Bryan Steam Deaerator Sizing Program

highlighted cells are for job conditions and to be entered by user Capacity Steam pressure to the PRV Saturated steam temperature at bop Deaerator operating pressure Saturated temp. at deaerator pressure Enthalpy of Steam Percentage of incoming Water Temperature of incoming Water Pressure of incoming Water Percentage of Condensate Return Temperature of Condensate Return 70000 5 228 5 228 960.1 100% 40 40 0% 10 PPH PSI Degrees PSI Degrees BTU's/ LB Degrees PSI Degrees revision date: 9/17/02

Water line information


Make-up water GPM required Incoming line Size (min.size) CV factor for water valve is 117.02 GPM 3.5'' based on 4ft per second 23.76 12606.41

Steam line Information


Steam required in PPH

Income line size (min. size) Connection to Deaerator (min. size)

10'' 10''

based on 7000 ft per minute