Fresh Air Sensible-Heat-Recovery Aeration System Content

. Summarize ............................................................................................ 1 1. Feature of products ............................................................................. 1 2. Naming Rule ..................................................................................... 2 . Performance Character and Specifications ............................................................. 3 1. Outline View .................................................................................... 3 2. Specifications ..................................................................... 4 . Installation Information. ............................................................................ 5 1. Outline dimension and space requirement ......................................................... 5 2. Electrical Part Information ..................................................................... 6 3. Maintenance and Trouble Shooting ................................................................ 7 Appendix: Unit Selection Example ......................................................................... 7

GREE COMMERCIAL AC

Fresh Air Sensible-Heat-Recovery Aeration System . Summarize The comprehensive using of air conditioning technology and equipments provide people a environment to escape the cold and hot climate, but which also cuase many inadvantages about peoples health. For example, some one who spends most of time in such environment with air conditioning might be into dizziness, nausea, dysphoria and tired etc. In 1983, WHO defined those health problems as Ill Architectural Syndrome. There are multiaspect reasons to cause this, while IAQ-Indoor Air Quality is one of the main matters. In order to improve the IAQ,people can open the windows sometime,or install a exhausting fan connect to outside.Anyhow this is not a good idea to get the fresh air in and it will also give burden on the air conditioning loading and get some unfiltered air with instable and inreliable features. The exhaust fan will give get the loading up and cost more investigation on the AC equipement and also the operating cost,which is big waste of energy. The Fresh Air Sensible-Heat-Recovery Aeration System can solve this problem, which can get more fitered fresh air into the room, reduce the amount of poisonous released from the building material while also get most of the heat or cooling reused.Such products provided by GREE company can be widely used in the civil building, offices, resterant, shopping mall, body building center and meeting room etc.
The basic theory of Sensible-Heat-Recovery

Aeration System is illustrated in the following picture

The air route inside the System (winter) The equipement is used to exchange the heat of air side to air side.For example,during the winter, the air from the outside is cold while the indoor is much warmer and wetter,if not adopting the heat recovery system,then it must install bigger capacity the air conditioning with humidifier to warm the air and add the humidity, such products will be quite expensive. While adopting the Sensible-HeatRecovery Aeration System, the unit can exchange the heat and humidity the exhausting air and fresh air, which will greatly save the energy and the investigation on the AC units. In summer,it will be the same situation.
1. Products feature:

Integrallty improve the IAQ:it can keeping on exhausting the griming air from the room to outside, while assure there is enough fresh air getting in, exchanging and get certain percent of the energy reused. There is sufficient insulation in the unit to prevent cross pollution and it can get the Air-Conditioning Sickness.

GREE COMMERCIAL AC

Fresh Air Sensible-Heat-Recovery Aeration System High efficient heat exchanging rate:High tech heat-exchange materials,with excellent humidity equalizing function,which enable the system ranks the first class enthalpy and temp. performance on this industry.The core part adopts Walf Structure,with antibacterial and mildewproof functions,which enable the Inlet Air sufficiently exchange the energy with the Outlet Air and assure much better IAQ. Excellent Energy Saving Performance: The system can pretreat the outdoor fresh air to get it close to the indoor situation, which can prevent discomfort caused by temp. difference and reduce total load on the air conditioning units. By adopting such heat recovery AHU system, the total operating load of air conditioning can be reduce 26% around. Flexible Control Mode:The system adopts luxury LCD with English and Chinese Language for option, can meet the control mode as: Half-and-Half air sending, Positive and Negtive Pressure air blowing, Energy Saving Mode, Humidifier and Weekly Timer etc. Several Heat-Recovery Aeration Units can be centrally controlled by one controller, and precisely control the on/off of each units in one week.If need, the units can also have the remote monitoring system by computer. The computer control system and central controller are optional products. Reliable and Easy to Maintain:There is only one moving part,fan motor,seldom maintenance, thus the unit can reliably run long term.While the filter and Heat-exchange Core can be easily pull out from the maintenance door to clean. Full Line Products to Select: There is 8 different capacity models,with capacity range from 150 2000m3/h,supplied by our company. The customer can choose the most suitable one,working at most efficient condition,which will greatly save the energy. Easy Installation:The unit can be installed into the hide ceiling, which dont take up the indoor room and dont influent the decoration. 2. Naming Rule: FH B QD / Design Serial No.:A,B,C, Rated Air Volume:Figure100,m3/h Installation Way:D for Ceiling Hide away. Heat Exchange Methods: Q for Sensible-Heat Structure of Core Part: B for Plate Type Fresh Air Type Symbol Example: FHBQ-D5 stands for the unit of rated air volume 500m3/h, with plate type Heat Exchange Core Part, Ceiling Suspending type Sensible-Heat-Recovery one.

GREE COMMERCIAL AC Fresh Air Sensible-Heat-Recovery Aeration System Performance Character and Specifications 1. Outside View

2. Specifications Model Name FHBQ-D Rated Voltage (V) Rated Frequency (Hz) Air Volum (m3/h) H M L H M L H M L H M L H M L 1.5 2.5 3.5 220 50 150 110 90 60 45 38 70 72 74 64 66 67 61 63 65 75 33 278 551 810 36 250 190 150 65 50 40 66 68 70 63 65 66 60 62 64 95 33 278 551 810 36 350 260 210 100 80 60 71 73 75 65 67 68 61 63 65 180 37 306 800 879 45 500 380 300 100 80 60 68 70 72 62 64 65 57 59 61 240 39 306 800 879 45 800 1000 600 750 1500 2000 480 600 150 150 120 120 170 170 95 95 70 75 73 71 72 77 74 79 63 66 65 62 65 68 67 70 60 62 62 64 60 58 64 65 400 440 600 950 45 46 48 50 387 387 460 460 832 1214 1214 1214 1111 1111 1200 1200 70 95 135 200 5 8 10 15 380 20

Static Pressure (Pa) Exchange Rate According to the Temperature (%) Heating Condition Enthalpy Rate(%) Cooling Condition Power Input (W) Noise Level [dB(A)] Dimension (mm) Weight (kg)

H D W

Note: Units with 220V power supply have three fan speed,while 380V units just one The Performance Data is tested under the following condition: Cooling Rate base on the indoor temp. 27DB, 50%RH,outdoor temp. 35DB, 60%RH. Heating Rate base on the indoor temp. 20 DB, 40%RH,outdoor temp. 7 DB, 70%RH. Noise level is tested in the Exclusive Noise Lab, so the actually operating might be noiser. Working temperature range:-15-+50no bigger than 80RH

GREE COMMERCIAL AC Fresh Air Sensible-Heat-Recovery Aeration System . Installation Information 1. Outline dimension and space requirement

Schematic of the Unit mm Model FHBQ-D1.5 FHBQ-D2.5 FHBQ-D3.5 FHBQ-D5 FHBQ-D8 A 810 810 879 879 A1 754 754 823 823 B 551 551 800 800 832 B1 603 603 852 852 884 C 278 278 306 306 387 387 460 460 C1 115 115 125 125 165 165 200 200 D 132 132 132 84 90 90 100 100 E 131 131 131 131 153 153 181 181 F 152 152 180 180 235 235 280 280 G 126 126 137 137 153 153 183 183 H 275 275 416 416 431 622 592 592 N 146 146 146 197 246 246 297 297 L 600 600 600 600 600 600 600 600

1111 1055

FHBQ-D10 1111 1055 1214 1266 FHBQ-D15 1200 1144 1214 1266 FHBQ-D20 1200 1144 1214 1266

GREE COMMERCIAL AC Fresh Air Sensible-Heat-Recovery Aeration System

A-A

Installation Schematic 2. Electrical Part Information

When using the Humidifier,please connect the Interface on the Humidifer Contactor with End2 on the Wiring Plate, and choose humidity sensor connect to HUMID end on the PCB. When using the Central Controller,please connect L and 1 on the wiring plate to Air Damper Patch Board Broken Line part is for option.

GREE COMMERCIAL AC Fresh Air Sensible-Heat-Recovery Aeration System 3. Maintenance and Trouble Shooting Installation Space: The following position is not suitable to install the Heat-Recovery Units: The place near high temperature or fire flame,which might cause over heating or fire damage. The place where has oil fog or oil vapor, for example Kitchen,might cause fire. The position surround by poisonous gas or corrosive material, for example Chemical Works or Mechanical Factories, which might cause fire,corrode the unit or lead poisonous gas into room. Bothroom etc. where is much too wet might cause power leakage and other problems. Position where near the radiation machine, might cause malfunction of the controlling. Make sure the air inlet and outlet part temperature within the required range. Installation Project Please correctly wiring the power cords, air-leading duct. Tightly suspend the unit to the ceiling by approved device. Daily Maintaining The filter and heat-exchange core should be cleaned termly,when the air volume is felt smaller definitely, please clean the mentioned two parts. The suitable term should be according to the actually using situation of the products The maintaining work should be carried of inducted by professionals with certain AC knowledge. Appendix: Selection Example Project of civil room with fresh air: No Smoking ROOM Normal Gymnasi Sickroom um Theater or Shopping Mall Offices A little Smoking Heavy Smoking

High Computer Meeting Restaurant Standard Room Room Bedroom

Fresh Air Per 17~42 8~20 8.5~21 25~62 40~100 20~50 30~75 50~125 Person Q(m3/h) Fresh Air changing Rate 1.06~2.65 0.50~1.25 1.06~2.66 1.56~3.90 2.50~6.25 1.25~3.13 1.88~4.69 3.13~7.81 Ptime/h) Introduction: 1Choose the fresh air amount according to the room size and persons by the recommending data in the mentioned table.According to the higher data to select the suitable units. 2If for the special condition, for example Hospital-operation room or special sickroom,Labs, industry works, please according to standard criterion for those place to calculate the fresh air amount. Calculation Example: Some compter room S=60m2net h3mpersons n10according to Fresh Air Per Person to calculate the fresh air volume. Q1nxq10x70700m3/h( q70m3/h) If according to Fresh Air changing Rate to calculate the fresh air amount.Make the Fresh Air changing Rate, p5times/hthus air amount Q2pxsxh5x60x3900m3/h As Q2>Q1we here choose Q2 as the standard, here the suitable model will be FHBQ-D8 or FHBQ-D10.Please accord to the distance and space to make the final decision.