You are on page 1of 3

1

N.W: Providing AC facilities and power plugs to Insurance ward at District Head

Quarters Hospital in Ramanathapuram.


Sl Qty No
1. 10 Pts.

Description of work
Wiring with 2 x 1.5sq.mm (22/0.3)PVC insulated single core unsheathed Cu. Conductor of 1100Vgrade in suitable PVC rigid pipe on wall and ceiling with PVC accessories and with TW switch box and 5A F.T. switch with painting of suitable colour for open PVC light point/Fan point (For Electronic regulator) (5 Points per coil) (SD-22) Renewal by supply and fixing of 1200 mm (48) AC ceiling fan complete with stepped electronic 300W regulator, with 300 mm down rod on the existing clamp. (SD-110) Supply and fixing of 400mm (16) wall mounting type oscillating fan with suitable electrical connection. [Data- A ] Supply and fixing of 20Amps DP Plug and socket in sheet enclosure with 32A DP MCB in flush with wall with earth connection (for AC plug) (Legrand (MDS)/Hager (L&T) make. (SD-140) Supply and fixing of 5A/15 A 3 Pin combined flush type wall socket with 15A flush type switch concealed in suitable MS Box in flush with wall with painting. [SD-137] Supply and fixing of fancy . Glass shade and 11 W CFL lamp for BH point. (SD-80) Supply and fixing of 4 way Buzzer suitable for 230 Volts 50 Hz Single phase AC supply on suitable TW Board covered with hylum sheet with suitable connection. (DATA-B) Supply and fixing of 3 Nos. 5Amps (3 pin and 2 pin) combined flush type wall socket with control switches concealed in suitable TW box covered with Hylem sheet in flush with wall with earth connection (combined plug socket) (SD-139) Supply and run of 2 of 2.5sqmm (22/0.3)PVC insulated SC unsheathed Cu.Conductor of 1100V grade in suitable PVC rigid pipe on wall and ceiling with continuous earth wire connection of 14 SWG TC wire with painting of suitable color(Run for combined plug) (DATA- C) C/O

Rate
763.80

Per Pt

Amount
7638.00

2. 6 Nos.

1590.40

Ea

9542.40

3. 1 No

1720.00 1787.90

Ea Ea

1720.00 3575.80

4. 2 No.

5. 4 Nos.

301.80

Ea

1207.20

6. 13 Nos. 7 3 Nos.

179.90 870.00

Ea Ea

2338.70 2610.00

8. 12 Nos.

314.90

Ea

3778.80

9. 140 Mts.

97.70

Mt

13678.00

46088.90

Sl Qty No
10. 140 Mts

Description of work
B/F Supply and run of 2 of 1.5sqmm (22/0.3)PVC insulated SC unsheathed Cu.Conductor of 1100V grade in suitable PVC rigid pipe on wall and ceiling with painting of suitable color)(Run for call bell) (Data-D) Renewal by Supply and run of 2 of 4sqmm (56/0.3)PVC insulated SC unsheathed Cu. Conductor of 1100V grade in suitable PVC rigid pipe on wall and ceiling with continuous earth wire connection of 14 SWG TC wire with painting suitable color. (Run for AC plug and 15A plug) (SD-56) Supply, erection, testing, and commissioning of 1.5 Ton(4500 k.cal/Hr) ABS Plastic split type Air. conditioner confirming to is:1391(part 2) 1992 Amdt No.1 to 2 fitted with Retry compressor operating Refrigerant R.22/ Non CFC suitable for wall mounting for operation on 230 volts, 50 HZ single phase AC supply with star rating of 5 as per BEE specification and capable of performing the functions of 1) cooling 2) de humidifying 3. Air circulating 4) filtering The installation works for the above split type AC units includes the following. 1. Mounting/fitting indoor and out door units at the respective locations. 2. Laying Refrigerant pipe line of required length connecting both units after drilling hole /holes in the wall if required. Thickness of copper tubing shall not be less than 0.7mm. 3. Insulating the suction pipe with expanded polyethylene foam 5mm tubing. 4. Laying 15mm dia Flexible PVC drain pipe to throw out. The condensate water being formed within Indoor unit. 5. Leakage testing the entire system. 6. Charging Refrigerant gas in the unit. 7. Suitable electric wiring to be provided with 2.5 sqmm. PVC insulated copper wire between indoor and out door units up to 6 meters length and up to Switch within 3 meters of location of in door Unit. (Carrier/voltas) (DGS & D Rates) C/O

Rate

Per

Amount
46088.90

68.90

Mt

9646.00

11. 70 Mts

129.50

Mt

9065.00

12. 6 Nos

35055.00

Ea

210330.00

275129.90

Sl Qty No
13. 6 Nos

Description of work
B/F Supply and Installation of 4.0 KVA Electronic Automatic voltage stabilizer V-Guard Make with Input voltage Range of 170 volt to 270 volt and output voltage range 200 volts to 240 volts with High and low voltage cut off and 3 minutes time delay relay with demonstration. (M.R) Charging refrigerant gas and servicing of 1.5 TR split AC unit (M.R) Supply and fixing of 4feet 40 W Twin Mirror optic suspension type fitting (Philips / Crompton / Wipro) complete with louvers cover complete with copper chokes and condenser with conduit pipe suspension with PVC unsheathed copper leads from the terminals to the fitting with flu. tubes. [Data-E] Supply and fixing of 5A ,250 V bell push on suitable TW box covered with hylum sheet with necessary connection. (Data-F)

Rate

Per

Amount
275129.90

3200.00

Ea

19200.00

14. 3 Nos 15. 2 Nos

2500.00

Ea

7500.00

3117.50

Ea

6235.00

16. 12 Nos

100.00

Ea

1200.00 309264.90 735.10 310000.00

PS Charges and Contingencies (Rupees Three Lakhs and Ten Thousand only)

Assistant Engineer, PWD Electrical Section-medical Works Ramanathapuram.

Assistant Executive Engineer ,PWD Electrical Sub Division(medical) Sivagangai.

You might also like