of mixing point m,


Website: http://guider55.4t.com

Refrigeration and Air Conditioning

& o ho + m
& R hR = m
& a hm
m
& a 47.3 + 0.5 m
& a 60.68 = m
& a hm
0.5 m
hm = 54 kJ / kg , m = 9 g / kg da

Processes m1SR, sensible cooling from m to 1, but S at cross of RSHF with


90 % RH, from S to 1 adiabatic line at cross with sensible cooling m1.
t1 = 23.6

C dbt, 1 = m

hS = 47 kJ / kg , S = 11.5 g / kg da , t S = 17.9

C db, t a = Adp = 16.6

Re-circulated air,
& a (hR hS ),
Qt = m

& a (60.68 47),


50 = m

& a = 3.655 kg / s
m

Cooling capacity of pr-cooler,


RC =

& a (hm h1 ) 3.655 (54 47)


m
=
= 7.31 TR
3.5
3.5

Air washer efficiency,


washer =

t1 t S 23.6 17.9
=
= 0.8143 = 1.43 %
t1 t a 23.6 16.6

Make up water in air washer,


&w = m
& a ( S 1 ),
m

& w = 3.655 (11.5 9) 10 3 60 = 0.5483 kg / min


m


(Summer air conditioning system with by pass)

Fig. 8-3 Summer air conditioning system with by pass


Website: http://guider55.4t.com

Refrigeration and Air Conditioning

( -)


( -) S
.

Fig. 8-4 Summer air conditioning processes with by pass

Example 8-3
A summer air conditioning systems consists of water chiller and air re-heater as
shown below. The return air is mixed partially before the water chiller and by
passed after it with equal masses. The inside conditions are 25C db and 50 % RH
and outside conditions are 38 C db and 26C wb. Fresh air for ventilation is 0.5
m3/s. The internal sensible heat gain is 21 kW and internal latent heat gain is 7
kW. The air leaving water chiller saturated at 10 oC and the temperature difference
between inside and supply air is 8 C db. Determine the refrigeration capacity of
the water chiller and the heating capacity of the air reheated.
Data: t R = 25 o C , RH R = 50 %, t o = 38 o C db, t o = 26 o C wb , m& o = 0.5 m3 / s
QS = 21 kW, Q L = 7 kW , t S = 25 8 = 17

C , RH 1 = 100 %, t1 = 10

Required: RSHF , m& a , RC, Power reh


Solution
Website: http://guider55.4t.com

Refrigeration and Air Conditioning

As shown in Fig. 8-4 of Psychrometric chart and the air properties are,
hR = 50.34 kJ / kg , ho = 80.05 kJ / kg , v o = 0.9047 m3 /kg, h1 = 29.5 kJ / kg
V&
0.5
& R1 = m
& R2 , m
&o = o =
m
= 0.5527 kg / s
v o 0.9047
Qt = QS + Q L = 21 + 7 = 28 kW
RSHF =

QS 21
=
= 0.75
Qt 28

State S is at cross of RSHF with ts = 17 oC


hS = 37.5 kJ / kg
& a (hR hS ),
Qt = m

& a (50.34 37.5),


28 = m

& a = 2.181 kg / s
m

& R1 + m
& R2 = m
&a m
&o
m
& R1 = m
& R2 = (2.181 0.5527) / 2 = 0.8142 kg / s
m

Heat balance of mixing point m,


& o ho + m
& R1 hR = (m
&o +m
& R1 )hm
m
0.5527 80.05 + 0.8142 50.34 = (0.5527 + 0.8142)hm , hm = 62.35 kJ / kg

Heat balance of mixing point 1 with R and m& R2 ,


&o + m
& R1 )h1 + m
& R 2 hR = m
& a h2
(m
(0.5527 + 0.8142) 29.5 + 0.8142 50.34 = 2.181 h2 , h2 = 37.28 kJ / kg

Cooling capacity water chiller,


RC =

& a (hm h1 ) 2.181 (62.35 29.5)


m
=
= 20.47 TR
3.5
3.5

Capacity of re-heater,
& a (hS h2 ) = 2.181 (37.5 37.28) = 0.479 kW
Power = m

Example 8-4
In an air conditioning unit, air is supplied at a rate of 0.65 m3/s with 25C db and
60 % RH. The unit consists of a cooling coil where air is cooled and dehumidified
Website: http://guider55.4t.com

Refrigeration and Air Conditioning

to 5C db and 4 C wb. Then, the air passes through an electric heater and leaves it
at 20C db. After that, air passes through an air washer, where it is humidified to
90 % RH. Part of the air is by passed across the air washer to have final air relative
humidity of 60 %. Calculate, the capacity of cooling coil, the heater power, the by
pass factor for air washer, and the bypassed low rate.
Data: t o = 25 o C , RH o = 60 %, t1 = 5 o C db, t1 = 4 o C wb , m& o = 0.65 m3 / s
t 2 = 25

C , RH 3 = 90 %, RH S = 60 %

Required: RC , Power , BFwasher , m& b


Solution

From Psychrometric chart and the air properties are,


ho = 55 kJ / kg , h1 = 16.6 kJ / kg , h2 = h3 = hS = 33 kJ / kg
2 = 4.8 g / kg da , 3 = 8.2 g / kg da , v o = 0.8613 m3 / kg
S = 6.8 g / kg da , a = 8.5 g / kg da
V&
0.65
&o = o =
m
= 0.755 kg / s
v o 0.8613
& o (ho h1 ), RC = 0.755 (55 16.6) = 28.992 kW = 8.283 TR
RC = m
& o (h2 h1 ),
Power = m

Power = 0.755 (55 33) = 16.61 kW

Website: http://guider55.4t.com

Refrigeration and Air Conditioning

Air washer efficiency and bypass factor,


3 2 8.2 4.8
= 0.9189 = 91.89 %
=
a 2 8.5 4.8

= washer

BFwashwe = 1 washer = 1 0.9189 = 0.081 = 8.1 %

Mass balance of air after bypassed and air washer,


& o m
& b ) 3 + m
& b 2 = m
& o S
(m
& b ) 8.2 + m
& b 4.8 = 0.755 6.8
(0.755 m

& o m
& b ) 3 + m
& b 2 = m
& o S ,
(m
& b = 0.311 kg / s
m

)(Winter Air Conditioning Systems







Pre-
heater Air washer
Re-heater ).(-

Fig. 8-5 Winter air conditioning system


) (-
S TS = TR + 5 ~ 10 o C
S S > R R
Refrigeration and Air Conditioning

Website: http://guider55.4t.com

SR R RSHF
S < R R S\
\

S\R R RSHF
. Humidification

Fig. 8-6 Winter air conditioning processes

Example 8-5
Air flow of 11 m3/min is supplied to air conditioning room at 24 oC db and 50 %
RH. The outside air conditions at 10 oC db and 90 % RH. The return air is mixed
with the fresh air before entering the primary heater in ratio of 2 to 1 by weight.
The air is first preheated until its wet bulb temperature is equal to the room wet
bulb temperature. Then, the air is adiabatic saturated in air washer to 90 % RH.
Finally the air is reheated to 35 oC before being supplied to the room. Determine
the heat added in both two heaters in kW, the mass of water evaporated in the air
washer, and the air washer efficiency.
Data: t R = 24

C db, RH R = 50 %, t o = 10

&R /m
& o = 2, t S = 35
m

& a = 11 m3 / min
C db, RH o = 90 %, m

C db, RH 2 = 90 %

Required: Power1 , Power 2 , washer


Solution
From Psychrometric chart as Fig. 8-6 and the air properties are,
Website: http://guider55.4t.com

Refrigeration and Air Conditioning

hR = 47.83 kJ / kg , v R = 0.8546 m3 / kg , ho = 27.35 kJ / kg , v o = 0.8111 m3 / kg


V&
11
&a = a =
m
= 0.215 kg / s
vR 60 0.8546

Heat balance of mixed point m,


& o ho + m
& R hR = m
& ahm, m
&R /m
& o = 2, m
&a = m
&R +m
& o = 3m
&o
m
& o 27.35 + 2m
& o 47.83 = (m
& o + 2m
& o )h m
m
hm = 41 kg / s, h1 = hR = h2 = 47.83 kg / s

Process m12S, sensible heating from m to 1at h1 = hR , adiabatic air washer


from 1 to 2 at 90 % RH, sensible heating from 2 to S at 35 oC db.
hS = 65 .3 kJ / kg , 1 = 8.5 g / kg da , 2 = 11 .8 g / kg da , a = 12 .3 g / kg da
& a (h1 hm ) = 0.215 (47.83 41) = 1.468 kW
Power1 = m
& a (hS h2 ) = 0.215 (65.3 47.83) = 3.756 kW
Power 2 = m
washer =

2 1 11.8 8.5
= 0.86.84 = 86.84 %
=
a 1 12.3 8.5

Example 8-6
A winter air conditioning unit, consists of preheating coil, adiabatic air washer and
reheating coil is used to maintain the condition inside a room at 25 oC db and 50 %
RH. The re-circulated air is mixed with fresh air at equal parts by weight before
the preheating coil. An amount of 56.6 m3/min fresh air is supplied to the unit at 5
o

C db and 90 % RH. The air leaves the humidifier at 85 % RH and leaves the

reheating coil at 33 oC db and 35 % RH. Representation the processes on the


Psychrometeric chart and calculate the heating capacity of each heating coil, the
rate of water to be consumed in the humidifier, and the humidifying efficiency.
Data: t R = 25 o C db, RH R = 50 %, t o = 5 o C db, RH o = 90 %, m& R = m& o
V&o = 56.6 m3 /min, RH 2 = 85 % t S = 33

C db, RH S = 35 %

Required: Power1 , Power 2 , m& w , washer


Solution
From Psychrometric chart as Fig. 8-5 and the air properties are,
hR = 50.34 kJ / kg , ho = 17.23 kJ / kg , v o = 0.7943 m3 / kg
V&
56.6
&o = o =
m
= 1.188 kg / s
vo 60 0.7943

Website: http://guider55.4t.com

Refrigeration and Air Conditioning

Heat balance of mixing process state R with state o by equal mass,


& o ho + m
& R hR = m
& a hm, m
&R = m
&o, m
&a = m
&R +m
& o = 2m
& o = 2 1.188 = 2.376 kg / s
m
&R = m
&o, m
&a = m
&R +m
& o = 2m
& o = 2 1.188 = 2.376 kg / s
m
& o 50.34 + m
& o 17.23 = 2m
& ohm
m
hm = 33.79 kg / s

State S at, t S = 33 o C db, RH S = 35 % , hS = 61.42 kJ / kg , S = 11.01 g / kg da


Process S2, sensible heating from 2 to S, state 2 at RH = 85 %
h2 = 46.1 kJ / kg , 2 = S = 11.01 g / kg da

Process 12, adiabatic air washer from 1 to 2 at 85 % RH,


h1 = 46.1 kJ / kg , 1 = m = 7.4 g / kg da , a = 11.5 g / kg da
& a (h1 hm ) = 2.376 (46.1 33.79) = 29.249 kW
Power1 = m
& a (hS h2 ) = 2.376 (61.42 46.1) = 36.4 kW
Power 2 = m
&w = m
& a ( 2 1 ) = 2.376 (11.01 7.4) 10 3 60 = 0.515 kg / s
m
washer =

2 1 11.01 7.4
=
= 0.8805 = 88.05 %
a 1 11.50 7.4

Example 8-7
A winter air conditioning unit consists of a preheating coil a spray system and a
reheating coil. The unit is designed to handle 3200 kg of air per hour and 100 % of
which is fresh air. The heat loss from the space is 9 kW. The outside air enters the
unit at 7 C db and 4 C wb. The air leaves the spray system at 90 % RH. The unit
delivers the air at 33 C db and 30 % RH. Note that SHF=1, determine the
condition maintained inside the space, and the heating capacities of preheating and
Website: http://guider55.4t.com

Refrigeration and Air Conditioning

reheating coil.
Data: t o = 7

C db, t o = 4

& a = 3200 kg / hr = 0.889 kg / s


C wb, RH 2 = 90 %, m

Qt = 9 kW, RSHF = 1, t S = 33

C db, RH S = 30 %

Required: Room conditions , Power1 , Power 2


Solution

From Psychrometric chart, and the air properties are,


hS = 57.5 kJ / kg , h2 = 38.5 kJ / kg , ho = 16.6 kJ / kg

Process 2S, sensible heating and state S at 33 oC db and 30 % RH. The state 2 is
at the horizontal line at RH = 90 %.
h2 = 38.5 kJ / kg , 2 = 9.6 g / kg da

Process 12, adiabatic air washer and state 1 at cross with sensible heating line
from state o which at 7 oC db and 4 oC wb.
h1 = 38.5 kJ / kg , 1 = 3.8 g / kg da

Room heat load from state S to state R horizontal line, SHF = 1


& a (hS hR ), 9 = 0.889 (57.5 hR ), hR = 47.4 kJ / kg
Qt = m
t1 = 23

C db, RH R = 55 %

& a (h1 ho ) = 0.889 (38.5 16.6) = 19.469 kW


Power1 = m
& a (hS h2 ) = 0.889 (57.5 38.5) = 16.891 kW
Power 2 = m

Example 8-8
In air conditioning system shown below, all dehumidification occurs in the
adsorbent dehumidifier (Adiabatic dehumidification). Sketch the cycle on the
Psychrometric chart and find the condition of air leaving the adsorbent
Website: http://guider55.4t.com

Refrigeration and Air Conditioning

dehumidifier, and the amount of water required for cooling the air in each cooler.
Data: t1 = 35 o C db, t1 = 24 o C wb, V&1 = 70.8 m3 / min, t 2 = t 5 = 27

t 8 = 27 C db, t 8 = 17.5 C wb, V&8 = 127 m / min


V&a = 85 m3 / min, V&b = 42 m3 / min
o

Qt = 9 kW, RSHF = 1, t S = 33

C db, RH S = 30 %

Required: Conditions of state 4, m& w1 , m& w2


Solution

From Psychrometric chart, and the air properties are,


h1 = 71.75 kJ / kg , v1 = 0.8931 m3 / kg , 1 = 14.24 g / kg da
Website: http://guider55.4t.com

Refrigeration and Air Conditioning

h8 = 49.06 kJ / kg , v8 = 0.8622 m3 / kg , 8 = 8.58 g / kg da


V&
70.8
& 1 = a1 =
m
= 1.321 kg / s
v1
60 0.8931
V&
85
& b1 = b1 =
m
= 1.643 kg / s
v8
60 0.8622
V&
42
& b2 = b2 =
m
= 0.812 kg / s
v8
60 0.8622

Process 12, sensible cooling and state 2 at 27 oC db, h2 = 63.49 kJ / kg


Heat balance at mixing point b1, to locate state 3 at 27 oC.
& 1h1 + m
& b1 h8 = (m
&1 + m
& b1 )h3
m
1.321 71.75 + 1.643 49.06 = (1.321 + 1.643) h3
h3 = 59.17 kJ / kg , 3 = 12.5 g / kg da

Supplied air and room total heat load,


& a = (m
&1 + m
& b1 + m
& b 2 ) = (1.321 + 1.643 + 0.812) = 3.776 kg / s
m
& a (h8 h7 ), 63 = 3.776 (49.06 h7 ), h7 = 32.38 kJ / kg
Qt = m

Room latent heat load, sensible heat, and room sensible heat factor,
& w h fg = (0.68 / 60) 2437.8 = 27.62 kJ / kg
QL = m
QS = Qt Q L = 63 27.62 = 35.37 kJ / kg
RSHF = QS / Qt = 35.37 63 = 0.56

State 7 at cross of RSHF with h7,


Process 67 sensible cooling and state 6 at 27 oC db, h6 = 41.5 kJ / kg
Heat balance at mixing point b2, to locate state 5 at at 27 oC db.
& 5 h5 + m
& b 2 h8 = (m
&5 + m
& b 2 )h6
m
(1.321 + 1.643) h5 + 0.812 49.06 = (1.321 + 1.643 + 0.812) 41.5
h5 = 39.43 kJ / kg

Process 45 sensible cooling and state 4 at the intersect of adiabatic line from
state 3 and horizontal line from state 5.
h4 = 59.17 kJ / kg , t 4 = 45.5

C db, 4 = 4.8 g / kg da

Heat balance of cooler 1,


& w1C Pw t w = m
& 1 (h1 h2 )
m
& w1 4.18 (17.5 13) = 1.321 (71.75 63.49), m
& w1 = 0.5801 kg/s
m

Heat balance of cooler 2,


& w2 C Pw t w = m
& 6 (h6 h7 )
m
& w2 4.18 (17.5 13) = 3.776 (41.5 32.38), m
& w2 = 1.8308 kg/s
m

Problems
1. A certain building is to be air conditioned in summer. The following data are
given. The outside air is 38 C db, 25 C wb, and inside air 24 C db, 50 % RH.
Website: http://guider55.4t.com

Refrigeration and Air Conditioning

Estimated heat from the building is 17.6 kW, electric lighting and machines are
40 kW. The total number of persons is 100, and sensible heat per person is 80
W and latent heat per person is 103 W. The ratio of return air and fresh air is
2:1 by mass. The air leaves the cooling coil at 90 % R.H. Determine the
sensible heat factor, the total amount of conditioned air, the cooling coil dew
point, the cooling coil capacity in TR, the cooling coil efficiency, and the rate
of water removed from the air.
2. In a summer air conditioning system, employing evaporative cooling equal
masses of fresh air and return air, after mixing air first pre-cooled then
adiabatically humidified to 100 % R.H by passing through a spray water
system. The outside air conditions are 35 C db and 17 C wb. The inside air
conditions are 27 C db, and 21 C wb. Internal sensible heat gain is 30 kW and
latent heat gain is 15 kW. Find the temperature to which the air is pre-cooled,
the temperature to which the sprayed water must be held, the amount of
supplied air, the capacity of the pre-cooler, and the make up water.
3. The following information was obtained in designing the summer air
conditioning plant. The outside design conditions are 38 C db, 28 C wb and
the inside design conditions are 21 C db, 70 % RH. Internal sensible heat gain
is 175 kW and internal latent heat gain is 65 kW. Outside fresh air to total air is
50 % by mass. Temperature difference between supply air and return air is 8 C
db. Determine the conditions of the supply air, the quantity of supply air, the
cooling capacity of the plant, the cooling coil efficiency and by pass factor, and
the rate of water removed from the air.
4. A summer air conditioning systems consists of water chiller and by pass. Uses
return air before the water chiller and by pass air after it. The given data are,
inside conditions 26C db & 50 % R.H and outside conditions 35C db & 26C
wb. Fresh air for ventilation is 2 m3/s. The internal sensible heat gain is 40 kW
and internal latent heat gain is 17.5 kW. The relative humidity of air leaving
water chiller is 90 % and the temperature difference between inside and supply
Website: http://guider55.4t.com

Refrigeration and Air Conditioning

air is 9 C db. Equal masses for return and by pass air. Determine the
refrigerating capacity of the water chiller and the condensate water by lit/min.
5. A winter air conditioning unit, consists of preheating coil, adiabatic air washer
and reheating coil is used to maintain the condition inside a room at 25 oC db
and 50 % RH. The re-circulated air is mixed with fresh air at equal parts by
weight before the preheating coil. An amount of 56.6 m3/min fresh air is
supplied to the unit at 5 oC db and 90 % RH. The air leaves the humidifier at 85
% RH and leaves the reheating coil at 30 oC db and 45 % RH. Draw a sketch
for this unit and its representation on the Psychrometeric chart. Then calculate
the heating capacity of each heating coil, the rate of water to be consumed in
the humidifier, and the humidifying efficiency.
6. A winter air conditioning unit consists of air pre-heater, air washer and air
reheater. The re-circulated air is admitted partially as return air before the air
preheated and the rest is by passed after the air washer. Inside condition is 25
C db and 50 % RH. Outside condition is 5 C db and 70 % RH. Fresh air
enters the systems at the rate of 28 m3/min. Temperature of air leaving preheater equal 21 C db and the relative humidity of air leaving air washer is 95
%. The temperature difference of supply air is high than room air by 7 C db.
Equal masses of fresh air, return air and by-pass air are used, draw the system
with its all details and represent it in the Psychrometric chart, then calculate the
capacity of both pre-heater and re-heater, internal heating load, and make up
water.

Website: http://guider55.4t.com

Refrigeration and Air Conditioning

You might also like