You are on page 1of 17

Ministry of Defence

Defence Standard

61-5(PART 4) /Issue 2

14 AUGUST 1992

ELECTRICAL POWER SUPPLY SYSTEMS BELOW 650 VOLTS PART 4:POWER SUPPLIES IN HM SHIPS

This Defence Standard supersedes Def Stan 61-5 (Part 4)/Issue 1 dated 17 September 1973

DEF STAN 61-5 (PART 4)/2 AMENDMENTS ISSUED SINCE PUBLICATION

AMD NO

DATE OF ISSUE

TEXT AFFECTED

SIGNATURE & DATE

Revision Note This Standard supersedes Defence Standard 61-5 (Part 4)/Issue 1. Historical Record Def Stan 61-5 (Part 4)/Issue 1 dated 17 September 1973 Arrangement of Defence Standard 61-5 Part 1 - Terminology and Definitions Part 2 - Ground Generating Set Characteristics Section 1 - Electrical Performance Characteristics and Methods of Measurement Section 2 - General Design Requirements Section 3 - Not Allocated Section 4 - Environmental Requirements Section 5 - Electromagnetic Compatibility Requirements Section 6 - Audio Noise, Methods of Measurement Part 3 - Distribution and Protection Requirements Section 1 - Earthing Part 4 - Power Supplies in HM Ships Part 5 - Not Allocated Part 6 - 28 Volt d.c. Electrical Systems in Military Vehicles

DEF STAN 61-5 (PART 4)/2 ELECTRICAL POWER SUPPLY SYSTEMS BELOW 650 VOLTS PART 4: POWER SUPPLIES IN HM SHIPS PREFACE

This Defence Standard supersedes Def Stan 61-5 (Part 4)/Issue 1 dated 17 September 1973

i This Part of the Def Stan 61-5 applies to Electrical Power Supply Systems in HM Surface Ships and Submarines, for Ministry of Defence use. ii This Part of the Standard implements STANAG 1008, Characteristics of Shipboard Electrical Power Systems in Warships of the North Atlantic Treaty Navies (Edition No 7). The substance of this agreement, together with any UK reservations is included in annex A. iii This Part of the Standard has been agreed by the authorities concerned with its use and shall be incorporated whenever relevant in all future designs, contracts, orders etc and whenever practicable by amendment to those already in existence. If any difficulty arises which prevents application of the Defence Standard, the Directorate of Standardization shall be informed so that a remedy may be sought. iv Any enquiries regarding this Part of the Standard in relation to an invitation to tender or a contract in which it is invoked are to be addressed to the responsible technical or supervising authority named in the invitation to tender or contract. v This Part of the Standard has been devised for the use of the Crown and its contractors in the execution of contracts for the Crown. The Crown hereby excludes all liability (other than liability for death or personal injury) whatsoever and howsoever arising (including, but without limitation, negligence on the part of the Crown its servants or agents) for any loss or damage however caused where the Standard is used for any other purpose.

DEF STAN 61-5 (PART 4)/2 CONTENTS Preface Scope WARNING Related Documents Definitions User Equipment Requirements Characteristics of Electrical Power Supplies in HM Surface Ships and Submarines 7 400 Hz Power Supply Characteristics at User Equipment Terminals 8 DC Power Supply Characteristics at User Equipment Terminals 9 Characteristics of Electrical Power Supplies in HM Surface Ships and Submarines when Supplied from HM Dockyard and Naval Bases 1 2 3 4 5 6 Table A Table B Table B.1 Characteristics of Standard 60 Hz Supplies Characteristics of Standard 400 Hz Supplies PAGE 1 3 3 3 4 4 5 6 6 7

8 9 B-1 B-2

Characteristics of HM Surface Ship Main 60 Hz Supplies at the User Equipment Terminals Under Abnormal and Fault Conditions Table B.2 Characteristics of HM Submarine Main 60 Hz Supplies at the User Equipment Terminals Under Abnormal and Fault Conditions Annex A Annex B STANAG 1008 - Substance of Agreement Characteristics of Electrical Power Supplies in HM Surface Ships and Submarines During Abnormal Supply Conditions

A-1

B-1

DEF STAN 61-5 (PART 4)/2 ELECTRICAL POWER SUPPLY SYSTEMS BELOW 650 VOLTS PART 4: POWER SUPPLIES IN HM SHIPS 1 Scope This Part of the Defence Standard details the characteristics of power supplies available in HM Surface Ships and Submarines, but does not include aircraft servicing supplies, and does not include low power supplies for domestic electrical equipment. 1.1 Supply characteristics have been aligned, where practicable, with those of NATO standardization document STANAG 1008. The exceptions, limitations and additions applied to STANAG 1008 are specified. NOTE: Reference in this Part of the Standard to STANAG 1008 means Edition No 7 of STANAG 1008. 1.2 Transients which can be expected to occur on HM Surface Ship and Submarine electrical supply systems under abnormal or fault conditions are detailed in annex B of this Standard. 2 WARNING This Standard calls for the use of substances and/or procedures that may be injurious to health if adequate precautions are not taken. It refers only to technical suitability and in no way absolves either the designer, the producer, the supplier or the user from statutory and all other legal obligations relating to health and safety at any stage of manufacture or use. 3 Related Documents 3.1 The following documents and publications are referred to in this Part of the Standard: IEC Publication 50 IEC Publication 60-2 IEC Publication 445 International Electrotechnical Vocabulary High Voltage Test Techniques (Part 2) Identification of Apparatus Terminals and General Rules for a Uniform System of Terminal Marking, using an Alphanumeric Notation. STANAG 1008 (Edition No 7) Characteristics of Shipboard Electrical Power Systems in Warships of the North Atlantic Treaty Navies. Related documents are available from the following addresses: DOCUMENT IEC Publications SOURCE BSI Sales Department Linford Wood MILTON KEYNES MK14 6LE Directorate of Standardization Stan 2 Kentigern House 65 Brown Street GLASGOW G2 8EX 3

STANAG

DEF STAN 61-5(PART 4)/2 3.2 Reference in this Part of the Standard to any related document means in any invitation to tender or contract, the edition and all amendments current at the date of such tender or contract unless a specified edition is indicated. 4 Definitions

4.1 For the purpose of this Part of Def Stan 61-5 the following definitions apply in addition to those listed in STANAG 1008. 4.2 Alternative supply. A permanent power supply source from which an equipment can obtain power when the normal supply is not available. The alternative supply is derived from a different distribution point from that which provides the normal supply, and the supply cable follows a route different from the normal supply cable route to minimize the risk of losing both normal and alternative supplies through a single damage incident. NOTE: Change over from normal to alternative supply may be made by an automatic switch with a changeover time in the range 0.3 - 5.0 seconds, or a hand operated changeover switch. 4.3 Converted supply. Any supply, a.c. or d.c., which is derived from the main supply. Conversion is effected by rotating machinery, transformers, or solid state equipment. 4.4 Emergency supply. A power supply obtained by rigging a temporary system of emergency cables connected to fixed and portable plugs and sockets, or a permanently connected power supply system for providing power to essential equipment following failure of the ships main power supply. 4.5 Healthy supply system. A power supply system which under normal operating conditions will ensure that the voltage and frequency at user equipment terminals do not exceed the tolerances detailed in STANAG 1008. 4.6 Main power supply. In a.c. Ships and Nuclear Submarines the 440 V, 60 Hz, 3-phase power supply system or, in d.c. Ships, the 220 V power supply system. In Patrol Submarines the 440 V or 480 V (nominal) battery supply. 4.7 Maintained supply. A no-break supply in which one of the supplies is derived from a battery and is available only for a specified period. The power supply source from which an equipment 4.8 Normal supply. normally obtains power.

DEF STAN 61-5(PART 4)/2 5 User Equipment Requirements 5.1 The main power supply system in a.c. Surface Ships and Nuclear Submarines is 440 V, 60 Hz, 3-phase unearthed. 115 V, 60 HZ iS supplied through transformers for lighting and miscellaneous low power services. A large proportion of the electrical load of a warship can be taken from the ships main power supply, which does not require very close regulation. Equipments which cannot be designed to operate from these supplies for operational reasons will require provision of non standard supplies. It is emphasized that requests for such supplies will be strongly resisted unless it can be demonstrated that significant advantages can be achieved by their use. Equipment designers should consult the relevant MOD(PE) authority at an early stage of the design regarding the availability and characteristics of non-standard supplies. 5.2 Details of user equipment requirements and the characteristics of the main supply of electrical power in HM Surface Ships and Submarines are given in STANAG 1008. 6 Characteristics of Electrical Power Supplies in HM Surface Ships and Submarines 6.1 440 Volt and 115 Volt, 60 Hz power supply characteristics at user equipment terminals 6.1.1 The following supplies are available for general use: (a) 440V, 3-phase, 3 wire, 60Hz. (b) 115 V, 3-phase, 3 wire, 60 Hz (transformed from the 440V, 60 Hz System). 6.1.1.1 The characteristics of these supplies are given in table A (reproduced from STANAG 1008). 6.1.1.2 All tolerances are expressed as a percentage of the nominal voltage or frequency, and are applicable to main supply systems operated in split or parallel configuration. 6.1.1.3 All tolerances are based on healthy system performance (see 4.5). 6.1.1.4 Guidance regarding the transients which may occur under abnormal and fault conditions is given in annex B. 6.1.1.5 The main power supply system is designed to ensure that transients following supply interruptions due to automatic changeover switch operation are within the tolerances given in table A. 6.1.1.6 The 440 V, 60 Hz, distribution system is designed to ensure that, when an individual motor is started, the sustained voltage at its terminals (after generator voltage recovery) will not fall below 375 volts unless otherwise stated by the relevant MOD(PE) authority. Recovery time of motor terminal voltage will depend on the motor run-up time. The voltage at other loads will not fall below the values given in table A. 6.1.1.7 The 115 V, 60 Hz, distribution system is designed to ensure that, when an individual motor is started, the sustained voltage at its terminals

DEF STAN 61-5 (PART 4)/2 6.1.1.7 (Contd) will not fall below 98 volts. Recovery time of motor terminal voltage will depend on the motor run-up time. The voltage at other loads will not fall below the values given in table A. 6.1.1.8 The system 3-phase r.m.s. symmetrical short circuit current at the terminals of user equipment will normally not exceed 33 kA for 440 V systems and 5 kA for 115 V systems. 6.2 Continuity of power supply. The supplies to user equipments with alternative sources of supply are liable to interruptions of between 0.3-5.0 seconds where automatic changeover switches are used and longer where hand changeover switches are provided. Utilization equipment should be designed to withstand such supply interruptions without damage or subsequent malfunction. Details of equipment incapable of withstanding such supply interruptions shall be discussed with the relevant MOD(PE) Department at an early stage of the design. 7 400 Hz Power Supply Characteristics at User Equipment Terminals 7.1 440 and 115 V, single and 3-phase 400 Hz supplies. The characteristics of these supplies are given in table B (reproduced from STANAG 1008). 8 DC Power Supply Characteristics at User Equipment Terminals 8.1 Provision of d.c. supplies. The d.c. power requirements of an equipment shall normally be met by internal power conditioning and connected to a 60 Hz supply conforming to the specifications detailed in STANAG 1008. In cases where this is not practicable a supply at 24 volts will be provided by transformer/rectifier units supplied from the 440 V, 60 Hz, 3-phase main supply. The availability of these supplies is limited and prospective users must obtain agreement from the appropriate MOD(PE) Authority. 8.1.1 Characteristics of low voltage dc supplies. These are given in STANAG 1008, subject to the reservations at annex A. 8.1.2 Choice of voltage. Normally only 24 V d.c. will be provided. Battery support may be available for those equipments which require it, but its use must be agreed by the MOD(PE) Authority. 8.2 Vessels with d.c. main supply systems. The following will be available in HM Surface Ships and Submarines having d.c. power supply systems: (a) Battery supply at 440 V or 480 V (nominal) for patrol submarines. (b) Battery supply at 240 V or 270 V (nominal) for nuclear submarines. (c) 220 V d.c. for surface ships. The characteristics of these supplies, which may have a wide operating voltage range, are not detailed in this Standard. Designers of equipment intended for use with the above should consult MOD(PE), Sea Systems Controllerate, ME 312, Block B, Foxhill, Bath, BA1 5AB who are the first point of contact for information regarding power supply characteristics:

DEF STAN 61-5 (PART 4)/2 9 Characteristics of Electrical Power Supplies in HM Surface Ships and Submarines when Supplied from HM Dockyard and Naval Bases 9.1 440 volt and 115 volt, 60 Hz, power supply characteristics at user equipment terminals 9.1.1 The characteristics of standard 60 Hz electrical power supplies are given in table A subject to the reservation in 9.2 of this Standard. NOTE 1: All tolerances are expressed as a percentage of the nominal voltage or frequency. NOTE 2: All tolerances are based on healthy system performance (see 4.5).

NOTE 3: The system 3-phase r.m.s. symmetrical short circuit current at the terminals of user equipment will not exceed 33 kA for 440 V systems and 5 kA for 115 V systems. 9.2 Voltage recovery time following transient excursions will be longer than specified in table A due to the slower response of the shore transformer voltage regulator.

DEF STAN 61-5 (PART 4)/2 Table A Characteristics of Standard 60 Hz Supplies

Voltage

Nominal User Voltage User Voltage Tolerances (a) average of three-to-line voltages (1) - see Note A. (b) any one line-to-line voltage including (a) above and line voltage unbalance tolerance. Voltage Modulation (2) Line Voltage Unbalance Tolerance (3) Voltage Transient Tolerance - see note B Voltage Transient Recovery Time Voltage Spike (peak value)

440V or 115V

5%

7% 2% 3% 16% 2 seconds 2.5 kV 5% 3% 5% 60 Hz 3%

Waveform

Total Harmonic Distortion Individual Harmonic Deviation Factor Nominal Frequency Frequency Frequency Frequency Frequency Tolerance (4) - see note C Modulation (5) - see note C Transient Tolerance (6) - see note C Transient Recovery Time

Frequency

0.5%
4% 2 seconds

NOTE A: Except under transient or fault conditions the maximum departure from nominal user voltage, due to the combined effects of (1), (2), (3) will not exceed 6% for average of three line-to-line voltages 8% for any one line-to-line voltage. NOTE B: Except under fault conditions the maximum excursion due to the combined effects of transients and (l), (2), (3) above will not exceed 20% for the average of three line-to-line voltages; 22% for any one line-to-line voltage. Excursions of this order will only occur infrequently, which means not more than 10 times in a period of 24 hours. NOTE C: Except under fault conditions the maximum departure from 60 Hz resulting from (4), (5) and (6) above will not exceed 5.5%.

DEF STAN 61-5 (PART 4)/2 Table B Characteristics of Standard 400 Hz Supplies

Voltage

Nominal User Voltage User Voltage Tolerances: (a) Average of 3 line voltages (1) - see Note A. (b) Any one line-to-line voltage including (a) above and line voltage unbalance tolerance. Voltage Modulation (2) Line Voltage Unbalance Tolerance (3) Voltage Transient Tolerance - see note B Voltage Transient Recovery Time Voltage Spike (peak value)

440V or 115V

5%

7% 2% 3% 16% 2 seconds 2.5 kV 5% 3% 3% 400 Hz 5% 0.5% 4% 2 seconds

Waveform

Total Harmonic Distortion Individual Harmonic Deviation Factor Nominal Frequency Frequency Frequency Frequency Frequency Tolerance (4) - see note C Modulation (5) - see note C Transient Tolerance (6) - see note C Transient Recovery Time

Frequency

NOTE A: Except under transient or fault conditions the maximum departure from nominal user voltage, due to the combined effects of (l), (2) and (3) will not exceed 6% for average of three line-to-line voltages; 8% for any one line-to-line voltage. NOTE B: Except under fault conditions the maximum excursion due to the combined effects of transients and (l), (2) and (3) above will not exceed 20% for the average of three line-to-line voltages; 22% for any one line-to-line voltage. Excursions of this order will only occur infrequently, which means not more than 10 times in a period of 24 hours. NOTE C: Except under fault conditions the maximum departure from 400 Hz resulting from (4), (5) and (6) above will not exceed 6.5%.

Blank Page

DEF STAN 61-5 (PART 4)/2 ANNEX A STANAG 1008 - Substance of Agreement NATO STANAG 1008 (EDITION No 7) 25 MAY 1988 CHARACTERISTICS OF SHIPBOARD ELECTRICAL POWER SYSTEMS IN WARSHIPS OF THE NORTH ATLANTIC TREATY NAVIES SUBSTANCE OF AGREEMENT The NATO Military Committee through participating nations have agreed to standardize, in new construction warships, certain characteristics of the ship service power supply system. UK Reservations User equipments designed to operate from the main 60 Hz supply system of HM Surface Ships and Nuclear Submarines are to be capable of withstanding a rare transient in excess of values given in the STANAG. (See annex B). Wherever practicable, all machinery and equipment shall be designed for connection to a 440 V, 60 Hz, 3-phase system. On equipment rated at less than 5 kVA, if this is either undesirable (eg for personnel safety) or not practicable, the following shall be the order of preference: (a) 115 volts, 3-phase. (b) 115 volts, single phase. (c) 440 volts, single phase (use is discouraged). In HM Surface Ships maximum use is to be made of balanced, ie 3-phase supplies, and for this reason the order of preference of supplies given in the STANAG is unacceptable. The tolerances given in the STANAG apply to all shipboard 440 V or 115 V, single or 3-phase 400 Hz systems with the exception of aircraft servicing supplies. Owing to differences in present design between 24 V d.c. supply systems in HM Surface Ships and Submarines and those of other NATO Navies the user voltage limits for standard low voltage d.c. supplies in the STANAG shall not apply. The user voltage limits for equipments supplied with 24 volt d.c. in HM Surface Ships and Submarines shall be: (a) Non maintained systems. 20-26 volts. (b) Maintained systems, 18-26 volts.

A-1

DEF STAN 61-5 (PART 4)/2 ANNEX B Characteristics of Electrical Power Supplies in HM Surface Ships and Submarines During Abnormal Supply Conditions B.1 Introduction. STANAG 1008 gives power supply tolerances based on healthy system performance. The purpose of this annex is to detail transients which may occur following abnormal electrical system operations or under fault conditions. B.2 Characteristics of Electrical Power Supplies in HM Surface Ships During Abnormal and Fault Conditions B.2.1 The characteristics of 440 V and 115 V, 60 Hz, power supplies at user equipment terminals under abnormal and fault conditions are given in table B.1. B.2.1.1 All tolerances are expressed as a percentage of the nominal voltage or frequency. B.2.1.2 The Rare Transient category is written for events following abnormal operation of the electrical plant. B.2.1.3 The Extremely Rare Transient should only occur under fault conditions such as failure of generator AVR or overspeed protection. applicable only to power systems supported by a single generator. It iS

B.2.2 The first point of contact for guidance on the required performance of user equipments under abnormal and fault conditions is MOD(PE), Sea Systems Controllerate ME 312, Block B, Foxhill, Bath, BA1 5AB. Table B.1 Characteristics of HM Surface Ship Main 60 Hz Supplies at the User Equipment Terminals Under Abnormal and Fault Conditions

Nominal Voltage. Nominal Frequency. Voltage Extremely Rare Over Voltage Transient. (See B.2.1.3). Extremely Rare Over Frequency Transient (see B.2.1.3). Rare Frequency Transient (see B.2.1.2) Recovery Time.

440 V or 115 V 60 Hz

+50%

Frequency

+17%

Frequency

-10% 5 seconds

B-1

DEF STAN 61-5 (PART 4)/2 ANNEX B (Concluded) B.3 Characteristics of Electrical Power Supplies in HM Submarines During Abnormal and Fault Conditions B.3.1 The characteristics of 440 V and 115 V, 60 Hz, power supplies at user equipment terminals under abnormal and fault conditions are given in table B.2. B.3.1.1 All tolerances are expressed as a percentage of the nominal voltage or frequency. B.3.1.2 The Rare Transient category is written for events following abnormal operation of the electrical plant. It is written for power systems supported by a single generator and applies to all vessels of the VALIANT, RESOLUTION, SWIFTSURE and TRAFALGAR classes. B.3.1.3 The Extremely Rare Transient should only occur under fault conditions such as failure of generator AVR or overspeed protection. It is written for power systems supported by a single generator and applies to present and future submarine designs. B.3.2 For future Nuclear Submarine classes, the Rare Transient limits will be less severe than those given in table B.2. The first point of contact for guidance on the required performance of user equipments under abnormal and fault conditions is MOD(PE), Sea Systems Controllerate, ME 312, Block B, Foxhill, Bath, BA1 5AB who will also advise on the revised limits for future submarine designs. Table B.2 Characteristics of HM Submarine Main 60 Hz Supplies at the User Equipment Terminals Under Abnormal and Fault Conditions

Nominal Voltage. Rare Voltage Transient (see B.3.1.2). High limit. Recovery time. Low limit. Recovery time. Extremely Rare Overvoltage Transient (see B.3.1.3). Nominal Frequency. Frequency Rare Frequency Transient (see B.3.1.2). Recovery time. Extremely Rare Over Frequency Transient (see B.3.1.3).

440V or 115 V

Voltage

+23% 5 seconds

-40% 5 seconds +50%

60 Hz

-10%
5 seconds +17%

B-2

Blank Page

DEF STAN 61-5 (PART 4)/2

o
C

Crown Copyright 1992

Published by and obtainable from: Ministry of Defence Directorate of Standardization Kentigern House 65 Brown Street GLASGOW G2 8EX Tel No: 041-248 7890

This Standard may be fully reproduced except for sale purposes. The following conditions must be observed: The Royal Coat of Arms and the 1 publishing imprint are to be omitted. 2 The following statement is to be inserted on the cover: Crown Copyright. Reprinted by (name of organization) with the permission of Her Majestys Stationery Office. Requests for commercial reproduction should be addressed to MOD Stan 1, Kentigern House, 65 Brown Street, Glasgow G2 8EX

The following Defence Standard file reference relates to the work on this Standard - D/D Stan/319/01/17. Contract Requirements When Defence Standards are incorporated into contracts users are responsible for their correct application and for complying with contract requirements. Revision of Defence Standards Defence Standards are revised when necessary by the issue either of amendments or of revised editions. It is important that users of Defence Standards should ascertain that they are in possession of the latest amendments or editions. Information on all Defence Standards is contained in Def Stan 00-00 (Part 3) Section 4, Index of Standards for Defence Procurement - Defence Standards Index published annually and supplemented periodically by Standards in Defence News. Any person who, when making use of a Defence Standard encounters an inaccuracy or ambiguity is requested to notify the Directorate of Standardization without delay in order that the matter may be investigated and appropriate action taken.

92/80007

You might also like